Reyrolle Protection Devices 7SR21 & 7SR22 Argus Overcurrent Relay Energy Management Contents Technical Manual Sections 1. Description of Operation 2. Configuration Guide 3. 7SR210 Instrumentation Guide 4. 7SR210 Settings Guide 5. 7SR220 Instrumentation Guide 6. 7SR220 Settings Guide 7. Performance Specification 8. Data Communications Definitions 9. Installation Guide 10. Commissioning and Maintenance Guide 11. Applications Guide The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2013 Siemens Protection Devices Limited Contents 7SR11 and 7SR12 Page 2 of 2 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 7SR210 Non-Directional Relay 7SR220 Directional Relay Description Of Operation Unrestricted The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Document Release History This document is issue 2018/09. The list of revisions up to and including this issue is: 2011/05 First issue. 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions amended drawings and added data. Updated in line with software release. 2015/07 Amended drawings. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/11 Redundancy added to electrical ethernet interface 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. 2018/09 Typographical revisions. Software Revision History 2011/05 2435H85008R7a-7a (7SR210) First Release 2435H85009R7a-7a (7SR220) 2013/01 2435H85008R7c-7b (7SR210) 2435H85009R7c-7b (7SR220) 2014/06 2435H85008R7f-7d (7SR210) 2435H85009R7f-7d (7SR220) 2015/06 2435H85008R8a-7f (7SR210) 2435H85009R8a-7f (7SR220) 2016/02 2435H85008R8b-7f (7SR210) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Added Fault Locator feature and Check Sync feature. Fault data transmission over IEC 60870-5-103. Additional communications data, control features, meters. Added Power Factor Meters, Load Blinding feature, Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. 2435H85009R8b-7f (7SR220) 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing, 67SEF Compensated Network, 67SEF Wattmetric. Increased I/O. Event Data on LCD. Unrestricted (c)2018 Siemens Protection Devices Limited Page 2 of 94 7SR210 & 7SR220 Description of Operation Contents Document Release History ................................................................................................................................. 2 Software Revision History .................................................................................................................................. 2 Contents............................................................................................................................................................ 3 List of Figures .................................................................................................................................................... 5 Section 1: Introduction ....................................................................................................................................... 8 1.1 Current Transformer Circuits .............................................................................................................. 8 1.2 External Resistors.............................................................................................................................. 8 1.3 Fibre Optic Communication ................................................................................................................ 8 1.4 Front Cover ....................................................................................................................................... 8 1.5 Disposal ............................................................................................................................................ 8 Section 2: Hardware Description ...................................................................................................................... 15 2.1 General ........................................................................................................................................... 15 2.2 Case ............................................................................................................................................... 16 2.3 Front Cover ..................................................................................................................................... 16 2.4 Power Supply Unit (PSU) ................................................................................................................. 16 2.5 Operator Interface/ Fascia................................................................................................................ 16 2.6 Current Inputs.................................................................................................................................. 21 2.7 Voltage Inputs ................................................................................................................................. 21 2.8 Binary Inputs ................................................................................................................................... 21 2.9 Binary Outputs (Output Relays) ........................................................................................................ 22 2.10 Virtual Input/Outputs ........................................................................................................................ 23 2.11 Self Monitoring ................................................................................................................................ 23 2.11.1 Protection Healthy/Defective............................................................................................... 24 Section 3: Protection Functions ........................................................................................................................ 25 3.1 Current Protection: Phase Overcurrent (67, 51, 50)........................................................................... 25 3.1.1 Directional Control of Overcurrent Protection (67) - 7SR22 ................................................. 25 3.1.2 Instantaneous Overcurrent Protection (50) .......................................................................... 27 3.1.3 Time Delayed Overcurrent Protection (51) .......................................................................... 28 3.2 Current Protection: Voltage Controlled Overcurrent (51V) - 7SR22 ................................................... 30 3.3 Current Protection: Derived Earth Fault (67N, 51N, 50N)................................................................... 31 3.3.1 Directional Control of Derived Earth Fault Protection (67N) - 7SR22.................................... 31 3.3.2 Instantaneous Derived Earth Fault Protection (50N) ............................................................ 32 3.3.3 Time Delayed Derived Earth Fault Protection (51N)............................................................. 33 3.4 Current Protection: Measured Earth Fault (67G, 51G, 50G)............................................................... 35 3.4.1 Directional Control of Measured Earth Fault Protection (67G) - 7SR22 ................................ 35 3.4.2 Instantaneous Measured Earth Fault Protection (50G)......................................................... 36 3.4.3 Time Delayed Measured Earth Fault Protection (51G) ......................................................... 37 3.5 Current Protection: Sensitive Earth Fault (67SEF, 51SEF, 50SEF) .................................................... 38 3.5.1 Directional Control of Sensitive Earth Fault Protection (67SEF) - 7SR22 ............................. 38 3.5.2 Instantaneous Sensitive Earth Fault Protection (50SEF) ...................................................... 39 3.5.3 Time Delayed Sensitive Earth Fault Protection (51SEF) ...................................................... 41 3.6 Current Protection: High Impedance Restricted Earth Fault (64H) ..................................................... 43 3.7 Current Protection: Cold Load (51c) ................................................................................................. 44 3.8 Current Protection: Negative Phase Sequence Overcurrent (46NPS) ................................................ 45 3.9 Current Protection: Under-Current (37, 37G & 37SEF) ...................................................................... 46 3.10 Current Protection: Under-Current Guarded (37)............................................................................... 46 3.11 Current Protection: Thermal Overload (49) ....................................................................................... 47 3.12 Current Protection: Arc Flash Detector (50 AFD)............................................................................... 49 3.13 Voltage Protection: Phase Under/Over Voltage (27/59) - 7SR22 ....................................................... 50 3.14 Voltage Protection: Negative Phase Sequence Overvoltage (47) - 7SR22 ........................................ 51 3.15 Voltage Protection: Neutral Overvoltage (59N) - 7SR22 ................................................................... 52 3.16 Voltage Protection: Under/Over Frequency (81) - 7SR22.................................................................. 53 3.17 Power Protection: Power (32) - 7SR22 ............................................................................................ 54 3.18 Power Protection: Sensitive Power (32S) - 7SR22 ........................................................................... 55 3.19 Power Protection: Power Factor (55) - 7SR22 ................................................................................. 56 Section 4: Control & Logic Functions ................................................................................................................ 57 4.1 Auto-Reclose (79) ............................................................................................................................ 57 4.1.1 Overview............................................................................................................................ 57 4.1.2 Auto Reclose sequences .................................................................................................... 59 4.2 Autoreclose Prot'n Menu .................................................................................................................. 60 4.3 Autoreclose Config Menu ................................................................................................................. 60 4.4 P/F Shots Sub-Menu........................................................................................................................ 62 4.5 E/F Shots Sub-Menu........................................................................................................................ 62 4.6 SEF Shots Sub-Menu ...................................................................................................................... 62 Unrestricted (c)2018 Siemens Protection Devices Limited Page 3 of 94 7SR210 & 7SR220 Description of Operation 4.7 Extern Shots Sub-Menu .................................................................................................................. 63 4.8 Manual Control................................................................................................................................ 65 4.9 Synchronising ................................................................................................................................. 66 4.9.1 Reclosure Modes............................................................................................................... 66 4.9.2 Charge Delays................................................................................................................... 66 4.9.3 Voltage monitoring elements .............................................................................................. 66 4.9.4 Check Synchronising Mode................................................................................................ 68 4.9.5 System Split Detector ........................................................................................................ 69 4.9.6 System Sync Reversion ..................................................................................................... 69 4.9.7 System Synchronising Mode .............................................................................................. 70 4.9.8 Close on Zero Mode .......................................................................................................... 70 4.10 Live/Dead Indication........................................................................................................................ 71 4.11 Circuit Breaker ................................................................................................................................ 72 4.12 Quick Logic ..................................................................................................................................... 75 Section 5: Supervision Functions ..................................................................................................................... 77 5.1 Circuit Breaker Failure (50BF) ......................................................................................................... 77 5.2 VT Supervision (60VTS) - 7SR22.................................................................................................... 78 5.3 Busbar VT Fail (60VTF-Bus) - 7SR22 ............................................................................................. 79 5.4 CT Supervision (60CTS & 60CTS-I)................................................................................................. 80 5.4.1 (60CTS-I) - 7SR21 & 7SR22 ............................................................................................. 80 5.4.2 (60CTS) - 7SR22 .............................................................................................................. 80 5.5 Broken Conductor (46BC) ............................................................................................................... 81 5.6 Trip / Close Circuit Supervision (74TCS & 74CCS) ........................................................................... 81 5.7 Inrush Restraint (81HBL2) ............................................................................................................... 82 5.8 Over Fluxing Detector (81HLB5) ...................................................................................................... 83 5.9 Load Blinder (21) ............................................................................................................................ 84 5.9.1 Load Blinder (21) Three-Phase .......................................................................................... 84 5.9.2 Load Blinder (21) Single-Phase. ......................................................................................... 85 Section 6: Other Features................................................................................................................................ 87 6.1 Data Communications ..................................................................................................................... 87 6.2 Maintenance ................................................................................................................................... 87 6.2.1 I2t CB Wear ....................................................................................................................... 88 6.2.2 Output Matrix Test ............................................................................................................. 88 6.3 Data Storage................................................................................................................................... 89 6.3.1 General ............................................................................................................................. 89 6.3.2 Event Records ................................................................................................................... 89 6.3.3 Waveform Records. ........................................................................................................... 89 6.3.4 Fault Records .................................................................................................................... 90 6.3.5 Demand ............................................................................................................................ 90 6.3.6 Data Log ........................................................................................................................... 90 6.3.7 Energy Storage ................................................................................................................. 91 6.3.8 Fault Locator ..................................................................................................................... 92 6.4 Metering ......................................................................................................................................... 92 6.5 Operating Mode .............................................................................................................................. 93 6.6 Control Mode .................................................................................................................................. 93 6.7 Real Time Clock.............................................................................................................................. 93 6.7.1 Time Synchronisation - Data Communication Interface ....................................................... 94 6.7.2 Time Synchronisation - Binary Input .................................................................................. 94 6.7.3 Time Synchronisation - IRIG-B (Optional) .......................................................................... 94 6.8 Settings Groups .............................................................................................................................. 94 6.9 Password Feature ........................................................................................................................... 94 Unrestricted Page 4 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation List of Figures Figure 1.5-1 Functional Diagram of 7SR21 Relay .............................................................................. 10 Figure 1.5-2 Connections Diagram for 7SR21 Relay ......................................................................... 11 Figure 1.5-3 Functional Diagram of 7SR22 Relay .............................................................................. 13 Figure 1.5-4 Connection Diagram for 7SR22 Relay ........................................................................... 14 Figure 2.5-1 7SR21 with 3 + 8 LEDs in E6 Case ............................................................................... 17 Figure 2.5-2 7SR220 with 3 + 16 LEDs in E8 Case ........................................................................... 17 Figure 2.5-3 7SR22 with Function Keys and 3 + 8 LEDs in E8 Case.................................................. 17 Figure 2.5-4 7SR22 with Function Keys & 3 + 8 LEDs in E8 Case and Ethernet Communication Interface............................................................................................... 18 Figure 2.8-1 Binary Input Logic.......................................................................................................... 21 Figure 2.9-1 Binary Output Logic ....................................................................................................... 22 Figure 2.11-1 Start-up Counter Meter ................................................................................................ 23 Figure 2.11-2 Start-up Counter Meter ................................................................................................ 23 Figure 2.11-3 Start-up Counter Meter Events .................................................................................... 24 Figure 3.1.1-1 Logic Diagram: Directional Overcurrent Element (67) ............................................. 26 Figure 3.1.2-1 Logic Diagram: Instantaneous Over-current Element.............................................. 27 Figure 3.1.3-1 Logic Diagram: Time Delayed Overcurrent Element ............................................... 29 Figure 3.2-1 Logic Diagram: Voltage Controlled Overcurrent Protection............................................. 30 Figure 3.3.1-1 Logic Diagram: Derived Directional Earth Fault Element......................................... 32 Figure 3.3.2-1 Logic Diagram: Derived Instantaneous Earth Fault Element ................................... 33 Figure 3.3.3-1 Logic Diagram: Derived Time Delayed Earth Fault Protection................................. 34 Figure 3.4.1-1 Logic Diagram: Measured Directional Earth Fault Protection .................................. 35 Figure 3.4.2-1 Logic Diagram: Measured Instantaneous Earth-fault Element................................. 36 Figure 3.4.3-1 Logic Diagram: Measured Time Delayed Earth Fault Element (51G) ...................... 37 Figure 3.5.1-1 Logic Diagram: SEF Directional Element (67SEF) .................................................. 39 Figure 3.5.2-1 Logic Diagram: 50 SEF Instantaneous Element...................................................... 40 Figure 3.5.2-2 Logic Diagram: 50 SEF Instantaneous Element Compensated Networks................ 40 Figure 3.5.3-1 Logic Diagram: 51 SEF Time Delayed Element ...................................................... 42 Figure 3.5.3-2 Logic Diagram: 51 SEF Time Delayed Element Compensated Networks ................ 42 Figure 3.6-1 Logic Diagram: High Impedance REF (64H) .................................................................. 43 Figure 3.7-1 Logic Diagram: Cold Load Settings (51c) ....................................................................... 44 Figure 3.8-1 Logic Diagram: Negative Phase Sequence Overcurrent (46NPS) .................................. 45 Figure 3.9-1 Logic Diagram: Undercurrent Detector (37, 37G & 37SEF) ............................................ 46 Figure 3.10-1 Logic Diagram: Undercurrent Guarded Detector (37).............................................. 46 Figure 3.11-1 Logic Diagram: Thermal Overload Protection (49S)................................................ 48 Figure 3.12-1 Logic Diagram: Arc Flash Detector (50 AFD) .......................................................... 49 Figure 3.13-1 Logic Diagram: Under/Over Voltage Elements (27/59) ........................................... 50 Figure 3.14-1 Logic Diagram: NPS Overvoltage Protection (47) ................................................... 51 Figure 3.15-1 Logic Diagram: Neutral Overvoltage Element ......................................................... 52 Figure 3.16-1 Logic Diagram: Under/Over Frequency Detector (81) ............................................. 53 Figure 3.17-1 Logic Diagram: Power Protection (32) .................................................................... 54 Figure 3.18-1 Logic Diagram: Sensitive Power Protection (32S)................................................... 55 Figure 3.19-1 Logic Diagram: Power Factor Protection (55) ......................................................... 56 Figure 4.1.2-1 Typical Sequence with 3 Instantaneous and 1 Delayed trip .................................... 59 Figure 4.7-1 Basic Auto-Reclose Sequence Diagram ........................................................................ 64 Figure 4.9.3-1 Voltage Detector Operation .................................................................................... 67 Figure 4.9.4-1 Check Sync Function ............................................................................................. 68 Figure 4.9.7-1 System Sync Function ........................................................................................... 70 Figure 4.9.8-1 Close On Zero Function ......................................................................................... 71 Figure 4.9.8-2 Close On Zero Timing ............................................................................................ 71 Figure 4.10-1 Voltage Detector Operation .................................................................................... 72 Figure 4.11-1 Logic Diagram: Circuit Breaker Status .................................................................... 73 Figure 4.12-1Sequence Diagram: Quick Logic PU/DO Timers (Counter Reset Mode Off) .................. 76 Figure 5.1-1 Logic Diagram: Circuit Breaker Fail Protection (50BF) ................................................... 77 Figure 5.2-1 Logic Diagram: VT Supervision Function (60VTS) ......................................................... 79 Figure 5.4.1-1 Logic Diagram: CT Supervision Function (60CTS-I) - 7SR21 & 7SR22 .................. 80 Figure 5.4.2-1 Logic Diagram: CT Supervision Function (60CTS) - 7SR22 ................................... 80 Figure 5.5-1 Logic Diagram: Broken Conductor Function (46BC) ....................................................... 81 Unrestricted (c)2018 Siemens Protection Devices Limited Page 5 of 94 7SR210 & 7SR220 Description of Operation Figure 5.6-1 Logic Diagram: Trip Circuit Supervision Feature (74TCS) ............................................. 81 Figure 5.6-2 Logic Diagram: Close Circuit Supervision Feature (74CCS) .......................................... 82 Figure 5.7-1 Logic Diagram: Harmonic Block Feature (81HBL2) ........................................................ 82 Figure 5.8-1 Logic Diagram: Over Fluxing Detector (81HLB5) ........................................................... 83 Figure 5.9.1-1 Logic Diagram: Load Blinder Three-Phase ............................................................. 84 Figure 5.9.2-1 Logic Diagram: Load Blinder Single-Phase ............................................................ 85 Figure 5.9.2-2 Load Blinder and Angle .......................................................................................... 86 Figure 6.3.7-1 Energy Direction Convention.................................................................................. 91 LIST OF TABLES Table 1.5-1 Table 1.5-2 Table 2.1-1 Table 6.5-1 Ordering Information - 7SR21 Non-Directional Overcurrent ............................................. 9 Ordering Information - 7SR22 Directional Overcurrent .................................................. 12 Summary of Overcurrent Relay Configurations .............................................................. 15 Operation Mode ............................................................................................................ 93 Unrestricted Page 6 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Symbols and Nomenclature The following notational and formatting conventions are used within the remainder of this document: * Setting Menu Location MAIN MENU>SUB-MENU * Setting: Elem name -Setting * Setting value: value * Alternatives: [1st] [2nd] [3rd] Elem Char Dir Binary input signal Elem Inhibit Binary Output visible to user Elem Starter List of settings associated with a specific function Appropriate list is TRUE when setting selected. Common setting for multiple functions Digital signal to/from another element Digital signal not visible to user, internal to this element Analogue signal with signal description And Gate (2 inputs shown) Or Gate (3 inputs shown) PhaseAFwd L1 Dir Blk IL1 Common control input (c) for multiple functions. All functions are enabled when control input is TRUE. Function. Forward Reverse Elem Reset Delay c start c trip start Individual functions are enabled when associated control input (c) is TRUE. c trip & 1 EVENT: IEC, Modbus or DNP Where applicable Relay instrument Exclusive Or (XOR) Gate (3 inputs shown) Non-Dir EVENT INST. 1 Unrestricted (c)2018 Siemens Protection Devices Limited Page 7 of 94 7SR210 & 7SR220 Description of Operation Section 1: Introduction This manual is applicable to the following relays: * 7SR210 Multi-Function Non-directional Overcurrent and Earth Fault Relay * 7SR220 Multi-Function Directional Overcurrent and Directional Earth Fault Relay The 7SR210 and 7SR220 relays integrate the protection and control elements required to provide a complete overcurrent based protection. The `Ordering Options' Tables summarise the features available in each model. General Safety Precautions 1.1 Current Transformer Circuits ! ! The secondary circuit of a live CT must not be open circuited. Non-observance of this precaution can result in injury to personnel or damage to equipment. 1.2 External Resistors Where external resistors are fitted to the circuit, these may present a danger of electric shock or burns, if touched. 1.3 Fibre Optic Communication ! ! Where fibre optic communication ports are fitted, the lasers are Class 1 devices but recommend they should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device. 1.4 Front Cover The front cover provides additional securing of the relay element within the case. The relay cover should be in place during normal operating conditions. 1.5 Disposal ! The Relay should be disposed of in a manner which does not provide a threat to health or the environment. All laws and regulations specific to the country of disposal should be adhered to. The relays and protection systems manufactured under the Reyrolle brand currently do not come within the scope of either the European WEEE or RoHS directives as they are equipment making up a fixed installation. Unrestricted Page 8 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Table 1.5-1 Ordering Information - 7SR21 Non-Directional Overcurrent Product description Variants Order No. 7 S R 2 Protection Product Family Overcurrent - Non Directional 1 0 - 1 A - 0 A 0 1 Relay Type 0 1) Case, I/O and Fascia E6 case, 4 CT, 9 Binary Inputs, 8 Binary Outputs, 8 LEDs E8 case, 4 CT, 19 Binary Inputs, 16 Binary Outputs, 16 LEDs E8 case, 4 CT, 19 Binary Inputs, 16 Binary Outputs, 8 LEDs + 6 keys E12 case, 4 CT, 39 Binary Inputs / 16 Binary Outputs, 32 LEDs E12 case, 4 CT, 39 Binary Inputs / 16 Binary Outputs, 16 LEDs, 12 keys 2 3 4 5 6 Measuring input 1 A or 5 A, 50 Hz or 60 Hz Auxiliary voltage PSU Rated: 30 to 220V DC. Binary Input threshold 19V DC (Rated: 24-250V DC) PSU Rated: 30 to 220V DC. Binary Input threshold 88V DC (Rated: 110-250V DC) PSU Rated: 24-250V DC / 100-230V AC. Binary Input threshold 19V DC (Rated: 24-250V DC) PSU Rated: 24-250V DC / 100-230V AC. Binary Input threshold 88V DC (Rated: 110-250V DC) 1 A B M N Spare A Communication Interface Standard version - included in all models, USB front port, RS485 rear port Standard version - plus additional rear F/O ST connectors (x2) and IRIG-B Standard version - plus additional rear RS485 and IRIG-B Standard version - plus additional rear RS232 and IRIG-B Standard version - plus additional rear Electrical Ethernet RJ45 (x2) Standard version - plus additional rear Optical Ethernet Duplex (x2) Protocol IEC 60870-5-103 and Modbus RTU (user selectable) IEC 60870-5-103 and Modbus RTU and DNP 3.0 (user selectable) IEC 60870-5-103 and Modbus RTU and DNP 3.0 (user selectable) and IEC61850 1 2 3 4 7 8 7 7 7-8 1 2 7 Spare 0 Protection Function Packages Standard version - included in all models 37 Undercurrent 46BC Broken conductor/load unbalance 46NPS Negative phase sequence overcurrent 49 Thermal overload 50 Instantaneous phase fault overcurrent 50BF Circuit breaker fail 50G/50N Instantaneous earth fault/SEF 50 AFD Arc Flash Detector 51 Time delayed phase fault overcurrent 51G/51N Time delayed earth fault/SEF 60CTS-I CT supervision 64H High impedance REF 74TC/CCS Trip & close circuit supervision 81HBL2 Inrush Detector 81HBL5 Overfluxing Detector 86 Lockout Cold load pickup Programmable logic CB Control Standard version - plus 79 Autoreclose Additional Functionality No additional functionality C D A Spare 0 Export Data HS: 8536900 ECCN: N AL: N Unrestricted (c)2018 Siemens Protection Devices Limited Page 9 of 94 7SR210 & 7SR220 Description of Operation Figure 1.5-1 Functional Diagram of 7SR21 Relay Unrestricted (c)2018 Siemens Protection Devices Limited Page 10 of 94 7SR210 & 7SR220 Description of Operation 2 4 6 8 10 12 14 16 18 20 22 24 7SR21 +ve -ve BI 10 BO 9 BI 11 BO 10 3 7 BO 11 BI 13 BO 12 11 BI 14 15 BO 13 17 BO 14 21 28 +ve BI 16 24 4 A Optional I/O PSU Analogue Blank Optional I/O 27 28 6 8 2 25 4 6 8 +ve 10 +ve BI 19 12 C 10 12 BO 1 -ve 16 GND. 5 16 Screen 18 B 1 3 BO 3 BI 2 BI 3 5A 27 28 18 20 22 24 26 28 +ve -ve +ve BI 21 BI 31 +ve BI 22 BI 32 BI 23 BI 33 BI 24 BI 34 BI 25 BI 35 +ve +ve +ve +ve +ve +ve -ve +ve BI 26 BI 36 BI 27 BI 37 BI 28 BI 38 +ve +ve +ve +ve +ve -ve -ve +ve +ve -ve -ve +ve BI 29 D BI 39 -ve 1 3 5 7 9 11 13 15 17 19 21 23 25 27 23 26 27 +ve BI 4 IL1 (IA) +ve +ve BI 6 IL2 (IB) -ve +ve BI 7 1A 5A 18 20 +ve +ve 1A BO 7 5A 16 NOTES BI = Binary Input BO = Binary Output 22 25 24 26 BI 8 IL3 (I C) BI 9 14 15 28 BI 30 BI 20 21 B 12 13 27 25 1A 10 11 19 BO 6 8 9 28 BI 5 6 7 17 BO 5 4 5 13 BO 4 1A 5A 27 +ve 15 Term. 2 -ve 11 +ve A 20 9 BI 1 +ve 14 28 +ve 7 +ve -ve 27 1 +ve -ve Data Comms (Optional) Rear View Arrangement of terminals and modules 27 BI 17 -ve 2 B 23 BO 2 2 1 C BO 16 3 28 2 D 14 22 1 E BO 15 +ve -ve 2 19 BI 15 BI 18 26 1 13 +ve -ve 2 9 +ve +ve 1 5 +ve BI 12 2 1 +ve -ve 1 I4 (IG/ISEF) A BO 8 -ve 28 27 19 17 23 21 Shows contacts internal to relay case assembly. Contacts close when the relay chassis is withdrawn from case Figure 1.5-2 Connections Diagram for 7SR21 Relay Unrestricted (c)2018 Siemens Protection Devices Limited Page 11 of 94 7SR210 & 7SR220 Description of Operation Table 1.5-2 Ordering Information - 7SR22 Directional Overcurrent Product description Variants Order No. 7 S R 2 Protection Product Family Overcurrent - Directional 2 0 - 2 A - 0 A 0 2 Relay Type 0 1) Case, I/O and Fascia E6 case, 5 CT, 4 VT, 3 Binary Inputs, 6 Binary Outputs, 8 LEDs E8 case, 5 CT, 4 VT, 13 Binary Inputs, 14 Binary Outputs, 16 LEDs E8 case, 5 CT, 4 VT, 13 Binary Inputs, 14 Binary Outputs, 8 LEDs + 6 keys E12 case, 5 CT, 4 VT, 33 Binary Inputs / 14 Binary Outputs, 32 LEDs E12 case, 5 CT, 4 VT, 33 Binary Inputs / 14 Binary Outputs, 16 LEDs, 12 keys 2 3 4 5 6 C Measuring input 1 A or 5 A, 40 V to 160 V, 50 Hz or 60 Hz 2 Auxiliary voltage PSU Rated: 30 to 220V DC. Binary Input threshold 19V DC (Rated: 24-250V DC) PSU Rated: 30 to 220V DC. Binary Input threshold 88V DC (Rated: 110-250V DC) PSU Rated: 24-250V DC / 100-230V AC. Binary Input threshold 19V DC (Rated: 24-250V DC) PSU Rated: 24-250V DC / 100-230V AC. Binary Input threshold 88V DC (Rated: 110-250V DC) A B M N Spare A Communication Interface Standard version - included in all models, USB front port, RS485 rear port Standard version - plus additional rear F/O ST connectors (x2) and IRIG-B Standard version - plus additional rear RS485 and IRIG-B Standard version - plus additional rear RS232 and IRIG-B Standard version - plus additional rear Electrical Ethernet RJ45 (x2) Standard version - plus additional rear Optical Ethernet Duplex (x2) Protocol IEC 60870-5-103 and Modbus RTU (user selectable) IEC 60870-5-103 and Modbus RTU and DNP 3.0 (user selectable) IEC 60870-5-103 and Modbus RTU and DNP 3.0 (user selectable) and IEC61850 1 2 3 4 7 8 7 7 7-8 1 2 7 Spare 0 Protection Function Packages Standard version - included in all models 21FL Fault Locator 21LB Load Blinder 1) Under/overvoltage 27/59 32 Power 32S Sensitive Power 37 Undercurrent Ground Undercurrent 37G1) 1) SEF Undercurrent 37SEF 46BC Broken conductor/load unbalance 46NPS Negative phase sequence overcurrent 1) Negative phase sequence voltage 47 49 Thermal overload 50 Instantaneous phase fault overcurrent 50BF Circuit breaker fail 50G/50N Instantaneous earth fault 50 AFD Arc Flash Detector 51V Voltage dependent overcurrent 55 Power factor 59N Neutral voltage displacement 60CTS CT supervision 60CTS-I CT supervision 60VTS VT supervision 64H High impedance REF 67/50 Directional instantaneous phase fault overcurrent 67/50G Directional instantaneous earth fault/SEF 67/50N 67/51 Directional time delayed phase fault overcurrent 67/51G Directional tIme delayed earth fault/SEF 67/51N Trip & close circuit supervision Under/overfrequency Inrush Detector Overfluxing Lockout Cold load pickup Programmable logic CB Control Standard version - plus 79 Autoreclose Standard version - plus 79 + 25 Autoreclose + Check Sync C 74TC/CCS 81 81HBL2 81HBL5 86 Additional Functionality No additional functionality D E A Spare 0 1) 5CT is configured as 3PF + EF/SEF + EF/SEF (user selectable setting). Export Data HS: 8536900 ECCN: N AL: N Unrestricted Page 12 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) I4 (IG) I5 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 46 BC 46 NPS (x2) 60 CTS 60 VTS 67/ 50/51N (x4) 51c 81 HBL 2/5N 37G (x2) 37 50 BF 67/ 50/51G (x4) 37 50 BF 67/ 50/51S (x4) (ISEF) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 47 (x2) 32 81 (x6) 59N (x2) 32S 21FL 74 TCS 79 Figure 1.5-3 55 25 Optional Functional Diagram of 7SR22 Relay Unrestricted (c)2018 Siemens Protection Devices Limited Page 13 of 94 7SR210 & 7SR220 Description of Operation 2 4 6 8 10 12 14 7SR22 +ve -ve BI 4 BO 7 BI 5 BO 8 BI 6 BO 9 BI 7 BO 10 -ve 18 20 22 5 26 28 9 13 22 24 28 BO 11 17 BO 12 19 4 +ve BI 10 6 8 10 12 Optional I/O Optional I/O PSU Analogue Blank 27 28 2 4 6 10 BI 13 12 C 1 +ve 3 GND. 5 B Term. BO 3 BI 2 5A 27 28 27 28 27 28 27 28 22 24 19 21 BO 5 26 28 +ve +ve -ve BI 24 BI 14 +ve -ve +ve BI 15 BI 25 +ve BI 16 BI 26 BI 17 BI 27 BI 18 BI 28 BI 19 BI 29 +ve +ve +ve +ve +ve +ve -ve +ve BI 20 BI 30 BI 21 BI 31 BI 22 BI 32 +ve +ve +ve +ve +ve -ve -ve +ve +ve -ve -ve +ve BI 23 D BI 33 -ve 1 3 5 7 9 11 13 15 17 19 21 23 25 27 23 25 BO 6 26 B 27 1A (ISEF) 17 18 I5 IL1 (I A) 5A 19 20 1A 6 7 20 17 BO 4 BI 3 4 5 18 13 15 1A 2 3 11 +ve 20 16 9 BI 1 +ve 18 1 7 +ve Screen 14 BO 1 -ve 16 Data Comms (Optional) Rear View Arrangement of terminals and modules 27 +ve A 2 A 25 BI 12 14 1 B 23 +ve -ve 2 C BO 14 BI 11 -ve 1 D BO 13 +ve -ve 2 21 BI 9 BO 2 2 1 15 +ve -ve 2 E 8 24 1 11 +ve -ve 2 7 +ve +ve 1 3 +ve BI 8 16 1 5A IL2 (I B) VL1 (VA) 21 VL2 (VB) 23 VL3 (VC) 25 22 8 9 1A 10 11 5A IL3 (IC) 12 13 1A 14 15 5A I4 (I G) A 16 V4 (VX) 24 26 27 28 NOTES BI = Binary Input BO = Binary Output Shows contacts internal to relay case assembly. Contacts close when the relay chassis is withdrawn from case Figure 1.5-4 Unrestricted Page 14 of 94 Connection Diagram for 7SR22 Relay (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Section 2: Hardware Description 2.1 General The structure of the relay is based upon the Multi-function hardware platform. The relays are supplied in either size E6 or size E8 cases (where 1 x E = width of 26 mm). The hardware design provides commonality between products and components across the Multi-function range of relays. Table 2.1-1 Relay Summary of Overcurrent Relay Configurations Current Voltage Binary Output Inputs Inputs Inputs Relays LEDs Function Case Keys 7SR2102 4 9 8 8 E6 7SR2103 4 19 16 16 E8 7SR2104 4 19 16 8 7SR2105 4 39 16 32 7SR2106 4 39 16 16 7SR2202 5 4 3 6 8 E6 7SR2203 5 4 13 14 16 E8 7SR2204 5 4 13 14 8 7SR2205 5 4 33 14 32 7SR2206 5 4 33 14 16 6 E8 E12 12 6 E12 E8 E12 12 E12 Relays are assembled from the following modules: 1. Front Fascia with three fixed function LEDs and ordering options of configurable LEDs/Function Keys. 2. Processor module 3. Analogue Input module, either * 4 x Current + 6 x Binary Inputs + 2 x Binary Outputs (7SR21), or * 5 x Current + 4 x Voltage (7SR22). 4. Power Supply and 3 x Binary Inputs (BI) and 6 x Binary Outputs (BO). 5. Optional Binary Input/Output Module 6. * 10 x Binary Inputs + 8 x Binary Outputs * 20 x Binary Inputs Optional Communications Module (2x rear fibre optic + 1x IRIG-B ports), (1x rear RS485 + 1x IRIG-B port), (1x rear RS232 + 1x IRIG-B port), (2x Electrical Ethernet for IEC 61850), (2x Optical Ethernet for IEC 61850). Unrestricted (c)2018 Siemens Protection Devices Limited Page 15 of 94 7SR210 & 7SR220 Description of Operation 2.2 Case The relays are housed in cases designed to fit directly into standard panel racks. The three case options have widths of 156 mm (E6), 208 mm (E8) and 304 mm (E12), with a height of 177 mm (4U). The required panel depth (with wiring clearance) is 242 mm. An additional 75 mm depth clearance should be allowed to accommodate the bending radius of fibre optic data communications cables if fitted. Relays with IEC 61850 communications option require a depth of 261.5 mm to allow for the communication module and a clearance from devices fitted below the relay of 75 mm to accommodate fitment of the Ethernet cables. The complete relay assembly is withdrawable from the front of the case. Contacts in the case ensure that the CT circuits remain short-circuited when the relay is removed. For the IEC 61850 variant options the rear retaining screw must be re-fitted following re-insertion to ensure relay performance claims. The rear terminal blocks comprise M4 female terminals for wire connections. Each terminal can accept two 4 mm crimps. Located at the top rear of the case is a screw-clamp earthing point, this must be connected to the main panel earth. 2.3 Front Cover With the transparent front cover in place the user only has access to the and TEST/RESET buttons, via blue push buttons, allowing all areas of the menu system to be viewed, but preventing setting changes and control actions. The only `action' that is permitted is to reset the Fault Data display, latched binary outputs and LEDs by using the TEST/RESET 4 button. The front cover is used to secure the relay assembly in the case. 2.4 Power Supply Unit (PSU) The relay PSU can be directly connected to any substation dc system rated from 24 V dc to 250 V dc / 100 V ac to 230 V ac. In the event of the station battery voltage level falling below the relay minimum operating level, the PSU will automatically switch itself off and latch out - this prevents any PSU overload conditions occurring. The PSU is reset by switching the auxiliary supply off and on. Typically the PSU is connected to the auxiliary supply via an external HRC fuse rated at 6A (BS88/IEC60259). Isolation links may also be installed in accordance with user requirements. 2.5 Operator Interface/ Fascia The operator interface is designed to provide a user-friendly method of controlling, entering settings and retrieving data from the relay. The warning and information labels on the relay fascia provide the following information: Dielectric Test Voltage 2kV Impulse Test Above 5kV Caution: Refer to Equipment Documentation Caution: Risk of Electric Shock Unrestricted Page 16 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Figure 2.5-1 Figure 2.5-2 Figure 2.5-3 7SR21 with 3 + 8 LEDs in E6 Case 7SR220 with 3 + 16 LEDs in E8 Case 7SR22 with Function Keys and 3 + 8 LEDs in E8 Case NOTE: Pushbuttons on cover not shown Unrestricted (c)2018 Siemens Protection Devices Limited Page 17 of 94 7SR210 & 7SR220 Description of Operation The fascia is an integral part of the relay. Handles are located at each side of the element to allow it to be withdrawn from the relay case. Figure 2.5-4 7SR22 with Function Keys & 3 + 8 LEDs in E8 Case and Ethernet Communication Interface Relay Information Above the LCD three labels are provided, these provide the following information: 1) Product name and order code. 2) Nominal current rating, rated frequency, voltage rating, auxiliary dc supply rating, binary input supply rating, configuration and serial number. 