For more Information
please call
1-800-Belden1
General Description:
Fire Alarm Cable, Riser-FPLR, 2-18 AWG solid bare copper conductors with polyolefin insulation, Overall
Beldfoil® shield, PVC jacket with ripcord
Usage (Overall)
Suitable Applications: Fire Protection, Alarm, Signal, Monitor/Detection, Audio Circuits, Control Circuits, Initiating Circuits,
Notification Circuits
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
218 Solid BC - Bare Copper
Total Number of Conductors: 2
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
PP - Polyproylene 0.178
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Outer Shield Material Coverage (%)
Beldfoil® Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
24 Solid TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.432
Outer Jacket Ripcord: Yes
Overall Cable
Overall Cabling Lay Length & Direction:
Length (mm) Direction Twists (twist/m)
69.850 Left Hand 14.436
Overall Cabling Color Code Chart:
Number Color
1Black
2Red
Overall Nominal Diameter: 3.734 mm
Mechanical Characteristics (Overall)
Operating Temperature Range: -20°C To +75°C
UL Temperature Rating: 75°C
Bulk Cable Weight: 29.764 Kg/Km
Max. Recommended Pulling Tension: 236.644 N
Min. Bend Radius/Minor Axis: 38.100 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: FPLR
NEC Articles: 760
Page 1 of 3 01-09-2015
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
5320FL Multi-Conductor - Commercial Applications - 2 Conductors Cabled
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Flame Test
UL Flame Test: UL1666 Vertical Shaft
CSA Flame Test: FT4
Plenum/Non-Plenum
Plenum Number: 6320FL
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/m)
0.492
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
180.455
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
324.819
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
20.9984
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
58.730
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Description Current
10C Temperature Rise 5 Amps per conductor @ 25°C
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
5320FL D15U1000 1,000 FT 18.000 LB BLUE 2 #18 PP FS FRPVC
5320FL D151000 1,000 FT 18.000 LB BLUE C 2 #18 PP FS FRPVC
5320FL 002U1000 1,000 FT 18.000 LB RED 2 #18 PP FS FRPVC
5320FL 002U500 500 FT 9.500 LB RED 2 #18 PP FS FRPVC
5320FL 0021000 1,000 FT 18.000 LB RED C 2 #18 PP FS FRPVC
5320FL 003C500 500 FT 8.000 LB ORANGE 2 #18 PP FS FRPVC
5320FL 004C500 500 FT 8.000 LB YELLOW 2 #18 PP FS FRPVC
5320FL 0041000 1,000 FT 18.000 LB YELLOW 2 #18 PP FS FRPVC
5320FL 0071000 1,000 FT 18.000 LB VIOLET 2 #18 PP FS FRPVC
Notes:
C = CRATE REEL PUT-UP.
Revision Number: 3 Revision Date: 08-20-2013
© 2015 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
Page 2 of 3 01-09-2015
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
5320FL Multi-Conductor - Commercial Applications - 2 Conductors Cabled
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3 01-09-2015
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
5320FL Multi-Conductor - Commercial Applications - 2 Conductors Cabled