3) Blank label for user defined information. A `template' is available to allow users to create and print customised labels. Liquid Crystal Display (LCD) A 4-line by 20-character liquid crystal display indicates settings, instrumentation, fault data and control commands. To conserve power the display backlighting is extinguished when no buttons are pressed for a user defined period. A setting within the "SYSTEM CONFIG" menu allows the timeout to be adjusted from 1 to 60 minutes and "Off" (backlight permanently on). Pressing any key will re-activate the display. The LCD contrast can be adjusted using a flat blade screwdriver to turn the screw located below the contrast symbol . Turning the screw clockwise increases the contrast, anti-clockwise reduces the contrast. User defined indentifying text can be programmed into the relay using the System config/Relay Identifier setting. The `Relay Identifier' text is displayed on the LCD display at the top level of the menu structure and is used in communication with Reydisp to identify the relay. Pressing the Cancel button several times will always return the user to this screen. `PROTECTION HEALTHY' LED This green LED is steadily illuminated to indicate that DC voltage has been applied to the relay power supply and that the relay is operating correctly. If the internal relay watchdog detects an internal fault then this LED will continuously flash. Unrestricted Page 18 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation `PICKUP' LED This yellow LED is illuminated to indicate that a user selectable function(s) has picked up. The LED will self reset after the initiating condition has been removed. The same LED can be assigned two different colours dependent upon whether a Pickup (PU) or Operate condition exists. Functions are assigned to the PICKUP LED in the OUTPUT CONFIG>PICKUP CONFIG menu. `TRIP' LED This red LED is steadily illuminated to indicate that a user selectable function has operated to trip the circuit breaker. Functions are assigned to the `Trip' LED using the OUTPUT CONFIG>Trip Contacts setting. Operation of the LED is latched and can be reset by either pressing the TEST/RESET button, energising a suitably programmed binary input, or, by sending an appropriate command over the data communications channel(s). Indication LEDs (Numbered 1 to 8, 1 to 16 or 1 to 32) Relays have either 8, 16 or 32 user programmable Tri-colour (red, green or yellow) LED indicators, depending upon the variant ordered. They are configured via the menu: Settings\ Output Config\LED Config menu or LED tab in Reydisp Evolution. They can be designated as either: Pick-Up (PU) LEDs (they respond upon the detection of a condition i.e. overcurrent detection), or Operation LEDs (they respond to the action of a condition i.e. CB trip operation). Configuration options are: Self Reset LEDs - automatically reset upon loss of initiating condition. PU Self Reset LEDs - automatically reset upon loss of initiating condition Green LEDs - illuminate green Red LEDs - illuminate red Yellow LEDs - illuminate yellow (when both red and green are selected) PU Green LEDs - illuminate green in response to the detection of a condition PU Red LEDs - illuminate red in response to the detection of a condition Colour selection is achieved by checking (ticking) the appropriate box i.e. red or green. To select yellow, check both red & green boxes. Functions are assigned to the LEDs in the OUTPUT CONFIG>OUTPUT MATRIX menu. Each LED can be labelled by withdrawing the relay and inserting a label strip into the pocket behind the front fascia. A `template' is available to allow users to create and print customised legends. This can be found in: Reydisp Evolution\Help\Open Relay LED Template\Open RM LED Template Each LED can be user programmed as hand or self -resetting. Hand reset LEDs can be reset by either pressing the TEST/RESET button, energising a suitably programmed binary input, or, by sending an appropriate command over the data communications channel(s). The status of hand reset LEDs is maintained by a back up storage capacitor in the event of an interruption to the d.c. supply voltage. Standard Pushbuttons The relay is supplied as standard with five pushbuttons. The buttons are used to navigate the menu structure and control relay functions. They are labelled: Increases a setting or moves up menu. Decreases a setting or moves down menu. TEST/RESET Moves right, can be used to reset selected functionality and for LED test (at relay identifier screen). ENTER Used to initiate and accept settings changes. CANCEL Used to cancel settings changes and/or move up the menu structure by one level per press. NOTE: All settings and configuration of LEDs, BI, BO and function keys can be accessed and set by the user using these keys. Alternatively configuration/settings files can be loaded into the relay using `Reydisp Evolution'. Unrestricted (c)2018 Siemens Protection Devices Limited Page 19 of 94 7SR210 & 7SR220 Description of Operation Function Keys/ LEDs (Ordering Option) Six additional programmable pushbuttons can be specified. These can be configured by the user to initiate selected functions from the Control menu (INPUT CONFIG > FUNCTION KEY MATRIX). Each pushbutton has an associated LED. LEDs can be programmed as hand or self reset and can be illuminated as green, yellow or red (OUTPUT CONFIG > LED CONFIG). Function keys can be used with Quick Logic. Unrestricted Page 20 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 2.6 Current Inputs Four current inputs are provided in the 7SR21 relay and five inputs are provided in the 7SR22 relay. Current inputs are located on the Analogue Input module. Terminals are available for both 1 A and 5 A inputs. Current is sampled at 1600 Hz for both 50 Hz and 60 Hz system frequencies. Protection and monitoring functions of the relay use either the Fundamental Frequency RMS or the True RMS value of current appropriate to the individual function. The waveform recorder samples and displays current input waveforms at 1600 Hz. NB: The Relay has a flat frequency response measuring harmonic currents up to and including the 50th Harmonic but does not measure the content at the aliasing frequencies i.e. 800 Hz (16th harmonic) + 1600 Hz (32nd harmonic) + 2400 Hz (48th harmonic). 2.7 Voltage Inputs Four voltage inputs are provided in the 7SR22 relay. Voltage inputs are located on the Analogue Input module. Voltage is sampled at 1600 Hz for both 50 Hz and 60 Hz system frequencies. Protection and monitoring functions of the relay use fundamental frequency voltage measurement. The waveform recorder samples and displays voltage input waveforms at 1600 Hz. 2.8 Binary Inputs The binary inputs are operated from a suitably rated dc supply. Relays are fitted with 3, 9, 13, 19, 33 or 39 binary inputs (BI). The user can assign any binary input to any of the available functions (INPUT CONFIG > INPUT MATRIX). The Power Supply module includes the relay basic I/O. The module includes 3 x BI and 6 x BO. Non-directional (7SR21) relays have an additional 6 x BI on the analogue module. Additional I/O modules may be fitted, these provide 10 x BI. Pick-up (PU) and drop-off (DO) time delays are associated with each binary input. Where no pick-up time delay has been applied the input may pick up due to induced ac voltage on the wiring connections (e.g. cross site wiring). The default pick-up time of 20 ms provides ac immunity. Each input can be programmed independently. Each input may be logically inverted to facilitate integration of the relay within the user scheme. When inverted the relay indicates that the BI is energised when no d.c. is applied. Inversion occurs before the PU & DO time delay, see fig. 2.8-1. Each input may be mapped to any front Fascia indication LED and/or to any Binary output contact and can also be used with the internal user programmable logic. This allows the relay to provide panel indications and alarms. The binary inputs are sampled every 5 ms. Figure 2.8-1 Binary Input Logic Unrestricted (c)2018 Siemens Protection Devices Limited Page 21 of 94 7SR210 & 7SR220 Description of Operation 2.9 Binary Outputs (Output Relays) Relays are fitted with 6, 8, 14 or 16 binary outputs (BO). All outputs are fully user configurable and can be programmed to operate from any or all of the available functions. The Power Supply module includes the relay basic 6 x BO contacts configured as 1 x normally closed (NC), 2 x change-over (CO) and 3 x normally open (NO) contacts. Non-directional (7SR21) relays have two additional binary outputs providing 2 x NO contacts on the analogue module. Additional I/O modules may be fitted providing an extra 8 x NO contacts. In the default mode of operation binary outputs are self reset and remain energised for a user configurable minimum time of up to 60 seconds. If required, outputs can be programmed to operate as `hand reset' or `pulsed'. If the output relay is programmed to be `hand reset' and `pulsed' then the output will be `hand reset' only. The binary outputs can be used to operate the trip coils of the circuit breaker directly where the trip coil current does not exceed the 'make and carry' contact rating. The circuit breaker auxiliary contacts or other in-series auxiliary device must be used to break the trip coil current. Any BO can be assigned as a `Trip Contact' in the OUTPUT CONFIG>TRIP CONFIG menu. Operation of a `Trip Contact' will operate any LED or virtual assigned from the trip triggered feature in the same menu and will initiate the fault record storage, actuate the `Trip Alert' screen where enabled and CB Fail protection when enabled. When the relay is withdrawn from the case all normally closed contacts will be open circuited. This should be considered in the design of the control and protection circuitry. Notes on Pulsed Outputs When operated, the output will reset after a user configurable time of up to 60 seconds regardless of the initiating condition. Notes on Self Reset Outputs Self reset operation has a minimum reset time of 100 ms. With a failed breaker condition the relay may remain operated until current flow is interrupted by an upstream device. When the current is removed the relay will then reset and attempt to interrupt trip coil current flowing via its output contact. Where this current level is above the break rating of the output contact an auxiliary relay with heavy-duty contacts should be utilised in the primary system to avoid damage to the relay. Notes on Hand Reset Outputs Hand reset outputs can be reset by either pressing the TEST/RESET button, by energising a suitably programmed binary input, or, by sending an appropriate command over the data communications channel(s). On loss of the auxiliary supply hand-reset outputs will reset. When the auxiliary supply is re-established the binary output will remain in the reset state unless the initiating condition is still present. Logic signals, e.g. '51-1' Reset LEDs & Outputs (TEST/RESET key, Binary Input, Data Comms) BO 1 S R Hand Reset 1 Min Operate Time OUTPUT CONFIG> OUTPUT MATRIX Event & & BO 1 hand reset Output 1 Q & 1 (Or gates) OUTPUT CONFIG> BINARY OUTPUT CONFIG OUTPUT CONFIG> BINARY OUTPUT CONFIG BO n S R Event & & BO n hand reset Output n Q 1 1 & Figure 2.9-1 Binary Output Logic Unrestricted Page 22 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 2.10 Virtual Input/Outputs The relays have 16 virtual input/outputs, these are internal logic states. Virtual I/O is assigned in the same way as physical Binary Inputs and Binary Outputs. Virtual I/O is mapped from within the INPUT CONFIG > INPUT MATRIX and OUTPUT CONFIG > OUTPUT MATRIX menus. The status of the virtual inputs and outputs is volatile i.e. not stored during power loss. 2.11 Self Monitoring The relay incorporates a number of self-monitoring features. Each of these features can initiate a controlled reset recovery sequence. Supervision includes a power supply watchdog, code execution watchdog, memory checks by checksum and processor/ADC health checks. When all checks indicate the relay is operating correctly the `Protection Healthy' LED is illuminated. If an internal failure is detected, a message will be displayed. The relay will reset in an attempt to rectify the failure. This will result in de-energisation of any binary output mapped to `protection healthy' and flashing of the protection healthy LED. If a successful reset is achieved by the relay the LED and output contact will revert back to normal operational mode, and the relay will restart, therefore ensuring the circuit is protected for the maximum time. A Start-up Counter Meter is provided to display the number of start-ups the relay has performed. Once the number of start-ups has exceeded a set number, an Alarm output can be given. Figure 2.11-1 Start-up Counter Meter Reset of the counter can be done from the meter or via a binary input or a command. Various types of start-up are monitored by the relay: 1. power-on starts (auxiliary supply initiation) 2. expected starts (user initiated via comms, language changes, custom protection curve etc.) 3. unexpected starts (caused by the relay watchdog) Any combination of these can be selected for the start-up count. This is done in the MAINTENANCE MENU>START COUNT menu using the Start Up Types setting. All the start-up types selected will be added to the overall start-up count. The number of restarts before the alarm output is raised is set in the MAINTENANCE MENU>START COUNT menu using the Start Up Count Target setting. When the number of relay start-ups reaches the target value an output is raised, OUTPUT MATRIX>Start Up Count Alarm, which can be programmed to any combination of binary outputs, LED's or virtual outputs. As a further safeguard, if the Relay performs a number of unexpected starts SYSTEM CONFIG>Unexpected Restart Count in a given time SYSTEM CONFIG>Unexpected Restart Period, it can be configured using the SYSTEM CONFIG>Unexpected Restart Blocking setting to remove itself from service. In this case the Relay will display a typical error message such as: - Figure 2.11-2 Start-up Counter Meter Unrestricted (c)2018 Siemens Protection Devices Limited Page 23 of 94 7SR210 & 7SR220 Description of Operation The relay will enter a locked-out mode, while in this mode it will disable operation of all LED's, Binary Outputs, including Protection Healthy, pushbuttons and any data communications activity. Once the Relay has failed in this manner, it is non-recoverable at site and must be returned to the manufacturer for repair. A meter, Miscellaneous Meters>Unexpected Restarts, is provided to show how many Unexpected Restarts have occurred during the previous Unexpected Restart Period. This is resettable from the front fascia. The following screen-shot shows the events, which are generated when the relay re-starts. The highlighted events show the cause of the re-start. The event which comes next shows the type of restart followed by the relay: Warm, Cold or Re-Start. Figure 2.11-3 Start-up Counter Meter Events 2.11.1 Protection Healthy/Defective When the relay has an auxiliary DC supply and it has successfully passed its self-checking procedure then the front facia Protection Healthy LED is turned on. A normally open contact can be used to signal protection healthy. When the relay has DC supply and it has successfully passed its self-checking procedure then the Protection Healthy contacts are made. A changeover or normally closed contact can be mapped via the binary output matrix to provide an external protection defective signal. With the `Protection Healthy' this contact is open. When the auxiliary DC supply is not applied to the relay or a problem is detected within the relay then this output contact closes to provide external indication. An alarm can be provided if the relay is withdrawn from the case. A contact is provided in the case at positions 25-26 of the PSU module, this contact closes when the relay is withdrawn. Unrestricted Page 24 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Section 3: Protection Functions 3.1 Current Protection: Phase Overcurrent (67, 51, 50) All phase overcurrent elements can be set to measure either fundamental frequency RMS or True RMS current i.e. True RMS current: - 50 Measurement = RMS 51 Measurement = RMS Fundamental Frequency RMS current: - 50 Measurement = Fundamental 51 Measurement = Fundamental 3.1.1 Directional Control of Overcurrent Protection (67) - 7SR22 The directional element produces forward and reverse outputs for use with overcurrent elements. These outputs can then be mapped as controls to each shaped and instantaneous over-current element. If a protection element is set as non-directional then it will operate independently of the output of the directional detector. However, if a protection element is programmed for forward directional mode then operation will occur only for a fault lying within the forward operate zone. Conversely, if a protection element is programmed for reverse directional mode then operation will occur only for a fault lying within the reverse operate zone. Typically the forward direction is defined as being `away' from the busbar or towards the protected zone. The Characteristic angle is the phase angle by which the polarising voltage must be adjusted such that the directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it. The reverse operate zone is the mirror image of the forward zone. Voltage polarisation is achieved for the phase-fault elements using the quadrature voltage i.e. at unity power factor I leads V by 90. Each phase current is compared to the voltage between the other two phases: IL1 ~ V23 IL2 ~ V31 IL3 ~ V12 The characteristic angle can be user programmed to any angle between -95 and +95 using the 67 Char Angle setting. The voltage is the reference phasor (Vref) and the 67 Char Angle setting is added to this to adjust the forward and reverse zones. The centre of the forward zone is set by (Vref Angle + 67 Char Angle) and should be set to correspond with Ifault Angle for maximum sensitivity i.e. For fault current of -60 (I lagging V by 60) a 67 Char Angle of +30 is required for maximum sensitivity (i.e. due to quadrature connection 90 - 60 = 30) OR For fault current of -45 (I lagging V by 45) a 67 Char Angle of +45 is required for maximum sensitivity (i.e. due to quadrature connection 90 - 45 = 45). Two-out-of-three Gate When the 67 2-Out-Of-3 Logic setting is set to Enabled, the directional elements will only operate for the majority direction, e.g. if IL1 and IL3 are detected as forward flowing currents and IL2 is detected as reverse current flow, phases L1 and L3 will operate forwards, while phase L2 will be inhibited. Unrestricted (c)2018 Siemens Protection Devices Limited Page 25 of 94 7SR210 & 7SR220 Description of Operation Minimum Polarising Voltage The 67 Minimum Voltage setting defines the minimum polarising voltage level. Where the measured polarising voltage is below this level no directional output is given and operation of protection elements set as directional will be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise voltages can be present. Figure 3.1.1-1 Unrestricted Page 26 of 94 Logic Diagram: Directional Overcurrent Element (67) (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.1.2 Instantaneous Overcurrent Protection (50) Two instantaneous overcurrent elements are provided in the 7SR21 relay. Four elements are provided in the 7SR22 e.g. giving the option of using two elements set to forward and two to reverse. Each instantaneous element (50-n) has independent settings. 50-n Setting for pick-up current and 50-n Delay follower time delay. The instantaneous elements have transient free operation. Where directional elements are present the direction of operation can be set using 50-n Dir. Control setting. Directional logic is provided independently for each 50-n element. Operation of the instantaneous overcurrent elements can be inhibited from: Inhibit 50-n A binary input, virtual input, function key or remote data Comms. 79 P/F Inst Trips: 50-n When `delayed' trips only are allowed in the auto-reclose sequence (79 P/F Prot'n Trip n = Delayed). 50-n Inrush Action: Inhibit Operation of the inrush current detector function. 50-n VTS Action: Inhibit Operation of the VT Supervision function (7SR22). Figure 3.1.2-1 Logic Diagram: Instantaneous Over-current Element Unrestricted (c)2018 Siemens Protection Devices Limited Page 27 of 94 7SR210 & 7SR220 Description of Operation 3.1.3 Time Delayed Overcurrent Protection (51) Two time delayed overcurrent elements are provided in the 7SR21 relay. Four elements are provided in the 7SR22 relay e.g. giving the option of using two elements set to forward and two to reverse. 51-n Setting sets the pick-up current level. Where the voltage controlled overcurrent function (51VCO) is used (7SR22 relays only) a multiplier is applied to this setting where the voltage drops below the setting VCO Setting, see section 3.2. A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is selected from IEC and ANSI curves using 51-n Char. A time multiplier is applied to the characteristic curves using the 51-n Time Mult setting. Alternatively, a definite time lag delay (DTL) can be chosen using 51-n Char. When Delay (DTL) is selected the time multiplier is not applied and the 51-n Delay (DTL) setting is used instead. The 51-n Reset setting can apply a definite time delayed reset, or when configured as an ANSI characteristic an ANSI (DECAYING) reset. If ANSI (DECAYING) reset is selected for an IEC characteristic, the reset will be instantaneous. The reset mode is significant where the characteristic has reset before issuing a trip output - see `Applications Guide'. A minimum operate time for the characteristic can be set using 51-n Min. Operate Time setting. A fixed additional operate time can be added to the characteristic using 51-n Follower DTL setting. Where directional elements are present the direction of operation can be set using 51-n Dir. Control setting. Directional logic is provided independently for each 51-n element. Operation of the time delayed overcurrent elements can be inhibited from: Inhibit 51-n A binary input, virtual input, function key or remote data Comms 79 P/F Inst Trips: 51-n When `delayed' trips only are allowed in the auto-reclose sequence (79 P/F Prot'n Trip n = Delayed). 51c Activation of the cold load settings (see section 3.7). 51-n Inrush Action: Inhibit Operation of the inrush current detector function. 51-n VTSAction: Inhibit Operation of the VT Supervision function (7SR22). Unrestricted Page 28 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation L1 L2 L3 See Voltage Controlled Overcurrent (51V) 51-n Element Enabled Disabled AUTORECLOSE 79 P/F Inst Trips = 51-n 79 P/F Prot'n Trip n = Delayed 51-n Setting 51-n Charact & Inhibit 51-n 51-n Time Mult & 51-n Delay (DTL) 51-n Min. Operate Time Inhibit 51-n 51-n Follower DTL 51c 51-n Inrush Action L1 81HBL2 51-n Reset c & L1 Dir En & c Off General Pickup 1 Pickup General Pickup trip Inhibit L2 81HBL2 & L2 Dir En & c Pickup NB: For a comprehensive list of input & output signals see Data Comms Definitions trip L3 81HBL2 & L3 Dir En & c 1 Pickup trip 51-n 51-n 50/51 Measurement IL1 IL2 IL3 51-n Dir Control 51-n VTS Action Non-Dir Off Forward Non Dir Reverse Inhibit If directional elements are not present this block is omitted and all 'Lx Dir En' signals are set TRUE. & & 60VTS & IL1 Fwd 1 & & IL1 Rev & IL2 Fwd & IL3 Fwd & IL3 Rev Figure 3.1.3-1 L1 Dir En 1 & & IL2 Rev 1 1 L2 Dir En 1 & 1 L3 Dir En Logic Diagram: Time Delayed Overcurrent Element Unrestricted (c)2018 Siemens Protection Devices Limited Page 29 of 94 7SR210 & 7SR220 Description of Operation 3.2 Current Protection: Voltage Controlled Overcurrent (51V) - 7SR22 Voltage controlled overcurrent is available in the 7SR22 relay. Each shaped overcurrent element 51-n Setting can be independently controlled by the level of measured (control) input voltage. For applied voltages above VCO Setting the 51-n element operates in accordance with its normal current setting (see 3.1.3). For input Ph-Ph control voltages below VCO Setting a multiplier (51-n Multiplier) is applied to reduce the 51-n pickup current setting. 51-n Multiplier is applied to each phase independently when its control phase-phase voltage falls below VCO Setting. The voltage levels used for each phase over-current element are shown in the table below. Relays with a Ph-N connection automatically calculate the correct Ph-Ph control voltage. Current Element Control Voltage IL1 V12 IL2 V23 IL3 V31 The Voltage Controlled Overcurrent function (51V) can be inhibited from: VCO VTSAction: Inhibit Operation of the VT Supervision function. 51V Element Enabled Disabled 51V VTS Action Off Inhibit & & VT Fail 51V Setting c VL1 VL2 VL3 V12 V23 V31 51-n Multiplier c < < < c x IL1 51-n Setting c x IL2 51-n Setting c x IL3 51-n Setting L1 L2 L3 See Delayed Overcurrent (51-n) Figure 3.2-1 Logic Diagram: Voltage Controlled Overcurrent Protection Unrestricted Page 30 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.3 Current Protection: Derived Earth Fault (67N, 51N, 50N) The earth current is derived by calculating the sum of the measured line currents. The elements measure the fundamental frequency RMS current. 3.3.1 Directional Control of Derived Earth Fault Protection (67N) - 7SR22 The directional element produces forward and reverse outputs for use with derived earth fault elements. These outputs can be mapped as controls to each shaped and instantaneous element. If a protection element is set as non-directional then it will operate independently of the output of the directional detector. However, if a protection element is programmed for forward directional mode then operation will occur only for a fault lying within the forward operate zone. Conversely, if a protection element is programmed for reverse directional mode then operation will occur only for a fault lying within the reverse operate zone. Typically the forward direction is defined as being `away' from the busbar or towards the protected zone. The Characteristic angle is the phase angle by which the polarising voltage must be adjusted such that the directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it. The reverse operate zone is the mirror image of the forward zone. The derived directional earth fault elements can use either zero phase sequence (ZPS) or negative phase sequence (NPS) polarising. This is selected using the 67N Polarising Quantity setting. Whenever a zerosequence voltage is available (a five-limb VT that can provide a zero sequence path or an open-delta VT connection) the earth-fault element can use zero-sequence voltage and current for polarisation. If zero-sequence polarising voltage is not available e.g. when a two phase (phase to phase) connected VT is installed, then negative-sequence voltage and negative-sequence currents must be used. The type of VT connection is specified by Voltage Config (CT/VT CONFIG menu). Settings advice is given in the Applications Guide. Voltage polarisation is achieved for the earth-fault elements by comparison of the appropriate current with its equivalent voltage: 67N Polarising Quantity: ZPS I0 ~ V0 67N Polarising Quantity: NPS I2 ~ V2 The characteristic angle can be user programmed to any angle between -95 and +95 using the 67N Char Angle setting. The voltage is the reference phasor (Vref) and the 67N Char Angle setting is added to this to adjust the forward and reverse zones. The centre of the forward zone is set by (Vref Angle + 67N Char Angle) and should be set to correspond with Ifault Angle for maximum sensitivity e.g. For fault current of -15 (I lagging V by 15) a 67N Char Angle of -15 is required for maximum sensitivity OR For fault current of -45 (I lagging V by 45) a 67 Char Angle of -45 is required for maximum sensitivity. Unrestricted (c)2018 Siemens Protection Devices Limited Page 31 of 94 7SR210 & 7SR220 Description of Operation Minimum Polarising Voltage The 67N Minimum Voltage setting defines the minimum polarising voltage level. Where the measured polarising voltage is below this level no directional output is given and operation of protection elements set as directional will be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise voltages can be present. Figure 3.3.1-1 3.3.2 Logic Diagram: Derived Directional Earth Fault Element Instantaneous Derived Earth Fault Protection (50N) Two instantaneous derived earth fault elements are provided in the 7SR21 relay. Four elements are provided in the 7SR22 relay e.g. giving the option of using two elements set to forward and two to reverse. Each instantaneous element has independent settings for pick-up current 50N-n Setting and a follower time delay 50N-n Delay. The instantaneous elements have transient free operation. Where directional elements are present the direction of operation can be set using 50N-n Dir. Control setting. Directional logic is provided independently for each 50-n element. Operation of the instantaneous earth fault elements can be inhibited from: Inhibit 50N-n A binary input, virtual input, function key or remote data Comms. 79 E/F Inst Trips: 50N-n When `delayed' trips only are allowed in the auto-reclose sequence (79 E/F Prot'n Trip n = Delayed). 50N-n VTSAction: Inhibit Operation of the VT Supervision function (7SR22). 50N-n Inrush Action: Inhibit Operation of the current inrush detector function. Unrestricted Page 32 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 50N-n Element Disabled Enabled 50N-n Inrush Action Inhibit 50N-n Off Inhibit 50N-n Inhibit & & General Pickup 81HBL2 General Pickup AUTORECLOSE 79 P/F Inst Trips = 50N-n 79 P/F Prot'n Trip n = Delayed 50N-n Setting 50N-n Dir En & 50N-n Delay c IL1 > IN IL2 50N-n 50N-n IL3 If directional elements are not present this block is omitted and the '50N-n Dir En' signal is set TRUE. 50N-n VTS Action 50N-n Dir Off Non Dir Non-Dir Inhibit Forward Reverse & & VT Fail 1 67N Fwd 67N Rev Figure 3.3.2-1 3.3.3 & 50N-n Dir En & 1 & Logic Diagram: Derived Instantaneous Earth Fault Element Time Delayed Derived Earth Fault Protection (51N) Two time-delayed derived earth fault elements are provided in the 7SR21 relay. Four elements are provided in the 7SR22 relay e.g. giving the option of using two elements set to forward and two to reverse. 51N-n Setting sets the pick-up current level. A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is selected from IEC and ANSI curves using 51N-n Char. A time multiplier is applied to the characteristic curves using the 51N-n Time Mult setting. Alternatively, a definite time lag delay (DTL) can be chosen using 51N-n Char. When Delay (DTL) is selected the time multiplier is not applied and the 51N-n Delay (DTL) setting is used instead. The 51N-n Reset setting can apply a definite time delayed reset, or when configured as an ANSI characteristic an ANSI (DECAYING) reset. If ANSI (DECAYING) reset is selected for an IEC characteristic, the reset will be instantaneous. The reset mode is significant where the characteristic has reset before issuing a trip output - see `Applications Guide'. A minimum operate time for the characteristic can be set using the 51N-n Min. Operate Time setting. A fixed additional operate time can be added to the characteristic using the 51N-n Follower DTL setting. Where directional elements are present the direction of operation can be set using 51N-n Dir. Control setting. Directional logic is provided independently for each 51N-n element. Unrestricted (c)2018 Siemens Protection Devices Limited Page 33 of 94 7SR210 & 7SR220 Description of Operation Operation of the time delayed earth fault elements can be inhibited from: Inhibit 51N-n A binary or virtual input, function key or remote data Comms. 79 E/F Inst Trips: 51N-n When `delayed' trips only are allowed in the auto-reclose sequence (79 E/F Prot'n Trip n = Delayed). 51N-n Inrush Action: Inhibit Operation of the current inrush detector function. 51N-n VTSAction: Inhibit Operation of the VT Supervision function (7SR22). Figure 3.3.3-1 Unrestricted Page 34 of 94 Logic Diagram: Derived Time Delayed Earth Fault Protection (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.4 Current Protection: Measured Earth Fault (67G, 51G, 50G) The earth current is measured directly via a dedicated current analogue input. All phase overcurrent elements can be set to measure either fundamental frequency RMS or True RMS current i.e. True RMS current: - 50 Measurement = RMS 51 Measurement = RMS Fundamental Frequency RMS current: - 50 Measurement = Fundamental 51 Measurement = Fundamental 3.4.1 Directional Control of Measured Earth Fault Protection (67G) - 7SR22 The directional element produces forward and reverse outputs for use with measured earth fault elements. These outputs can be mapped as controls to each shaped and instantaneous element. If a protection element is set as non-directional then it will operate independently of the output of the directional detector. However, if a protection element is programmed for forward directional mode then operation will occur only for a fault lying within the forward operate zone. Conversely, if a protection element is programmed for reverse directional mode then operation will occur only for a fault lying within the reverse operate zone. Typically the forward direction is defined as being `away' from the busbar or towards the protected zone. The Characteristic angle is the phase angle by which the polarising voltage must be adjusted such that the directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it. The reverse operate zone is the mirror image of the forward zone. The measured directional earth fault elements use zero phase sequence (ZPS) polarising. Voltage polarisation is achieved for the earth-fault elements by comparison of the appropriate current with its equivalent voltage: I0 ~ V0 The characteristic angle can be user programmed to any angle between -95 and +95 using the 67G Char Angle setting. The voltage is the reference phasor (Vref) and the 67G Char Angle setting is added to this to adjust the forward and reverse zones. The centre of the forward zone is set by (Vref Angle + 67G Char Angle) and should be set to correspond with Ifault Angle for maximum sensitivity e.g. For fault current of -15 (I lagging V by 15) a 67G Char Angle of -15 is required for maximum sensitivity, OR For fault current of -45 (I lagging V by 45) a 67G Char Angle of -45 is required for maximum sensitivity. Minimum Polarising Voltage The 67G Minimum Voltage setting defines the minimum polarising voltage level. Where the measured polarising voltage is below this level no directional output is given and. Operation of protection elements set as directional will be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise voltages can be present. Figure 3.4.1-1 Logic Diagram: Measured Directional Earth Fault Protection Unrestricted (c)2018 Siemens Protection Devices Limited Page 35 of 94 7SR210 & 7SR220 Description of Operation 3.4.2 Instantaneous Measured Earth Fault Protection (50G) Two instantaneous measured earth fault elements are provided in the 7SR21 relay. Four elements are provided in the 7SR22 relay e.g. giving the option of using two elements set to forward and two to reverse. Each instantaneous element has independent settings for pick-up current 50G-n Setting and a follower time delay 50G-n Delay. The instantaneous elements have transient free operation. Where directional elements are present the direction of operation can be set using 50G-n Dir. Control setting. Directional logic is provided independently for each 50G-n element. Operation of the instantaneous measured earth fault elements can be inhibited from: Inhibit 50G-n A binary or virtual input, function key or remote data Comms. 79 E/F Inst Trips: 50G-n When `delayed' trips only are allowed in the auto-reclose sequence (79 E/F Prot'n Trip n = Delayed). 50G-n Inrush Action: Inhibit Operation of the current inrush detector function. 50G-n VTSAction: Inhibit Operation of the VT Supervision function (7SR22). Figure 3.4.2-1 Unrestricted Page 36 of 94 Logic Diagram: Measured Instantaneous Earth-fault Element (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.4.3 Time Delayed Measured Earth Fault Protection (51G) Two time delayed measured earth fault elements are provided in the 7SR21 relay. Four elements are provided in the 7SR22 relay e.g. giving the option of using two elements set to forward and two to reverse. 51G-n Setting sets the pick-up current level. A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is selected from IEC and ANSI curves using 51G-n Char. A time multiplier is applied to the characteristic curves using the 51G-n Time Mult setting. Alternatively, a definite time lag (DTL) can be chosen using 51G-n Char. When DTL is selected the time multiplier is not applied and the 51G-n Delay (DTL) setting is used instead. The 51G-n Reset setting can apply a definite time delayed reset, or when configured as an ANSI characteristic an ANSI (DECAYING) reset. If ANSI (DECAYING) reset is selected for an IEC characteristic, the reset will be instantaneous. The reset mode is significant where the characteristic has reset before issuing a trip output - see `Applications Guide'. A minimum operate time for the characteristic can be set using 51G-n Min. Operate Time setting. A fixed additional operate time can be added to the characteristic using 51G-n Follower DTL setting. Where directional elements are present the direction of operation can be set using 51G-n Dir. Control setting. Directional logic is provided independently for each 51G-n element. Operation of the time delayed measured earth fault elements can be inhibited from: Inhibit 51G-n A binary or virtual input, function key or remote data Comms. 79 E/F Inst Trips: 51G-n When `delayed' trips only are allowed in the auto-reclose sequence (79 E/F Prot'n Trip n = Delayed). 51G-n Inrush Action: Inhibit Operation of the inrush current detector function. 51G-n VTSAction: Inhibit Operation of the VT Supervision function (7SR22). Figure 3.4.3-1 Logic Diagram: Measured Time Delayed Earth Fault Element (51G) Unrestricted (c)2018 Siemens Protection Devices Limited Page 37 of 94 7SR210 & 7SR220 Description of Operation 3.5 Current Protection: Sensitive Earth Fault (67SEF, 51SEF, 50SEF) Current for the Sensitive Earth Fault (SEF) elements is measured directly via a dedicated current analogue input. SEF elements measure the fundamental frequency RMS current. 3.5.1 Directional Control of Sensitive Earth Fault Protection (67SEF) - 7SR22 The directional element produces forward and reverse outputs for use with SEF elements. These outputs can be mapped as controls to each shaped and instantaneous element. If a protection element is set as non-directional then it will operate independently of the output of the directional detector. However, if a protection element is programmed for forward directional mode then operation will occur only for a fault lying within the forward operate zone. Conversely, if a protection element is programmed for reverse directional mode then operation will occur only for a fault lying within the reverse operate zone. Typically the forward direction is defined as being `away' from the busbar or towards the protected zone. The Characteristic angle is the phase angle by which the polarising voltage must be adjusted such that the directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it. The reverse operate zone is the mirror image of the forward zone. The directional sensitive earth fault elements use zero phase sequence (ZPS) polarising. Voltage polarisation is achieved for the earth-fault elements by comparison of the appropriate current with its equivalent voltage: I0 ~ V0 The characteristic angle can be user programmed to any angle between -95 and +95 using the 67SEF Char Angle setting. The voltage is the reference phasor (Vref) and the 67SEF Char Angle setting is added to this to adjust the forward and reverse zones. The centre of the forward zone is set by (Vref Angle + 67SEF Char Angle) and should be set to correspond with Ifault Angle for maximum sensitivity i.e. For fault current of -15 (I lagging V by 15) a 67SEF Char Angle of -15 is required for maximum sensitivity OR For fault current of -45 (I lagging V by 45) a 67SEF Char Angle of -45 is required for maximum sensitivity. For resonant grounded systems where compensation (Petersen) coils are fitted, earth fault current is deliberately reduced to zero and therefore is difficult to measure for protection purposes. However, the wattmetric component in the capacitive charging currents, which are close to the directional zone boundary, can be used to indicate fault location. It is advantageous to increase the directional limits towards 90 so that the directional boundary can be used to discriminate between faulted and healthy circuits. A 67SEF Compensated Network Enable user setting is provided to provide this feature for use with compensated networks only. Minimum Polarising Voltage The 67SEF Minimum Voltage setting defines the minimum polarising voltage level. Where the measured polarising voltage is below this level no directional output is given and. Operation of protection elements set as directional will be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise voltages can be present. Unrestricted Page 38 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Figure 3.5.1-1 3.5.2 Logic Diagram: SEF Directional Element (67SEF) Instantaneous Sensitive Earth Fault Protection (50SEF) Two instantaneous SEF elements are provided in the 7SR21 relay. Four elements are provided in the 7SR22 relay e.g. giving the option of using two elements set to forward and two to reverse. Each instantaneous element has independent settings for pick-up current 50SEF-n Setting and a follower time delay 50SEF-n Delay. The instantaneous elements have transient free operation. Where directional elements are present the direction of operation can be set using 50SEF-n Dir. Control setting. Directional logic is provided independently for each 50SEF-n element. Operation of the instantaneous earth fault elements can be inhibited from: Inhibit 50SEF-n A binary or virtual input, function key or remote data Comms 79 SEF Inst Trips: 50SEF-n When `delayed' trips only are allowed in the auto-reclose sequence (79 SEF Prot'n Trip n = Delayed). 50SEF-n VTSAction: Inhibit Operation of the VT Supervision function (7SR22). Directional elements will not operate unless the zero sequence voltage (V0) is above the 67SEF Minimum Voltage setting i.e. the residual voltage is greater than 3 times this setting and the phase is in the Forward/Reverse operating range. If 67SEF Wattmetric is set to Enabled, the calculated residual real power must be above the 67SEF Wattmetric Power setting for any SEF element operation. The residual power Pres is equal to the wattmetric component of 3V0ISEF and therefore the wattmetric component of 9V0I0 Unrestricted (c)2018 Siemens Protection Devices Limited Page 39 of 94 7SR210 & 7SR220 Description of Operation Figure 3.5.2-1 Figure 3.5.2-2 Unrestricted Page 40 of 94 Logic Diagram: 50 SEF Instantaneous Element Logic Diagram: 50 SEF Instantaneous Element Compensated Networks (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.5.3 Time Delayed Sensitive Earth Fault Protection (51SEF) Two time delayed sensitive earth fault elements are provided in the 7SR21 relay. Four elements are provided in the 7SR22 relay e.g. giving the option of using two elements set to forward and two to reverse. 51SEF-n Setting sets the pick-up current level. A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is selected from IEC and ANSI curves using 51SEF-n Char. A time multiplier is applied to the characteristic curves using the 51SEF-n Time Mult setting. Alternatively, a definite time lag (DTL) can be chosen using 51SEF-n Char. When DTL is selected the time multiplier is not applied and the 51SEF-n Delay (DTL) setting is used instead. The 51SEF-n Reset setting can apply a definite time delayed reset, or when configured as an ANSI characteristic an ANSI (DECAYING) reset. If ANSI (DECAYING) reset is selected for an IEC characteristic, the reset will be instantaneous. The reset mode is significant where the characteristic has reset before issuing a trip output - see `Applications Guide'. A minimum operate time for the characteristic can be set using 51SEF-n Min. Operate Time setting. A fixed additional operate time can be added to the characteristic using 51SEF-n Follower DTL setting. Where directional elements are present the direction of operation can be set using 51SEF-n Dir. Control setting. Directional logic is provided independently for each 51SEF-n element. Operation of the time delayed earth fault elements can be inhibited from: Inhibit 51SEF-n A binary or virtual input, function key or remote data Comms 79 SEF Inst Trips: 51SEF-n When `delayed' trips only are allowed in the auto-reclose sequence (79 SEF Prot'n Trip n = Delayed). 51SEF-n VTSAction: Inhibit Operation of the VT Supervision function (7SR22). Directional elements will not operate unless the zero sequence voltage (V0) is above the 67SEF Minimum Voltage setting i.e. the residual voltage is greater than 3 times this setting and the phase is in the Forward/Reverse operating range. If 67SEF Wattmetric is set to Enabled, the calculated residual real power must be above the 67SEF Wattmetric Power setting. The residual power Pres is equal to the wattmetric component of 3V0ISEF and therefore the wattmetric component of 9V0I0 Unrestricted (c)2018 Siemens Protection Devices Limited Page 41 of 94 7SR210 & 7SR220 Description of Operation Figure 3.5.3-1 Figure 3.5.3-2 Unrestricted Page 42 of 94 Logic Diagram: 51 SEF Time Delayed Element Logic Diagram: 51 SEF Time Delayed Element Compensated Networks (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.6 Current Protection: High Impedance Restricted Earth Fault (64H) One high impedance Restricted Earth Fault (REF) element is provided. The relay utilises fundamental current measurement values for this function. The single phase current input is derived from the residual output of line/neutral CTs connected in parallel. An external stabilising resistor must be connected in series with this input to ensure that this element provides a high impedance path. 64H Current Setting sets the pick-up current level. An output is given after elapse of the 64H Delay setting. External components - a series stabilising resistor and a non-linear resistor - are used with this function. See `Applications Guide' for advice in specifying suitable component values. Operation of the high impedance element can be inhibited from: Inhibit 64H A binary or virtual input, function key or remote data Comms Figure 3.6-1 Logic Diagram: High Impedance REF (64H) Unrestricted (c)2018 Siemens Protection Devices Limited Page 43 of 94 7SR210 & 7SR220 Description of Operation 3.7 Current Protection: Cold Load (51c) The setting of each shaped overcurrent element (51-n) can be inhibited and alternative `cold load' settings (51c-n) can be applied for a period following circuit switch in. The Cold Load settings are applied after the circuit breaker has been open for longer than the Pick-Up Time setting. Following circuit breaker closure the `cold load' overcurrent settings will revert to those defined in the Phase Overcurrent menu (51-n) after either elapse of the Drop-Off Time setting or when the measured current falls below the Reduced Current Level setting for a time in excess of Reduced Current Time setting. During cold load settings conditions any directional settings applied in the Phase Overcurrent menu are still applicable. A CB `Don't Believe It' (DBI) condition is not acted on, causing the element to remain operating in accordance with the relevant 51-n settings. Where the Reduced Current setting is set to OFF reversion to 51-n settings will only occur at the end of the Drop-Off Time. If any element is picked up on expiry of Drop-Off Time the relay will issue a trip (and lockout if a recloser is present). If the circuit breaker is re-opened before expiry of the Drop-Off Time the drop-off timer is held but not reset. Resetting the timer for each trip could result in damaging levels of current flowing for a prolonged period during a rapid sequence of trips/closes. Cold load trips use the same binary output(s) as the associated 51-n element. Figure 3.7-1 Logic Diagram: Cold Load Settings (51c) Unrestricted Page 44 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.8 Current Protection: Negative Phase Sequence Overcurrent (46NPS) The negative sequence phase (NPS) component of current (I2) is derived from the three phase currents. It is a measure of the quantity of unbalanced current in the system. Two NPS current elements are provided - 46IT and 46DT. The 46IT element can be configured to be either definite time lag (DTL) or inverse definite minimum time (IDMT), 46IT Setting sets the pick-up current level for the element. A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is selected from IEC and ANSI curves using 46IT Char. A time multiplier is applied to the characteristic curves using the 46IT Time Mult setting. Alternatively, a definite time lag delay (DTL) can be chosen using 46ITChar. When Delay (DTL) is selected the time multiplier is not applied and the 46IT Delay (DTL) setting is used instead. The 46IT Reset setting can apply a, definite time delayed or ANSI (DECAYING) reset. The 46DT element has a DTL characteristic. 46DT Setting sets the pick-up current and 46DT Delay the follower time delay. Operation of the negative phase sequence overcurrent elements can be inhibited from: Inhibit 46IT A binary or virtual input, function key or remote data Comms Inhibit 46DT A binary or virtual input, function key or remote data Comms Figure 3.8-1 Logic Diagram: Negative Phase Sequence Overcurrent (46NPS) Unrestricted (c)2018 Siemens Protection Devices Limited Page 45 of 94 7SR210 & 7SR220 Description of Operation 3.9 Current Protection: Under-Current (37, 37G & 37SEF) Two under-current elements are provided for each 37, 37G & 37SEF protection function. Each phase has an independent level detector and current-timing element. 37-n Setting sets the pick-up current. An output is given after elapse of the 37-n Delay setting. Operation of the under-current elements can be inhibited from: Inhibit 37-n A binary or virtual input, function key or remote data Comms Figure 3.9-1 Logic Diagram: Undercurrent Detector (37, 37G & 37SEF) 3.10 Current Protection: Under-Current Guarded (37) A level detector 37-n U/I Guard Setting sets the pick-up current. Figure 3.10-1 Logic Diagram: Undercurrent Guarded Detector (37) Unrestricted Page 46 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.11 Current Protection: Thermal Overload (49) The relay provides a thermal overload suitable for the protection of static plant. Phase segregated elements are provided. The temperature of the protected equipment is not measured directly. Instead, thermal overload conditions are calculated using the measure True RMS current. Should the current rise above the 49 Overload Setting for a defined time an output signal will be initiated. Operate Time (t): - i I 2 - I 2P u t = t ln i 2 2y i I - (k I B ) Where T = Time in minutes t = 49 Time Constant setting (minutes) In = Log Natural I = measured current IP = Previous steady state current level k = Constant IB = Basic current, typically the same as In k.IB = 49 Overload Setting (Iq) Additionally, an alarm can be given if the thermal state of the system exceeds a specified percentage of the protected equipment's thermal capacity 49 Capacity Alarm setting. For the heating curve: - = I2 I 2 x (1 - e -t ) 100% Where: q = thermal state at time t I = measured thermal current Iq = 49 Overload setting (or k.IB) The final steady state thermal condition can be predicted for any steady state value of input current where t >t, F = I2 I 2 100% Where: qF = final thermal state before disconnection of device 49 Overload Setting Iq is expressed as a multiple of the relay nominal current and is equivalent to the factor k.IB as defined in the IEC255-8 thermal operating characteristics. It is the value of current above which 100% of thermal capacity will be reached after a period of time and it is therefore normally set slightly above the full load current of the protected device. The thermal state may be reset from the fascia or externally via a binary input. Thermal overload protection can be inhibited from: Inhibit 49 A binary or virtual input, function key or remote data Comms. Unrestricted (c)2018 Siemens Protection Devices Limited Page 47 of 94 7SR210 & 7SR220 Description of Operation Figure 3.11-1 Logic Diagram: Thermal Overload Protection (49S) Unrestricted Page 48 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.12 Current Protection: Arc Flash Detector (50 AFD) By employing an optical detection technique, Arc Fault Protection results in fast clearance of arcing faults. Arc fault protection is achieved in the relays via the 7XG31xx series of equipment being connected to the binary inputs. Should the sensor operate when the current is above the 50AFD Setting then an output signal will be initiated. Refer to 7XG31 documentation for further details. 50AFD Disabled Enabled AFD Zone 1 Flash & AFD Zone 1 AFD Zone 1 Flash Arc Detector Binary Input AFD Zone 6 Flash & AFD Zone 6 AFD Zone 6 Flash 50AFD Setting IA c IB 50 AFD IC 50 AFD PhA 50 AFD PhB 50 AFD PhC Figure 3.12-1 Logic Diagram: Arc Flash Detector (50 AFD) Unrestricted (c)2018 Siemens Protection Devices Limited Page 49 of 94 7SR210 & 7SR220 Description of Operation 3.13 Voltage Protection: Phase Under/Over Voltage (27/59) 7SR22 In total five under/over voltage elements are provided in the 7SR22 relay. Four elements are provided for the `Phase' Voltages and one for the `Auxiliary' input voltage. The relay utilises fundamental frequency RMS voltage for this function. All under/over voltage elements have a common setting to measure phase to phase (Ph-Ph) or phase to neutral (Ph-N) voltage using the Voltage Input Mode setting. Voltage elements can be blocked if all phase voltages fall below the 27/59 U/V Guard setting. 27/59-n (27/59-Vx) Setting sets the pick-up voltage level for the element. The sense of the element (undervoltage or overvoltage) is set by the 27/59-n Operation (27/59-Vx Operation) setting. The 27/59-n O/P Phases setting determines whether the time delay is initiated for operation of any phase or only when all phases have detected the appropriate voltage condition. An output is given after elapse of the 27/59-n Delay (27/59-Vx Delay) setting. The 27/59-n Hysteresis (27/59-Vx Hysteresis) setting allows the user to vary the pick-up/drop-off ratio for the element. Operation of the under/over voltage elements can be inhibited from: Inhibit 27/59-n A binary or virtual input, function key or remote data Comms. 27/59-n VTSInhibit: Yes Operation of the VT Supervision function. 27/59-n U/V Guarded Under voltage guard element. Figure 3.13-1 Logic Diagram: Under/Over Voltage Elements (27/59) Unrestricted Page 50 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.14 Voltage Protection: Negative Phase Sequence Overvoltage (47) - 7SR22 Negative phase sequence (NPS) voltage (V2) is a measure of the quantity of unbalanced voltage in the system. The relay derives the NPS voltage from the three input voltages (VL1, VL2 and VL3). Two elements are provided in the 7SR22 relay. 47-n Setting sets the pick-up voltage level for the element. The 47-n Hysteresis setting allows the user to vary the pick-up/drop-off ratio for the element. An output is given after elapse of the 47-n Delay setting. Operation of the negative phase sequence voltage elements can be inhibited from: Inhibit 47-n A binary or virtual input, function key or remote data Comms. Figure 3.14-1 Logic Diagram: NPS Overvoltage Protection (47) Unrestricted (c)2018 Siemens Protection Devices Limited Page 51 of 94 7SR210 & 7SR220 Description of Operation 3.15 Voltage Protection: Neutral Overvoltage (59N) - 7SR22 Two Neutral Overvoltage (or Neutral Voltage Displacement) elements are provided in the 7SR22 relay. 59N Voltage Source setting selects the source of the residual voltage to be measured. The voltage is measured directly from the Vx input or derived from the line voltages where suitable VT connections are present. The relay utilises fundamental voltage measurement values for this function. One of the elements can be configured to be either definite time lag (DTL) or inverse definite minimum time (IDMT). The Neutral Inverse Time Lag 59NIT Setting sets the pick-up voltage level (3V0) for the element. An inverse definite minimum time (IDMT) can be selected using 59NIT Char. A time multiplier is applied to the characteristic curves using the 59NIT Time Mult setting (M): - e M u t op = e 3Vo us 1 [ ] e Vs u Alternatively, a definite time lag delay (DTL) can be chosen using 59NITChar. When Delay (DTL) is selected the time multiplier is not applied and the 59NIT Delay (DTL) setting is used instead. An instantaneous or definite time delayed reset can be applied using the 59NIT Reset setting. The second element has a DTL characteristic. The Neutral Definite Time Lag 59NDT Setting sets the pick-up voltage (3V0) and 59NDT Delay the follower time delay. Operation of the neutral overvoltage elements can be inhibited from: Inhibit 59NIT A binary or virtual input, function key or remote data Comms. Inhibit59NDT A binary or virtual input, function key or remote data Comms. It should be noted that neutral voltage displacement can only be applied to VT arrangements that allow zero sequence flux to flow in the core i.e. a 5-limb VT or 3 single phase VTs. The VT primary winding neutral must be earthed to allow the flow of zero sequence current. Figure 3.15-1 Logic Diagram: Neutral Overvoltage Element Unrestricted Page 52 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.16 Voltage Protection: Under/Over Frequency (81) - 7SR22 Six under/over frequency elements are provided in the 7SR22 relay. The relay utilises fundamental voltage measurement values for this function. The frequency calculation is based on the highest input voltage derived from the voltage selection algorithm. Frequency elements are blocked if all phase voltages fall below the 81 U/V Guard setting. The sense of the element (under-frequency or over-frequency) is set by the 81-n Operation setting. 81-n Setting sets the pick-up voltage level for the element. An output is given after elapse of the 81-n Delay setting. The 81-n Hysteresis setting allows the user to vary the pick-up/drop-off ratio for the element. Operation of the under/over frequency elements can be inhibited from: Inhibit 81-n A binary or virtual input, function key or remote data Comms. 81-n U/V Guarded Under voltage guard element. 81-n Element Enabled Disabled Inhibit 81-n Inhibit 81-n & 81-n U/V Guarded Yes & 81 U/V Guard Setting 81-n Operation 81-n Setting < < General Pickup & 81-n Hysteresis General Pickup < c 81-n Delay VL1 VL2 Voltage Selection F > or < VL3 81-n 81-n Figure 3.16-1 Logic Diagram: Under/Over Frequency Detector (81) Unrestricted (c)2018 Siemens Protection Devices Limited Page 53 of 94 7SR210 & 7SR220 Description of Operation 3.17 Power Protection: Power (32) - 7SR22 Two under/over power elements are provided and can measure real, reactive or apparent power. Gn 32-n Setting sets the pick-up power level for the element. Under-power or over-power operation can be set by the Gn 32-n Operation setting. Gn 32-n 1ph/3ph Power allows the settings to be based on any one phase exceeding the power pick up level or on the total power of all three phases. An output is given after elapse of the Gn 32-n Delay setting. Operation of the under/over power elements can be inhibited when: The measured current is below the Gn 32-n U/C Guard setting A VT Fail condition is detected Inhibit 32-n A binary or virtual input. Gn 32-n Element Enabled Gn 32-n VTS Action Inhibit & VT Fail Inhibit 32-n Gn32: Operation: Under/Over Gn32: 1ph/3ph Power Gn 32-n U/C Guarded Gn32: Power: P, Q, R Enabled Gn32: Direction Gn32: Setting Gn 32-n U/C Guard Setting & < < En. & & < Gn 32-n Delay IL1 IL2 IL3 -W -VAr +W -VAr -W +VAr +W +VAr V1 32-n General Pickup V2 V3 Figure 3.17-1 Logic Diagram: Power Protection (32) Unrestricted Page 54 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 3.18 Power Protection: Sensitive Power (32S) - 7SR22 Two under/over sensitive power elements are provided in the 7SR22 models. The elements can measure real, reactive or apparent power. Sensitive power functionality utilises the ISEF current input i.e. a single CT input is used. Balanced load conditions are assumed. Any one of the three phase currents can be wired to the IG current input - the POWER PROT'N > SENSITIVE POWER > Gn 32S Phase Selection setting is used to ensure that the correct power is measured. Gn 32S-n Setting sets the pick-up power level for the element. Under-power or over-power operation can be set by the Gn 32S-n Operation setting. An output is given after elapse of the Gn 32S-n Delay setting. Operation of the under/over power elements can be inhibited when: The measured current is below the Gn 32S U/C Guard setting A VT Fail condition is detected Inhibit 32S-n A binary or virtual input. Gn 32S-n Element Enabled Gn 32S-n VTS Action Inhibit & VT Fail Inhibit 32S-n Gn32S: Phase Selection Gn32S-n: Operation: Under/Over Gn 32S-n U/C Guard Gn32S-n: Power: P, Q, R Enabled Gn32S-n: Direction Gn32S-n: Setting Gn 32S-n U/C Guard Setting < & En. & 32S CT Angle Comp ISEF Gn 32S-n Delay V1 -W -VAr +W -VAr -W +VAr +W +VAr V2 32S-n General Pickup V3 Figure 3.18-1 Logic Diagram: Sensitive Power Protection (32S) Unrestricted (c)2018 Siemens Protection Devices Limited Page 55 of 94 7SR210 & 7SR220 Description of Operation 3.19 Power Protection: Power Factor (55) - 7SR22 Two power factor elements are provided. Gn 55-n Setting sets the pick-up power factor of the element. Under-power factor or over-power factor operation can be set by the Gn 55-n Operation setting. Gn 55-n 1ph/3ph Power allows the settings to be based on any one phase power factor or the average power factor of all three phases. An output is given after elapse of the Gn 55-n Delay setting. Operation of the power factor elements can be inhibited when: The measured current is below the Gn 55 U/C Guard setting A VT Fail condition is detected Inhibit 55-n A binary or virtual input. Figure 3.19-1 Logic Diagram: Power Factor Protection (55) Unrestricted Page 56 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Section 4: Control & Logic Functions 4.1 Auto-Reclose (79) 4.1.1 Overview A high proportion of faults on an Overhead Line (OHL) network are transient. These faults can be cleared and the network restored quickly by using Instantaneous (Fast) Protection trips followed by an automated sequence of Circuit Breaker (CB) re-closures after the line has been dead for a short time. This `deadtime' allows the fault current arc to fully extinguish. Typically this auto reclose (AR) sequence of Instantaneous Trip(s) and Reclose Delays (Dead times) followed by Delayed Trip(s) provide the automatic optimum method of clearing all types of fault i.e. both Transient and Permanent, as quickly as possible and achieving the desired outcome of keeping as much of the Network inservice as possible. The AR function, therefore, has to: Control the type of Protection trip applied at each stage of a sequence Control the Auto Reclose of the Circuit Breaker to provide the necessary network Dead times, to allow time for Arc extinction Co-ordinate its Protection and Auto Reclose sequence with other fault clearing devices. A typical sequence would be - 2 INST+1Delayed+HighSet Trips with 1 sec & 10 sec dead times. The Auto Reclose feature may be switched in and out of service by a number of methods, these are: 79 Autoreclose ENABLE/DISABLE (AUTORECLOSE CONFIG menu) A keypad change from the CONTROL MODE Via the data communications channel(s), From a 79 OUT binary input. Note the 79 OUT binary input has priority over the 79 IN binary input - if both are raised the auto-reclose will be Out of Service. Knowledge of the CB position status is integral to the auto-reclose functionality. CB auxiliary switches must be connected to CB Closed and CB Open binary inputs. A circuit breaker's service status is determined by its position i.e. from the binary inputs programmed CB Open and CB Closed. The circuit breaker is defined as being in service when it is closed. The circuit memory functionality prevents autoreclosing when the line is de-energised, or normally open. AR is started by a valid protection operation that is internally mapped to trip in the 79 Autoreclose protection menu or an external trip received via a binary input 79 Ext Trip, while the associated circuit breaker is in service. The transition from AR started to deadtime initiation takes place when the CB has opened and the protection pickups have reset and the trip relay has reset. If any of these do not occur within the 79 Sequence Fail Timer setting the relay will Lockout. This prevents the AR being primed indefinitely. 79 Sequence Fail Timer can be switched to 0 (= OFF). Once an AR sequence has been initiated, up to 4 reclose operations can be attempted before the AR is lockedout. The relay is programmed to initiate a number of AR attempts, the number is determined by 79 Num Shots. Each reclosure (shot) is preceded by a time delay - 79 Elem Deadtime n - giving transient faults time to clear. Separate dead-time settings are provided for each of the 4 recloses and for each of the four fault types - P/F, E/F, SEF and External. Once a CB has reclosed and remained closed for a specified time period (the Reclaim time), the AR sequence is re-initialised and a Successful Close output issued. A single, common Reclaim time is used (Reclaim Timer). When an auto-reclose sequence does not result in a successful reclosure the relay goes to the lockout state. Unrestricted (c)2018 Siemens Protection Devices Limited Page 57 of 94 7SR210 & 7SR220 Description of Operation Indications The Instruments Menu includes the following meters relevant to the status of the Auto-Reclose and Manual Closing of the circuit breaker: Autoreclose Status Out of Service Close Shot. CB Open Countdown Timer CB Close Countdown Timer Inputs External inputs to the recloser functionality need to be wired to the binary inputs. Functions which can be mapped to these binary inputs include: 79 Out (edge triggered) 79 In (edge triggered) CB Closed CB Open 79 Ext Trip 79 Ext Pickup 79 Block Reclose Block Close CB Close CB 79 Trip & Reclose 79 Trip & Lockout 79 Line Check Hot Line In Hot Line Out Outputs Outputs are fully programmable to either binary outputs or LEDs. Programmable outputs include: 79 Out Of Service 79 In Service 79 In Progress 79 AR Close CB 79 Successful AR 79 Lockout 79 Close Onto Fault 79 CB Fail to Close 79 Trip _Reclose 79 Trip _Lockout 79 Block Extern Unrestricted Page 58 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 4.1.2 Auto Reclose sequences The CONTROL & LOGIC>AUTO RECLOSE PROT'N and CONTROL & LOGIC>AUTORECLOSE CONFIG' menus, allow the user to set independent Protection and Auto Reclose sequences for each type of fault i.e. Phase Fault (P/F), Derived/Measured Earth Fault (E/F), Sensitive Earth Fault (SEF) or External Protections (EXTERN). Each Auto Reclose sequence can be user set to up to four-shots i.e. five trips + four reclose sequence, with independently configurable type of Protection Trip. Overcurrent and earth fault elements can be assigned to any combination of Fast (Inst), Delayed or highset (HS) trips. Deadtime Delay time settings are independent for each AR shot. The user has programming options for Auto Reclose Sequences up to the maximum shot count i.e.:Inst or Delayed Trip 1 + (DeadTime 1: 0.1s-14400s) + Inst or Delayed Trip 2 + (DeadTime 2: 0.1s-14400s) + Inst or Delayed Trip 3 + (DeadTime 3: 0.1s-14400s) + Inst or Delayed Trip 4 + (DeadTime 4: 0.1s-14400s) + Inst or Delayed Trip 5 - Lockout. The AR function recognizes developing faults and, as the shot count advances, automatically applies the correct type of Protection and associated Dead time for that fault-type at that point in the sequence. A typical sequence would consist of two Inst trips followed by at least one Delayed trip. This sequence enables transient faults to be cleared quickly by the Inst trip(s) and permanent fault to be cleared by the combined Delayed trip. The delayed trip must be `graded' with other Recloser/CB's to ensure system discrimination is maintained, ie. that as much of the system as possible is live after the fault is cleared. A HS trips to lockout setting is provided such that when the number of operations of elements assigned as HS trips reach the setting the relay will go to lockout. The number of Shots (Closes) is user programmable, note: - only one Shot Counter is used to advance the sequence, the Controller selects the next Protection characteristic/Dead time according to the type of the last Trip in the sequence e.g. PF, EF, SEF or EXTERNAL. Reclose Dead Time User programmable dead times are available for each protection trip operation. The dead time is initiated when the trip output contact reset, the pickup is reset and the CB is open. The CB close output relay is energised after the dead time has elapsed. 1st Trip (Inst) 2nd Trip (Inst) 1st Dead Time Figure 4.1.2-1 2nd Dead Time 3rd Trip (Inst) 3rd Dead Time 4th Trip (Delayed) 4th Dead Time Typical Sequence with 3 Instantaneous and 1 Delayed trip Unrestricted (c)2018 Siemens Protection Devices Limited Page 59 of 94 7SR210 & 7SR220 Description of Operation 4.2 Autoreclose Prot'n Menu This menu presents the Overcurrent Protection elements available for each type of Fault i.e. P/F, E/F or SEF and allows the user to select those that are to be applied as Inst trips; those that are to be applied as Delayed Trips; and those that are to be applied as HS Trips (HighSet), as required by the selected sequence. There is no corresponding setting for External as the External protection type is not normally controlled by the Auto Reclose Relay. The resultant configuration enables the Auto Reclose function to correctly apply the required Protection for each shot in a sequence. 4.3 Autoreclose Config Menu This menu allows the following settings to be made:79 Autoreclose Enabled turns ON all AutoReclose Functions. 79 Num Shots Sets the allowed number of AutoReclose attempts in a sequence. 79 Retry Enable Enabled configures the relay to perform further attempts to automatically Close the Circuit Breaker where the CB has initially failed to close in response to a Close command. If the first attempt fails the relay will wait for the 79 Retry Interval to expire then attempt to Close the CB again. 79 Retry Attempts Sets the maximum number of retry attempts. 79 Retry Interval Sets the time delay between retry attempts. 79 Reclose Blocked Delay If the CB is not ready to receive a Close command or if system conditions are such that the CB should not be closed immediately e.g. a close-spring is not charged, then a Binary input mapped to Reclose Block can be raised and the Close pulse will not be issued but will be held-back. The 79 Reclose Blocked Delay sets the time Reclose Block is allowed to be raised, if this time delay expires the Relay will go to Lockout. If Reclose Block is cleared, before this time expires, then the CB Close pulse will be issued at that point in time. Dead Time + Reclose Blocked Delay = Lockout. 79 Sequence Fail Timer Sets the time that AutoReclose start can be primed. Where this time expires before all the DAR start signals are not received i.e. the CB has opened, protection pickups have reset and the trip relay has reset, the Relay goes to Lockout. 79 Minimum LO Delay Sets the time that the Relay's Lockout condition is maintained. After the last allowed Trip operation in a specific sequence the Circuit Breaker will be left locked-out in the open position and can only be closed by manual or remote SCADA operation. The 79 Minimum Lockout Delay timer can be set to delay a too-fast manual close after lockout, this prevents an operator from manually closing onto the same fault too quickly and thus performing multiple sequences and possibly burning-out Plant. 79 Reset LO by Timer Set to Enabled this ensures that the Lockout condition is reset when the timer expires, Lockout indication will be cleared; otherwise, set to Disabled, the Lockout condition will be maintained until the CB is Closed by a Close command. 79 Sequence Co-Ord When set to Enabled the Relay will co-ordinate its sequence and shot count such that it automatically keeps in step with downstream devices as they advance through their sequence. The Relay detects that a pickup has operated followed by current switchoff. It then increments its Shot count and advances to the next stage of the autoreclose sequence without issuing a trip. This is repeated as long as the fault is being cleared by the downstream device such that the Relay moves through the sequence bypassing the INST Trips and moving on to the Delayed Trip to maintain Grading margins. Unrestricted Page 60 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Notes on the `Lockout' State The Lockout state can be reached for a number of reasons. Lockout will occur for the following: - * At the end of the 79 Sequence Fail Timer. * At the end of the Reclaim timer if the CB is in the open position. * A protection operates during the final Reclaim time. * If a Close Pulse is given and the CB fails to close. * The 79 Lockout binary input is active. * At the end of the 79 Reclose Blocked Delay due to presence of a persistent Block signal. * When the 79 Elem HS Trips to Lockout count is reached. * When the 79 Elem Delayed Trips to Lockout count is reached. Once lockout has occurred, an alarm (79 Lockout) is issued and all further Close commands, except manual close, are inhibited. If the Lockout command is received while a Manual Close operation is in progress, the feature is immediately locked-out. Once the Lockout condition has been reached, it will be maintained until reset. The following will reset lockout: - * By a Manual Close command, from fascia, comms or Close CB binary input. * By a 79 Reset Lockout binary input, provided there is no signal present that will cause Lockout. * At the end of the 79 Minimum LO Delay time setting if 79 Reset LO by Timer is selected to ENABLED, provided there is no signal present which will cause Lockout. * Where Lockout was entered by an A/R Out signal during an Autoreclose sequence then a 79 In signal must be received before Lockout can reset. * By the CB Closed binary input, provided there is no signal present which will cause Lockout. The Lockout condition has a delayed drop-off time of 2s. The Lockout condition cannot be reset if there is an active lockout input. Note: If the `CB Total Trip Count' or the `CB Frequent Ops Count' target is reached the relay will do one delayed tip and lockout. Unrestricted (c)2018 Siemens Protection Devices Limited Page 61 of 94 7SR210 & 7SR220 Description of Operation 4.4 P/F Shots Sub-Menu This menu allows the Phase fault trip/reclose sequence to be parameterized:79 P/F Prot'n Trip1 The first protection Trip in the P/F sequence can be set to either Inst or Delayed. 79 P/F Deadtime 1 Sets the first Reclose Delay (Dead time) in the P/F sequence. 79 P/F Prot'n Trip2 The second protection Trip in the P/F sequence can be set to either Inst or Delayed. 79 P/F Deadtime 2 Sets the second Reclose Delay (Dead time) in the P/F sequence. 79 P/F Prot'n Trip3 The third protection Trip in the P/F sequence can be set to either Inst or Delayed. 79 P/F Deadtime 3 Sets the third Reclose Delay (Dead time) in the P/F sequence. 79 P/F Prot'n Trip 4 The fourth protection Trip in the P/F sequence can be set to either Inst or Delayed. 79 P/F Deadtime 4 Sets the fourth Reclose Delay (Dead time) in the P/F sequence. 79 P/F Prot'n Trip5 The fifth and last protection Trip in the P/F sequence can be set to either Inst or Delayed. 79 P/F HighSet Trips to Lockout Sets the number of allowed HighSet trips. The relay will go to Lockout on the last HighSet Trip. This function can be used to limit the duration and number of high current trips that the Circuit Breaker is required to perform, if the fault is permanent and close to the Circuit Breaker then there is no point in forcing a number of Delayed Trips before the Relay goes to Lockout - that sequence will be truncated. 79 P/F Delayed Trips to Lockout Sets the number of allowed Delayed trips, Relay will go to Lockout on the last Delayed Trip. This function limits the number of Delayed trips that the Relay can perform when the Instantaneous protection Elements are externally inhibited for system operating reasons - sequences are truncated. 4.5 E/F Shots Sub-Menu This menu allows the Earth Fault trip/reclose sequence to be parameterized:As above but E/F settings. 4.6 SEF Shots Sub-Menu This menu allows the Sensitive Earth trip/reclose sequence to be parameterized:As above but SEF Settings, Note: - SEF does not have HighSets Unrestricted Page 62 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 4.7 Extern Shots Sub-Menu This menu allows the External Protection auto-reclose sequence to be parameterized:79 P/F Prot'n Trip1 Not Blocked/Blocked - Blocked raises an output which can be mapped to a Binary output to Block an External Protection's Trip Output. 79 P/F Deadtime 1 Sets the first Reclose Delay (Deadtime) for the External sequence. 79 P/F Prot'n Trip2 Not Blocked/Blocked - Blocked raises an output which can be mapped to a Binary Output to Block an External Protection's second Trip output. 79 P/F Deadtime 2 Sets the second Reclose Delay (Deadtime) in the External sequence. 79 P/F Prot'n Trip3 Not Blocked/Blocked - Blocked raises an output which can be mapped to a Binary output to Block an External Protection's third Trip Output. 79 P/F Deadtime 3 Sets the third Reclose Delay (Deadtime) in the External sequence. 79 P/F Prot'n Trip4 Not Blocked/Blocked - Blocked raises an output which can be mapped to a Binary output to Block an External Protection's fourth Trip Output. 79 P/F Deadtime 4 Sets the fourth Reclose Delay (Deadtime) in the External sequence. 79 P/F Prot'n Trip5 Not Blocked/Blocked - Blocked raises an output which can be mapped to a Binary output to Block an External Protection's fifth Trip Output. 79 P/F Extern Trips to Lockout - Sets the number of allowed External protection' trips, Relay will go to Lockout on the last Trip. These settings allow the user to set-up a separate AutoReclose sequence for external protection(s) having a different sequence to P/F, E/F or SEF protections. The ` Blocked ` setting allows the Autoreclose sequence to raise an output at any point in the sequence to Block further Trips by the External Protection thus allowing the Overcurrent P/F or Earth Fault or SEF elements to apply Overcurrent Grading to clear the fault. Other Protection Elements in the Relay can also be the cause of trips and it may be that AutoReclose is required; the External AutoReclose sequence can be applied for this purpose. By setting-up internal Quick Logic equation(s) the user can define and set what should occur when any one of these other elements operates. Unrestricted (c)2018 Siemens Protection Devices Limited Page 63 of 94 7SR210 & 7SR220 Description of Operation Figure 4.7-1 Basic Auto-Reclose Sequence Diagram Unrestricted Page 64 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 4.8 Manual Control A Manual Close Command can be initiated in one of three ways: via a Close CB binary input, via the data communication Channel(s) or from the relay CONTROL MODE menu. It causes an instantaneous operation via Manual Close CB binary output, over-riding any DAR sequence in progress. Repeated Manual Closes are avoided by checking for Positive edge triggers. Even if the Manual Close input is constantly energised the relay will only attempt one close. A Manual Close will initiate Line Check if Line Check Trip is enabled. If a fault appears on the line during the Close Pulse or during the Reclaim Time with Line Check enabled, the relay will initiate a Trip and Lockout. This prevents a CB being repeatedly closed onto a faulted line. Where Line Check Trip = DELAYED then instantaneous protection is inhibited until the reclaim time has elapsed. Manual Close resets Lockout, if the conditions that caused Lockout have reset, i.e. there is no trip or Lockout input present. Manual Close cannot proceed if there is a Lockout input present. With the Autoreclose function set to Disabled the Manual Close control is still active. Close CB Delay The Close CB Delay is applicable to manual CB close commands received through a Close CB binary input or via the Control Menu. Operation of the Manual Close CB binary output is delayed by the Close CB Delay setting. The status of this delay is displayed on the relay fascia as it decrements towards zero. Only when the delay reaches zero will the close command be issued and related functionality initiated. Blocked Close Delay The close command may be delayed by a Block Close CB signal applied to a binary input. This causes the feature to pause before it issues the CB close command and can be used, for example, to delay CB closure until the CB energy has reached an acceptable level. If the Block signal has not been removed before the end of the defined time, Blocked Close Delay, the relay will go to the lockout state. The output Close CB Blocked indicates this condition. Open CB Delay The Open CB Delay setting is applicable to CB trip commands received through an Open CB binary input or via the Control Menu. Operation of the Open CB binary output is delayed by the Open CB Delay setting. The status of this delay is displayed on the relay fascia as it decrements towards zero. Only when the delay reaches zero will the trip command be issued and related functionality initiated. It should be noted that a CB trip initiated by an Open CB command is fundamentally different from a CB trip initiated by a protection function. A CB trip caused by a CB Open command will not initiate functionality such as circuit-breaker fail, fault data storage, I2t measurement and operation counter. CB Controls Latched CB controls for manually closing and tripping can be latched for extra security. With Reset operation, the control resets when the binary input drops off. This can lead to multiple control restarts due to bounce on the binary input signal. With Latch operation, the close or trip sequence always continues to completion (or sequence failure) and bounce on the binary input is ignored. Reset operation can be useful, however, as it allows a close or trip sequence to be aborted by dropping off the binary input signal. Unrestricted (c)2018 Siemens Protection Devices Limited Page 65 of 94 7SR210 & 7SR220 Description of Operation 4.9 Synchronising The optional Synchronising function is used to check that the voltage conditions, measured by the voltage transformers on either side of the open circuit breaker, indicate that it is safe to close without risk of damage to the circuit breaker of disturbance to the system. The timing of closure, for charging lines which are dead following fault clearance, is controlled to co-ordinate with other devices. The window of time in which voltage conditions must be met is applied as a setting or can be disabled such that an indefinite period is allowed. 4.9.1 Reclosure Modes The Synchronising element can be set to allow the autoreclose sequence to proceed for various system voltage conditions. The voltage conditions selected must be met within the Synch Close Window time if this is Enabled, this time can be set and starts at the end of the deadtime for autoreclose or the receipt of a Close CB command. The voltage applied to the V4 input is considered to be the BUSBAR voltage and the voltages applied to inputs V1,V2 & V3 are the LINE voltage. 79 Dead Bar Charge, when set to Enabled, allows AR to proceed when the Line voltage is live and the Busbar is dead. Manual Close DBC, when set to Enabled, allows MC to proceed when the Line voltage is live and the Busbar is dead. 79 Dead Line Charge, when set to Enabled, allows AR to proceed when the Busbar voltage is live and the Line is dead. Manual Close DLC, when set to Enabled, allows MC to proceed when the Busbar voltage is live and the Line is dead. 79 Dead Line & Dead Bar Close, when set to Enabled, allows AR to proceed when the Line voltage and the Busbar voltage are dead. Manual Close DLDB, when set to Enabled, allows MC to proceed when the Line voltage and the Busbar voltage are dead. 79 Check Sync Close, when set to Enabled, allows AR to proceed when both the Line and Busbar are considered live AND other synchronising requirements are met. Manual Close CS, when set to Enabled, allows MC to proceed when both the Line and Busbar are considered live AND other synchronising requirements are met. 79 Unconditional Close, when set to Enabled, allows AR to proceed regardless of the voltage condition of the Bus or Line. Unconditional Manual Close, when set to Enabled, allows MC to proceed regardless of the voltage condition of the Bus or Line. Separate Enable/Disable settings are thus provided for each option for Autoreclose and Manual Close. 4.9.2 Charge Delays Separate autoreclose delay settings are provided for Dead Line Charge and Dead Bus Charge closure by the 79 DLC Delay and 79 DBC Delay settings. These are applied after the autoreclose Dead Time when voltage conditions are checked and met, at the Close Inhibit stage of the sequence. This feature effectively allows the dead time to be set differently for faults on each side of the recloser. 4.9.3 Voltage monitoring elements The single phase voltage source used for synchronising can be selected as any phase-to-phase or phase-to-earth voltage for flexibility. The voltage is compared to the corresponding voltage from the three-phase arrangement on the other side of the circuit-breaker. Voltage settings are set as a percentage of the nominal voltage specified in the CT/VT Config menu. Unrestricted Page 66 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Voltage detectors Voltage detectors determine the status of the line or bus. If the voltages on either the line or bus are below a set threshold level they can be considered to be `dead'. If the voltages are within a setting around the nominal voltage they are classed as `live'. Independent voltage detectors are provided for both line and bus. If a voltage is in the dead band range then it will be classed as dead until it has reached the live band area. Similarly, if a voltage is live, it continues to be live until it has reached the dead band area. This effectively allows for variable amounts of hysteresis to be set. Figure 4.9.3-1 illustrates the voltage detector operation. Note: the area between the dead and live zones is not indeterminate. When any voltage is applied to the relay it will ramp up the software RMS algorithm and always pass through the dead zone first. A wide range is provided for live and dead voltage detector levels but the live and dead zones must not overlap. Figure 4.9.3-1 Voltage Detector Operation Under-voltage detectors The under-voltage detectors, if enabled, can block a close output command if either the line voltage is below the 25 Line Undervolts setting value or the bus voltage is below the 25 Bus Undervolts setting value. Both line and bus have their own independent settings and are applied to the single-phase voltage inputs. Differential voltage detectors The differential voltage detector, if enabled, can block a close output command if the difference between the line and bus voltages is greater than the differential voltage setting value. Unrestricted (c)2018 Siemens Protection Devices Limited Page 67 of 94 7SR210 & 7SR220 Description of Operation 4.9.4 Check Synchronising Mode The Man Override Sync input is provided to bypass the voltage and synchronising checks to provide an emergency close function. Similarly, check synchronising can be overridden by the 79 Override Sync input during autoreclose. Override can be set by binary inputs, Control commands and the function keys. For the relay to issue a Check Sync Close the following conditions have to be met: The Line and Bus voltages must both be considered live. 25 Check Sync Angle - the phase difference between the line and bus voltages has to be less than the phase angle setting value. Whilst within the limits the phase angle can be increasing or decreasing and the element will still issue a valid close signal. 25 Check Sync Slip, [if enabled] - the frequency difference between line and bus has to be less than the slip frequency setting value. 25 Check Sync Timer, [if enabled] - the phase angle and voltage blocking features have to be within their parameters for the length of the slip timer setting. If either the phase angle or the voltage elements fall outside of their limits the slip timer is reset. If they subsequently come back in then the slip timer has to time out before an output is given. (This ensures that a close output will not be given if there is a transient disturbance on the system due to e.g. some remote switching operations). 25 Line Undervolts, [if enabled] - the line voltage has to be above the line under-voltage setting value and also above 5V for an output to be given. 25 Bus Undervolts, [if enabled] - the bus voltage has to be above the bus under-voltage setting value and also above 5V for an output to be given. 25 Volt Differential, [if enabled] - the difference between the line and bus voltages has to be less than the differential voltage detector setting value for an output to be given. The synchronising is always started in the Check Synchronising mode of operation and the Check Synchronising limits are applied. To proceed to System Synchronisation a system split must be detected as described in section 4.9.5 SLIP Slip Within Range ? Slip Frequency Setting F Angle Phase Within Range ? Slip Timer Phase Angle Setting Line U/V Block Block Bus U/V BLock Block D V Block Block Figure 4.9.4-1 Unrestricted Page 68 of 94 & & CheckSync Close Slip Timer Setting Check Sync Function (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 4.9.5 System Split Detector A system split occurs where part of the system becomes islanded and operates separately. Under these conditions the frequencies of the voltages either side of the breaker are asynchronous and therefore high phase angle differences can occur as the voltage phasors slip past each other. The decision to change to System Split settings, apply Close on Zero function, Lockout or ignore, during autoreclose and manual closing is set separately by the 25 DAR Split Mode and 25 MC Split Mode settings. The System Split condition is detected when either the measured phase difference angle exceeds the pre-set 25 Slip Angle value or if the slip frequency exceeds a pre-set 25 Split Slip rate based on the selection of 25 System Split Mode setting. Note : the system split setting is effectively an absolute value and therefore a split will occur at the value regardless of the direction of the frequency slip e.g. if an angle of 170 is selected, then starting from 0, a split will occur at +170 or -170 (effectively +190). If a system split occurs during an autoreclose Check Sync operation, with 25 System Sync set to Enabled, the following events occur: - * A System Split event is recorded. * If the 25 DAR Split Mode is set to CS, Check Sync will continue. * If the 25 DAR Split Mode setting has been set to SS, the System Sync function is started. The 25 SS In Progress can be mapped to an output relay or led for alarm indication. The mapped LED will stay on for a minimum time, or can be latched using non self reset LEDs. * If the 25 DAR Split Mode setting has been set to COZ, the Close On Zero function is started. The 25 COZ In Progress can be mapped to an output relay or led for alarm indication. * If the 25 DAR Split Mode has been set to LO, then, a 25 System Split LO output is given which can be mapped to an output relay or led for alarm indication. The relay will stay in this lockout mode until one of the following methods of resetting it is performed: - * 1. The relay is reset from Lockout by binary input or a command. * 2. The CB is manually closed Similarly if a system split occurs during a Manual Close Check Sync operation, with 25 System Sync set to Enabled, the following events occur: - * A System Split event is recorded. * If the 25 MC Split Mode is set to CS, Check Sync will continue. * If the 25 MC Split Mode setting has been set to SS, the System Sync function is started. The 25 SS In Progress can be mapped to an output relay or led for alarm indication. * If the 25 DAR Split Mode setting has been set to COZ, the Close On Zero function is started. The 25 COZ In Progress can be mapped to an output relay or led for alarm indication. 4.9.6 System Sync Reversion If the close conditions of System Sync are not met and a zero slip condition is subsequently detected, by the slip falling below the 25 Split Slip setting, the relay will exit from System Sync mode and revert to Check Synchronising mode. The reversion allows the device to use the wider Check Sync parameters, to allow a close following the restoration of normal operation when the islanded network has been reconnected to the main network by successful reclosure of a parallel connection. Unrestricted (c)2018 Siemens Protection Devices Limited Page 69 of 94 7SR210 & 7SR220 Description of Operation 4.9.7 System Synchronising Mode For the relay to issue a System Sync Close the following conditions have to be met: Both the Bus and Line voltages must be considered Live by the Voltage Monitoring elements. 25 System Sync Angle - the phase difference between the line and bus voltages has to be less than the phase angle setting value and the phase angle has to be decreasing before the element will issue a valid close signal. 25 System Sync Slip, [if Enabled] - the frequency difference between line and bus has to be less than the slip frequency setting value. Slip frequency must be above the 25 Split Slip setting to avoid reversion to Check Synchronising conditions. The settings for 25 System Sync Slip and 25 Split Slip must differ by at least 20 mHz. 25 System Sync Timer, [if Enabled] - the phase angle and voltage blocking features have to be within their parameters for the length of the slip timer setting. If either the phase angle or the voltage elements fall outside of their limits the slip timer is reset. If they subsequently come back in then the slip timer has to time out before an output is given. (This ensures that a close output will not be given if there is a transient disturbance on the system due to e.g. some remote switching operations). 25 Line Undervolts, [if Enabled] - the line voltage has to be above the line under-voltage setting value and also above 5V for an output to be given. 25 Bus Undervolts, [if Enabled] - the bus voltage has to be above the line under-voltage setting value and also above 5V for an output to be given. 25 Volt Differential, [if Enabled] - the difference between the line and bus voltages has to be less than the detector setting value for an output to be given. V The System Synchronising operation of the relay will only be started after a System Split is detected as described in section 4.9.6 during an autoreclose or manual close sequence. SLIP Slip Within Range ? Slip Frequency Setting F Angle Phase Within Range ? AND Phase Decreasing ? Slip Timer Phase Angle Setting Live Line & Live Bus Line U/V Block Block Bus U/V BLock Block D V Block Block Figure 4.9.7-1 4.9.8 & SystemSync Close Slip Timer Setting System Sync Function Close on Zero Mode If the 25 DAR Split Mode or 25 MC Split Mode is set to COZ the relay will apply a Close-On-Zero to the respective closing operation if the synchronising mode changes to System Split. The measured slip frequency and the measured phase difference are used to provide a Close Pulse which will close the CB when the phase difference is reducing and timed with the setting 25 CB Close Time such that the instant of closure is when the phase difference is zero. The slip frequency must be less than the 25 COZ Slip Freq but greater than the 25 Split Slip setting to avoid reversion to Check Synchronising conditions. Since this feature is part of the System Synchronising function, 25 System Sync must also be set to Enabled. Unrestricted Page 70 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation SLIP Slip Within Range ? (> Split Slip & < COZ slip) & Split Slip Setting COZ Slip Frequency Setting F Angle Phase Difference Phase Decreasing & ? & CB Close Time COZ Close Live Line Live Bus Line U/ V Block Block Bus U/ V BLock Block D V Block Block & Figure 4.9.8-1 Close On Zero Function Close on Zero will not be accurate if slow CB times are applied in conjunction with fast slip rates during testing. Practical application limits are shown below: 2 Maximum Slip Frequency (Hz) 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 0 0 200 400 600 800 CB Close Time (ms) Figure 4.9.8-2 Close On Zero Timing 4.10 Live/Dead Indication Outputs are provided to identify each voltage input as either Live or Dead using voltage user settings. These outputs are controlled independently of the 25 Check Synchronising Voltage monitoring elements but operate in the same way. Voltage detectors are provided for each phase input A, B, C & X and inputs Y & Z when fitted. If the voltage on the respective input is below a set threshold level they can be considered to be `dead'. If the voltages are above a voltage setting they are classed as `live'. Independent voltage detectors are provided for both line and bus. If a voltage is in the dead band range then it will be classed as dead until it has reached the live band area. Similarly, if a voltage is live, it continues to be live until it has reached the dead band area. This effectively allows for variable amounts of hysteresis to be set. Figure 4.10-1 illustrates the voltage detector operation. Note: the area between the dead and live zones is not indeterminate. When any voltage is applied to the relay it will ramp up the software RMS algorithm and always pass through the dead zone first. A wide range is provided for live and dead voltage detector levels but the live and dead zones must not overlap. Unrestricted (c)2018 Siemens Protection Devices Limited Page 71 of 94 7SR210 & 7SR220 Description of Operation Figure 4.10-1 Voltage Detector Operation Live and Dead outputs are provided for each voltage input: A Live, B Live, C Live, A Dead, B Dead, C Dead, X Live, Y Live, Z Live, X Dead, Y Dead & Z Dead, Combined outputs are also provided separately to indicate ALL phases Live or Dead: ABC Live, ABC Dead, XYZ Live & XYZ Dead 4.11 Circuit Breaker This menu includes relay settings applicable to both manual close (MC) and auto-reclose (AR) functionality. CB Controls Latched CB controls for closing and tripping can be latched i.e. until confirmation that the action has been completed i.e. binary input is edge triggered when latched. Close CB Delay The Close CB Delay is applicable to manual CB close commands received through a Close CB binary input or via the Control Menu. Operation of the Manual Close CB binary output is delayed by the Close CB Delay setting. NB: During the close countdown period the operation can be terminated by pressing `Cancel' on the fascia. Close CB Pulse The duration of the CB Close Pulse is settable to allow a range of CBs to be used. The Close pulse will be terminated if any protection pick-up operates or a trip occurs. This is to prevent Close and Trip Command pulses existing simultaneously. A 79 Close On Fault Output is given if a pick-up or trip operates during the Close Pulse. This can be independently wired to Lockout. `CB Failed To Open' and `CB Failed to Close' features are used to confirm that a CB has not responded correctly to each Trip and Close Command. If a CB fails to operate, the AR feature will go to lockout. '79 CB Close Fail' is issued if the CB is not closed at the end of the close pulse, CB Close Pulse. Reclaim Timer The `Reclaim time' will start each time a Close Pulse has timed out and the CB has closed. Where a protection pickup is raised during the reclaim time the relay advances to the next part of the reclose sequence. The relay goes to the Lockout state if the CB is open at the end of the reclaim time or a protection operates during the final reclaim time. Unrestricted Page 72 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Blocked Close Delay The close command may be delayed by a Block Close CB signal applied to a binary input. This causes the feature to pause before it issues the CB close command and can be used, for example, to delay CB closure until the CB energy has reached an acceptable level. If the Block signal has not been removed before the end of the defined time, Blocked Close Delay, the relay will go to the lockout state. Open CB Delay The Open CB Delay setting is applicable to CB trip commands received through an Open CB binary input or via the Control Menu. Operation of the Open CB binary output is delayed by the Open CB Delay setting. NB: During the open countdown period the operation can be terminated by pressing `Cancel' on the fascia. Open CB Pulse The duration of the CB open Command pulse is user settable to allow a range of CBs to be used. CB Failed to Open is taken from the Circuit Breaker Failure Element. CB Travel Alarm (DBI) The CB Open and CB Closed binary inputs are continually monitored to track the CB Status. The CB should only ever be in 3 states: CB Status CB Open binary input CB Closed binary input CB is Open 1 0 CB is Closed 0 1 CB is Travelling between the above 2 states 0 0 The Relay goes to Lockout and the CB Alarm output is given where the Travelling condition exists for longer than the CB Travel Alarm setting. An instantaneous CB Alarm is given for a 1/1 state - i.e. where the CB indicates it is both Open and Closed at the same time. Figure 4.11-1 Logic Diagram: Circuit Breaker Status Unrestricted (c)2018 Siemens Protection Devices Limited Page 73 of 94 7SR210 & 7SR220 Description of Operation Trip Time Alarm The CB Trip Time meter displays the measured time between the trip being issued and the CB auxiliary contacts changing state. If this measured time exceeds the Trip Time Alarm time, a Trip Time Alarm output is issued. Trip Time Adjust This allows for the internal delays caused by the relay - especially the delay before a binary input operates - to be subtracted from the measured CB trip time. This gives a more accurate measurement of the time it took for the CB to actually trip. Hot Line In/Out The Hot Line function can be used to provide an immediate trip and auto-reclose inhibit for any Overcurrent, Earth Fault or Sensitive Earth Fault detection. This function is used to increase safety when personnel are working in the vicinity of live primary equipment. When Hot Line is enabled, pickup of any 50, 51, 50G, 51G, 50SEF or 51SEF element will cause an instantaneous trip, bypassing any time delay setting of the element. Any auto-reclose sequence will be inhibited and Autoreclose Lockout will be raised. This feature is not triggered by pick-up or operation of other protection elements such as under/over voltage, frequency, thermal or negative sequence over-current. Additionally, when Hot Line is In, Manual Close is inhibited. This can help to prevent unintended energisation of a dead circuit whilst personnel are working nearby. Hot Line must be switched to Out before the Manual Close action will be successful. Hot Line can be configured to be switched In/Out by binary inputs, function keys or by commands via the communications protocols. There are no other configurable options for Hot Line. Unrestricted Page 74 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 4.12 Quick Logic The `Quick Logic' feature allows the user to input up to 16 logic equations (E1 to E16) in text format. Equations can be entered using Reydisp or at the relay fascia. Each logic equation is built up from text representing control characters. Each can be up to 20 characters long. Allowable characters are: 0, 1, 2, 3, 4, 5, 6, 7, 8, 9 Digit () Parenthesis ! `NOT' Function . `AND' Function ^ `EXCLUSIVE OR' Function + `OR' Function En Equation (number) Fn Function Key (number) `1' = Key pressed, `0' = Key not pressed In Binary Input (number) `1' = Input energised, `0' = Input de-energised Ln LED (number) `1' = LED energised, `0' = LED de-energised On Binary output (number) `1' = Output energised, `0' = Output de-energised Vn Virtual Input/Output (number) `1' = Virtual I/O energised, `0' = Virtual I/O de-energised Example Showing Use of Nomenclature E1= ((I1^F1).!O2)+L1 Equation 1 = ((Binary Input 1 XOR Function Key 1) AND NOT Binary Output 2) OR LED 1 When the equation is satisfied (=1) it is routed through a pick-up timer (En Pickup Delay), a drop-off timer (En Dropoff Delay), and a counter which instantaneously picks up and increments towards its target (En Counter Target). The counter will either maintain its count value En Counter Reset Mode = OFF, or reset after a time delay: En Counter Reset Mode = Single Shot: The En Counter Reset Time is started only when the counter is first incremented (i.e. counter value = 1) and not for subsequent counter operations. Where En Counter Reset Time elapses and the count value has not reached its target the count value is reset to zero. En Counter Reset Mode = Multi Shot: The En Counter Reset Time is started each time the counter is incremented. Where En Counter Reset Time elapses without further count increments the count value is reset to zero. Unrestricted (c)2018 Siemens Protection Devices Limited Page 75 of 94 7SR210 & 7SR220 Description of Operation O D. P. U .D AY EL EL AY .D Figure 4.12-1Sequence Diagram: Quick Logic PU/DO Timers (Counter Reset Mode Off) When the count value = En Counter Target the output of the counter (En) = 1 and this value is held until the initiating conditions are removed when En is instantaneously reset. The output of En is assigned in the OUTPUT CONFIG>OUTPUT MATRIX menu where it can be programmed to any binary output (O), LED (L) or Virtual Input/Output (V) combination. Protection functions can be used in Quick Logic by mapping them to a Virtual Input / Output. Refer to Applications Guide for examples of Logic schemes. Unrestricted Page 76 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Section 5: Supervision Functions 5.1 Circuit Breaker Failure (50BF) The circuit breaker fail function has two time delayed outputs that can be used for combinations of re-tripping or back-tripping. CB Fail outputs are given after elapse of the 50BF-1 Delay or 50BF-2 Delay settings. The two timers run concurrently. The circuit breaker fail protection time delays are initiated either from: An output Trip Contact of the relay (MENU: OUTPUT CONFIG\BINARY OUTPUT CONFIG\Trip Contacts), or A binary or virtual input assigned to 50BF Ext Trig (MENU: INPUT CONFIG\INPUT MATRIX\50BF Ext Trig). A binary or virtual input assigned to 50BF Mech Trip (MENU: INPUT CONFIG\INPUT MATRIX\ 50BF Mech Trip). CB Fail outputs will be issued providing any of the 3 phase currents are above the 50BF Setting or the current in the fourth CT is above 50BF-I4 for longer than the 50BF-n Delay setting, or for a mechanical protection trip the circuit breaker is still closed when the 50BF-n Delay setting has expired - indicating that the fault has not been cleared. Both 50BF-1 and 50BF-2 can be mapped to any output contact or LED. If the CB Faulty input (MENU: INPUT CONFIG\INPUT MATRIX\50BF CB Faulty) is energised when a CB trip is given the time delays 50BF-n Delay will be by-passed and the output given immediately. Operation of the CB Fail elements can be inhibited from: Inhibit 50BF A binary input, virtual input or remote data Comms. Figure 5.1-1 Logic Diagram: Circuit Breaker Fail Protection (50BF) Unrestricted (c)2018 Siemens Protection Devices Limited Page 77 of 94 7SR210 & 7SR220 Description of Operation 5.2 VT Supervision (60VTS) - 7SR22 1 or 2 Phase Failure Detection Normally the presence of negative phase sequence (NPS) or zero phase sequence (ZPS) voltage in a power system is accompanied by NPS or ZPS current. The presence of either of these sequence voltages without the equivalent level of the appropriate sequence current is used to indicate a failure of one or two VT phases. The 60VTS Component setting selects the method used for the detection of loss of 1 or 2 VT phases i.e. ZPS or NPS components. The sequence component voltage is derived from the line voltages; suitable VT connections must be available. The relay utilises fundamental voltage measurement values for this function. The element has user settings 60VTS V and 60VTS I. A VT is considered to have failed where the voltage exceeds 60VTS V while the current is below 60VTS I for a time greater than 60VTS Delay. 3 Phase Failure Detection Under normal load conditions rated PPS voltage would be expected along with a PPS load current within the circuit rating. Where PPS load current is detected without corresponding PPS voltage this could indicate a three phase VT failure. To ensure these conditions are not caused by a 3 phase fault the PPS current must also be below the fault level. The element has a 60VTS VPPS setting, an 60VTS IPPS Load setting and a setting for 60VTS IPPS Fault. A VT is considered to have failed where positive sequence voltage is below 60VTS VPPS while positive sequence current is above IPPS Load and below IPPS Fault level for more than 60VTS Delay then a VT failure will be detected. External MCB A binary input can be set as Ext_Trig 60VTS to allow the 60VTS Delay element to be started from an external MCB operating. Once a VT failure condition has occurred the output is latched on and is reset by any of the following: Voltage is restored to a healthy state i.e. above VPPS setting while NPS voltage is below VNPS setting. Ext Reset 60VTS A binary or virtual input, or function key and a VT failure condition no longer exists. Inhibit 60VTS A binary, virtual input, function key or remote data Comms. Unrestricted Page 78 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 60VTS Element Enabled Disabled & 60VTS Inhibit 60VTS Inhibit 1 or 2 Phase Fail 60VTS Component VL1 VL2 VL3 IL1 IL2 IL3 V Setting V V0 Phase Seq. Filter > V1 V2 I0 Phase Seq. Filter 60VTS Pick-Up NPS/ZPS I Setting I1 I I2 & 60VTS Delay & < >1 3 Phase Fail Ipps Load I1 > S Q R 60VTS Operated 60VTS Operated Ipps I1 < & Vpps Setting V1 < & >1 60VTS Ext_Trig 60VTS Ext_Reset Figure 5.2-1 Logic Diagram: VT Supervision Function (60VTS) 5.3 Busbar VT Fail (60VTF-Bus) - 7SR22 When the optional synchronising function is fitted, the synchronising voltage transformer is utilised to provide an additional monitoring function to check the validity of the measured line and busbar voltages. When the circuit breaker is closed, both voltages should be either Live or Dead. If the Bus voltage indicates that the VT is Dead but the corresponding Line voltage is Live, this raises the Bus VT Fail output. A time delay setting is provided to avoid spurious operations during transient switching conditions. Additionally, this output can be enabled by a setting, 79 LO Bus VT Fail, to apply a Lockout signal to the autoreclose function so that a sequence will not be attempted after a trip occurs if it is known that the voltage measurement is not reliable. A similar setting is available, 79 LO Line VT Fail, which when Enabled will provide a Lockout for a Line VT failure detected by the 60VTS function. Unrestricted (c)2018 Siemens Protection Devices Limited Page 79 of 94 7SR210 & 7SR220 Description of Operation 5.4 CT Supervision (60CTS & 60CTS-I) The relay has two methods of detecting a CT failure, depending on the relay variant. 5.4.1 (60CTS-I) - 7SR21 & 7SR22 The current from each of the Phase Current Transformers is monitored. If one or two of the three input currents falls below the CT supervision current setting CTS-I for more than 60CTS-I Delay then a CT failure output (60CTS-I Operated) is given. If all three input currents fall below the setting, CT failure is not raised. Operation of the CT supervision elements can be inhibited from: Inhibit 60CTS-I A binary input, virtual input or remote data Comms. 60CTS-I Element Enabled Disabled & Inhibit 60CTS 60CTS-I Pick-UP Inhibit 60CTS 60CTS-I Delay 60CTS I 60CTS-I Operated & IL1 < IL2 Any 2 phases but not all 3 IL3 Figure 5.4.1-1 5.4.2 60CTS-I Operated Logic Diagram: CT Supervision Function (60CTS-I) - 7SR21 & 7SR22 (60CTS) - 7SR22 Normally the presence of negative phase sequence (NPS) current in a power system is accompanied by NPS voltage. The presence of NPS current without NPS voltage is used to indicate a current transformer failure. The element has a setting for NPS current level 60CTS Inps and a setting for NPS voltage level 60CTS Vnps. If the negative sequence current exceeds its setting while the negative sequence voltage is below its setting for more than 60CTS Delay then a CT failure output (60CTS Operated) is given. Operation of the CT supervision elements can be inhibited from: Inhibit 60CTS A binary input, virtual input or remote data Comms. 60CTS Element Enabled Disabled Inhibit 60CTS & 60CTS Pick-Up Inhibit 60CTS 60CTS Delay & 60CTS Operated 60CTS Operated VL1 VL2 60CTS Vnps NPS Filter V2 < VL3 IL1 IL2 & 60CTS Inps NPS Filter I2 IL3 > Figure 5.4.2-1 Unrestricted Page 80 of 94 Logic Diagram: CT Supervision Function (60CTS) - 7SR22 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 5.5 Broken Conductor (46BC) The element calculates the ratio of NPS to PPS currents. Where the NPS:PPS current ratio is above 46BC Setting an output is given after the 46BC Delay. The Broken Conductor function can be inhibited from: Inhibit 46BC A binary input, virtual input or remote data Comms. Gn 46BC U/I Guarded Operation of the undercurrent guard function. Figure 5.5-1 Logic Diagram: Broken Conductor Function (46BC) 5.6 Trip / Close Circuit Supervision (74TCS & 74CCS) The relay provides three trip and three close circuit supervision elements. All elements are identical in operation and independent from each other allowing three trip and three close circuits to be monitored. One or more binary inputs can be mapped to 74TCS-n. The inputs are connected into the trip circuit such that at least one input is energised when the trip circuit wiring is intact. If all mapped inputs become de-energised, due to a break in the trip circuit wiring or loss of supply an output is given. The 74TCS-n Delay setting prevents failure being incorrectly indicated during circuit breaker operation. This delay should be greater than the operating time of the circuit breaker. The use of one or two binary inputs mapped to the same Trip Circuit Supervision element (e.g. 74TCS-n) allows the user to realise several alternative monitoring schemes - see `Applications Guide'. Figure 5.6-1 Logic Diagram: Trip Circuit Supervision Feature (74TCS) Unrestricted (c)2018 Siemens Protection Devices Limited Page 81 of 94 7SR210 & 7SR220 Description of Operation Figure 5.6-2 5.7 Logic Diagram: Close Circuit Supervision Feature (74CCS) Inrush Restraint (81HBL2) Inrush restraint detector elements are provided, these monitor the line currents. The inrush restraint detector can be used to block the operation of selected elements during transformer magnetising inrush conditions. The 81HBL2 Bias setting allows the user to select between Phase, Sum and Cross methods of measurement: Phase Each phase is inhibited separately. Sum With this method the square root of the sum of the squares of the second harmonic in each phase is compared to each operate current individually. Cross All phases are inhibited when any phase detects an inrush condition. An output is given where the measured value of the second harmonic component is above the 81HBL2 setting. Figure 5.7-1 Logic Diagram: Harmonic Block Feature (81HBL2) Unrestricted Page 82 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 5.8 Over Fluxing Detector (81HLB5) Over fluxing detector elements monitor the line currents. The inrush restraint detector can be used to block the operation of selected elements during transformer magnetising inrush conditions. The 81HBL5 Bias setting allows the user to select between Phase, Sum and Cross methods of measurement: Phase Each phase is inhibited separately Sum The inrush current from each phase is summated and compared to each operate current individually Cross All phases are inhibited when any phase detects an inrush condition An output is given where the measured fifth harmonic component content is above the 81HBL5 setting. Figure 5.8-1 Logic Diagram: Over Fluxing Detector (81HLB5) Unrestricted (c)2018 Siemens Protection Devices Limited Page 83 of 94 7SR210 & 7SR220 Description of Operation 5.9 Load Blinder (21) Load Blinders are used with directional overcurrent protection elements to block tripping during sustained heavy load periods in distribution networks. A Load Blinder element is provided in the 7SR22 relay with two operating modes, three-phase and single-phase. 5.9.1 Load Blinder (21) Three-Phase Three-phase mode uses positive sequence impedance Z1. Both the negative sequence overcurrent threshold (Blinder I2 > Block) and the under-voltage threshold (Blinder V< Block) are used to block the function. 21LB-3P Angle sets the angle for the load blinder region. 21LB-3P Impedance sets the impedance of the load blinder region. 21LB-3P VPPS sets the level of positive phase sequence voltage. 21LB-3P IPPS sets the level of negative phase sequence current. Operation of the element can be inhibited from: Inhibit LB A binary input, virtual input, function key or remote data communications The design of Load Blinder 3Ph makes consideration that protection blocking should be issued only during definable allowable system power flow conditions i.e. an overcurrent blocking signal can only be issued when: a. b. c. Positive Sequence Voltage Vpps is not significantly changed, when the Vpps is above the 21LB-3P VPPS Setting. AND Negative Sequence Current Inps is lower than 21LB-3P INPS Setting AND Distributed generators feed in PPS current into the system. In case of high load in system due to distributed generation hence resulting in change of Zpps. Zpps is calculated from Vpps and Ipps. The magnitude and angle of Zpps is compared with 21LB-3P Impedance and 21LB-3P Angle to determine if the impedance is in operate or block and/or FWD or REV zone. Figure 5.9.1-1 Unrestricted Page 84 of 94 Logic Diagram: Load Blinder Three-Phase (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 5.9.2 Load Blinder (21) Single-Phase. Single-phase mode uses the normal impedance (Z) of each phase. The overcurrent blocking is phase segregated and is dependent on the individual overcurrent settings per phase. Only the under-voltage threshold (Blinder V < block) can block the function. Distributed generation can cause power flow in reverse direction to normal system operation. Load Impedance Blinders are used to block overcurrent operation for loads above a particular level and angle. A Blinder is an impedance sensing element with a straight-line characteristic when plotted on the R - X plane Figure 5.9.2-1 Logic Diagram: Load Blinder Single-Phase Unrestricted (c)2018 Siemens Protection Devices Limited Page 85 of 94 7SR210 & 7SR220 Description of Operation Load blinders used to block overcurrent relay so that tripping does not occur for load current levels with a P.F. 0.94 to Unity. T1 T2 90MVA 132/33kV -10% to +20% (1%) Z = 8% 1574A Overcurrent Fwd setting: = 90% of 50% =40.5MVA = 709A @ 33kV 1600/1A 33000/110V Fwd Nominal Impedance Z = 1p.u. = VL / (3 x I) +X Point 8 Point 7 Operate Zone Vpps value Block Zone a b Load Impedance Block Zone Phase Fault b -R 0 Load 360 Impedance +R c c a a = 21LB-3P Impedance setting b = 21LB-3P Angle +ve setting c = 21LB-3P Angle -ve setting Point 10 Point 9 Point 1 Point 2 Trip Level I = Vs / Z Point 6 Point 5 Point 3 Point 4 -X Figure 5.9.2-2 Unrestricted Page 86 of 94 Load Blinder and Angle (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation Section 6: Other Features 6.1 Data Communications Two communication ports, COM1 and COM2 are provided. RS485 connections are available on the terminal blocks at the rear of the relay (COM1). A USB port, COM 2, is provided at the front of the relay for local access using a PC. Optionally, additional communication ports are available: 2x fibre optic with ST connectors and 1x IRIG-B - (COM3 and COM 4), 1x RS485 and 1x IRIG-B - (COM 3), 1x RS232 and IRIG-B - (COM 3), 2x Electrical Ethernet with RJ45 connectors IEC 61850 - (COM 3 and COM 4), 2x Optical Ethernet with Duplex LC 100BaseF connectors IEC 61850 - (COM 3 and COM 4). Communication is compatible with Modbus-RTU, IEC60870-5-103 FT 1.2, DNP 3.0 and IEC 61850 transmission and application standards. For communication with the relay via a PC (personal computer) a user-friendly software package, Reydisp Evolution, is available to allow transfer of relay settings, waveform records, event records, fault data records, Instruments/meters and control functions. Reydisp Evolution is compatible with IEC60870-5-103. Data communications operation is described in detail in the Data Communications Definitions section. 6.2 Maintenance The following CB maintenance counters are provided: CB Total Trip Count: Increments on each trip command issued. CB Total Trip Manual Open Selects whether the CB Total Trip Counter is incremented for Manual Open Operations. If disabled, the CB Total Counter will only increment for protection trip commands. CB Delta Trip Count: Additional counter which can be reset independently of the Total Trip Counter. This can be used, for example, for recording trip operations between visits to a substation. CB Delta Trip Manual Open Selects whether the CB Delta Trip Counter is incremented for Manual Open Operations. If disabled, the CB Delta Trip Counter will only increment for protection trip commands. CB Count to AR Block: (Only in Auto-reclose models) Displays the number of CB trips experienced by the CB before the AR is blocked. When the target is reached the relay will only do 1 Delayed Trip to Lockout. An output is available to reset this value. CB Count to AR Block Manual Open: (Only in Auto-reclose models) Selects whether the CB Count to AR Block is incremented for Manual Open Operations. If disabled, the CB Count to AR Block will only increment for protection trip commands. CB Frequent Ops Count Logs the number of trip operations in a rolling window period of one hour. An output is available to reset this counter. Unrestricted (c)2018 Siemens Protection Devices Limited Page 87 of 94 7SR210 & 7SR220 Description of Operation Binary outputs can be mapped to each of the above counters, these outputs are energised when the user defined Count Target or Alarm Limit is reached. The above counters can be triggered and reset from a binary input or command. 6.2.1 I2t CB Wear An I2t counter is also included; this can provide an estimation of contact wear and maintenance requirements. The algorithm works on a per phase basis, measuring the arcing current during faults. The I2t value at the time of trip is added to the previously stored value and an alarm is given when any one of the three phase running counts exceeds the set Alarm limit. The (t) value is the time between CB contacts separation when an arc is formed, Separation Time, and the CB Clearance time. The I2t value can also triggered and reset from a binary input or command. 6.2.2 Output Matrix Test The feature is only visible from the Relay fascia and allows the user to operate the relays functions. The test of the function will automatically operate any Binary Inputs or LED's already assigned to that function. Any protection function which is enabled in the setting menu will appear in the Output Matrix Test. Unrestricted Page 88 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 6.3 Data Storage 6.3.1 General The relay stores three types of data records: relay event records, analogue/digital waveform records and fault records. Data records are backed up in non-volatile memory and are permanently stored even in the event of loss of auxiliary d.c. supply voltage. 6.3.2 Event Records The event recorder feature allows the time tagging of any change of state (Event) in the relay. As an event occurs, the actual event condition is logged as a record along with a time and date stamp to a resolution of 1 millisecond. There is capacity for a maximum of 5000 event records that can be stored in the relay and when the event buffer is full any new record will over-write the oldest. Stored events can be erased using the DATA STORAGE>Clear Events setting. The following events are logged: Change of state of Binary outputs. Change of state of Binary inputs. Change of Settings and Settings Group. Change of state of any of the control functions of the relay. Protection element operation. All events can be blocked or made available and uploaded over the data communications channel(s) and can be displayed in the `Reydisp Evolution' package in chronological order, allowing the sequence of events to be viewed. Events are also made available spontaneously to an IEC 60870-5-103, Modbus RTU or DNP3.0 compliant control system. The function number and event number can also be changed. The events are selected and edited using the Reydisp software tool. 6.3.3 Waveform Records. Waveform records provide a trace of the instantaneous magnitude of each analogue input channel and the status of each binary channel i.e. each binary input, binary output, virtual I/O and LED, against time for the duration of the record. The values are recorded at every digital sampling point used by the relay software. Each recorded analogue waveform displays an input identifier, minimum value, maximum value and the instantaneous values at both cursor positions (user variable). Each binary waveform displays the input/output number and the initiating condition(s) e.g. external input or protection element. Triggering of waveform storage is configured from the `Settings > DATA STORAGE > WAVEFORM STORAGE' menu. Triggering is automatically initiated from operation of any of the selected protection or control elements. Waveform storage can also be triggered from the relay fascia, from a suitably programmed binary input or via the data comms channel(s). Waveforms are sampled at a rate of 32 samples per cycle. The latest 10 records are stored; the most recent is waveform 1. Records are archived by the relay during quiescent periods. The duration of each stored record is 1s, 2s, 5s or 10s. The user can also specify the percentage of waveform storage prior to waveform triggering. When the waveform archive buffer is full (i.e. 10 records are stored) the triggering of a new waveform record causes the oldest record - waveform 10 - to be overwritten. Stored waveforms can be deleted from the relay fascia using the DATA STORAGE > Clear Waveforms setting or via Reydisp. Unrestricted (c)2018 Siemens Protection Devices Limited Page 89 of 94 7SR210 & 7SR220 Description of Operation 6.3.4 Fault Records Up to 100 fault records are stored and can be downloaded from the relay through the communication interface, with time & date of trip, measured quantities and type of fault. The last 10 fault records are displayed on the relay fascia. Fault records provide a summary of the relay status at the time of trip, i.e. the element that issued the trip, any elements that were picked up, the fault type, LED indications, date and time. The Max Fault Rec. Time setting sets the time period from fault trigger during which the operation of any LEDs is recorded. The relay can be set to automatically display the fault record on the LCD when a fault occurs by enabling the SYSTEM CONFIG> Trip Alert setting. When the trip alert is enabled the fault record will be displayed until the fault is removed. When examined together the event records and the fault records will detail the full sequence of events leading to a trip. Fault records are stored in a rolling buffer, with the oldest faults overwritten. The fault storage can be cleared with the DATA STORAGE>Clear Faults setting or using Reydisp Evolution via Relay > Data Records > Reset Data Log Record. 6.3.5 Demand The Demand feature can be used to build trend and maximum/minimum demand records. Up to 10,080 individual time stamped records can be stored at a user defined rate e.g. 35 days @ 5 minute intervals and > 1 year @ 1 hour intervals. Maximum, minimum and mean values of line current, voltage and power (where applicable) are available as instruments which can be read in the relay INSTRUMENTS MENU or via Reydisp Evolution. In the menu DATA STORAGE > DEMAND / DATA LOG: The Data Log Period setting is used to define the period between stored samples. The Gn Demand Window setting defines the maximum period of time over which the demand values are calculated. A new set of demand values is established after expiry of the set time. The Gn Demand Window Type is the mode used to calculate demand values and can be set to FIXED or PEAK or ROLLING: When set to FIXED the maximum, minimum and mean values demand statistics are calculated over fixed Window duration. At the end of each window the internal statistics are reset and a new window is started. When set to PEAK the maximum and minimum values since the feature was reset are recorded. When set to ROLLING the maximum, minimum and mean values demand statistics are calculated over a moving Window duration. The internal statistics are updated when the window advances. The statistics can be reset from a binary input or communication command, after a reset the update period and window are immediately restarted. 6.3.6 Data Log The Data log feature can be used to build trend and maximum/minimum demand records. Up to 10,080 individual time stamped records of each phase current and voltage (where fitted) analogue signal are recorded and stored at a user defined rate e.g. 35 days @ 5 minute intervals and > 1 year @ 1 hour intervals. Unrestricted Page 90 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 6.3.7 Energy Storage The measured Power is continuously integrated (over a one-second window) to produce 4 Energy quantities: * Active Export Energy (W) * Active Import Energy (W) * Reactive Export Energy (VAr) * Reactive Import Energy (VAr) The Direction of Energy transfer is set by: SYSTEM CONFIG> Export Power/Lag VAr. With both Export Power (W) and Lag VAr (VAr) set to be +ve, the Direction of Energy transfer will follow the IEC convention, as shown in the figure. REACTIVE ENERGY IMPORT (vars reverse) IEC CONVENTION : -ve vars +90 POWER FACTOR LAGGING ACTIVE (W) IMPORT REACTIVE (VAr) IMPORT ACTIVE ENERGY IMPORT (watts reverse) IEC CONVENTION : -ve watts POWER FACTOR LEADING ACTIVE (W) EXPORT REACTIVE (VAr) IMPORT 0 180 POWER FACTOR LEADING ACTIVE (W) IMPORT REACTIVE (VAr) EXPORT ACTIVE ENERGY EXPORT (watts forward) IEC CONVENTION : +ve watts POWER FACTOR LAGGING ACTIVE (W) EXPORT REACTIVE (VAr) EXPORT -90 REACTIVE ENERGY EXPORT (vars forward) IEC CONVENTION : +ve vars Figure 6.3.7-1 Energy Direction Convention Setting either the Export Power (W) or Lag VAr (VAr) to be -ve, will reverse the Direction of the Energy transfer for these quantities. So forward VAr will then be reported as Imported Reactive Energy, and forward Watts will be reported as Exported Active Energy. When the accumulated Energy quantities reach a set increment, the Relay issues a pulse to the binary outputs: OUTPUT CONFIG/OUTPUT MATRIX> Active Exp Pulse, Active Imp Pulse, Reactive Exp Pulse and Reactive Imp Pulse. The Energy increments are set by the settings: DATA STORAGE/ENERGY STORAGE> Active Exp Energy Unit, Active Imp Energy Unit, Reactive Exp Energy Unit and Reactive Imp Energy Unit. These setting also define the resolution of the stored energy values reported by instruments and communications protocols. The value is stored in the range 0-999999 which continues from zero automatically when 999999 is reached. Unrestricted (c)2018 Siemens Protection Devices Limited Page 91 of 94 7SR210 & 7SR220 Description of Operation 6.3.8 Fault Locator The relay provides a single-end type fault locator which is able to estimate the fault position using analogue information measured by the relay at one end of the protected circuit during the short duration of the fault. Following relay operation due to a system fault, the fault waveform record is automatically evaluated to establish the fault type in terms of the phase(s) affected and the relevant current and voltage is used to calculate the fault impedance. The relay compares this information to a line model based on characteristic impedance parameters which are input to the relay as settings and provides an output estimate of the fault location. This data is presented as a percentage of line length or a distance in miles or kilometres. The Positive Sequence Impedance on the protected line must be provided to the relay as settings for impedance magnitude and characteristic phase angle to enable the distance to fault to be calculated. The Earth Fault return impedance is specified in terms of the ratio of zero to positive sequence impedance magnitudes and the characteristic phase angle of the zero sequence impedance. The characteristic angle of the zero sequence impedance is often significantly different to that of the positive sequence impedance. When power systems are earthed through compensation (Peterson) coils, the earth fault currents are extremely low and are not proportional to fault location. Impedance based fault location cannot be used for earth faults. Phase-to-phase fault location can be estimated. On networks of this type it is possible to have two earth-faults on the network simultaneously on different phases of the same circuit which will appear as a phase-to-phase fault. This is known as a Cross-Country fault. In these cases the measured impedance cannot give an accurate estimate of the fault condition. The 7SR22 relay provides detection of this condition using the measured zero sequence voltage to positive sequence voltage ratio (U0/U1) to allow the possible cross-country fault to be reported. This threshold is adjustable by a user setting. Fault Location is reported for faults calculated in a zone which extends to 200 % of the forward line impedance and 10 % in the reverse direction. High resistance fault results where fault resistance is calculated as up to 20 times the line impedance are reported. For faults beyond these limits, the message `No Location' is reported. The Fault Location estimation is initiated by operation of the Trip Output. Some protection elements may be set to provide tripping for system conditions where a fault location is not applicable. The initiation of the Fault Locator can be inhibited by user settings. The settings for the Fault Locator are found as a sub-menu in the Data Storage menu. The Fault Locator result data is available in the Fault Data records and can be viewed at the relay fascia and downloaded from the relay. 6.4 Metering The metering feature provides real-time data available from the relay fascia in the `Instruments Mode' or via the data communications interface. The Primary values are calculated using the CT and VT ratios set in the CT/VT Config menu. The text displayed in the relays `Instruments Mode' associated with each value can be changed from the default text using the Reydisp software tool. The user can add the meters that are most commonly viewed to a `Favourites' window by pressing the `ENTER' key when viewing a meter. The relay will scroll through these meters at an interval set in the System Config/Favourite Meters Timer menu. Unrestricted Page 92 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Description of Operation 6.5 Operating Mode The relay has three operating modes, Local, Remote and Out of Service. The following table identifies the functions operation in each mode. The modes can be selected by the following methods: SYSTEM CONFIG>RELAY MODE setting, a Binary Input or Command Table 6.5-1 Operation Mode OPERATION REMOTE MODE LOCAL MODE SERVICE MODE Enabled Disabled Disabled Setting Option Enabled Disabled Enabled Enabled Setting Option Enabled Disabled Disabled Disabled Enabled Disabled Enabled Enabled Enabled Enabled Disabled Disabled Enabled Enabled Enabled Enabled Enabled Enabled Disabled Disabled Disabled Changing of Settings Rear Ports Fascia USB Enabled Enabled Disabled Disabled Enabled Enabled Enabled Enabled Enabled Historical Information Waveform Records Event Records Fault Information Setting Information Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Enabled Control Rear Ports Fascia (Control Mode) USB Binary Inputs Binary Outputs Reporting Spontaneous IEC DNP General Interrogation IEC DNP MODBUS 6.6 Control Mode This mode provides convenient access to commonly used relay control and test functions. When any of the items listed in the Control Mode list are selected, control is initiated by pressing the ENTER key. The user is prompted to confirm the action, again by pressing the ENTER key, before the command is executed. Control Mode commands are password protected using the Control Password function - see section 6.9. 6.7 Real Time Clock Time and date can be set either via the relay fascia using appropriate commands in the System Config menu, via the data comms channel(s) or via the optional IRIG-B input. Time and date are maintained while the relay is deenergised by a back up storage capacitor. In order to maintain synchronism within a substation, the relay can be synchronised to the nearest second or minute using the IEC 60870-5-103 protocol, optional IRIG-B input or binary input. The default date is set at 01/01/2000 deliberately to indicate the date has not yet been set. When editing the Time, only the hours and minutes can be edited. When the user presses ENTER after editing the seconds are zeroed and the clock begins running. Unrestricted (c)2018 Siemens Protection Devices Limited Page 93 of 94 7SR210 & 7SR220 Description of Operation 6.7.1 Time Synchronisation - Data Communication Interface Where the data comms channel(s) is connected the relay can be directly time synchronised using the global time synchronisation. This can be from a dedicated substation automation system or from `Reydisp Evolution' communications support software. 6.7.2 Time Synchronisation - Binary Input A binary input can be mapped Clock Sync from BI. The seconds or minutes will be rounded up or down to the nearest value when the BI is energised. This input is leading edge triggered. 6.7.3 Time Synchronisation - IRIG-B (Optional) A BNC connector on the relay rear provides an isolated IRIG-B time synchronisation port. The IRIG-B input expects a modulated 3-6 Volt signal and provides time synchronisation to the nearest millisecond. 6.8 Settings Groups The relay provides eight groups of settings - Group number (Gn) 1 to 8. At any one time only one group of settings can be `active' - SYSTEM CONFIG>Active Group setting. It is possible to edit one group while the relay operates in accordance with settings from another `active' group using the View/Edit Group setting. Some settings are independent of the active group setting i.e. they apply to all settings groups. This is indicated on the top line of the relay LCD - where only the Active Group No. is identified. Where settings are group dependent this is indicated on the top line of the LCD by both the Active Group No. and the View Group No. being displayed. A change of settings group can be achieved either locally at the relay fascia, remotely over the data comms channel(s) or via a binary input. When using a binary input an alternative settings group is selected only whilst the input is energised (Select Grp Mode: Level triggered) or latches into the selected group after energisation of the input (Select Grp Mode: Edge triggered). 6.9 Password Feature The relay incorporates two levels of password protection - one for settings, the other for control functions. The programmable password feature enables the user to enter a 4 character alpha numeric code to secure access to the relay functions. A Password of NONE indicates that a Password has not been set and that the Password feature is disabled. Where a Relay is delivered with the Password already set, this will be AAAA. The password must be entered twice as a security measure against accidental changes. Once a password has been entered then it will be required thereafter to change settings or initiate control commands. Passwords can be deactivated by using the password to gain access and by entering the password NONE. Again this must be entered twice to de-activate the security system. As soon as the user attempts to change a setting or initiate control the password is requested before any changes are allowed. Once the password has been validated, the user is `logged on' and any further changes can be made without re-entering the password. If no more changes are made within 1 hour then the user will automatically be `logged off', re-enabling the password feature. The Settings Password prevents unauthorised changes to settings from the front fascia or over the data comms channel(s). The Control Password prevents unauthorised operation of controls in the relay Control Menu from the front fascia. The password validation screen also displays a numerical code. If the password is lost or forgotten, this code should be communicated to Siemens Protection Devices Ltd. and the password can be retrieved. Unrestricted Page 94 of 94 (c)2018 Siemens Protection Devices Limited 7SR210 Non-Directional Relay 7SR220 Directional Relay Configuration Guide Unrestricted The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Configuration Guide Document Release History This document is issue 2017/12. The list of revisions up to and including this issue is: 2011/05 First issue 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions amended drawings and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/11 Typographical revisions and format. 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions. Software Revision History 2011/05 2435H85008R7a-7a (7SR210) First Release 2435H85009R7a-7a (7SR220) 2013/01 2435H85008R7c-7b (7SR210) 2435H85009R7c-7b (7SR220) 2014/06 2435H85008R7f-7d (7SR210) 2435H85009R7f-7d (7SR220) 2015/06 2435H85008R8a-7e (7SR210) 2435H85009R8a-7f (7SR220) 2016/02 2435H85008R8b-7f (7SR210) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Added Fault Locator feature and Check Sync feature. Fault data transmitted over 103. Additional communications data, control features, meters. Added Power Factor Meters, Load Blinding feature, Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. 2435H85009R8b-7f (7SR220) 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Unrestricted Page 2 of 14 Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing, 67SEF Compensated Network, 67SEF Wattmetric. Increased I/O. Event Data on LCD. (c) 2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Configuration Guide Contents Document Release History ................................................................................................................................. 2 Software Revision History .................................................................................................................................. 2 Contents............................................................................................................................................................ 3 Section 1: Introduction ....................................................................................................................................... 4 1.1 Relay Menus And Display .................................................................................................................. 4 1.2 Operation Guide ................................................................................................................................ 6 1.2.1 User Interface Operation ...................................................................................................... 6 Section 2: Configuring the Relay Using Reydisp Evolution .................................................................................. 9 2.1 Physical Connection .......................................................................................................................... 9 2.1.1 Front USB connection .......................................................................................................... 9 2.1.2 Standard rear RS485 connection ........................................................................................ 10 2.1.3 Optional rear fibre optic connection ..................................................................................... 10 2.1.4 Optional rear RS485 + IRIG-B connection ........................................................................... 11 2.1.5 Optional rear RS232 + IRIG-B connection ........................................................................... 11 2.1.6 Optional Rear EN100 Ethernet Module ............................................................................... 12 2.1.7 Configuring Relay Data Communication .............................................................................. 12 2.1.8 Connecting to the Relay via Reydisp Evolution .................................................................... 14 List of Figures Figure 1.1-1 Menu Navigation ............................................................................................................................ 4 Figure 1.1-2 Fascia Contrast symbol .................................................................................................................. 4 Figure 1.1-3 Relay Fascia (Please note fascia may differ from illustration) ........................................................... 5 Figure 1.2.1-1 Relay Identifier Screen................................................................................................................. 6 Figure 1.2.1-2 Typical Menu Structure for 7SR21 relay ....................................................................................... 7 Figure 1.2.1-3 Typical Menu Structure for 7SR22 relay ....................................................................................... 8 Figure 2.1.1-1 USB connection to a PC .............................................................................................................. 9 Figure 2.1.2-1 Standard rear RS485 connection to a PC ................................................................................... 10 Figure 2.1.3-1 Additional (Optional) rear fibre optic connection to a PC.............................................................. 10 Figure 2.1.4-1 Additional (Optional) rear RS485 + IRIG-B connection to a PC .................................................... 11 Figure 2.1.5-1 Additional (Optional) rear RS232 + IRG-B connection to a PC ..................................................... 11 Figure 2.1.6-1 EN100 Ethernet Module............................................................................................................. 12 Figure 2.1.8-1 PC Comm Port Selection ........................................................................................................... 14 Unrestricted (c) 2018 Siemens Protection Devices Limited Page 3 of 1 7SR210 & 7SR220 Configuration Guide Section 1: Introduction 1.1 Relay Menus And Display All relay fascias contain the same access keys although the fascias may differ in appearance from model to model. The basic menu structure is also the same in all products and consists of four main menus, these being, Settings Mode - allows the user to view and (if allowed via the settings mode password) change settings in the relay. Instruments Mode - allows the user to view the relay meters e.g. current, voltage etc. Fault Data Mode - allows the user to view the type and data of any fault that the relay has detected. Control Mode - allows the user to control external plant under the relays control for example the CB (if allowed via the control mode password) Event Data Mode - allows the user to view the events which have occured within the relay. The menus can be viewed via the LCD by pressing the access keys as below, Figure 1.1-1 Menu Navigation Pressing CANCEL returns to the Identifier screen LCD Contrast To change the contrast on the LCD insert a flat nosed screwdriver into the screwhead below the contrast symbol, turning the screwhead left or right decreases and increases the contrast of the LCD. Figure 1.1-2 Fascia Contrast symbol Unrestricted Page 4 of 14 (c) 2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Configuration Guide Figure 1.1-3 Relay Fascia (Please note fascia may differ from illustration) Unrestricted (c) 2018 Siemens Protection Devices Limited Page 5 of 1 7SR210 & 7SR220 Configuration Guide 1.2 Operation Guide 1.2.1 USER INTERFACE OPERATION The basic menu structure flow diagram is shown in Figure 1.2-2. This diagram shows the main modes of display: Settings Mode, Instrument Mode, Fault Data Mode and Control Mode. When the relay leaves the factory all data storage areas are cleared and the settings set to default as specified in settings document. When the relay is first energised the user is presented with the following message: 7SR220 _______________________________ ENTER to CONTROL Figure 1.2.1-1 Relay Identifier Screen On the factory default setup the relay LCD should display the relay identifier, on each subsequent power-on the screen that was showing before the last power-off will be displayed. The push-buttons on the fascia are used to display and edit the relay settings via the LCD, to display and activate the control segment of the relay, to display the relays instrumentation and Fault data and to reset the output relays and LED's. The five push-buttons have the following functions: READ DOWN READ UP Used to navigate the menu structure. ENTER The ENTER push-button is used to initiate and accept setting changes. When a setting is displayed pressing the ENTER key will enter the edit mode, the setting will flash and can now be changed using the or buttons. When the required value is displayed the ENTER button is pressed again to accept the change. When an instrument is displayed pressing ENTER will toggle the instruments favourite screen status. CANCEL This push-button is used to return the relay display to its initial status or one level up in the menu structure. Pressed repeatedly will return to the Relay Identifier screen. It is also used to reject any alterations to a setting while in the edit mode. TEST/RESET This push-button is used to reset the fault indication on the fascia. When on the Relay Identifier screen it also acts as a lamp test button, when pressed all LEDs will momentarily light up to indicate their correct operation. It is also moves the cursor right when navigating through menus and settings. Unrestricted Page 6 of 14 (c) 2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Configuration Guide 7SR21 ARGUS ENTER to CONTROL SETTINGS MODE CONTROL MODE CB TRAVELLING CLOSE I OPEN AR : OUT OF SERVICE IN I OUT AR : TRIP & RECLOSE CONFIRM ACTION AR : TRIP & LOCKOUT CONFIRM ACTION HOTLINE WORKING : OUT IN I OUT E/F IN IN I OUT SEF IN IN I OUT INST PROT'N : IN IN I OUT Set L Or R : L Or R CONFIRM ACTION Set Remote : L Or R CONFIRM ACTION INSTRUMENTS MODE FAULT DATA MODE SYSTEM CONFIG FAVOURITE METERS NUMBER OF FAULTS CT/VT CONFIG CURRENT METERS THERMAL METERS FUNCTION CONFIG CURRENT PROT'N EVENT DATA MODE PHASE OVERCURRENT 51-1 51-2 50-1 50-2 AUTORECLOSE METERS MAINTENANCE METERS GENERAL ALARM METERS COLD LOAD DERIVED E/F MEASURED E/F CONFIRM ACTION Set Service : L Or R CONFIRM ACTION 51G-1 51G-2 50G-1 50G-2 DEMAND METERS BINARY INPUT METERS BINARY OUTPUT METERS VIRTUAL METERS COMMUNICATION METERS SENSITIVE E/F Set Local : L Or R 51N-1 51N-2 50N-1 50N-2 51SEF-1 51SEF-2 50SEF-1 50SEF-2 MISCELLANEOUS METERS QUICKLOGIC METERS RESTRICTED E/F NPS OVERCURRENT 46IT 46DT UNDER CURRENT 37-1 37-2 37G-1 37G-2 THERMAL SUPERVISION CB FAIL CT SUPERVISION BROKEN CONDUCTOR TRIP CCT SUPERVISION INRUSH DETECTOR CONTROL & LOGIC AUTORECLOSE PROT'N AUTORECLOSE CONFIG MANUAL CB CLOSE CIRCUIT BREAKER QUICK LOGIC INPUT CONFIG INPUT MATRIX FUNCTION KEY MATRIX BINARY INPUT CONFIG GENERAL ALARMS OUTPUT CONFIG OUTPUT MATRIX BINARY OUTPUT CONFIG LED CONFIG PICKUP CONFIG MAINTENANCE CB COUNTERS I^2T CB WEAR DATA STORAGE DEMAND/DATA LOG WAVEFORM STORAGE FAULT STORAGE COMMUNICATIONS Figure 1.2.1-2 Typical Menu Structure for 7SR21 relay Unrestricted (c) 2018 Siemens Protection Devices Limited Page 7 of 1 7SR210 & 7SR220 Configuration Guide 7SR22 ARGUS ENTER to CONTROL CONTROL MODE CB TRAVELLING CLOSE I OPEN SETTINGS MODE INSTRUMENTS MODE FAULT DATA MODE SYSTEM CONFIG FAVOURITE METERS NUMBER OF FAULTS CURRENT METERS AR : OUT OF SERVICE IN I OUT CT/VT CONFIG AR : TRIP & RECLOSE CONFIRM ACTION FUNCTION CONFIG AR : TRIP & LOCKOUT CONFIRM ACTION HOTLINE WORKING : OUT IN I OUT E/F IN IN I OUT SEF IN IN I OUT INST PROT'N : IN IN I OUT CURRENT PROT'N EVENT DATA MODE VOLTAGE METERS PHASE OVERCURRENT VOLTAGE CONT O/C 51-1 51-2 51-3 51-4 50-1 50-2 50-3 50-4 FREQUENCY METERS POWER METERS ENERGY METERS COLD LOAD DERIVED E/F 51N-1 51N-2 51N-3 51N-4 50N-1 50N-2 50N-3 50N-4 MEASURED E/F 51G-1 51G-2 51G-3 51G-4 50G-1 50G-2 50G-3 50G-4 SENSITIVE E/F 51SEF-1 51SEF-2 51SEF-3 51SEF-4 50SEF-1 50SEF-2 50SEF-3 50SEF-4 RESTRICTED E/F NPS OVERCURRENT 46IT 46DT UNDER CURRENT 37-1 37-2 DIRECTIONAL METERS THERMAL METERS AUTORECLOSE METERS MAINTENANCE METERS GENERAL ALARM METERS BINARY INPUT METERS BINARY OUTPUT METERS VIRTUAL METERS THERMAL VOLTAGE PROT'N PHASE U/O VOLTAGE 27/59-1 27/59-2 27/59-3 27/59-4 Vx U/O VOLTAGE NPS OVERVOLTAGE NEUTRAL OVERVOLTAGE U/O FREQUENCY SUPERVISION CB FAIL COMMUNICATION METERS MISCELLANEOUS METERS 47-1 47-2 59NIT 59NDT 81-1 81-2 81-3 81-4 81-5 81-6 VT SUPERVISION CT SUPERVISION BROKEN CONDUCTOR TRIP CCT SUPERVISION INRUSH DETECTOR DEMAND CONTROL & LOGIC AUTORECLOSE PROT'N AUTORECLOSE CONFIG MANUAL CLOSE CIRCUIT BREAKER QUICK LOGIC INPUT CONFIG INPUT MATRIX FUNCTION KEY MATRIX BINARY INPUT CONFIG FUNCTION KEY CONFIG GENERAL ALARMS OUTPUT CONFIG OUTPUT MATRIX BINARY OUTPUT CONFIG LED CONFIG PICKUP CONFIG CB MAINTENANCE CB COUNTERS I^2T CB WEAR DATA STORAGE COMMUNICATIONS Figure 1.2.1-3 Typical Menu Structure for 7SR22 relay Unrestricted Page 8 of 14 (c) 2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Configuration Guide Section 2: Configuring the Relay Using Reydisp Evolution To set the relay using the communication port the user will need the following:PC with Reydisp Evolution Installed. (This can be download from our website www.energy.siemens.com and found under the submenu `Software'). This software requires windows 2000-service pack 4 or above, or windows XP with service pack 2 or above. 2.1 Physical Connection The relay can be connected to Reydisp Evolution via any of the communication ports on the relay. Suitable communication Interface cable and converters are required depending which port is being used. 2.1.1 FRONT USB CONNECTION To connect your pc locally via the front USB port. Figure 2.1.1-1 USB connection to a PC Unrestricted (c) 2018 Siemens Protection Devices Limited Page 9 of 1 7SR210 & 7SR220 Configuration Guide 2.1.2 STANDARD REAR RS485 CONNECTION Figure 2.1.2-1 Standard rear RS485 connection to a PC 2.1.3 OPTIONAL REAR FIBRE OPTIC CONNECTION Figure 2.1.3-1 Additional (Optional) rear fibre optic connection to a PC Sigma devices have a 25 pin female D connector with the following pin out. Pin 2 3 4 5 6 7 8 20 Unrestricted Page 10 of 14 Function Transmit Data Received Data Request to Send Clear to Send Data set ready Signal Ground Received Line Signal Detector Data Terminal Ready (c) 2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Configuration Guide 2.1.4 OPTIONAL REAR RS485 + IRIG-B CONNECTION Figure 2.1.4-1 Additional (Optional) rear RS485 + IRIG-B connection to a PC 2.1.5 OPTIONAL REAR RS232 + IRIG-B CONNECTION Figure 2.1.5-1 Additional (Optional) rear RS232 + IRG-B connection to a PC Pin 1 2 3 4 5 6 7 8 9 Function Carrier Direct (CD) Receive Data (RXD) Transmit Data (TXD) Data Terminal Ready (DTR) Signal Ground (GND) Data set ready (DSR) Request to send (RTS) Clear to Send (CTS) Ring Indicator (RI) Unrestricted (c) 2018 Siemens Protection Devices Limited Page 11 of 7SR210 & 7SR220 Configuration Guide 2.1.6 OPTIONAL REAR EN100 ETHERNET MODULE Connections are made on the rear underside of the relay either RJ45 sockets (electrical) or Duplex LC (fibre optic) connectors depending on the option ordered. Ethernet - EN100-E Ethernet - EN100-O Ch 1 Ch 2 Ch 1 LED yellow LED yellow LED green Ch 2 LED green EN100 Module - RJ45 Interface EN100 Module - Duplex-LC Interface Green LED (Physical Link) Off - No link On - Link present Yellow LED (Activity) Off - No traffic On/flashing - Traffic Figure 2.1.6-1 EN100 Ethernet Module 2.1.7 CONFIGURING RELAY DATA COMMUNICATION Using the keys on the relay fascia scroll down the settings menu's into the `communications' menu and change the settings for the communication port used on the relay. All of the below settings may not be available in all relay types. Reydisp Evolution software uses IEC60870-5-103 protocol to communicate. COM1 - Standard RS485 Rear Port COM2 - USB Port COM3 - Optional Fibre Optic, RS485, RS232 or Ethernet Port COM4 - Additional (Optional) Rear Connection** LAN - Optional Ethernet Ports Unrestricted Page 12 of 14 (c) 2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Configuration Guide Setting name Range Default Units Address given to relay to identify that relay from others which may be using the same path for communication as other relays for example in a fibre optic hub COM1 is the rear mounted RS485 port 1 - 254 for IEC60870-5-103 Station Address 0 - 247 for Modbus RTU 0 0 - 65520 for DNP3.0 OFF, IEC60870-5-103, COM1-RS485 Protocol MODBUS-RTU, DNP3.0 Notes IEC60870-5103 COM1-RS485 Baud Rate 75 110 150 300 600 1200 2400 4800 9600 19200 38400 19200 COM1-RS485 Parity NONE, ODD, EVEN EVEN COM2-USB Protocol OFF, IEC60870-5-103, DNP3.0, MODBUS-RTU, ASCII IEC60870-5103 COM2 is the front USB port COM2-USB Baud Rate 75 110 150 300 600 1200 2400 4800 9600 19200 38400 57600 115200 230400 460800 921600 Auto detects Auto detects baud rate via Connection Manager Setting COM2-USB Parity NONE, ODD, EVEN EVEN COM3 Protocol OFF, IEC60870-5-103, MODBUS-RTU, DNP3.0 IEC6-0870-5103 COM3 Baud Rate 75 110 150 300 600 1200 2400 4800 9600 19200 38400 57600 115200 57600 COM3 Parity NONE, ODD, EVEN EVEN COM3 Line Idle* LIGHT ON, LIGHT OFF LIGHT OFF COM3 Data echo* ON, OFF OFF COM4 Protocol** OFF, IEC60870-5-103, MODBUS-RTU, DNP3.0 OFF COM4 Baud Rate** 75 110 150 300 600 1200 2400 4800 9600 19200 38400 19200 COM4 Parity** NONE, OFF, EVEN EVEN COM4 Line Idle** LIGHT ON, LIGHT OFF LIGHT OFF COM4 Data echo** ON, OFF OFF DNP3 Unsolicited Events ENABLED, DISABLED DISABLED Setting is only visible when a port protocol is set to DNP3. DNP3 Destination Address 0 ... 65534 0 Setting is only visible when a port protocol is set to DNP3. DNP3 Application Timeout 5, 6 ... 299, 300 10s COM3 This is an optional rear mounted connection COM4 This is an optional rear mounted connection Secon ds Setting is only visible when a port Protocol is set to DNP3 *Not applicable for RS485 or RS232 interface modules. **Fibre Optic Module only Unrestricted (c) 2018 Siemens Protection Devices Limited Page 13 of 7SR210 & 7SR220 Configuration Guide 2.1.8 CONNECTING TO THE RELAY VIA REYDISP EVOLUTION When Reydisp Evolution software is running all available communication ports of the PC will automatically be detected. On the start page tool bar open up the sub-menu File > Connect. The `Communication Manager' window will display all available communication ports. With the preferred port highlighted, select the `Properties' option and ensure the baud rate and parity match that selected in the relay Data Comms settings. Select `Connect' to initiate the relay-PC connection. Figure 2.1.8-1 PC Comm Port Selection Via the Relay > Set Address > Address set the relay address (1-254) or alternatively search for connected devices using the Relay > Set Address > Device Map. The relay can now be configured using the Reydisp Evolution software. Please refer to the Reydisp Evolution Manual for further guidance. Unrestricted Page 14 of 14 (c) 2018 Siemens Protection Devices Limited 7SR210 Non-Directional Relay Instrumentation Guide Unrestricted The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2018 Siemens Protection Devices Limited 7SR210 Instrumentation Guide Document Release History This document is issue 2017/12. The list of revisions up to and including this issue is: - 2011/05 First issue 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/11 Typographical revisions and format 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. Software Revision History 2011/05 2435H85008R7a-7a (7SR210) First Release 2013/01 2435H85008R7c-7b (7SR210) 2014/06 2435H85008R7f-7d (7SR210) 2015/06 2435H85008R8a-7f (7SR210) 2016/02 2435H85008R8b-7f (7SR210) 2435H85008R8e-8a (7SR210) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Fault data transmitted over 103. Additional communications data control features, meters. Added Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. Event Data on LCD. 2017/08 Unrestricted Page 2 of 12 (c) 2018 Siemens Protection Devices Limited 7SR210 Instrumentation Guide Contents Document Release History................................................................................. 2 Software Revision History .................................................................................. 2 1. Function Diagram........................................................................................... 4 2. Menu Structure .............................................................................................. 5 1. Relay Instrumentation .................................................................................... 6 1.1. Favourite Meters.................................................................................... 6 1.2. Current Meters....................................................................................... 6 1.3. Thermal Meters ..................................................................................... 8 1.4. Auto-Reclose Meters ............................................................................. 8 1.5. Maintenance Meters .............................................................................. 8 1.6. General Alarm Meters ........................................................................... 9 1.7. Demand Meters ..................................................................................... 9 1.8. Binary Input Meters ............................................................................. 10 1.9. Binary Output Meters........................................................................... 11 1.10. Virtual Meters ...................................................................................... 11 1.11. Communication Meters ........................................................................ 11 1.12. Miscellaneous Meters .......................................................................... 12 1.13. Quick Logic Meters .............................................................................. 12 Unrestricted (c)2018 Siemens Protection Devices Limited Page 3 of 12 7SR210 Instrumentation Guide 1.Function Diagram Unrestricted Page 4 of 12 (c) 2018 Siemens Protection Devices Limited 7SR210 Instrumentation Guide 2.Menu Structure Unrestricted (c)2018 Siemens Protection Devices Limited Page 5 of 12 7SR210 Instrumentation Guide 1. Relay Instrumentation 1.1. Favourite Meters Instrument Description -------------------FAVOURITE METERS > to view This allows the user to view his previously constructed list of `favourite meters' by pressing TEST/RESET button and the READ DOWN button to scroll though the meters added to this sub-group To construct a sub-group of favourite meters, first go to the desired meter then press ENTER this will cause a message to appear on the LCD `Add To Favourites YES pressing ENTER again will add this to the FAVOURITE METERS Sub-menu. To remove a meter from the FAVOURITE METERS submenu go to that meter each in the FAVOURITE METERS sub-menu or at its Primary location press ENTER and the message `Remove From Favourites' will appear press ENTER again and this meter will be removed from the FAVOURITE METERS sub-group 1.2. Current Meters Instrument Description -------------------CURRENT METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Current TEST/RESET allows access to this sub-group Primary Current Ia 0.00A Ib 0.00A Ic 0.00A Secondary Current Ia 0.00A Ib 0.00A Ic 0.00A Nom Current o Ia 0.00xIn ---o Ib 0.00xIn ---o Ic 0.00xIn ---Pri Earth Current In 0.000A Ig 0.000A Sec Earth Current In 0.000A Ig 0.000A Nom Earth Current o In 0.000xIn ---o Ig 0.000xIn ---I Seq Components Izps 0.00xIn ----o o Ipps 0.00xIn ---o Inps 0.00xIn ---nd 2 Harmonic Current Ia 0.00xIn Ib 0.00xIn Ic 0.00xIn Unrestricted Page 6 of 12 Displays the 3 phase currents Primary RMS values Displays the 3 phase currents Secondary RMS values Displays the 3 phase currents Nominal RMS values & phase angles with respect to PPS current. Displays the 3 Earth currents Primary RMS values Displays the 3 Earth currents Secondary RMS values Displays the 3 Earth currents Nominal RMS values & phase angles with respect to PPS current. Displays the Current Sequence components Nominal RMS values & phase angles with respect to PPS current. nd Displays the 3 phase currents 2 Harmonic components Nominal RMS values. (c) 2018 Siemens Protection Devices Limited 7SR210 Instrumentation Guide Instrument Description th 5 Harmonic Current Ia 0.00xIn Ib 0.00xIn Ic 0.00xIn Last Trip P/F Ia Ib Ic Last Trip E/F In Ig 0.00A 0.00A 0.00A 0.00A 0.00A th Displays the 3 phase currents 5 Harmonic components Nominal RMS values. Displays the Last Trip Fault Current.. Displays the Last Trip Fault Current.. Unrestricted (c)2018 Siemens Protection Devices Limited Page 7 of 12 7SR210 Instrumentation Guide 1.3. Thermal Meters Instrument Description -------------------THERMAL METERS > to view This is the sub-group that includes all the meters that are associated with Thermal TEST/RESET allows access to this sub-group Thermal Status Phase A Phase B Phase C 0.0% 0.0% 0.0% Displays the thermal capacity 1.4. Auto-Reclose Meters Instrument Description -------------------AUTORECLOSE METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Autoreclose TEST/RESET allows access to this sub-group. Only seen on models that have the 79 option Autoreclose Status Out Of Service Close Shot 0 Status of the autoreclose. 1.5. Maintenance Meters Instrument Description -------------------MAINTENANCE METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Maintenance TEST/RESET allows access to this sub-group CB Total Trips Count Target CB Phase A Trips Count Target CB Phase B Trips Count Target CB Phase C Trips Count Target CB Phase E/F Trips Count Target CB Delta Trips Count Target Unrestricted Page 8 of 12 0 100 0 100 0 100 0 100 0 100 0 100 Displays the number of CB trips experienced by the CB Displays the number of CB Phase A Trips experienced by the CB Displays the number of CB Phase B Trips experienced by the CB Displays the number of CB Phase C Trips experienced by the CB Displays the number of CB Phase E/F Trips experienced by the CB Displays the number of CB trips experienced by the CB (c) 2018 Siemens Protection Devices Limited 7SR210 Instrumentation Guide Instrument Description CB Count To AR Block Count 0 Target 100 CB Freq Ops Count Count 0 Target 10 CB Wear Phase A 0.00MA^2s Phase B 0.00MA^2s Phase C 0.00MA^2s CB Wear Remaining Phase A 100% Phase B 100% Phase C 100% CB Trip Time 0.0ms Displays the number of CB trips experienced by the CB. When the target is reached the relay will only do 1 Delayed Trip to Lockout. Displays the number of CB trips experienced by the CB over the last rolling 1 hr period. When the target is reached the relay will only do 1 Delayed Trip to Lockout. Displays the current measure of circuit breaker wear. Displays the current measure of circuit breaker wear remaining Displays the trip time for the circuit breaker. 1.6. General Alarm Meters Instrument Description -------------------GENERAL ALARM METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with the Binary inputs TEST/RESET allows access to this sub-group General Alarms -------------------ALARM 1 Cleared Displays the state of General Alarm ... General Alarms -------------------ALARM 20 Cleared 1.7. Demand Meters Instrument Description -------------------DEMAND METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with the demand metering. TEST/RESET allows access to this sub-group I Phase A Demand Max Min Mean I Phase B Demand Max Min Mean I Phase C Demand 0.00A 0.00A 0.00A 0.00A 0.00A 0.00A Shows the Max, Min and Mean for Phase A. Shows the Max, Min and Mean for Phase B. Shows the Max, Min and Mean for Phase C. Unrestricted (c)2018 Siemens Protection Devices Limited Page 9 of 12 7SR210 Instrumentation Guide Instrument Description Max 0.00A Min 0.00A Mean 0.00A Power P 3P Demand Max 0.00W Min 0.00W Mean 0.00W Power Q 3P Demand Max 0.00VAr Min 0.00VAr Mean 0.00VAr Power S 3P Demand Max 0.00VA Min 0.00VA Mean 0.00VA Shows the Max, Min and Mean for Power P 3P Demand. Shows the Max, Min and Mean for Power Q 3P Demand. Shows the Max, Min and Mean for Power S 3P Demand. 1.8. Binary Input Meters Instrument Description -------------------BINARY INPUT METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with the Binary inputs TEST/RESET allows access to this sub-group BI 1-8 BI 9-16 BI 17-24 BI 25-32 BI 33-39 ---- -------.-------.-------.-------.--- Unrestricted Page 10 of 12 Displays the state of DC binary inputs 1 to 39 (The number of binary inputs may vary depending on model) (c) 2018 Siemens Protection Devices Limited 7SR210 Instrumentation Guide 1.9. Binary Output Meters Instrument Description -------------------BINARY OUTPUT METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with the Binary Outputs TEST/RESET allows access to this sub-group BO 1-8 BO 9-16 ---- -------.---- Displays the state of DC binary Outputs 1 to 16. (The number of binary outputs may vary depending on model) 1.10. Virtual Meters Instrument Description -------------------VIRTUAL METERS > to view -------------------- This is the sub-group that shows the state of the virtual status inputs in the relay TEST/RESET allows access to this sub-group V 1-8 V 9-16 ---- ------- ---- Displays the state of Virtual Outputs 1 to 16 (The number of virtual inputs will vary depending on model) 1.11. Communication Meters Instrument Description -------------------COMMUNICATION METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Communications ports TEST/RESET allows access to this sub-group COM1 COM2 COM3 COM4 COM1 TRAFFIC Tx1 Rx1 Rx1 Errors COM2 TRAFFIC Tx2 Rx2 Rx2 Errors COM3 TRAFFIC Tx3 Rx3 Rx3 Errors COM4 TRAFFIC Tx4 Rx4 Rx4 Errors Displays which com ports are currently active 0 0 0 0 0 0 0 0 0 0 0 0 Displays traffic on Com1 Displays traffic on Com2 Displays traffic on Com3 Displays traffic on Com4 Unrestricted (c)2018 Siemens Protection Devices Limited Page 11 of 12 7SR210 Instrumentation Guide 1.12. Miscellaneous Meters Instrument Description -------------------MISCELLANEOUS METERS > to view -------------------- This is the sub-group that includes indication such as the relays time and date, the amount of fault and waveform records stored in the relay TEST/RESET allows access to this sub-group Start Alarm Count 0 Target 100 Hrs In Service Time Time 0Hrs Date 01/01/2000 Time 22:41:44 Waveform Recs 0 Fault Recs 0 Event Recs 0 Data Log Recs 0 Settings Group 1 This meter displays the Start Alarm count. This meter displays the amount of time in service This meter displays the Date, Time, the number of Waveform Records and Fault Records stored in the relay. This meter displays the number of Event Records, Data Log Records and the Active Settings Group number stored in the relay. 1.13. Quick Logic Meters Instrument Description -------------------QUICK LOGIC METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with QuickLogic. TEST/RESET allows access to this sub-group E 1-8 E 9-16 E1 Equation EQN TMR CNT ---- ------- ---- Shows the state of all the equations 0-0 0-1 =0 =0 =0 E16 Equation EQN TMR 0-0 CNT 0-1 =0 =0 =0 Shows the state of an individual equation. EQN shows the equation state. TMR shows the timer progress and state for the equation. CNT shows the count progress and state for the equation. ... Unrestricted Page 12 of 12 Shows the state of an individual equation. EQN shows the equation state. TMR shows the timer progress and state for the equation. CNT shows the count progress and state for the equation. (c) 2018 Siemens Protection Devices Limited 7SR210 Non-Directional Relay Settings Guide Unrestricted The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Document Release History This document is issue 2017/12. The list of revisions up to and including this issue is: 2011/05 First issue 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/11 Typographical revisions and formatting 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. Software Revision History 2011/05 2435H85008R7a-7a (7SR210) First Release 2013/01 2435H85008R7c-7b (7SR210) 2014/06 2435H85008R7f-7d (7SR210) 2015/06 2435H85008R8a-7f (7SR210) 2016/02 2435H85008R8b-7f (7SR210) 2435H85009R8b-7f (7SR220) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Fault data transmission over IEC 60870-5-103. Additional communications data, control features, meters. Added Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Unrestricted Page 2 of 61 Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing. Increased I/O. (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Contents Document Release History................................................................................. 2 Software Revision History .................................................................................. 2 1. Function Diagram........................................................................................... 5 2. Menu Structure .............................................................................................. 6 3. Relay Settings ................................................................................................ 7 3.1. 3.2. 3.3. 3.4. System Config ....................................................................................... 7 CT/VT Config ......................................................................................... 8 Function Config ..................................................................................... 8 Current Protection ............................................................................... 10 3.4.1. Phase Overcurrent .................................................................... 10 3.4.1.1. 51-1 ................................................................................ 10 3.4.1.2. 51-2 ................................................................................ 10 3.4.1.3. 50-1 ................................................................................ 11 3.4.1.4. 50-2 ................................................................................ 11 3.4.2. Cold Load.................................................................................. 11 3.4.3. Derived E/F ............................................................................... 12 3.4.3.1. 51N-1 .............................................................................. 12 3.4.3.2. 51N-2 .............................................................................. 13 3.4.3.3. 50N-1 .............................................................................. 13 3.4.3.4. 50N-2 .............................................................................. 13 3.4.4. Measured E/F ........................................................................... 14 3.4.4.1. 51G-1 ............................................................................. 14 3.4.4.2. 51G-2 ............................................................................. 14 3.4.4.3. 50G-1 ............................................................................. 15 3.4.4.4. 50G-2 ............................................................................. 15 3.4.5. Sensitive E/F ............................................................................. 15 3.4.5.1. 51SEF-1 ......................................................................... 15 3.4.5.2. 51SEF-2 ......................................................................... 16 3.4.5.3. 50SEF-1 ......................................................................... 16 3.4.5.4. 50SEF-2 ......................................................................... 16 3.4.6. Restricted E/F ........................................................................... 17 3.4.7. NPS Overcurrent ....................................................................... 17 3.4.7.1. 46IT ................................................................................ 17 3.4.7.2. 46DT ............................................................................... 17 3.4.8. Under Current ........................................................................... 18 3.4.8.1. 37-1 ................................................................................ 18 3.4.8.2. 37-2 ................................................................................ 18 3.4.8.3. 37G-1 ............................................................................. 18 3.4.8.4. 37G-2 ............................................................................. 18 3.4.9. Thermal ..................................................................................... 19 3.4.10. ARC Flash Detector ............................................................. 19 3.5. Supervision .......................................................................................... 19 3.5.1. CB Fail ...................................................................................... 19 3.5.2. CT Supervision ......................................................................... 19 Unrestricted (c)2018 Siemens Protection Devices Limited Page 3 of 61 7SR210 Settings Guide 3.5.3. Broken Conductor ..................................................................... 20 3.5.4. Trip CCT Supervision ................................................................ 20 3.5.5. Close CCT Supervision ............................................................. 20 3.5.6. Inrush Detector .......................................................................... 21 3.6. Control & Logic .................................................................................... 21 3.6.1. Autoreclose Prot'n ..................................................................... 21 3.6.2. Autoreclose Config .................................................................... 22 3.6.2.1. P/F Shots ........................................................................ 22 3.6.2.2. E/F Shots ........................................................................ 23 3.6.2.3. SEF Shots....................................................................... 24 3.6.2.4. Extern Shots ................................................................... 24 3.6.3. Manual Close ............................................................................ 24 3.6.4. Circuit Breaker .......................................................................... 25 3.6.5. QUICK LOGIC ........................................................................... 25 3.7. Input Config ......................................................................................... 33 3.7.1. Input Matrix................................................................................ 33 3.7.2. Binary Input Config.................................................................... 40 3.7.3. General Alarms ......................................................................... 41 3.8. Output Config....................................................................................... 42 3.8.1. Output Matrix ............................................................................. 42 3.8.2. Binary Output Config ................................................................. 55 3.8.3. LED Config ................................................................................ 56 3.8.4. Pickup Config ............................................................................ 56 3.9. CB Maintenance .................................................................................. 57 3.9.1. CB Counters .............................................................................. 57 3.9.2. I^2T CB Wear ............................................................................ 58 3.9.3. START COUNT ......................................................................... 58 3.10. Data Storage ........................................................................................ 58 3.10.1. Demand Data/Log ................................................................ 58 3.10.2. Waveform Storage ............................................................... 59 3.10.3. Fault Storage ....................................................................... 59 3.10.4. Event Storage ...................................................................... 59 3.10.5. Communications .................................................................. 60 Unrestricted Page 4 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 1.Function Diagram Unrestricted (c)2018 Siemens Protection Devices Limited Page 5 of 61 7SR210 Settings Guide 2.Menu Structure Unrestricted Page 6 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.Relay Settings 3.1. System Config Description Range Default 50, 60 50 Hz Disabled, Enabled Enabled Off, 1, 2, 5, 10, 15, 30, 60 60 min Off, 1, 2, 5, 10, 15, 30, 60 5 min xNom, Primary, Secondary xNom xNom, Primary, Secondary xNom Edge triggered, Level triggered Edge triggered Disabled, Seconds, Minutes Minutes Out Of Service, Local, Remote, Local Or Remote Local Or Remote (Password) NONE (Password) NONE Disabled, Enabled Enabled Disabled, Enabled Enabled Active Group Selects which settings group is currently activated System Frequency Selects the Power System Frequency from 50 or 60 Hz View/Edit Group Selects which settings group is currently being displayed Setting Dependencies When enabled only active settings are displayed and all others hidden Favourite Meters Timer Selects the time delay after which, if no key presses have been detected, the relay will begin to poll through any screens which have been selected as favourite instruments Backlight timer Controls when the LCD backlight turns off Date Sets the date, this setting can only be changed on the fascia or via Relay->Control->Set Time and Date Time Sets the time, this setting can only be changed on the fascia or via Relay->Control->Set Time and Date Curr Set Display Select whether the Pickup values are shown in terms of x Nominal, Primary or Secondary values on the Relay Fascia E/F Curr Set Display As Above Select Grp Mode Mode of operation of the group change from status input. Edge triggered ignores the status input once it has changed to the relevant group, where as with Level triggered the relay will only stay in the group it has changed to whilst the status input is being driven, after which it returns to the previous group. Clock Sync. From BI Real time clock may be synchronised using a binary input (See Clock Sync. in Binary Input Menu) Operating Mode Selects the current operating mode of the relay. This can also be changed by a binary input mode selection. Setting Password Allows a 4 character alpha code to be entered as the password. Note that the display shows a password dependant encrypted code on the second line of the display Control Password As Above Trip Alert When Enabled the occurrence of a Trip will cause the relay to display the Trip Alert Screen, the only way to leave this screen is by acknowledging the trip through the TEST/RESET button on the relay fascia General Alarm Alert Unrestricted (c)2018 Siemens Protection Devices Limited Page 7 of 61 7SR210 Settings Guide Description Range Default Relay Identifier (16 Character String) 7SR210 An alphanumeric string shown on the LCD normally used to identifier the circuit the relay is attached to or the relays purpose Circuit Identifier (16 Character String) 3.2. CT/VT Config Description Range Default Phase Current Input 1, 5 1A ( 6 Character String) 2000 A 0.2, 0.21 ... 2, 2.1.....7 1 1, 5 1A ( 6 Character String) 2000 A 0.2, 0.21 ... 2, 2.1.....7 1 Description Range Default Gn Phase Overcurrent Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Selects whether 1 or 5 Amp terminals are being used for phase inputs Phase CT Ratio Prim Phase CT ratio to scale primary current instruments Phase CT Ratio Sec Phase CT ratio to scale secondary current instruments Earth Current Input Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs Earth CT Ratio Prim Measured Earth CT ratio to scale primary current instruments Earth CT Ratio Sec Measured Earth CT ratio to scale secondary current instruments 3.3. Function Config When set to Disabled, no Phase Overcurrent elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Cold Load When set to Disabled, no Cold Load elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Derived E/F When set to Disabled, no Derived E/F elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Measured E/F When set to Disabled, no Measured E/F elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Sensitive E/F When set to Disabled, no Sensitive E/F elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Restricted E/F When set to Disabled, no Restricted E/F elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn NPS Overcurrent When set to Disabled, no NPS Overcurrent elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Unrestricted Page 8 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Gn Under Current Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled When set to Disabled, no Under Current elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Thermal When set to Disabled, no Thermal elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn CT Supervision When set to Disabled, no CT Supervision elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn CB Fail When set to Disabled, no CB Fail elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Broken Conductor When set to Disabled, no Broken Conductor elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Trip Cct Supervision When set to Disabled, no Trip Cct Supervision elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Close Cct Supervision When set to Disabled, no Close Cct Supervision elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Inrush Detector When set to Disabled, no Inrush Detector elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn CB Counters When set to Disabled, no Gn CB Counter elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn I^2t CB Wear When set to Disabled, no Gn I^2t CB Wear elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Arc Flash Detector When set to Disabled, no Arc Flash Detector elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Unrestricted (c)2018 Siemens Protection Devices Limited Page 9 of 61 7SR210 Settings Guide 3.4. Current Protection 3.4.1. Phase Overcurrent Description Range Default Gn 51/50 Measurement RMS, Fundamental RMS Description Range Default Gn 51-1 Element Disabled, Enabled Disabled 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit Off Description Range Default Gn 51-2 Element Disabled, Enabled Disabled 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated at fundamental frequency 3.4.1.1. 51-1 Selects whether the 51-1 IDMTL Overcurrent element is enabled Gn 51-1 Setting Pickup level Gn 51-1 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51-1 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51-1 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51-1 Min Operate Time Minimum operate time of element. Gn 51-1 Follower DTL Additional definite time added after characteristic time Gn 51-1 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51-1 Inrush Action Selects if the 51-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.1.2. 51-2 Selects whether the 51-2 IDMTL Overcurrent element is enabled Gn 51-2 Setting Pickup level Gn 51-2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51-2 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51-2 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51-2 Min Operate Time Minimum operate time of element. Gn 51-2 Follower DTL Additional definite time added after characteristic time Unrestricted Page 10 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Gn 51-2 Reset (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit Off Description Range Default Gn 50-1 Element Disabled, Enabled Disabled 0.05, 0.06 ... 49.5, 50 1 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit Off Description Range Default Gn 50-2 Element Disabled, Enabled Disabled 0.05, 0.06 ... 49.5, 50 1 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit Off Description Range Default Cold Load Disabled, Enabled Disabled 1, 1.1 ... 14100, 14400 600 s 1, 1.1 ... 14100, 14400 600 s Disabled, Enabled Disabled 0.05, 0.1 ... 2.45, 2.5 0.25 xIn 1, 1.1 ... 14100, 14400 600 s 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51-2 Inrush Action Selects if the 51-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.1.3. 50-1 Selects whether the INST/ DTL Overcurrent element is enabled Gn 50-1 Setting Pickup level Gn 50-1 Delay Sets operate delay time Gn 50-1 Inrush Action Selects if the 50-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.1.4. 50-2 Selects whether the INST/ DTL Overcurrent element is enabled Gn 50-2 Setting Pickup level Gn 50-2 Delay Sets operate delay time Gn 50-2 Inrush Action Selects if the 50-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.2. Cold Load Selects whether the Cold Load element is enabled Pick-up Time Cold Load operate time delay Drop-off Time Cold Load reset time delay Reduced Current Selects whether reduced current functionality is to be used Reduced Current Level Selects current level below which Reduced Current Time is used for Cold Load reset delay Reduced Current Time Cold Load reset time delay used when reduced current active Gn 51c-1 Setting 51-1 element parameter used when Cold Load operates Gn 51c-1 Char 51-1 element parameter used when Cold Load operates Unrestricted (c)2018 Siemens Protection Devices Limited Page 11 of 61 7SR210 Settings Guide Description Range Default Gn 51c-1 Time Mult (IEC/ANSI) 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Description Range Default Gn 51N-1 Element Disabled, Enabled Disabled 0.05, 0.06 ... 2.49, 2.5 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s 51-1 element parameter used when Cold Load operates Gn 51c-1 Delay (DTL) 51-1 element parameter used when Cold Load operates Gn 51c-1 Min Operate Time 51-1 element parameter used when Cold Load operates Gn 51c-1 Follower DTL 51-1 element parameter used when Cold Load operates Gn 51c-1 Reset 51-1 element parameter used when Cold Load operates Gn 51c-2 Setting 51-2 element parameter used when Cold Load operates Gn 51c-2 Char 51-2 element parameter used when Cold Load operates Gn 51c-2 Time Mult (IEC/ANSI) 51-2 element parameter used when Cold Load operates Gn 51c-2 Delay (DTL) 51-2 element parameter used when Cold Load operates Gn 51c-2 Min Operate Time 51-2 element parameter used when Cold Load operates Gn 51c-2 Follower DTL 51-2 element parameter used when Cold Load operates Gn 51c-2 Reset 51-2 element parameter used when Cold Load operates 3.4.3. Derived E/F 3.4.3.1. 51N-1 Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled Gn 51N-1 Setting Pickup level Gn 51N-1 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51N-1 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51N-1 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51N-1 Min Operate Time Minimum operate time of element. Gn 51N-1 Follower DTL Additional definite time added after characteristic time Gn 51N-1 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Unrestricted Page 12 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Gn 51N-1 Inrush Action Off, Inhibit Off Description Range Default Gn 51N-2 Element Disabled, Enabled Disabled 0.05, 0.06 ... 2.49, 2.5 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit Off Description Range Default Gn 50N-1 Element Disabled, Enabled Disabled 0.05, 0.06 ... 49.5, 50 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit Off Description Range Default Gn 50N-2 Element Disabled, Enabled Disabled 0.05, 0.06 ... 49.5, 50 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit Off Selects if the 51N-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.3.2. 51N-2 Selects whether the 51N-2 IDMTL derived Earth Fault element is enabled Gn 51N-2 Setting Pickup level Gn 51N-2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51N-2 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51N-2 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51N-2 Min Operate Time Minimum operate time of element. Gn 51N-2 Follower DTL Additional definite time added after characteristic time Gn 51N-2 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51N-2 Inrush Action Selects if the 51N-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.3.3. 50N-1 Selects whether the DTL derived Earth fault element is enabled Gn 50N-1 Setting Pickup level Gn 50N-1 Delay Sets operate delay time Gn 50N-1 Inrush Action Selects if the 50N-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.3.4. 50N-2 Selects whether the DTL derived Earth fault element is enabled Gn 50N-2 Setting Pickup level Gn 50N-2 Delay Sets operate delay time Gn 50N-2 Inrush Action Selects if the 50N-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates Unrestricted (c)2018 Siemens Protection Devices Limited Page 13 of 61 7SR210 Settings Guide 3.4.4. Measured E/F Description Range Default Gn 51G/50G Measurement RMS, Fundamental RMS Description Range Default Gn 51G-1 Element Disabled, Enabled Disabled 0.005, 0.006 ... 0.995, 1 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit Off Description Range Default Gn 51G-2 Element Disabled, Enabled Disabled 0.005, 0.006 ... 0.995, 1 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Selects whether the RMS value used by the 51G & 50G elements is True RMS or only calculated at fundamental frequency 3.4.4.1. 51G-1 Selects whether the 51G-1 IDMTL measured Earth Fault element is enabled Gn 51G-1 Setting Pickup level Gn 51G-1 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51G-1 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51G-1 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51G-1 Min Operate Time Minimum operate time of element. Gn 51G-1 Follower DTL Additional definite time added after characteristic time Gn 51G-1 Reset Selects between an ANSI decaying reset characteristic or DTL reset Gn 51G-1 Inrush Action Selects if the 51G-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.2. 51G-2 Selects whether the 51G-2 IDMTL measured Earth Fault element is enabled Gn 51G-2 Setting Pickup level Gn 51G-2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51G-2 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51G-2 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51G-2 Min Operate Time Minimum operate time of element. Gn 51G-2 Follower DTL Additional definite time added after characteristic time Gn 51G-2 Reset Selects between an ANSI decaying reset characteristic or DTL reset Unrestricted Page 14 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Gn 51G-2 Inrush Action Off, Inhibit Off Description Range Default Gn 50G-1 Element Disabled, Enabled Disabled 0.005, 0.006 ... 24.95, 25 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit Off Description Range Default Gn 50G-2 Element Disabled, Enabled Disabled 0.005, 0.006 ... 24.95, 25 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit Off Description Range Default Gn 51SEF-1 Element Disabled, Enabled Disabled 0.005, 0.006 ... 0.995, 1 0.2 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s Selects if the 51G-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.3. 50G-1 Selects whether the DTL measured Earth fault element is enabled Gn 50G-1 Setting Pickup level Gn 50G-1 Delay Sets operate delay time Gn 50G-1 Inrush Action Selects if the 50G-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.4. 50G-2 Selects whether the DTL measured Earth fault element is enabled Gn 50G-2 Setting Pickup level Gn 50G-2 Delay Sets operate delay time Gn 50G-2 Inrush Action Selects if the 50G-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.5. Sensitive E/F 3.4.5.1. 51SEF-1 Selects whether the 51SEF-1 IDMTL Sensitive Earth Fault element is enabled Gn 51SEF-1 Setting Pickup level Gn 51SEF-1 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51SEF-1 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51SEF-1 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51SEF-1 Min Operate Time Minimum operate time of element. Gn 51SEF-1 Follower DTL Additional definite time added after characteristic time Unrestricted (c)2018 Siemens Protection Devices Limited Page 15 of 61 7SR210 Settings Guide Description Range Default Gn 51SEF-1 Reset (ANSI) Decaying, 0 ... 59, 60 0s Description Range Default Gn 51SEF-2 Element Disabled, Enabled Disabled 0.005, 0.006 ... 0.995, 1 0.2 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Description Range Default Gn 50SEF-1 Element Disabled, Enabled Disabled 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 50SEF-2 Element Disabled, Enabled Disabled 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Selects between an ANSI decaying reset characteristic or DTL reset 3.4.5.2. 51SEF-2 Selects whether the 51SEF-2 IDMTL derived Earth Fault element is enabled Gn 51SEF-2 Setting Pickup level Gn 51SEF-2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51SEF-2 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51SEF-2 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51SEF-2 Min Operate Time Minimum operate time of element. Gn 51SEF-2 Follower DTL Additional definite time added after characteristic time Gn 51SEF-2 Reset Selects between an ANSI decaying reset characteristic or DTL reset 3.4.5.3. 50SEF-1 Selects whether the DTL measured Earth fault element is enabled Gn 50SEF-1 Setting Pickup level Gn 50SEF-1 Delay Sets operate delay time 3.4.5.4. 50SEF-2 Selects whether the DTL measured Earth fault element is enabled Gn 50SEF-2 Setting Pickup level Gn 50SEF-2 Delay Sets operate delay time Unrestricted Page 16 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.4.6. Restricted E/F Description Range Default Gn 64H Element Disabled, Enabled Disabled 0.005, 0.006 ... 0.945, 0.95 0.2 xIn 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 46IT Element Disabled, Enabled Disabled 0.05, 0.06 ... 2.49, 2.5 0.25 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s (ANSI) Decaying, 0 ... 59, 60 0s Description Range Default Gn 46DT Element Disabled, Enabled Disabled 0.05, 0.06 ... 3.99, 4 0.1 xIn 0, 0.01 ... 14300, 14400 0.02 s High impedance restricted earth fault current element Gn 64H Setting Pickup level Gn 64H Delay Sets operate delay time 3.4.7. NPS Overcurrent 3.4.7.1. 46IT Selects whether the 46IT IDMTL/DTL negative phase sequence current element is enabled Gn 46IT Setting Pickup level Gn 46IT Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 46IT Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 46IT Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 46IT Reset Selects between an ANSI decaying reset characteristic or a definite time reset 3.4.7.2. 46DT Selects whether the 46DT INST/DTL negative sequence current element is enabled Gn 46DT Setting Pickup level Gn 46DT Delay Sets operate delay time Unrestricted (c)2018 Siemens Protection Devices Limited Page 17 of 61 7SR210 Settings Guide 3.4.8. Under Current 3.4.8.1. 37-1 Description Range Default Gn 37-1 Element Disabled, Enabled Disabled 0.05, 0.1 ... 4.95, 5 0.25 xIn 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 37-2 Element Disabled, Enabled Disabled 0.05, 0.1 ... 4.95, 5 0.25 xIn 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 37G-1 Element Disabled, Enabled Disabled Gn 37G-1 Setting 0.005, 0.006 ... 4.995, 5 0.2 xIn Gn 37G-1 Delay 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 37G-2 Element Disabled, Enabled Disabled Gn 37G-2 Setting 0.005, 0.006 ... 4.995, 5 0.2 xIn Gn 37G-2 Delay 0, 0.01 ... 14300, 14400 0s Phase under current element 37-1 Gn 37-1 Setting Pickup level Gn 37-1 Delay Sets operate delay time 3.4.8.2. 37-2 Phase under current element 37-2 Gn 37-2 Setting Pickup level Gn 37-2 Delay Sets operate delay time 3.4.8.3. 3.4.8.4. 37G-1 37G-2 Unrestricted Page 18 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.4.9. Thermal Description Range Default Gn 49 Thermal Overload Disabled, Enabled Disabled 0.1, 0.11 ... 2.99, 3 1.05 xIn 1, 1.5 ... 999.5, 1000 10 minutes Disabled, 50 ... 99, 100 Disabled Description Range Default Gn 50AFD Disabled, Enabled Disabled 1, 2,...10 2 xIn Description Range Default Gn 50BF Element Disabled, Enabled Disabled 0.05, 0.055 ... 1.995, 2 0.2 xIn Gn 50BF-I4 Setting 0.005, 0.01 ... 1.995, 2 0.05 xIn Gn 50BF-1 Delay 20, 25 ... 59995, 60000 60 ms 20, 25 ... 59995, 60000 120 ms Description Range Default Gn 60CTS-I Element Disabled, Enabled Disabled Gn 60CTS-I Setting 0.05, 0.1 ... 1.95, 2 0.05 xIn Gn 60CTS-I Delay 0.03, 0.04 ... 14300, 14400 10 s Selects whether the thermal overload protection element is enabled Gn 49 Overload Setting Pickup level Gn 49 Time Constant (Minutes) Thermal time constant Gn 49 Capacity Alarm Selects whether thermal capacity alarm enabled 49 Reset Therm State Control that allows thermal state to be manually reset 3.4.10. ARC Flash Detector Selects whether the ARC Flash Detector element is enabled Gn 50AFD Setting Pickup level 3.5. Supervision 3.5.1. CB Fail Selects whether the Circuit Breaker Fail element is enabled Gn 50BF Setting Breaker Fail Current Pickup level. If the current falls below this level then the CB is deemed to have opened and the element is reset. Delay before Circuit Breaker Fail stage 1 operates Gn 50BF-2 Delay Delay before Circuit Breaker Fail stage 2 operates 3.5.2. CT Supervision Unrestricted (c)2018 Siemens Protection Devices Limited Page 19 of 61 7SR210 Settings Guide 3.5.3. Broken Conductor Description Range Default Gn 46BC U/C Guard Setting 0.05, 0.1 ... 4.95, 5 0.25 xIn Gn 46BC U/C Guarded No, Yes No Gn 46BC Element Disabled, Enabled Disabled 20, 21 ... 99, 100 20 % 0.03, 0.04 ... 14300, 14400 20 s Description Range Default Gn 74TCS-1 Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Description Range Default Gn 74CCS-1 Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Selects whether the definite time broken conductor element is enabled Gn 46BC Setting NPS Current to PPS Current ratio Gn 46BC Delay Sets operate delay time 3.5.4. Trip CCT Supervision Selects whether the trip circuit supervision element 74TCS-1 is enabled Gn 74TCS-1 Delay Time delay before trip circuit supervision operates Gn 74TCS-2 Selects whether the trip circuit supervision element 74TCS-2 is enabled Gn 74TCS-2 Delay Time delay before trip circuit supervision operates Gn 74TCS-3 Selects whether the trip circuit supervision element 74TCS-3 is enabled Gn 74TCS-3 Delay Time delay before trip circuit supervision operates 3.5.5. Close CCT Supervision Selects whether the trip circuit supervision element 74CCS-1 is enabled Gn 74CCS-1 Delay Time delay before trip circuit supervision operates Gn 74CCS-2 Selects whether the trip circuit supervision element 74CCS-2 is enabled Gn 74CCS-2 Delay Time delay before trip circuit supervision operates Gn 74CCS-3 Selects whether the trip circuit supervision element 74CCS-3 is enabled Gn 74CCS-3 Delay Time delay before trip circuit supervision operates Unrestricted Page 20 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.5.6. Inrush Detector Description Range Default Gn 81HBL2 Element Disabled, Enabled Disabled Phase, Cross, Sum Cross 0.1, 0.11 ... 0.49, 0.5 0.2 xI Description Range Default Gn 79 P/F Inst Trips Combination of ( 51-1, 51-2, 50-1, 50-2 ) ---- Combination of ( 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G1, 50G-2 ) -------- Combination of ( 51SEF-1, 51SEF2, 50SEF-1, 50SEF-2 ) ---- Combination of ( 51-1, 51-2, 50-1, 50-2 ) 51-1, 51-2, 50-1, 50-2 Combination of ( 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G1, 50G-2 ) 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2 Combination of ( 51SEF-1, 51SEF2, 50SEF-1, 50SEF-2 ) 51SEF-1, 51SEF2, 50SEF-1, 50SEF-2 Combination of ( 50-1, 50-2 ) -- Combination of ( 50N-1, 50N-2, 50G-1, 50G-2 ) ---- Selects whether the phase inrush detector 81HBL2 is enabled Gn 81HBL2 Bias Selects the bias method used for magnetising inrush. Phase - Segregated, each phase blocks itself. Cross - Blocked, each phase can block the operation of other phases. Sum - Of Squares, each phase blocks itself using the square root of the sum of squares of the 2nd harmonic. Gn 81HBL2 Setting The magnetising inrush detector operates when the 2nd harmonic current exceeds a set percentage of the fundamental current 3.6. Control & Logic 3.6.1. Autoreclose Prot'n Selects which phase fault protection elements are classed as Instantaneous elements and start an autoreclose sequence. These will be blocked from operating during Delayed autoreclose sequences. See autoreclose section of manual for detail of what elements can cause only Delayed protection to be used. Gn 79 E/F Inst Trips Selects which earth fault protection elements are classed as Instantaneous elements and start an autoreclose sequence. These will be blocked from operating during Delayed autoreclose sequences. See autoreclose section of manual for detail of what elements can cause only Delayed protection to be used. Gn 79 SEF Inst Trips Selects which sensitive earth fault protection elements are classed as Instantaneous elements and start an autoreclose sequence. These will be blocked from operating during Delayed autoreclose sequences. See autoreclose section of manual for detail of what elements can cause only Delayed protection to be used. Gn 79 P/F Delayed Trips Selects which phase fault protection are classed as Delayed elements, any selected elements operating will start an autoreclose sequence. Gn 79 E/F Delayed Trips Selects which earth fault protection are classed as Delayed elements, any selected elements operating will start an autoreclose sequence. Gn 79 SEF Delayed Trips Selects which sensitive earth fault elements are classed as Delayed elements, any selected elements operating will start an autoreclose sequence. Gn 79 P/F HS Trips Selects which phase fault elements are classed as High Set elements, any selected elements operating will start an autoreclose sequence. Gn 79 E/F HS Trips Selects which earth fault elements are classed as High Set elements, any selected elements operating will start an autoreclose sequence. Unrestricted (c)2018 Siemens Protection Devices Limited Page 21 of 61 7SR210 Settings Guide 3.6.2. Autoreclose Config Description Range Default Gn 79 Autoreclose Disabled, Enabled Disabled 1, 2, 3, 4 1 Disabled, Enabled Disabled 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 1 0, 1 ... 599, 600 60 s 0, 1 ... 599, 600 60 s 0, 1 ... 599, 600 60 s Disabled, Enabled Enabled Off, Delayed Off Description Range Default Gn 79 P/F Prot'n Trip 1 Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s If disabled then all attempts to control the AR IN/OUT status will fail and the AR will be permanently Out Of Service. When enabled the AR IN/OUT state may be controlled via the CONTROL MODE menu option, via Binary Input or via local or remote communications. Gn 79 Num Shots Selects the number of auto-reclose attempts before the Autorecloser locks out Gn 79 Retry Enable Selects whether the Retry close functionality is enabled Gn 79 Retry Attempts Selects the number of retries allowed per shot Gn 79 Retry Interval Time delay between retries Gn 79 Reclose Blocked Delay Specifies the maximum time that the Autorecloser can be blocked before proceeding to the lockout state. (NOTE: The block delay timer only starts after the Deadtime.) Gn 79 Sequence Fail Timer Time before lockout occurs on an incomplete reclose sequence. (i.e Trip & starter conditions have not been cleared after Sequence Fail Time.) Gn 79 Sequence Co-ord Selects whether Sequence co-ordination functionality is used or not. Gn 79 Cold Load Action Selects whether the relay will perform Delayed Trips or not when Cold Load is active. 3.6.2.1. P/F Shots Selects whether the first phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F Deadtime 1 Time period between the fault being cleared and the close pulse being issued Gn 79 P/F Prot'n Trip 2 Selects whether the second phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F Deadtime 2 Time period between the fault being cleared and the close pulse being issued Gn 79 P/F Prot'n Trip 3 Selects whether the third phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F Deadtime 3 Time period between the fault being cleared and the close pulse being issued Unrestricted Page 22 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Gn 79 P/F Prot'n Trip 4 Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 1, 2, 3, 4, 5 5 1, 2, 3, 4, 5 5 Description Range Default Gn 79 E/F Prot'n Trip 1 Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 1, 2, 3, 4, 5 5 1, 2, 3, 4, 5 5 Selects whether the fourth phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F Deadtime 4 Time period between the fault being cleared and the close pulse being issued Gn 79 P/F Prot'n Trip 5 Selects whether the fifth phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F HS Trips To Lockout Selects how many High Set trips are allowed before going to Lockout Gn 79 P/F Delayed Trips To Lockout Selects how many Delayed trips are allowed before going to Lockout 3.6.2.2. E/F Shots Selects whether the first earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F Deadtime 1 Time period between the fault being cleared and the close pulse being issued Gn 79 E/F Prot'n Trip 2 Selects whether the second earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F Deadtime 2 Time period between the fault being cleared and the close pulse being issued Gn 79 E/F Prot'n Trip 3 Selects whether the third earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F Deadtime 3 Time period between the fault being cleared and the close pulse being issued Gn 79 E/F Prot'n Trip 4 Selects whether the fourth earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F Deadtime 4 Time period between the fault being cleared and the close pulse being issued Gn 79 E/F Prot'n Trip 5 Selects whether the fifth earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F HS Trips To Lockout Selects how many High Set trips are allowed before going to Lockout Gn 79 E/F Delayed Trips To Lockout Selects how many Delayed trips are allowed before going to Lockout Unrestricted (c)2018 Siemens Protection Devices Limited Page 23 of 61 7SR210 Settings Guide 3.6.2.3. SEF Shots Description Range Default Gn 79 SEF Prot'n Trip 1 Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 1, 2, 3, 4, 5 5 Description Range Default Gn Line Check Trip Disabled, Enabled Enabled Inst, Delayed Inst Inst, Delayed Inst Inst, Delayed Inst Selects whether the first sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Deadtime 1 Time period between the fault being cleared and the close pulse being issued Gn 79 SEF Prot'n Trip 2 Selects whether the second sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Deadtime 2 Time period between the fault being cleared and the close pulse being issued Gn 79 SEF Prot'n Trip 3 Selects whether the third sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Deadtime 3 Time period between the fault being cleared and the close pulse being issued Gn 79 SEF Prot'n Trip 4 Selects whether the fourth sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Deadtime 4 Time period between the fault being cleared and the close pulse being issued Gn 79 SEF Prot'n Trip 5 Selects whether the fifth sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Delayed Trips To Lockout Selects how many Delayed trips are allowed before going to Lockout 3.6.2.4. Extern Shots 3.6.3. Manual Close Selects whether line check trip is enabled, if enabled no AR sequence initiated Gn P/F Line Check Trip Selects whether a phase fault line check trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn E/F Line Check Trip Selects whether an earth fault line check trip is Instantaneous or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn SEF Line Check Trip Selects whether a sensitive earth fault line check trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Unrestricted Page 24 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Gn Extern Line Check Trip Not Blocked, Blocked Not Blocked 0, 0.1 ... 899, 900 10 s 0, 1 ... 599, 600 5s 0, 0.1 ... 899, 900 10 s Latch, Reset Latch Description Range Default Gn Close CB Pulse 0, 0.1 ... 19.9, 20 2s 0, 1 ... 599, 600 2s Gn Minimum LO Delay 0, 1 ... 599, 600 2s Gn Reset LO By Timer Disabled, Enabled Enabled Gn Trip Time Alarm 0, 0.01 ... 1.99, 2 0.2 s 0, 0.005 ... 1.995, 2 0.015 s 0.01, 0.02 ... 1.99, 2 1s 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8, 1.9, 2 1s 0, 0.01, ... 1.1, 1.11 ... 2 0s Selects whether an external line check trip is Instantaneous (Fast) or Delayed Gn Close CB Delay Delay between a Close CB control being received and the Close CB contacts being operated to allow operator walk away. Gn Blocked Close Delay Selects the maximum time that the manual Close CB may be blocked by interlocking before the command or control is cancelled. The relay will signal "Blocked by Interlocking". Gn Open CB Delay Delay between an Open CB control being received and the Open CB contacts being operated. Gn CB Controls Latched Selects whether Binary Input triggers of Close CB and Open CB are latched. 3.6.4. Circuit Breaker Specifies the duration of the circuit breaker close pulse Gn Reclaim Timer The period of time after a CB has closed and remained closed before the reclosure is deemed to be successful and the AR is re-initialised. If the CB remains open at the end of the reclaim time then the AR goes to lockout. An alarm is issued when the Trip time is exceeded Gn Trip Time Adjust Adjustment to take into account any binary input delays for Trip Time Alarm Gn CB Travel Alarm Selects the maximum time that the CB should take to either Open or Close before a failure is recorded. Gn Open CB Pulse Selects the maximum time of the Open CB pulse. If the CB is not closed when this timer expires then an alarm will be raised to signify failure to close. Gn CB DBI Delay Selects the Delay before relay goes to Lockout following a simultaneous Open and Close condition indication. 3.6.5. QUICK LOGIC Description Range Default Quick Logic Disabled, Enabled Disabled Disabled, Enabled Disabled Enable or Disable all logic equations E1 Equation Enable or Disable logic equation E1 Unrestricted (c)2018 Siemens Protection Devices Limited Page 25 of 61 7SR210 Settings Guide Description Range Default E1 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E1 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E1 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E1 Counter Target Select number of times equation must be satisfied before equation output operates E1 Counter Reset Mode Select type of counter reset mode E1 Counter Reset Time Select counter reset time E2 Equation Enable or Disable logic equation E2 E2 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E2 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E2 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E2 Counter Target Select number of times equation must be satisfied before equation output operates E2 Counter Reset Mode Select type of counter reset mode E2 Counter Reset Time Select counter reset time E3 Equation Enable or Disable logic equation E3 E3 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 Unrestricted Page 26 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default E3 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E3 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E3 Counter Target Select number of times equation must be satisfied before equation output operates E3 Counter Reset Mode Select type of counter reset mode E3 Counter Reset Time Select counter reset time E4 Equation Enable or Disable logic equation E4 E4 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E4 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E4 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E4 Counter Target Select number of times equation must be satisfied before equation output operates E4 Counter Reset Mode Select type of counter reset mode E4 Counter Reset Time Select counter reset time E5 Equation Enable or Disable logic equation E5 E5 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E5 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Time before equation output operates, after equation satisfied E5 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E5 Counter Target Select number of times equation must be satisfied before equation output operates Unrestricted (c)2018 Siemens Protection Devices Limited Page 27 of 61 7SR210 Settings Guide Description Range Default E5 Counter Reset Mode Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Select type of counter reset mode E5 Counter Reset Time Select counter reset time E6 Equation Enable or Disable logic equation E6 E6 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E6 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E6 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E6 Counter Target Select number of times equation must be satisfied before equation output operates E6 Counter Reset Mode Select type of counter reset mode E6 Counter Reset Time Select counter reset time E7 Equation Enable or Disable logic equation E7 E7 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E7 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E7 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E7 Counter Target Select number of times equation must be satisfied before equation output operates E7 Counter Reset Mode Select type of counter reset mode E7 Counter Reset Time Select counter reset time E8 Equation Enable or Disable logic equation E8 Unrestricted Page 28 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range E8 (20 Character String) Default Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E8 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E8 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E8 Counter Target Select number of times equation must be satisfied before equation output operates E8 Counter Reset Mode Select type of counter reset mode E8 Counter Reset Time Select counter reset time E9 Equation Enable or Disable logic equation E9 E9 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E9 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E9 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E9 Counter Target Select number of times equation must be satisfied before equation output operates E9 Counter Reset Mode Select type of counter reset mode E9 Counter Reset Time Select counter reset time E10 Equation Enable or Disable logic equation E10 E10 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 Unrestricted (c)2018 Siemens Protection Devices Limited Page 29 of 61 7SR210 Settings Guide Description Range Default E10 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E10 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E10 Counter Target Select number of times equation must be satisfied before equation output operates E10 Counter Reset Mode Select type of counter reset mode E10 Counter Reset Time Select counter reset time E11 Equation Enable or Disable logic equation E11 E11 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E11 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E11 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E11 Counter Target Select number of times equation must be satisfied before equation output operates E11 Counter Reset Mode Select type of counter reset mode E11 Counter Reset Time Select counter reset time E12 Equation Enable or Disable logic equation E12 E12 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E12 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Time before equation output operates, after equation satisfied E12 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E12 Counter Target Select number of times equation must be satisfied before equation output operates Unrestricted Page 30 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default E12 Counter Reset Mode Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Select type of counter reset mode E12 Counter Reset Time Select counter reset time E13 Equation Enable or Disable logic equation E13 E13 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E13 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E13 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E13 Counter Target Select number of times equation must be satisfied before equation output operates E13 Counter Reset Mode Select type of counter reset mode E13 Counter Reset Time Select counter reset time E14 Equation Enable or Disable logic equation E14 E14 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E14 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E14 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E14 Counter Target Select number of times equation must be satisfied before equation output operates E14 Counter Reset Mode Select type of counter reset mode E14 Counter Reset Time Select counter reset time E15 Equation Enable or Disable logic equation E15 Unrestricted (c)2018 Siemens Protection Devices Limited Page 31 of 61 7SR210 Settings Guide Description Range Default E15 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E15 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E15 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E15 Counter Target Select number of times equation must be satisfied before equation output operates E15 Counter Reset Mode Select type of counter reset mode E15 Counter Reset Time Select counter reset time E16 Equation Enable or Disable logic equation E16 E16 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E16 Pickup Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Time before equation output operates, after equation satisfied E16 Dropoff Delay Time before equation output resets, after equation nolonger satisfied E16 Counter Target Select number of times equation must be satisfied before equation output operates E16 Counter Reset Mode Select type of counter reset mode E16 Counter Reset Time Select counter reset time Unrestricted Page 32 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.7. Input Config 3.7.1. Input Matrix Description Range Default Inhibit Cold Load Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Inhibit 51-1 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Selects which inputs inhibit the 51-1 element Inhibit 51-2 Selects which inputs inhibit the 51-2 element Inhibit 50-1 Selects which inputs inhibit the 50-1 element Inhibit 50-2 Selects which inputs inhibit the 50-2 element Inhibit 51N-1 Selects which inputs inhibit the 51N-1 element Inhibit 51N-2 Selects which inputs inhibit the 51N-2 element Inhibit 50N-1 Selects which inputs inhibit the 50N-1 element Inhibit 50N-2 Selects which inputs inhibit the 50N-2 element Inhibit 51G-1 Selects which inputs inhibit the 51G-1 element Inhibit 51G-2 Selects which inputs inhibit the 51G-2 element Inhibit 50G-1 Selects which inputs inhibit the 50G-1 element Inhibit 50G-2 Selects which inputs inhibit the 50G-2 element Inhibit 51SEF-1 Selects which inputs inhibit the 51SEF-1 element Unrestricted (c)2018 Siemens Protection Devices Limited Page 33 of 61 7SR210 Settings Guide Description Range Default Inhibit 51SEF-2 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Inhibit 37G-1 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Inhibit 37G-2 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Inhibit 49 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Inhibit 60CTS-I Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Inhibit 46BC Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Selects which inputs inhibit the 51SEF-2 element Inhibit 50SEF-1 Selects which inputs inhibit the 50SEF-1 element Inhibit 50SEF-2 Selects which inputs inhibit the 50SEF-2 element Inhibit 64H Selects which inputs inhibit the 64H element Inhibit 46IT Selects which inputs inhibit the 46IT element Inhibit 46DT Selects which inputs inhibit the 46DT element Inhibit 37-1 Selects which inputs inhibit the 37-1 element Inhibit 37-2 Selects which inputs inhibit the 37-2 element Selects which inputs inhibit the 49 thermal element Reset 49 Selects which inputs resets the 49 thermal model element Selects which inputs inhibit the 46 Broken Conductor element 74TCS-1 Selects which inputs are monitoring trip circuits 74TCS-2 As Above Unrestricted Page 34 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default 74TCS-3 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ As Above 74CCS-1 Selects which inputs are monitoring trip circuits 74CCS-2 As Above 74CCS-3 As Above Trig Trip Contacts Selects which inputs will trigger the Trip contacts Inhibit 50BF Selects which inputs inhibit the 50BF element 50BF CB Faulty Selects which input bypasses the 50BF timer due to a fault CB 50BF Mech Trip Selects which input allows a mechanical trip to start the 50BF element 50BF Ext Trip Selects which inputs can also start the 50BF element Reset CB Total Trip Selects which inputs Reset the CB Total Trip count Reset CB Delta Trip Selects which inputs Reset the CB Delta Trip count Reset ARBlock Count Selects which inputs Reset the AR Block count Reset Freq Ops Count Selects which inputs Reset the Frequent Ops count Reset I^2t CB Wear Selects which inputs Reset the I^2t CB Wear element Trigger I^2t CB Wear Selects which inputs will cause an external trigger of the I^2t CB Wear element Reset Trip Time Selects which inputs will reset the CB trip time alarm Unrestricted (c)2018 Siemens Protection Devices Limited Page 35 of 61 7SR210 Settings Guide Description Range Default General Alarm 1 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Selects which inputs will activate the General Alarm 1 text General Alarm 2 Selects which inputs will activate the General Alarm 2 text General Alarm 3 Selects which inputs will activate the General Alarm 3 text General Alarm 4 Selects which inputs will activate the General Alarm 4 text General Alarm 5 Selects which inputs will activate the General Alarm 5 text General Alarm 6 Selects which inputs will activate the General Alarm 6 text General Alarm 7 Selects which inputs will activate the General Alarm 7 text General Alarm 8 Selects which inputs will activate the General Alarm 8 text General Alarm 9 Selects which inputs will activate the General Alarm 9 text General Alarm 10 Selects which inputs will activate the General Alarm 10 text General Alarm 11 Selects which inputs will activate the General Alarm 11 text General Alarm 12 Selects which inputs will activate the General Alarm 12 text CB Open Selects which inputs are connected to the circuit breaker open contacts CB Closed Selects which inputs are connected to the circuit breaker closed contacts Reset Demand Selects which inputs will rest the Demand elements. Close CB Selects which inputs will issue a close to the circuit breaker. Unrestricted Page 36 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Block Close CB Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Selects which inputs will block the manual closing of the circuit breaker. Open CB Selects which inputs will issue an open to the circuit breaker. 79 Out Selects which inputs will switch the Auto-recloser out of service 79 In Selects which inputs will switch the Auto-recloser in service 79 Trip & Reclose Selects which inputs will trigger a trip & reclose 79 Trip & Lockout Selects which inputs will trigger a trip & lockout 79 Ext Trip Selects which input will start the external an Auto-relose sequence 79 Ext Pickup Selects which input should be connected to the pickup of the external elements required to start an Auto-reclose sequence 79 Block Reclose Selects which inputs will block the Auto-recloser 79 Reset Lockout Selects which inputs will force the Auto-recloser into the Lockout state 79 Line Check Selects which inputs will start the Line Check functionality of the Auto-recloser 79 Lockout Selects which inputs will force the Auto-recloser into the Lockout state Hot Line Out Selects which inputs will switch out Hot Line Working Hot Line In Selects which inputs will switch in Hot Line Working Inst Prot'n Out Selects which inputs will switch out the instantaneous protection elements Inst Prot'n In Selects which inputs will switch in the instantaneous protection elements Unrestricted (c)2018 Siemens Protection Devices Limited Page 37 of 61 7SR210 Settings Guide Description Range Default E/F Out Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Selects which inputs will switch out the E/F protection elements. E/F In Selects which inputs will switch in the E/F protection elements. SEF Out Selects which inputs will switch out the SEF protection elements SEF In Selects which inputs will switch in the SEF protection elements Trigger Wave Rec Selects which inputs can trigger a waveform record Trigger Fault Rec Selects which inputs can trigger a fault record Select Group 1 Switches active setting group to group 1 Select Group 2 Switches active setting group to group 2 Select Group 3 Switches active setting group to group 3 Select Group 4 Switches active setting group to group 4 Select Group 5 Switches active setting group to group 5 Select Group 6 Switches active setting group to group 6 Select Group 7 Switches active setting group to group 7 Select Group 8 Switches active setting group to group 8 Out Of Service Mode Selects which inputs will put the relay into Out Of Service Mode Local Mode Selects which inputs will put the relay into Local Mode Unrestricted Page 38 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Remote Mode Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------ Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13) BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13) BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13 Selects which inputs will put the relay into Remote Mode Local Or Remote Mode Selects which inputs will put the relay into Local Or Remote Mode Clock Sync. Selects which input is used to synchronise the real time clock Reset LEDs & O/Ps Selects which inputs will reset the latched LEDs and binary outputs Inverted Inputs Selects which inputs will be inverted Enable In Local Selects which inputs will be enabled in local mode Enable In Remote Selects which inputs will be enabled in remote mode Unrestricted (c)2018 Siemens Protection Devices Limited Page 39 of 61 7SR210 Settings Guide 3.7.2. Binary Input Config (Variants may differ) Description Range Default Inverted Inputs Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9 ) --------- 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9 ) 1, 2, 3, 4, 5, 6, 7, 8, 9 Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9 ) 1, 2, 3, 4, 5, 6, 7, 8, 9 Selects which inputs pickup when voltage is removed. BI 1 Pick-up Delay Delay on pickup of DC Binary Input 1 BI 1 Drop-off Delay Delay on dropoff of DC Binary Input 1 BI 39 Pick-up Delay Delay on pickup of DC Binary Input 9 BI 39 Drop-off Delay Delay on dropoff of DC Binary Input 9 Enabled In Local Selects which inputs are enabled when the relay is in Operating Mode 'Local' or 'Local Or Remote' Enabled In Remote Selects which inputs are enabled when the relay is in Operating Mode 'Remote' or 'Local Or Remote' Unrestricted Page 40 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.7.3. General Alarms Description Range Default General Alarm-1 (16 Character String) ALARM 1 (16 Character String) ALARM 2 (16 Character String) ALARM 3 (16 Character String) ALARM 4 (16 Character String) ALARM 5 (16 Character String) ALARM 6 (16 Character String) ALARM 7 (16 Character String) ALARM 8 (16 Character String) ALARM 9 (16 Character String) ALARM 10 (16 Character String) ALARM 11 (16 Character String) ALARM 12 (16 Character String) ALARM 13 (16 Character String) ALARM 14 (16 Character String) ALARM 15 (16 Character String) ALARM 16 (16 Character String) ALARM 17 (16 Character String) ALARM 18 (16 Character String) ALARM 19 (16 Character String) ALARM 20 Defines the text to be displayed for General Alarm 1 General Alarm-2 Defines the text to be displayed for General Alarm 2 General Alarm-3 Defines the text to be displayed for General Alarm 3 General Alarm-4 Defines the text to be displayed for General Alarm 4 General Alarm-5 Defines the text to be displayed for General Alarm 5 General Alarm-6 Defines the text to be displayed for General Alarm 6 General Alarm-7 Defines the text to be displayed for General Alarm 7 General Alarm-8 Defines the text to be displayed for General Alarm 8 General Alarm-9 Defines the text to be displayed for General Alarm 9 General Alarm-10 Defines the text to be displayed for General Alarm 10 General Alarm-11 Defines the text to be displayed for General Alarm 11 General Alarm-12 Defines the text to be displayed for General Alarm 11 General Alarm-13 Defines the text to be displayed for General Alarm 11 General Alarm-14 Defines the text to be displayed for General Alarm 11 General Alarm-15 Defines the text to be displayed for General Alarm 11 General Alarm-16 Defines the text to be displayed for General Alarm 11 General Alarm-17 Defines the text to be displayed for General Alarm 11 General Alarm-18 Defines the text to be displayed for General Alarm 11 General Alarm-19 Defines the text to be displayed for General Alarm 11 General Alarm-20 Defines the text to be displayed for General Alarm 12 Unrestricted (c)2018 Siemens Protection Devices Limited Page 41 of 61 7SR210 Settings Guide 3.8. Output Config 3.8.1. Output Matrix (Variants may differ) Description Range Default Protection Healthy Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) BO1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Grp 1 Relays selected are energised whilst relay self-monitoring does NOT detect any hardware or software errors and DC Supply is healthy. A changeover contact or normally closed contact may be used to generate Protection Defective from this output Active Setting Grp 1 Active Setting Grp 2 Active Setting Grp 3 Active Setting Grp 4 Active Setting Grp 5 Active Setting Grp 6 Active Setting Grp 7 Active Setting Grp 8 Unrestricted Page 42 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default 51-1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 51-1 IDMTL/DTL Overcurrent operated 51-2 51-2 IDMTL/DTL Overcurrent operated 50-1 50-1 INST/DTL Overcurrent operated 50-2 50-2 INST/DTL Overcurrent operated 51N-1 51N-1 IDMTL/DTL derived Earth Fault operated 51N-2 51N-2 IDMTL/DTL derived Earth Fault operated 50N-1 50N-1 INST/DTL derived Earth Fault operated 50N-2 50N-2 INST/DTL derived Earth Fault operated 51G-1 51G-1 IDMTL/DTL measured Earth Fault operated 51G-2 51G-2 IDMTL/DTL measured Earth Fault operated 50G-1 50G-1 INST/DTL measured Earth Fault operated 50G-2 50G-2 INST/DTL measured Earth Fault operated 51SEF-1 51SEF-1 IDMTL/DTL Sensitive Earth Fault operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 43 of 61 7SR210 Settings Guide Description Range Default 51SEF-2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- 37G-1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- 37G-2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- 49 Trip Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- 51SEF-2 IDMTL/DTL Sensitive Earth Fault operated 50SEF-1 50SEF-1 INST/DTL Sensitive Earth Fault operated 50SEF-2 50SEF-2 INST/DTL Sensitive Earth Fault operated 64H 64H Restricted Earth Fault element operated Cold Load Active Cold Load settings are active 46IT IDMTL/DTL NPS Overcurrent operated 46DT INST/DTL NPS Overcurrent operated 37-1 37-1 Under Current operated 37-2 37-2 Under Current operated Thermal capacity trip operated 49 Alarm Thermal capacity alarm operated Unrestricted Page 44 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default 60CTS-I Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- 46BC Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 81HBL2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- General Pickup Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- 46 Broken Conductor element operated 74TCS-1 Trip Circuit 1 fail operated 74TCS-2 Trip Circuit 2 fail operated 74TCS-3 Trip Circuit 3 fail operated 74CCS-1 Close Circuit 1 fail operated 74CCS-2 Close Circuit 2 fail operated 74CCS-3 Close Circuit 3 fail operated General Pickup operated 50BF-1 Circuit Breaker Fail stage 1 operated 50BF-2 Circuit Breaker Fail stage 2 operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 45 of 61 7SR210 Settings Guide Description Range Default 50BF PhA Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Circuit Breaker Fail Phase A 50BF PhB Circuit Breaker Fail Phase B 50BF PhC Circuit Breaker Fail Phase C 50BF EF Circuit Breaker Fail Earth Fault CB Total Trip Count Total CB trip count exceeded CB Ph A Trip Count Total CB Ph A trip count exceeded CB Ph B Trip Count Total CB Ph B trip count exceeded CB Ph C Trip Count Total CB Ph C trip count exceeded CB E/F Trip Count Total CB E/F trip count exceeded CB Delta Trip Count Delta CB trip count exceeded Unrestricted Page 46 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default CB Count To ARBlock Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L3 Count To AR Block CB trip count exceeded CB Freq Ops Count CB Frequent Operations count exceeded I^2t CB Wear I^2t CB Wear limit exceeded Trip Time Alarm Trip Time Alarm operated CB Open Indicates that the circuit breaker is in the open position. CB Closed Indicates that the circuit breaker is in the closed position. Close CB Blocked Indicates that the Close CB control is blocked by its interlocking logic. CB Alarm Indicates the CB is either in an illegal state or is stuck neither open or closed. Open CB Open pulse due to Manual Open being issued. Phase A A phase A element operated Phase B A phase B element operated Phase C A phase C element operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 47 of 61 7SR210 Settings Guide Description Range Default Derived E/F Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Start Count Alarm Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 50AFD PhA Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 50AFD Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 1 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Derive E/F element operated Measured E/F Measured E/F element operated Sensitive E/F Sensitive E/F element operated Arc Flash Detector Phase A operated 50AFD PhB Arc Flash Detector Phase B operated 50AFD PhC Arc Flash Detector Phase C operated Unrestricted Page 48 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default AFD Zone 1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 2 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 3 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 3 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 4 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 5 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Unrestricted (c)2018 Siemens Protection Devices Limited Page 49 of 61 7SR210 Settings Guide Description Range Default AFD Zone 6 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 6 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- User Output 1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- User Output 1 operated --User Output 32 User Output 32 operated En100 Life Raised when the En100 is communicating correctly with the Protection CPU En100 Error Raised when the En100 has detected an Error IEC61850 Configured Raised when the En100 and Protection CPU are configured for IEC 61850. En100 Ch1 Link Down Raised when En100 Ch 1 Link Down En100 Ch2 Link Down Raised when En100 Ch 2 Link Down Unrestricted Page 50 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default Manual Close CB Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Close pulse due to Manual close being issued 79 AR Close CB Close pulse due to auto-reclose sequence 79 Trip & Reclose Indicates the Trip & Reclose sequence being performed 79 Trip & Lockout Indicates the Trip & Lockout sequence being performed 79 Lockout Indicates the auto-recloser is in the Lockout state 79 Out Of Service Indicates the auto-recloser is out of service 79 In Service Indicates the auto-recloser is in service 79 In Progress Indicates an auto-reclose sequence is in progress 79 Block Extern Indicates that Extern for the current shot has been selected to be delayed. (This may be used to block external tripping elements in the same way as the internal protection elements are blocked to achieve Instantaneous / Delayed operation.) 79 CB Fail To Close Indicates the CB was not closed at the end of the Close Pulse 79 Close Onto Fault Indicates an element starter or trip operated during the Close Pulse 79 Successful AR Indicates that after a reclose and at the end of the Reclaim time the CB was closed and there were no auto-reclose trip elements operated. (This is issued for 2 secs) Successful Man Close Indicates that after a manual close and at the end of the Reclaim time the CB was closed and there were no autoreclose trip elements operated. (This is issued for 2 secs) Unrestricted (c)2018 Siemens Protection Devices Limited Page 51 of 61 7SR210 Settings Guide Description Range Default Hot Line Working Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Indicates that Hot LineWorking functionality has been selected Inst Prot'n Out Indicates that the protection elements selected to be Instantaneous elements are switched out E/F Out Indicates that the instantaneous protection elements are switched out. SEF Out Indicates that the SEF protection elements are switched out New Wave Stored The waveform recorder has stored new information Note: this is a pulsed output New Fault Stored The fault recorder has stored new information Note: this is a pulsed output Out Of Service Mode Indicates the relay is in Out Of Service Mode Local Mode Indicates the relay is in Local Mode Remote Mode Indicates the relay is in Remote Mode BI 1 Operated DC Binary Input 1 has operated BI 2 Operated DC Binary Input 2 has operated BI 3 Operated DC Binary Input 3 has operated BI 4 Operated DC Binary Input 4 has operated Unrestricted Page 52 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Description Range Default BI 5 Operated Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- DC Binary Input 5 has operated BI 6 Operated DC Binary Input 6 has operated BI 7 Operated DC Binary Input 7 has operated BI 8 Operated DC Binary Input 8 has operated BI 9 Operated DC Binary Input 9 has operated E1 Quick Logic equation 1 operated E2 Quick Logic equation 2 operated E3 Quick Logic equation 3 operated E4 Quick Logic equation 4 operated E5 Quick Logic equation 5 operated E6 Quick Logic equation 6 operated E7 Quick Logic equation 7 operated E8 Quick Logic equation 8 operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 53 of 61 7SR210 Settings Guide Description Range Default E9 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, L1, L2, L3, L4, L5, L6, L7, L8, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------- BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 ------------------------------------------- BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 ------------------------------------------- BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 -------------- BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 -------------- Quick Logic equation 9 operated E10 Quick Logic equation 10 operated E11 Quick Logic equation 11 operated E12 Quick Logic equation 12 operated E13 Quick Logic equation 13 operated E14 Quick Logic equation 14 operated E15 Quick Logic equation 15 operated E16 Quick Logic equation 16 operated Trip Contacts Assigns Output Contact as trip contact for fault trigger Hand Reset Outputs Assigns Output Contact as hand reset contact Pickup Outputs Selects which outputs can operate because a pickup condition exists Pulsed Outputs Selects which outputs are pulsed. The pulse width is set by the Min Operate Time setting for each output Unrestricted Page 54 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.8.2. Binary Output Config (Variants may differ) Description Range Default Trip Contacts Combination of ( BO1, to B16) -------- Combination of ( 1, to 16) -------- 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s Combination of ( 1 to 16) -------- Combination of ( 1 to 16) -------- The Binary Outputs selected by this setting are classed as Trip contacts. (When any of these BOs operate the Trip LED is lit, CB Fail is started, if enabled, & a Fault Record is stored) Hand Reset Outputs Relays selected, as Hand Reset will remain latched until manually reset from front panel or via communications link or by removing DC Supply. By default relays are Self Resetting and will reset when the driving signal is removed. Min Operate Time 1 Minimum operate time of output relay if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 8 Minimum operate time of output relay 8 if set to self reset, if also set to be pulsed then this is the pulse width Pick-up Outputs Selects which outputs can operate because a pickup condition exists Pulsed Outputs Selects which outputs are pulsed. The pulse width is set by the Min Operate Time setting for each output Unrestricted (c)2018 Siemens Protection Devices Limited Page 55 of 61 7SR210 Settings Guide 3.8.3. LED Config Description Range Default Self Reset LEDs Combination of ( 1 to 32) -------- Combination of ( 1 to 32) 1 to 32 Combination of ( 1 to 32) -------- Combination of ( 1 to 32) 1 to 32 Combination of ( 1 to 32) 1 to 32 Combination of ( 1 to 32) 1 to 32 Description Range Default Gn P/F Pickups Combination of ( 51-1, 51-2, 50-1, 50-2 ) 51-1, 51-2, 50-1, 50-2 Combination of ( 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G1, 50G-2 ) 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2 Combination of ( 51SEF-1, 51SEF2, 50SEF-1, 50SEF-2, 64H ) 51SEF-1, 51SEF-2, 50SEF-1, 50SEF-2, 64H Combination of ( 46IT, 46DT, 37-1, 37-2, 37G-1, 37G-2 ) 46IT, 46DT, 371, 37-2, 37G-1, 37G-2 LEDs selected, as Self Reset will automatically reset when the driving signal is removed. By default all LEDs are Hand Reset and must be manually reset either locally via the front fascia or remotely via communications. PU Self Reset LEDs LEDs selected, as Self Reset will automatically reset when the driving signal is removed. By default all PU LEDs are Self Reset. Green LEDs Selects which LEDs will be green when driven Red LEDs Selects which LEDs will be red when driven PU Green LEDs Selects which LEDs will be green when driven by a pickup PU Red LEDs Selects which LEDs will be red when driven by a pickup 3.8.4. Pickup Config When any of the selected pickups operate General Pickup is driven. Gn E/F Pickups As Above Gn SEF/REF Pickups As Above Gn Misc Pickups As Above Unrestricted Page 56 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.9. CB Maintenance 3.9.1. CB Counters Description Range Default Gn CB Total Trip Count Disabled, Enabled Disabled 0, 1 ... 9999, 10000 100 Disabled, Enabled Disabled Disabled, Enabled Disabled 0, 1 ... 9999, 10000 100 0, 1 ... 9999, 10000 100 0, 1 ... 9999, 10000 100 0, 1 ... 9999, 10000 100 Disabled, Enabled Disabled 0, 1 ... 9999, 10000 100 Disabled, Enabled Disabled 0, 1 ... 9999, 10000 100 Disabled, Enabled Disabled 0, 1 ... 9999, 10000 10 Selects whether the CB Total Trip Count counter is enabled Gn CB Total Trip Count Target Selects the number of CB trips allowed before CB Total Trip Count counter output operates Gn CB Total Trip Count Reset Resets CB Total Trip Count counter Gn CB Total Trip Manual Open Selects whether the CB Total Trip Manual Open is enabled Gn CB Phase Trip Counters Selects whether the CB Phase Trip Counters is enabled Gn CB Ph A Trip Count Target Selects the number of CB trips allowed before CB Ph A Trip Count counter output operates Gn CB Ph B Trip Count Target Selects the number of CB trips allowed before CB Ph B Trip Count counter output operates Gn CB Ph C Trip Count Target Selects the number of CB trips allowed before CB Ph C Trip Count counter output operates Gn CB E/F Trip Count Target Selects the number of CB trips allowed before CB E/F Trip Count counter output operates Gn CB Delta Trip Count Selects whether the CB Delta Trip Count counter is enabled Gn CB Delta Trip Count Target Selects the number of CB trips allowed before CB Delta Trip Count counter output operates Gn CB Delta Trip Count Reset Resets CB Delta Trip Count counter Gn CB Count To AR Block Selects whether the CB Count To AR Block counter is enabled Gn CB Count To AR Block Target Selects the number of CB trips allowed before CB Count To AR Block counter output operates. While count is above target the Autorecloser will only perform 1 x Delayed Shot and Lockout Gn CB Count To AR Block Reset Resets CB Count To AR Block counter Gn CB Freq Ops Count Selects whether the CB Frequent Operations Counter is enabled Gn CB Freq Ops Count Target Selects the number of CB trips allowed before CB Frequent Operations Counter output operates. While count is above target the Autorecloser will only perform 1 x Delayed Shot and Lockout Gn CB Freq Ops Count Reset Resets CB Frequent Operations Counter Unrestricted (c)2018 Siemens Protection Devices Limited Page 57 of 61 7SR210 Settings Guide 3.9.2. I^2T CB Wear Description Range Default Gn I^2t Counter Disabled, Enabled Disabled 10, 11 ... 99000, 100000 10 MA^2 s 0, 0.001 ... 0.199, 0.2 0.02 s 0, 0.001 ... 0.199, 0.2 0.04 s Description Range Default Start Types(s) Power On, Expected, Unexpected All 0, ...10000 100 Description Range Default Data Log Period 5, 6, 7, 8, 9, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 5 min 1, 2 ... 23, 24 24 hrs Fixed, Peak, Rolling Fixed Selects whether the I^2t CB Wear monitor is enabled Gn Alarm Limit Sets limit before alarm is issued Gn Separation Time Sets the time for CB mechanism to start moving, time before contacts start to separate Gn Clearance Time Time for CB to clear fault Reset I^2t Count Reset the CB wear count 3.9.3. START COUNT Selects which type of start-up Start Count Target Selects number of times star-up has occurred before output operatest 3.10. Data Storage 3.10.1. Demand Data/Log Selects period between stored samples Clear Data Log Clear the Data Log Gn Demand Window The time window over which the Min, Max and Mean values are calculated. Gn Demand Window Type Method used to calculate Demand values. Gn Demand Reset Reset all Demand values Unrestricted Page 58 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide 3.10.2. Waveform Storage Description Range Default Gn P/F Trig Storage Combination of ( 51-1, 51-2, 50-1, 50-2 ) 51-1, 51-2, 50-1, 50-2 Combination of ( 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2 ) 51N-1, 51N-2, 50N-1, 50N-2, 51G-1, 51G-2, 50G-1, 50G-2 Combination of ( 51SEF-1, 51SEF-2, 50SEF-1, 50SEF-2, 64H ) 51SEF-1, 51SEF-2, 50SEF-1, 50SEF-2, 64H Combination of ( 46IT, 46DT, 37-1, 37-2, 49 Trip, 49 Alarm, 37G-1, 37G-2 ) -------- Combination of ( AFD-1, AFD-2, AFD-3, AFD-4, AFD-5, AFD-6) ------ 10, 20, 30, 40, 50, 60, 70, 80, 90 20 % 10 Rec x 1 Sec, 5 Rec x 2 Sec, 2 Rec x 5 Sec, 1 Rec x 10 Sec 10 Rec x 1 Sec Select which elements trigger a waveform record Gn E/F Trig Storage As Above Gn SEF/REF Trig Storage As Above Gn Misc Current Storage As Above Gn AFD Trig Storage As Above Pre-trigger Storage Select Percentage of waveform record stored before the fault is triggered Record Duration Select waveform record duration Trigger Waveform Trigger waveform storage Clear Waveforms Clear all stored waveform records 3.10.3. Fault Storage Description Range Default Gn Max Fault Rec Time 0, 1 ... 59900, 60000 2000 ms Range Default Maximum time Fault record information will be stored and classed as same fault Clear Faults Clear all stored fault records 3.10.4. Event Storage Description Clear Events Clear all stored event records Data Log Selects whether the Data Logger is enabled Unrestricted (c)2018 Siemens Protection Devices Limited Page 59 of 61 7SR210 Settings Guide 3.10.5. Communications Description Range Default Station Address 0, 1 ... 65533, 65534 0 OFF, IEC60870-5-103, MODBUS-RTU, DNP3 IEC60870-5103 75, 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 19200 NONE, ODD, EVEN EVEN COM1-RS485 Mode Local, Remote, Local Or Remote Remote COM2-USB Protocol IEC60870-5-103 IEC60870-5103 COM2-USB Mode Local Local COM3 Protocol OFF, IEC60870-5-103, MODBUS-RTU, DNP3 IEC60870-5103 75, 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 19200 NONE, ODD, EVEN EVEN LIGHT OFF, LIGHT ON LIGHT OFF OFF, ON OFF COM3 Mode Local, Remote, Local Or Remote Remote COM4 Protocol OFF, IEC60870-5-103, MODBUS-RTU, DNP3 OFF 75, 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 19200 NONE, ODD, EVEN EVEN LIGHT OFF, LIGHT ON LIGHT OFF OFF, ON OFF COM4 Mode Local, Remote, Local Or Remote Remote DNP3 Unsolicited Events Disabled, Enabled Disabled 0, 1 ... 65533, 65534 0 IEC 60870-5-103 Station Address COM1-RS485 Protocol Selects protocol to use for COM1-RS485 COM1-RS485 Baud Rate Sets the communications baud rate for COM1-RS485 COM1-RS485 Parity Selects whether parity information is used Selects protocol to use for COM2-USB Selects protocol to use for COM3 COM3 Baud Rate Sets the communications baud rate for COM3 COM3 Parity Selects whether parity information is used COM3 Line Idle Selects the communications line idle sense COM3 Data Echo Enables echoing of data from RX port to TX port when operating relays in a Fibre Optic ring configuration Selects protocol to use for COM4 COM4 Baud Rate Sets the communications baud rate for COM4 COM4 Parity Selects whether parity information is used COM4 Line Idle Selects the communications line idle sense COM4 Data Echo Enables echoing of data from RX port to TX port when operating relays in a Fibre Optic ring configuration Allows unsolicited event support in the relay. When Enabled, unsolicited event transmission can be controlled by the Master. When Disabled, Master requests are ignored. DNP3 Destination Address The address of the master to which unsolicited events will be sent. Unrestricted Page 60 of 61 (c) 2018 Siemens Protection Devices Limited 7SR210 Settings Guide Unrestricted (c)2018 Siemens Protection Devices Limited Page 61 of 61 7SR220 Directional Relay Instrumentation Guide The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide Document Release History This document is issue 2017/12. The list of revisions up to and including this issue is: - 2011/05 First issue 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/11 Typographical revisions and format 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. Software Revision History 2011/05 2435H85009R7a-7a (7SR220) First Release 2013/01 2435H85009R7c-7b (7SR220) 2014/06 2435H85009R7f-7d (7SR220) 2015/06 2435H85009R8a-7f (7SR220) 2016/02 2435H85009R8b-7f (7SR220) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Added Fault Locator feature and Check Sync feature. Fault data transmitted over 103. Additional communications data, control features, meters. Added Power Factor Meters, Load Blinding feature, Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Page 2 of 20 Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing, 67SEF Compensated Network, 67SEF Wattmetric. Increased I/O. Event Data on LCD. (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide Contents Document Release History................................................................................. 2 Software Revision History .................................................................................. 2 1. Function Diagram........................................................................................... 4 2. Menu Structure .............................................................................................. 5 1. Relay Instrumentation .................................................................................... 6 1.1. Favourite Meters.................................................................................... 6 1.2. Current Meters....................................................................................... 6 1.3. Voltage Meters ...................................................................................... 8 1.4. Frequency Meters .................................................................................. 8 1.5. Power Meters....................................................................................... 10 1.6. Energy Meters ..................................................................................... 12 1.7. WATTMETRIC Meters......................................................................... 12 1.8. Directional Meters ............................................................................... 12 1.9. Thermal Meters ................................................................................... 12 1.10. Auto-Reclose Meters ........................................................................... 14 1.11. Synchronising Meters .......................................................................... 14 1.12. Maintenance Meters ............................................................................ 14 1.13. General Alarm Meters ......................................................................... 16 1.14. Demand Meters ................................................................................... 16 1.15. Binary Input Meters ............................................................................. 17 1.16. Binary Output Meters........................................................................... 17 1.17. Virtual Meters ...................................................................................... 19 1.18. Communication Meters ........................................................................ 19 Miscellaneous Meters .................................................................................. 20 1.19. Quick Logic Meters .............................................................................. 20 1.20. Fault Locator ....................................................................................... 20 (c) 2017 Siemens Protection Devices Limited Page 3 of 20 7SR220 Instrumentation Guide 1.Function Diagram Page 4 of 20 (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide 2.Menu Structure (c) 2017 Siemens Protection Devices Limited Page 5 of 20 7SR220 Instrumentation Guide 1. Relay Instrumentation 1.1. Favourite Meters Instrument Description -------------------FAVOURITE METERS > to view This allows the user to view his previously constructed list of `favourite meters' by pressing TEST/RESET button and the READ DOWN button to scroll though the meters added to this sub-group To construct a sub-group of favourite meters, first go to the desired meter then press ENTER this will cause a message to appear on the LCD `Add To Favourites YES pressing ENTER again will add this to the FAVOURITE METERS Sub-menu. To remove a meter from the FAVOURITE METERS submenu go to that meter each in the FAVOURITE METERS sub-menu or at its Primary location press ENTER and the message `Remove From Favourites' will appear press ENTER again and this meter will be removed from the FAVOURITE METERS sub-group 1.2. Current Meters Instrument Description -------------------CURRENT METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Current TEST/RESET allows access to this sub-group Primary Current Ia 0.00A Ib 0.00A Ic 0.00A Secondary Current Ia 0.00A Ib 0.00A Ic 0.00A Nom Current o Ia 0.00xIn ---o Ib 0.00xIn ---o Ic 0.00xIn ---Pri Earth Current In 0.000A Ig 0.000A Sec Earth Current In 0.000A Ig 0.000A Nom Earth Current o In 0.000xIn ---o Ig 0.000xIn ---I Seq Components Izps 0.00xIn ----o o Ipps 0.00xIn ---o Inps 0.00xIn ---nd 2 Harmonic Current Ia 0.00xIn Ib 0.00xIn Ic 0.00xIn Page 6 of 20 Displays the 3 phase currents Primary RMS values Displays the 3 phase currents Secondary RMS values Displays the 3 phase currents Nominal RMS values & phase angles with respect to PPS current. Displays the 3 Earth currents Primary RMS values Displays the 3 Earth currents Secondary RMS values Displays the 3 Earth currents Nominal RMS values & phase angles with respect to PPS current. Displays the Current Sequence components Nominal RMS values & phase angles with respect to PPS current. nd Displays the 3 phase currents 2 Harmonic components Nominal RMS values. (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide Instrument Description th 5 Harmonic Current Ia 0.00xIn Ib 0.00xIn Ic 0.00xIn Last Trip P/F Ia Ib Ic Last Trip E/F In Ig 0.00A 0.00A 0.00A 0.00A 0.00A th Displays the 3 phase currents 5 Harmonic components Nominal RMS values. Displays the Last Trip Fault Current.. Displays the Last Trip Fault Current.. (c) 2017 Siemens Protection Devices Limited Page 7 of 20 7SR220 Instrumentation Guide 1.3. Voltage Meters -------------------VOLTAGE METERS > to view -------------------Prim Ph-Ph Voltage Vab 0.00V Vbc 0.00V Vca 0.00V Sec Ph-Ph Voltage Vab 0.00V Vbc 0.00V Vca 0.00V Nominal Ph-Ph Voltage Vab 0.00xVn ----o Vbc 0.00xVn ----o Vca 0.00xVn ----o Prim Ph-N Voltage Va 0.00V Vb 0.00V Vc 0.00V Sec Ph-N Voltage Va 0.00V Vb 0.00V Vc 0.00V Nom Ph-N Voltage Va 0.00xVn ----o Vb 0.00xVn ----o Vc 0.00xVn ----o V Seq Components Izps 0.00V ----o Ipps 0.00V ----o Inps 0.00V ----o Calc Earth Voltage Pri 0.00V Sec 0.00V ----o CS/NVD Voltage (Vx) Pri 0.00V Sec 0.00V ----o Last Trip Voltage Va 0.00V Vb 0.00V Vc 0.00V This is the sub-group that includes all the meters that are associated with Voltage TEST/RESET allows access to this sub-group Displays the Phase to Phase Voltage Primary RMS values Displays the Phase to Phase Voltage Secondary RMS values & Angles with respect to PPS voltage. Displays the Phase to Phase Voltage Nominal RMS values Displays the Phase to Neutral Voltage Primary RMS values Displays the Phase to Neutral Voltage Secondary RMS values & Angles with respect to PPS voltage. Displays the Phase to Neutral Voltage Nominal RMS values Displays the Voltage Sequence components Nominal RMS values & phase angles with respect to PPS voltage. Displays the calculated Earth voltage both primary and secondary which also shows the secondary angle Displays the 4th voltage (Vx) both primary and secondary which also shows the secondary angle. This voltage can be used for NVD, Vx 27/59 or where available Checksync. Displays the Phase to Neutral Voltage Nominal RMS values from Last Trip 1.4. Frequency Meters Instrument Description -------------------FREQUENCY METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Frequency TEST/RESET allows access to this sub-group Displays the power system frequency. Page 8 of 20 (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide Frequency 0.000Hz (c) 2017 Siemens Protection Devices Limited Page 9 of 20 7SR220 Instrumentation Guide 1.5. Power Meters Instrument -------------------POWER METERS > to view -------------------Primary Power (P) Phase A 0.0W Phase B 0.0W Phase C 0.0W Secondary Power (P) Phase A 0.0W Phase B 0.0W Phase C 0.0W Nominal Power (P) Phase A 0.00xSn Phase B 0.00xSn Phase C 0.00xSn Primary Power (Q) Phase A 0.0VAr Phase B 0.0VAr Phase C 0.0VAr Secondary Power (Q) Phase A 0.0VAr Phase B 0.0VAr Phase C 0.0VAr Nominal Power (Q) Phase A 0.00xSn Phase B 0.00xSn Phase C 0.00xSn Primary Power (S) Phase A 0.0VA Phase B 0.0VA Phase C 0.0VA Secondary Power (S) Phase A 0.0VAr Phase B 0.0VAr Phase C 0.0VAr Nominal Power (S) Phase A 0.00xSn Phase B 0.00xSn Phase C 0.00xSn Primary Power (3P) P 0.0W Q 0.0VAr S 0.0VA Secondary Power (3P) P 0.0W Q 0.0VAr S 0.0VA Power Factor PF A 0.00 PF B 0.00 PF C 0.00 Page 10 of 20 Description This is the sub-group that includes all the meters that are associated with Power TEST/RESET allows access to this sub-group Displays Primary Real Power Displays Secondary Real Power Displays Nominal Real Power Displays Primary Reactive Power Displays Secondary Reactive Power Displays Nominal Reactive Power Displays Primary Apparent Power Displays Secondary Apparent Power Displays Nominal Apparent Power Displays 3-Phase Primary Power Displays 3-Phase Secondary Power Displays Power factor (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide PF (3P) 0.00 Primary Power (32S) P (32S) 0.0W Q (32S) 0.0VAr S (32S) 0.0VA Secondary Power (32S) P (32S) 0.0W Q (32S) 0.0VAr S (32S) 0.0VA Nominal Power (32S) P (32S) 0.00xSn Q (32S) 0.00xSn S (32S) 0.00xSn Power Factor (32S) PF (32S) 0.00 Displays 3-Phase Primary Power (32S) Displays 3-Phase Secondary Power (32S) Displays 3-Phase Nominal Power (32S) Displays Power Factor (32S) (c) 2017 Siemens Protection Devices Limited Page 11 of 20 7SR220 Instrumentation Guide 1.6. Energy Meters Instrument Description -------------------ENERGY METERS > to view -------------------Active Energy Exp 000000x10kWh Imp 000000x10kWh Reactive Energy Exp 000000x10kVArh Imp 000000x10kVArh This is the sub-group that includes all the meters that are associated with Energy TEST/RESET allows access to this sub-group Displays both imported and exported Active Energy Displays both imported and exported Reactive Energy 1.7. WATTMETRIC Meters Instrument Description -------------------WATTMETRIC METERS > to view -------------------Ires R 0.0xIn W Pres 0.0 xIn W Ires R Angle 0.0 I0-V0 Angle 0.0 This is the sub-group that includes all the meters that are associated with Wattmetric TEST/RESET allows access to this sub-group sub-group The Wattmetric component of residual current Wattmetric residual power Compensated residual phase angle Applied residual phase angle 1.8. Directional Meters Instrument Description -------------------DIRECTIONAL METERS > to view -------------------P/F Dir (67) -------------------No Dir Calc E/F Dir (67N) -------------------- This is the sub-group that includes all the meters that are associated with Directional elements TEST/RESET allows access to this sub-group. Only seen on models that have the 67 option The appropriate values from the selection will be displayed. No Dir, PhA Fwd, PhA Rev, PhB Fwd, PhB Rev, PhC Fwd, PhC Rev The appropriate values from the selection will be displayed. No Dir Meas E/F Dir (67G) -------------------- No Dir, E/F Fwd, E/F Rev The appropriate values from the selection will be displayed. No Dir SEF Dir (67SEF) -------------------- No Dir, E/F Fwd, E/F Rev The appropriate values from the selection will be displayed. No Dir No Dir, SEF Fwd, SEF Rev 1.9. Thermal Meters Instrument Description -------------------- This is the sub-group that includes all the meters that are associated with Page 12 of 20 (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide Instrument Description THERMAL METERS > to view Thermal TEST/RESET allows access to this sub-group Thermal Status Phase A Phase B Phase C 0.0% 0.0% 0.0% Displays the thermal capacity (c) 2017 Siemens Protection Devices Limited Page 13 of 20 7SR220 Instrumentation Guide 1.10. Auto-Reclose Meters Instrument Description -------------------AUTORECLOSE METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Autoreclose TEST/RESET allows access to this sub-group. Only seen on models that have the 79 option Autoreclose Status Out Of Service Close Shot 0 Status of the autoreclose. 1.11. Synchronising Meters SYNC METERS to view Line Volts Bus Volts Line Freq Bus Freq Phase Diff Slip Freq Voltage Diff 0.00V 0.00V 0.000Hz 0.000Hz 0.0Deg 0.000Hz 0% This is the sub-group that includes all the meters that are associated with Synchronising TEST/RESET allows access to this sub-group Displays the voltages used for synchronising in models that include this function Displays the calculated synchronising parameters in models that include this function 1.12. Maintenance Meters Instrument Description -------------------MAINTENANCE METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Maintenance TEST/RESET allows access to this sub-group CB Total Trips Count 0 Target 100 CB Phase A Trips Count 0 Target 100 CB Phase B Trips Count 0 Target 100 CB Phase C Trips Count 0 Target 100 CB Phase E/F Trips Count 0 Target 100 CB Delta Trips Count 0 Target 100 CB Count To AR Block Count 0 Page 14 of 20 Displays the number of CB trips experienced by the CB Displays the number of CB Phase A Trips experienced by the CB Displays the number of CB Phase B Trips experienced by the CB Displays the number of CB Phase C Trips experienced by the CB Displays the number of CB Phase E/F Trips experienced by the CB Displays the number of CB trips experienced by the CB Displays the number of CB trips experienced by the CB. When the target is reached the relay will only do 1 Delayed Trip to Lockout. (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide Instrument Target 100 CB Freq Ops Count Count 0 Target 10 CB Wear Phase A 0.00MA^2s Phase B 0.00MA^2s Phase C 0.00MA^2s CB Wear Remaining Phase A 100% Phase B 100% Phase C 100% CB Trip Time 0.0ms Description Displays the number of CB trips experienced by the CB over the last rolling 1 hr period. When the target is reached the relay will only do 1 Delayed Trip to Lockout. Displays the current measure of circuit breaker wear. Displays the current measure of circuit breaker wear remaining Displays the trip time for the circuit breaker. (c) 2017 Siemens Protection Devices Limited Page 15 of 20 7SR220 Instrumentation Guide 1.13. General Alarm Meters Instrument Description -------------------GENERAL ALARM METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with the Binary inputs TEST/RESET allows access to this sub-group General Alarms -------------------ALARM 1 Cleared Displays the state of General Alarm ... General Alarms -------------------ALARM 20 Cleared 1.14. Demand Meters Instrument Description -------------------DEMAND METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with the demand metering. TEST/RESET allows access to this sub-group V Phase A Demand Max 0.00V Min 0.00V Mean 0.00V V Phase B Demand Max 0.00V Min 0.00V Mean 0.00V V Phase C Demand Max 0.00V Min 0.00V Mean 0.00V V Phase AB Demand Max 0.00V Min 0.00V Mean 0.00V V Phase BC Demand Max 0.00V Min 0.00V Mean 0.00V V Phase CA Demand Max 0.00V Min 0.00V Mean 0.00V I Phase A Demand Max 0.00A Min 0.00A Mean 0.00A Page 16 of 20 Shows the Max, Min and Mean Voltage for Phase A. Shows the Max, Min and Mean Voltage for Phase AB. Shows the Max, Min and Mean Voltage for Phase AC. Shows the Max, Min and Mean Voltage for Phase AB. Shows the Max, Min and Mean Voltage for Phase BC. Shows the Max, Min and Mean Voltage for Phase CA. Shows the Max, Min and Mean for Phase A. (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide Instrument Description I Phase B Demand Max 0.00A Min 0.00A Mean 0.00A I Phase C Demand Max 0.00A Min 0.00A Mean 0.00A I Phase Ig Demand Max 0.00A Min 0.00A Mean 0.00A Power P 3P Demand Max 0.00W Min 0.00W Mean 0.00W Power Q 3P Demand Max 0.00VAr Min 0.00VAr Mean 0.00VAr Power S 3P Demand Max 0.00VA Min 0.00VA Mean 0.00VA Frequency Demand Max 0.000Hz Min 0.000Hz Mean 0.000Hz Power Factor 3P Demand Max 0.00 Min 0.00 Mean 0.00 Shows the Max, Min and Mean for Phase B. Shows the Max, Min and Mean for Phase C. Shows the Max, Min and Mean for Phase Ig. Shows the Max, Min and Mean for Power P 3P Demand. Shows the Max, Min and Mean for Power Q 3P Demand. Shows the Max, Min and Mean for Power S 3P Demand. Shows the Max, Min and Mean for System Frequency Demand. Shows the Max, Min and Mean for System Power Factor 3P Demand. 1.15. Binary Input Meters Instrument Description -------------------BINARY INPUT METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with the Binary inputs TEST/RESET allows access to this sub-group BI 1-8 BI 9-9 ---- ---- Displays the state of DC binary inputs 1 to 9 (The number of binary inputs may vary depending on model) 1.16. Binary Output Meters Instrument Description -------------------BINARY OUTPUT METERS > to view This is the sub-group that includes all the meters that are associated with the Binary Outputs TEST/RESET allows access to this subgroup (c) 2017 Siemens Protection Devices Limited Page 17 of 20 7SR220 Instrumentation Guide Instrument Description -------------------BO 1-8 Page 18 of 20 ---- ---- Displays the state of DC binary Outputs 1 to 8. (The number of binary outputs may vary depending on model) (c) 2017 Siemens Protection Devices Limited 7SR220 Instrumentation Guide 1.17. Virtual Meters Instrument Description -------------------VIRTUAL METERS > to view -------------------- This is the sub-group that shows the state of the virtual status inputs in the relay TEST/RESET allows access to this sub-group V 1-8 V 9-16 ---- ------- ---- Displays the state of Virtual Outputs 1 to 16 (The number of virtual inputs will vary depending on model) 1.18. Communication Meters Instrument Description -------------------COMMUNICATION METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with Communications ports TEST/RESET allows access to this sub-group COM1 COM2 COM3 COM4 COM1 TRAFFIC Tx1 0 Rx1 0 Rx1 Errors 0 COM2 TRAFFIC Tx2 0 Rx2 0 Rx2 Errors 0 COM3 TRAFFIC Tx3 0 Rx3 0 Rx3 Errors 0 COM4 TRAFFIC Tx4 0 Rx4 0 Rx4 Errors 0 EN100 INFORMATION Version : EN100 Version Info Part# BF1111111111 Network Config Mac 00000000 IP 000.000.000.000 NM 255.255.255.000 Gateway: 000.000.000.000 EN100 NTP info: EN100 Link 1/2 status info: EN100 Rx/Tx Count En100 Rx/Tx Error En100 Rx/Tx 10s CPU Load % EN100 Info Meters : 1-n (c) 2017 Siemens Protection Devices Limited Displays which com ports are currently active Displays traffic on Com1 Displays traffic on Com2 Displays traffic on Com3 Displays traffic on Com4 Displays EN100 information Displays EN100 network information Displays further EN100 61850 information Displays further EN100 61850 information Page 19 of 20 7SR220 Instrumentation Guide Miscellaneous Meters Instrument Description -------------------MISCELLANEOUS METERS > to view -------------------- This is the sub-group that includes indication such as the relays time and date, the amount of fault and waveform records stored in the relay TEST/RESET allows access to this sub-group Start Alarm Count 0 Target 100 Hrs In Service Time Time 0Hrs Date 01/01/2000 Time 22:41:44 Waveform Recs 0 Fault Recs 0 Event Recs 0 Data Log Recs 0 Settings Group 1 This meter displays the Start Alarm count. This meter displays the amount of time in service This meter displays the Date, Time, Waveform Records and the number of Fault Records stored in the relay This meter displays the Event Records, Data Log Records and Active Settings Group number stored in the relay 1.19. Quick Logic Meters Instrument Description -------------------QUICK LOGIC METERS > to view -------------------- This is the sub-group that includes all the meters that are associated with QuickLogic. TEST/RESET allows access to this sub-group E 1-8 E 9-16 E1 Equation EQN TMR CNT ---- ------- ---- Shows the state of all the equations 0-0 0-1 =0 =0 =0 E16 Equation EQN TMR 0-0 CNT 0-1 =0 =0 =0 Shows the state of an individual equation. EQN shows the equation state. TMR shows the timer progress and state for the equation. CNT shows the count progress and state for the equation. Shows the state of an individual equation. EQN shows the equation state. TMR shows the timer progress and state for the equation. CNT shows the count progress and state for the equation. 1.20. Fault Locator Instrument Description -------------------FAULT LOCATOR METER > to view -------------------- This is the sub-group that includes all the meters that are associated with the Fault Locator TEST/RESET allows access to this subgroup Distance Impedance Reactance Page 20 of 20 0.0% 0.0ohms 0.0ohms Displays the Fault Location. (c) 2017 Siemens Protection Devices Limited 7SR220 Directional Relay Settings Guide Unrestricted The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Document Release History This document is issue 2017/12. The list of revisions up to and including this issue is: - 2011/05 First issue 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. Software Revision History 2011/05 2435H85009R7a-7a (7SR220) First Release 2013/01 2435H85009R7c-7b (7SR220) 2014/06 2435H85009R7f-7d (7SR220) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Added Fault Locator feature and Check Sync feature. Fault data transmitted over 103. Additional communications data, control features, meters. 2015/06 2435H85009R8a-7f (7SR220) 2016/02 2435H85009R8b-7f (7SR220) 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Unrestricted Page 2 of 107 Added Power Factor Meters, Load Blinding feature, Arc Flash Detector. Over current TM setting range extended. EN100+ Compatibility. Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing. Increased I/O. (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Contents Document Release History .............................................................................................................. 2 Software Revision History............................................................................................................... 2 1. Function Diagram .................................................................................................................... 6 2. Menu Structure ........................................................................................................................ 7 3. Relay Settings .......................................................................................................................... 8 3.1. 3.2. 3.3. 3.4. System Config................................................................................................................. 8 CT/VT Config .................................................................................................................. 9 Function Config ............................................................................................................ 10 Current Prot'n................................................................................................................ 12 3.4.1. Phase Overcurrent ............................................................................................ 12 3.4.1.1. 51-1 ......................................................................................................... 12 3.4.1.2. 51-2 ......................................................................................................... 13 3.4.1.3. 51-3 ......................................................................................................... 14 3.4.1.4. 51-4 ......................................................................................................... 15 3.4.1.5. 50-1 ......................................................................................................... 15 3.4.1.6. 50-2 ......................................................................................................... 16 3.4.1.7. 50-3 ......................................................................................................... 16 3.4.1.8. 50-4 ......................................................................................................... 17 3.4.2. Voltage Controlled O/C .................................................................................... 17 3.4.3. Cold Load........................................................................................................... 18 3.4.4. Derived E/F ........................................................................................................ 19 3.4.4.1. 51N-1 ...................................................................................................... 19 3.4.4.2. 51N-2 ...................................................................................................... 20 3.4.4.3. 51N-3 ...................................................................................................... 20 3.4.4.4. 51N-4 ...................................................................................................... 21 3.4.4.5. 50N-1 ...................................................................................................... 22 3.4.4.6. 50N-2 ...................................................................................................... 22 3.4.4.7. 50N-3 ...................................................................................................... 22 3.4.4.8. 50N-4 ...................................................................................................... 23 3.4.5. Measured E/F .................................................................................................... 23 3.4.5.1. 51G-1 ...................................................................................................... 23 3.4.5.2. 51G-2 ...................................................................................................... 24 3.4.5.3. 51G-3 ...................................................................................................... 25 3.4.5.4. 51G-4 ...................................................................................................... 25 3.4.5.5. 50G-1 ...................................................................................................... 26 3.4.5.6. 50G-2 ...................................................................................................... 26 3.4.5.7. 50G-3 ...................................................................................................... 26 3.4.5.8. 50G-4 ...................................................................................................... 27 3.4.6. Sensitive E/F ..................................................................................................... 27 3.4.6.1. 51SEF-1 .................................................................................................. 27 3.4.6.2. 51SEF-2 .................................................................................................. 28 3.4.6.3. 51SEF-3 .................................................................................................. 28 3.4.6.4. 51SEF-4 .................................................................................................. 29 Unrestricted (c)2018 Siemens Protection Devices Limited Page 3 of 107 7SR220 Settings Guide 3.4.6.5. 50SEF-1 .................................................................................................. 30 3.4.6.6. 50SEF-2 .................................................................................................. 30 3.4.6.7. 50SEF-3 .................................................................................................. 30 3.4.6.8. 50SEF-4 .................................................................................................. 30 3.4.7. Restricted E/F .................................................................................................... 31 3.4.8. NPS Overcurrent ............................................................................................... 31 3.4.8.1. 46IT .......................................................................................................... 31 3.4.8.2. 46DT ........................................................................................................ 31 3.4.9. Under Current .................................................................................................... 32 3.4.9.1. 37-1 .......................................................................................................... 32 3.4.9.2. 37-2 .......................................................................................................... 32 3.4.9.3. 37G-1 ....................................................................................................... 32 3.4.9.4. 37G-2 ....................................................................................................... 32 3.4.9.5. 37SEF-1 .................................................................................................. 33 3.4.9.6. 37SEF-2 .................................................................................................. 33 3.4.10. Thermal ......................................................................................................... 33 3.4.11. ARC Flash Detector ..................................................................................... 33 3.5. Voltage Protection......................................................................................................... 33 3.5.1. Phase U/O Voltage ............................................................................................ 33 3.5.2. 27/59-1 ................................................................................................................ 34 3.5.3. 27/59-2 ................................................................................................................ 34 3.5.4. 27/59-3 ................................................................................................................ 35 3.5.5. 27/59-4 ................................................................................................................ 35 3.6. Vx U/O Voltage .............................................................................................................. 36 3.7. NPS Overvoltage .......................................................................................................... 36 3.7.1. 47-1 ..................................................................................................................... 36 3.7.2. 47-2 ..................................................................................................................... 36 3.8. Neutral Overvoltage ...................................................................................................... 37 3.8.1. 59NIT .................................................................................................................. 37 3.8.2. 59NDT ................................................................................................................. 37 3.9. U/O Frequency .............................................................................................................. 37 3.9.1. 81-1 ..................................................................................................................... 38 3.9.2. 81-2 ..................................................................................................................... 38 3.9.3. 81-3 ..................................................................................................................... 38 3.9.4. 81-4 ..................................................................................................................... 39 3.9.5. 81-5 ..................................................................................................................... 39 3.9.6. 81-6 ..................................................................................................................... 40 3.10. Supervision .................................................................................................................... 40 3.10.1. CB Fail .......................................................................................................... 40 3.10.2. VT Supervision ............................................................................................. 40 3.10.3. CT Supervision............................................................................................. 41 3.10.4. Broken Conductor ........................................................................................ 41 3.10.5. Trip CCT Supervision .................................................................................. 42 3.10.6. Close CCT Supervision ............................................................................... 42 3.10.7. Inrush Detector ............................................................................................. 42 3.10.8. Load Blinder ................................................................................................. 43 Unrestricted Page 4 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 3.10.8.1. 21LB-3P ............................................................................................. 43 3.10.8.2. 21LB-1P ............................................................................................. 43 3.11. Control & Logic ............................................................................................................. 43 3.11.1. Autoreclose Prot'n ....................................................................................... 43 3.11.2. Autoreclose Config ...................................................................................... 44 3.11.2.1. P/F Shots ........................................................................................... 45 3.11.2.2. E/F Shots ........................................................................................... 45 3.11.2.3. SEF Shots.......................................................................................... 46 3.11.2.4. Extern Shots ...................................................................................... 47 3.11.3. Synchronising Check .................................................................................. 47 3.11.4. Manual CB Control ...................................................................................... 48 3.11.5. Circuit Breaker ............................................................................................. 49 3.11.6. QUICK LOGIC ............................................................................................. 49 3.12. Input Config ................................................................................................................... 58 3.12.1. Input Matrix .................................................................................................. 58 3.12.2. Function Key Matrix .................................................................................... 71 3.12.3. Binary Input Config ..................................................................................... 73 3.12.4. Function Key Config.................................................................................... 74 3.12.5. General Alarms............................................................................................ 75 3.13. Output Config ................................................................................................................ 76 3.13.1. Output Matrix ............................................................................................... 76 3.13.2. Binary Output Config .................................................................................. 99 3.13.3. LED Config ..................................................................................................100 3.13.4. Pickup Config..............................................................................................101 3.14. Maintenance ................................................................................................................101 3.14.1. CB Counters ...............................................................................................102 3.14.2. I^2T CB Wear .............................................................................................102 3.14.3. START COUNT ..........................................................................................103 3.15. Data Storage ................................................................................................................103 3.15.1. Demand Data/Log ......................................................................................103 3.15.2. Waveform Storage .....................................................................................103 3.15.3. Fault Storage ..............................................................................................104 3.15.4. Event Storage .............................................................................................104 3.15.5. Energy Storage ...........................................................................................104 3.15.6. Fault Locator ...............................................................................................105 3.15.7. Communications .........................................................................................106 Unrestricted (c)2018 Siemens Protection Devices Limited Page 5 of 107 7SR220 Settings Guide 1.Function Diagram Unrestricted Page 6 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 2.Menu Structure 7SR22 ARGUS ENTER to CONTROL CONTROL MODE SETTINGS MODE INSTRUMENTS MODE FAULT DATA MODE CB TRAVELLING CLOSE I OPEN SYSTEM CONFIG FAVOURITE METERS NUMBER OF FAULTS AR : OUT OF SERVICE IN I OUT CT/VT CONFIG CURRENT METERS AR : TRIP & RECLOSE CONFIRM ACTION FUNCTION CONFIG AR : TRIP & LOCKOUT CONFIRM ACTION HOTLINE WORKING : OUT IN I OUT CURRENT PROT'N VOLTAGE METERS PHASE OVERCURRENT VOLTAGE CONT O/C E/F IN IN I OUT SEF IN IN I OUT INST PROT'N : IN IN I OUT EVENT DATA MODE 51-1 51-2 51-3 51-4 50-1 50-2 50-3 50-4 FREQUENCY METERS POWER METERS ENERGY METERS COLD LOAD DERIVED E/F 51N-1 51N-2 51N-3 51N-4 50N-1 50N-2 50N-3 50N-4 MEASURED E/F 51G-1 51G-2 51G-3 51G-4 50G-1 50G-2 50G-3 50G-4 SENSITIVE E/F 51SEF-1 51SEF-2 51SEF-3 51SEF-4 50SEF-1 50SEF-2 50SEF-3 50SEF-4 RESTRICTED E/F NPS OVERCURRENT 46IT 46DT UNDER CURRENT 37-1 37-2 DIRECTIONAL METERS THERMAL METERS AUTORECLOSE METERS MAINTENANCE METERS GENERAL ALARM METERS BINARY INPUT METERS BINARY OUTPUT METERS VIRTUAL METERS THERMAL VOLTAGE PROT'N PHASE U/O VOLTAGE 27/59-1 27/59-2 27/59-3 27/59-4 COMMUNICATION METERS Vx U/O VOLTAGE MISCELLANEOUS METERS NPS OVERVOLTAGE NEUTRAL OVERVOLTAGE U/O FREQUENCY SUPERVISION CB FAIL 47-1 47-2 59NIT 59NDT 81-1 81-2 81-3 81-4 81-5 81-6 VT SUPERVISION CT SUPERVISION BROKEN CONDUCTOR TRIP CCT SUPERVISION INRUSH DETECTOR DEMAND CONTROL & LOGIC AUTORECLOSE PROT'N AUTORECLOSE CONFIG MANUAL CLOSE CIRCUIT BREAKER QUICK LOGIC INPUT CONFIG INPUT MATRIX FUNCTION KEY MATRIX BINARY INPUT CONFIG FUNCTION KEY CONFIG GENERAL ALARMS OUTPUT CONFIG OUTPUT MATRIX BINARY OUTPUT CONFIG LED CONFIG PICKUP CONFIG CB MAINTENANCE CB COUNTERS I^2T CB WEAR DATA STORAGE COMMUNICATIONS Unrestricted (c)2018 Siemens Protection Devices Limited Page 7 of 107 7SR220 Settings Guide 3.Relay Settings 3.1. System Config Description Range Default 50, 60 50Hz Disabled, Enabled Enabled Off, 1, 2, 5, 10, 15, 30, 60 60 min Off, 1, 2, 5, 10, 15, 30, 60 5 min xNom, Primary, Secondary xNom xNom, Primary, Secondary xNom xNom, Primary, Secondary xNom +ve/+ve, +ve/-ve, -ve/+ve, -ve/-ve +ve/+ve Edge triggered, Level triggered Edge triggered Disabled, Seconds, Minutes Minutes Out Of Service, Local, Remote, Local Or Remote Local Or Remote (Password) NONE (Password) NONE Active Group Selects which settings group is currently activated System Frequency Selects the Power System Frequency from 50 or 60 Hz View/Edit Group Selects which settings group is currently being displayed Setting Dependencies When enabled only active settings are displayed and all others hidden Favourite Meters Timer Selects the time delay after which, if no key presses have been detected, the relay will begin to poll through any screens which have been selected as favourite instruments Backlight timer Controls when the LCD backlight turns off Date Sets the date, this setting can only be changed on the fascia or via Relay->Control->Set Time and Date Time Sets the time, this setting can only be changed on the fascia or via Relay->Control->Set Time and Date Curr Set Display Select whether the Pickup values are shown in terms of x Nominal, Primary or Secondary values on the Relay Fascia E/F Curr Set Display As Above SEF/REF Curr Set Display As Above Export Power/Lag VAr Selects the signs required for exporting power and lagging VArs Select Grp Mode Mode of operation of the group change from status input. Edge triggered ignores the status input once it has changed to the relevant group, where as with Level triggered the relay will only stay in the group it has changed to whilst the status input is being driven, after which it returns to the previous group. Clock Sync. From BI Real time clock may be synchronised using a binary input (See Clock Sync. in Binary Input Menu) Operating Mode Selects the current operating mode of the relay. This can also be changed by a binary input mode selection. Setting Password Allows a 4 character alpha code to be entered as the password. Note that the display shows a password dependant encrypted code on the second line of the display Control Password As Above Unrestricted Page 8 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Trip Alert Disabled, Enabled Enabled General Alarm Alert Disabled, Enabled Enabled Relay Identifier (16 Character String) ARGUS-M 7SR22 When Enabled the occurance of a Trip will cause the relay to display the Trip Alert Screen, the only way to leave this screen is by acknowledging the trip through the TEST/RESET button on the relay fascia An alphanumeric string shown on the LCD normally used to identify the relay or the relays purpose Circuit Identifier (16 Character String) An alphanumeric string shown on the LCD normally used to identifier the circuit the relay is attached to or the relays purpose 3.2. CT/VT Config Description Range Default Phase Nom Voltage 40, 40.1 ... 159.9, 160 63.5 V -20, -19.9 ... 19.9, 20 0V -45, -44.9 ... 44.9, 45 0 deg Van,Vbn,Vcn, Vab,Vbc,3V0, Va,Vb,Vc Van,Vbn,Vcn Phase VT Ratio Prim ( 6 Character String) 132000 V Phase VT Ratio Sec 40, 40.5 ... 159.5, 160 110 V Vx Nom Voltage 40, 40.1 ... 159.9, 160 63.5 V -20, -19.9 ... 19.9, 20 0V -45, -44.9 ... 44.9, 45 0 deg C Vx VT Ratio Prim ( 6 Character String) 132000 V Vx VT Ratio Sec 40, 40.5 ... 159.5, 160 110 V Phase Current Input 1, 5 1A ( 6 Character String) 1600 A 0.2, 0.21 ... 2, 2.1.....7 1 Selects the nominal voltage setting Vn of the voltage input Phase Voltage Trim Magnitude Allows trimming of voltage magnitude, the setting value should be the voltage required to be added to get back to Phase Nom Voltage. Phase Voltage Trim Angle Allows trimming of voltage angle, the setting value is added to the current voltage angle Phase Voltage Config Required to allow for different types of physical VT connections. Selects the nominal voltage setting Vn of the voltage input Vx Voltage Trim Magnitude Allows trimming of voltage magnitude, the setting value should be the voltage required to be added to get back to Vx Nom Voltage. Vx Voltage Trim Angle Allows trimming of voltage angle, the setting value is added to the current voltage angle Selects whether 1 or 5 Amp terminals are being used for phase inputs Phase CT Ratio Prim Phase CT ratio to scale primary current instruments Phase CT Ratio Sec Phase CT ratio to scale secondary current instruments Unrestricted (c)2018 Siemens Protection Devices Limited Page 9 of 107 7SR220 Settings Guide Description Range Default Earth Current Input 1, 5 1A ( 6 Character String) 2000 A 0.2, 0.21 ... 2, 2.1.....7 1 1, 5 1A ( 6 Character String) 2000 A 0.2, 0.21 ... 2, 2.1.....7 1 Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs Earth CT Ratio Prim Measured Earth CT ratio to scale primary current instruments Earth CT Ratio Sec Measured Earth CT ratio to scale secondary current instruments SEF/REF Current Input Selects whether 1 or 5 Amp terminals are being used for SEF/REF inputs SEF/REF CT Ratio Prim SEF/REF CT ratio to scale primary current instruments SEF/REF CT Ratio Sec SEF/REF CT ratio to scale primary current instruments 3.3. Function Config Description Range Default Gn Phase Overcurrent Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled When set to Disabled, no Phase Overcurrent elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Voltage Cont O/C When set to Disabled, no Voltage Cont O/C elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Cold Load When set to Disabled, no Cold Load elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Derived E/F When set to Disabled, no Derived E/F elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Measured E/F When set to Disabled, no Measured E/F elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Sensitive E/F When set to Disabled, no Sensitive E/F elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Restricted E/F When set to Disabled, no Restricted E/F elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn NPS Overcurrent When set to Disabled, no NPS Overcurrent elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Unrestricted Page 10 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn Under Current Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled When set to Disabled, no Under Current elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Thermal When set to Disabled, no Thermal elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Phase U/O Voltage When set to Disabled, no Phase U/O Voltage elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Vx U/O Voltage When set to Disabled, no Vx U/O Voltage elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn NPS Overvoltage When set to Disabled, no NPS Overvoltage elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Neutral Overvoltage When set to Disabled, no Neutral Overvoltage elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn U/O Frequency When set to Disabled, no U/O Frequency elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn CB Fail When set to Disabled, no CB Fail elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn VT Supervision When set to Disabled, no VT Supervision elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn CT Supervision When set to Disabled, no CT Supervision elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Broken Conductor When set to Disabled, no Broken Conductor elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Trip Cct Supervision When set to Disabled, no Trip Cct Supervision elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Unrestricted (c)2018 Siemens Protection Devices Limited Page 11 of 107 7SR220 Settings Guide Description Range Default Gn Close Cct Supervision Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Enabled, Disabled Disabled Description Range Default Gn 67 Char Angle -95, -94 ... 94, 95 45 deg 1, 1.5 ... 19.5, 20 1V Enabled, Disabled Disabled RMS, Fundamental RMS RMS, Fundamental RMS Description Range Default Gn 51-1 Element Disabled, Enabled Disabled When set to Disabled, no Close Cct Supervision elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Inrush Detector When set to Disabled, no Inrush Detector elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Load Blinder When set to Disabled, no Load Blinder elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn CB Counters When set to Disabled, no Gn CB Counter elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn I^2t CB Wear When set to Disabled, no Gn I^2t CB Wear elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). Gn Arc Flash Detector When set to Disabled, no Arc Flash Detector elements will be functional and all associated settings will be hidden. (The Setting Dependencies setting being set to Disabled will make all settings visible but will not allow them to operate). 3.4. Current Prot'n 3.4.1. Phase Overcurrent Maximum torque angle for phase overcurrent elements Gn 67 Minimum Voltage Selects the directional elements minimum voltage, below which the element will be inhibited Gn 67 2-out-of-3 Logic Selects whether 2 out of 3 voting logic is enabled for phase overcurrent elements Gn 50 Measurement Selects whether the RMS value used by the 50 elements is True RMS or only calculated at fundamental frequency Gn 51 Measurement Selects whether the RMS value used by the 51 elements is True RMS or only calculated at fundamental frequency 3.4.1.1. 51-1 Selects whether the 51-1 IDMTL Overcurrent element is enabled Unrestricted Page 12 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 51-1 Dir. Control Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Off, Inhibit Inhibit Off, Inhibit Off Description Range Default Gn 51-2 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s Selects whether 51-1 element is non-directional, forward or reverse Gn 51-1 Setting Pickup level Gn 51-1 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51-1 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51-1 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51-1 Min Operate Time Minimum operate time of element. Gn 51-1 Follower DTL Additional definite time added after characteristic time Gn 51-1 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51-1 VTS Action Selects whether 51-1 element is blocked or made nondirectional when VTS operates Gn 51-1 Inrush Action Selects if the 51-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates Gn 51-1 21LB-3P Action Selects if operation of the 51-1 element is blocked for defined load conditions Gn 51-1 21LB-1P Action Selects if operation of the 51-1 element is blocked for defined load conditions 3.4.1.2. 51-2 Selects whether the 51-2 IDMTL Overcurrent element is enabled Gn 51-2 Dir. Control Selects whether 51-2 element is non-directional, forward or reverse Gn 51-2 Setting Pickup level Gn 51-2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51-2 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51-2 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51-2 Min Operate Time Minimum operate time of element. Gn 51-2 Follower DTL Additional definite time added after characteristic time Unrestricted (c)2018 Siemens Protection Devices Limited Page 13 of 107 7SR220 Settings Guide Description Range Default Gn 51-2 Reset (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Off, Inhibit Inhibit Off, Inhibit Off Description Range Default Gn 51-3 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Off, Inhibit Inhibit Off, Inhibit Off Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51-2 VTS Action Selects whether 51-2 element is blocked or made nondirectional when VTS operates Gn 51-2 Inrush Action Selects if the 51-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates Gn 51-2 21LB-3P Action Selects if operation of the 51-2 element is blocked for defined load conditions Gn 51-2 21LB-1P Action Selects if operation of the 51-2 element is blocked for defined load conditions 3.4.1.3. 51-3 Selects whether the 51-3 IDMTL Overcurrent element is enabled Gn 51-3 Dir. Control Selects whether 51-3 element is non-directional, forward or reverse Gn 51-3 Setting Pickup level Gn 51-3 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51-3 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51-3 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51-3 Min Operate Time Minimum operate time of element. Gn 51-3 Follower DTL Additional definite time added after characteristic time Gn 51-3 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51-3 VTS Action Selects whether 51-3 element is blocked or made nondirectional when VTS operates Gn 51-3 Inrush Action Selects if the 51-3 element is blocked from operating when 2nd Harmonic Inrush Detector operates Gn 51-3 21LB-3P Action Selects if operation of the 51-3 element is blocked for defined load conditions Gn 51-3 21LB-1P Action Selects if operation of the 51-3 element is blocked for defined load conditions Unrestricted Page 14 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 3.4.1.4. 51-4 Description Range Default Gn 51-4 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Off, Inhibit Inhibit Off, Inhibit Off Description Range Default Gn 50-1 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 49.5, 50 1 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Selects whether the 51-4 IDMTL Overcurrent element is enabled Gn 51-4 Dir. Control Selects whether 51-4 element is non-directional, forward or reverse Gn 51-4 Setting Pickup level Gn 51-4 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51-4 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51-4 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51-4 Min Operate Time Minimum operate time of element. Gn 51-4 Follower DTL Additional definite time added after characteristic time Gn 51-4 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51-4 VTS Action Selects whether 51-4 element is blocked or made nondirectional when VTS operates Gn 51-4 Inrush Action Selects if the 51-4 element is blocked from operating when 2nd Harmonic Inrush Detector operates Gn 51-4 21LB-3P Action Selects if operation of the 51-4 element is blocked for defined load conditions Gn 51-4 21LB-1P Action Selects if operation of the 51-4 element is blocked for defined load conditions 3.4.1.5. 50-1 Selects whether the INST/ DTL Overcurrent element is enabled Gn 50-1 Dir. Control Selects whether 50-1 element is non-directional, forward or reverse Gn 50-1 Setting Pickup level Gn 50-1 Delay Sets operate delay time Gn 50-1 VTS Action Selects whether 50-1 element is blocked or made nondirectional when VTS operates Unrestricted (c)2018 Siemens Protection Devices Limited Page 15 of 107 7SR220 Settings Guide Description Range Default Gn 50-1 Inrush Action Off, Inhibit Off Off, Inhibit Inhibit Off, Inhibit Off Description Range Default Gn 50-2 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 49.5, 50 1 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Off, Inhibit Inhibit Off, Inhibit Off Description Range Default Gn 50-3 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 49.5, 50 1 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Selects if the 50-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates Gn 50-1 21LB-3P Action Selects if operation of the 50-1 element is blocked for defined load conditions Gn 50-1 21LB-1P Action Selects if operation of the 50-1 element is blocked for defined load conditions 3.4.1.6. 50-2 Selects whether the INST/ DTL Overcurrent element is enabled Gn 50-2 Dir. Control Selects whether 50-2 element is non-directional, forward or reverse Gn 50-2 Setting Pickup level Gn 50-2 Delay Sets operate delay time Gn 50-2 VTS Action Selects whether 50-2 element is blocked or made nondirectional when VTS operates Gn 50-2 Inrush Action Selects if the 50-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates Gn 50-2 21LB-3P Action Selects if operation of the 50-2 element is blocked for defined load conditions Gn 50-2 21LB-1P Action Selects if operation of the 50-2 element is blocked for defined load conditions 3.4.1.7. 50-3 Selects whether the INST/ DTL Overcurrent element is enabled Gn 50-3 Dir. Control Selects whether 50-3 element is non-directional, forward or reverse Gn 50-3 Setting Pickup level Gn 50-3 Delay Sets operate delay time Gn 50-3 VTS Action Selects whether 50-3 element is blocked or made nondirectional when VTS operates Gn 50-3 Inrush Action Selects if the 50-3 element is blocked from operating when 2nd Harmonic Inrush Detector operates Unrestricted Page 16 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 50-3 21LB-3P Action Off, Inhibit Inhibit Off, Inhibit Off Description Range Default Gn 50-4 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 49.5, 50 1 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Off, Inhibit Inhibit Off, Inhibit Off Description Range Default Gn 51V Element (Ph-Ph) Disabled, Enabled Disabled Gn 51V Setting 5, 5.5 ... 199.5, 200 30 V Off, Inhibit Off 0.25, 0.3, 0.35, 0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1 0.5 0.25, 0.3, 0.35, 0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1 0.5 0.25, 0.3, 0.35, 0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1 0.5 0.25, 0.3, 0.35, 0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1 0.5 Selects if operation of the 50-3 element is blocked for defined load conditions Gn 50-3 21LB-1P Action Selects if operation of the 50-3 element is blocked for defined load conditions 3.4.1.8. 50-4 Selects whether the INST/ DTL Overcurrent element is enabled Gn 50-4 Dir. Control Selects whether 50-4 element is non-directional, forward or reverse Gn 50-4 Setting Pickup level Gn 50-4 Delay Sets operate delay time Gn 50-4 VTS Action Selects whether 50-4 element is blocked or made nondirectional when VTS operates Gn 50-4 Inrush Action Selects if the 50-4 element is blocked from operating when 2nd Harmonic Inrush Detector operates Gn 50-4 21LB-3P Action Selects if operation of the 50-4 element is blocked for defined load conditions Gn 50-4 21LB-1P Action Selects if operation of the 50-4 element is blocked for defined load conditions 3.4.2. Voltage Controlled O/C The voltage below which 51V operates Gn 51V VTS Action Selects whether or not the 51V element is blocked when VTS operates Gn 51-1 Multiplier Multiplier applied to the 51-1 element when VCO element has operated Gn 51-2 Multiplier Multiplier applied to the 51-2 element when VCO element has operated Gn 51-3 Multiplier Multiplier applied to the 51-3 element when VCO element has operated Gn 51-4 Multiplier Multiplier applied to the 51-4 element when VCO element has operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 17 of 107 7SR220 Settings Guide 3.4.3. Cold Load Description Range Default Cold Load Disabled, Enabled Disabled 1, 1.1 ... 14100, 14400 600 s 1, 1.1 ... 14100, 14400 600 s Disabled, Enabled Disabled 0.05, 0.1 ... 2.45, 2.5 0.25 xIn 1, 1.1 ... 14100, 14400 600 s 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IE C-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 Selects whether the Cold Load element is enabled Pick-up Time Cold Load operate time delay Drop-off Time Cold Load reset time delay Reduced Current Selects whether reduced current functionality is to be used Reduced Current Level Selects current level below which Reduced Current Time is used for Cold Load reset delay Reduced Current Time Cold Load reset time delay used when reduced current active Gn 51c-1 Setting 51-1 element parameter used when Cold Load operates Gn 51c-1 Char As Above Gn 51c-1 Time Mult (IEC/ANSI) As Above Gn 51c-1 Delay (DTL) As Above Gn 51c-1 Min Operate Time As Above Gn 51c-1 Follower DTL As Above Gn 51c-1 Reset As Above Gn 51c-2 Setting 51-2 element parameter used when Cold Load operates Gn 51c-2 Char As Above Gn 51c-2 Time Mult (IEC/ANSI) As Above Gn 51c-2 Delay (DTL) As Above Gn 51c-2 Min Operate Time As Above Gn 51c-2 Follower DTL As Above Gn 51c-2 Reset As Above Gn 51c-3 Setting 51-3 element parameter used when Cold Load operates Gn 51c-3 Char As Above Gn 51c-3 Time Mult (IEC/ANSI) As Above Unrestricted Page 18 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 51c-3 Delay (DTL) 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s 0.05, 0.06 ... 2.49, 2.5 1 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Description Range Default Gn 67N Polarizing Quantity ZPS, NPS ZPS -95, -94 ... 94, 95 -15 deg 0.33, 0.5, 1, 1.5, 2, 2.5, 3 0.33 V Description Range Default Gn 51N-1 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 2.49, 2.5 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 As Above Gn 51c-3 Min Operate Time As Above Gn 51c-3 Follower DTL As Above Gn 51c-3 Reset As Above Gn 51c-4 Setting 51-4 element parameter used when Cold Load operates Gn 51c-4 Char As Above Gn 51c-4 Time Mult (IEC/ANSI) As Above Gn 51c-4 Delay (DTL) As Above Gn 51c-4 Min Operate Time As Above Gn 51c-4 Follower DTL As Above Gn 51c-4 Reset As Above 3.4.4. Derived E/F Allows the directional element to select which quantities to use. Gn 67N Char Angle Maximum torque angle for derived earth fault elements Gn 67N Minimum Voltage Selects the directional elements minimum voltage, below which the element will be inhibited 3.4.4.1. 51N-1 Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled Gn 51N-1 Dir. Control Selects whether 51N-1 element is non-directional, forward or reverse Gn 51N-1 Setting Pickup level Gn 51N-1 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51N-1 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Unrestricted (c)2018 Siemens Protection Devices Limited Page 19 of 107 7SR220 Settings Guide Description Range Default Gn 51N-1 Delay (DTL) 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 51N-2 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 2.49, 2.5 0.5xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 51N-3 Element Disabled, Enabled Disabled Delay (applicable only when DTL is selected for characteristic) Gn 51N-1 Min Operate Time Minimum operate time of element. Gn 51N-1 Follower DTL Additional definite time added after characteristic time Gn 51N-1 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51N-1 VTS Action Selects whether 51N-1 element is blocked or made nondirectional when VTS operates Gn 51N-1 Inrush Action Selects if the 51N-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.2. 51N-2 Selects whether the 51N-2 IDMTL derived Earth Fault element is enabled Gn 51N-2 Dir. Control Selects whether 51N-2 element is non-directional, forward or reverse Gn 51N-2 Setting Pickup level Gn 51N-2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51N-2 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51N-2 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51N-2 Min Operate Time Minimum operate time of element. Gn 51N-2 Follower DTL Additional definite time added after characteristic time Gn 51N-2 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51N-2 VTS Action Selects whether 51N-2 element is blocked or made nondirectional when VTS operates Gn 51N-2 Inrush Action Selects if the 51N-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.3. 51N-3 Selects whether the 51N-3 IDMTL derived Earth Fault element is enabled Unrestricted Page 20 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 51N-3 Dir. Control Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 2.49, 2.5 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 51N-4 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 2.49, 2.5 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Selects whether 51N-3 element is non-directional, forward or reverse Gn 51N-3 Setting Pickup level Gn 51N-3 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51N-3 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51N-3 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51N-3 Min Operate Time Minimum operate time of element. Gn 51N-3 Follower DTL Additional definite time added after characteristic time Gn 51N-3 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51N-3 VTS Action Selects whether 51N-3 element is blocked or made nondirectional when VTS operates Gn 51N-3 Inrush Action Selects if the 51N-3 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.4. 51N-4 Selects whether the 51N-4 IDMTL derived Earth Fault element is enabled Gn 51N-4 Dir. Control Selects whether 51N-4 element is non-directional, forward or reverse Gn 51N-4 Setting Pickup level Gn 51N-4 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51N-4 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51N-4 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51N-4 Min Operate Time Minimum operate time of element. Gn 51N-4 Follower DTL Additional definite time added after characteristic time Gn 51N-4 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51N-4 VTS Action Selects whether 51N-4 element is blocked or made nondirectional when VTS operates Unrestricted (c)2018 Siemens Protection Devices Limited Page 21 of 107 7SR220 Settings Guide Description Range Default Gn 51N-4 Inrush Action Off, Inhibit Off Description Range Default Gn 50N-1 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 49.5, 50 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 50N-2 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 49.5, 50 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 50N-3 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 49.5, 50 0.5 xIn Selects if the 51N-4 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.5. 50N-1 Selects whether the DTL derived Earth fault element is enabled Gn 50N-1 Dir. Control Selects whether 50N-1 element is non-directional, forward or reverse Gn 50N-1 Setting Pickup level Gn 50N-1 Delay Sets operate delay time Gn 50N-1 VTS Action Selects whether 50N-1 element is blocked or made nondirectional when VTS operates Gn 50N-1 Inrush Action Selects if the 50N-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.6. 50N-2 Selects whether the DTL derived Earth fault element is enabled Gn 50N-2 Dir. Control Selects whether 50N-2 element is non-directional, forward or reverse Gn 50N-2 Setting Pickup level Gn 50N-2 Delay Sets operate delay time Gn 50N-2 VTS Action Selects whether 50N-2 element is blocked or made nondirectional when VTS operates Gn 50N-2 Inrush Action Selects if the 50N-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.7. 50N-3 Selects whether the DTL derived Earth fault element is enabled Gn 50N-3 Dir. Control Selects whether 50N-3 element is non-directional, forward or reverse Gn 50N-3 Setting Pickup level Unrestricted Page 22 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 50N-3 Delay 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 50N-4 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.05, 0.06 ... 49.5, 50 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 67G Char Angle -95, -94 ... 94, 95 -15 deg 0.33, 0.5, 1, 1.5, 2, 2.5, 3 0.33 V RMS, Fundamental RMS RMS, Fundamental RMS Description Range Default Gn 51G-1 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 0.995, 1 0.5 xIn Sets operate delay time Gn 50N-3 VTS Action Selects whether 50N-3 element is blocked or made nondirectional when VTS operates Gn 50N-3 Inrush Action Selects if the 50N-3 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.4.8. 50N-4 Selects whether the DTL derived Earth fault element is enabled Gn 50N-4 Dir. Control Selects whether 50N-4 element is non-directional, forward or reverse Gn 50N-4 Setting Pickup level Gn 50N-4 Delay Sets operate delay time Gn 50N-4 VTS Action Selects whether 50N-4 element is blocked or made nondirectional when VTS operates Gn 50N-4 Inrush Action Selects if the 50N-4 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.5. Measured E/F Maximum torque angle for measured earth fault elements Gn 67G Minimum Voltage Selects the directional elements minimum voltage, below which the element will be inhibited Gn 50G Measurement Selects whether the RMS value used by the 50G elements is True RMS or only calculated at fundamental frequency Gn 51G Measurement Selects whether the RMS value used by the 51G elements is True RMS or only calculated at fundamental frequency 3.4.5.1. 51G-1 Selects whether the 51G-1 IDMTL measured Earth Fault element is enabled Gn 51G-1 Dir. Control Selects whether 51G-1 element is non-directional, forward or reverse Gn 51G-1 Setting Pickup level Unrestricted (c)2018 Siemens Protection Devices Limited Page 23 of 107 7SR220 Settings Guide Description Range Default Gn 51G-1 Char DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 51G-2 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 0.995, 1 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51G-1 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51G-1 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51G-1 Min Operate Time Minimum operate time of element. Gn 51G-1 Follower DTL Additional definite time added after characteristic time Gn 51G-1 Reset Selects between an ANSI decaying reset characteristic or DTL reset Gn 51G-1 VTS Action Selects whether 51G-1 element is blocked or made nondirectional when VTS operates Gn 51G-1 Inrush Action Selects if the 51G-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.5.2. 51G-2 Selects whether the 51G-2 IDMTL measured Earth Fault element is enabled Gn 51G-2 Dir. Control Selects whether 51G-2 element is non-directional, forward or reverse Gn 51G-2 Setting Pickup level Gn 51G-2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51G-2 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51G-2 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51G-2 Min Operate Time Minimum operate time of element. Gn 51G-2 Follower DTL Additional definite time added after characteristic time Gn 51G-2 Reset Selects between an ANSI decaying reset characteristic or DTL reset Gn 51G-2 VTS Action Selects whether 51G-2 element is blocked or made nondirectional when VTS operates Gn 51G-2 Inrush Action Selects if the 51G-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates Unrestricted Page 24 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 3.4.5.3. 51G-3 Description Range Default Gn 51G-3 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 0.995, 1 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 51G-4 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 0.995, 1 0.5 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s Selects whether the 51G-3 IDMTL measured Earth Fault element is enabled Gn 51G-3 Dir. Control Selects whether 51G-3 element is non-directional, forward or reverse Gn 51G-3 Setting Pickup level Gn 51G-3 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51G-3 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51G-3 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51G-3 Min Operate Time Minimum operate time of element. Gn 51G-3 Follower DTL Additional definite time added after characteristic time Gn 51G-3 Reset Selects between an ANSI decaying reset characteristic or DTL reset Gn 51G-3 VTS Action Selects whether 51G-3 element is blocked or made nondirectional when VTS operates Gn 51G-3 Inrush Action Selects if the 51G-3 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.5.4. 51G-4 Selects whether the 51G-4 IDMTL measured Earth Fault element is enabled Gn 51G-4 Dir. Control Selects whether 51G-4 element is non-directional, forward or reverse Gn 51G-4 Setting Pickup level Gn 51G-4 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51G-4 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51G-4 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51G-4 Min Operate Time Minimum operate time of element. Gn 51G-4 Follower DTL Additional definite time added after characteristic time Unrestricted (c)2018 Siemens Protection Devices Limited Page 25 of 107 7SR220 Settings Guide Description Range Default Gn 51G-4 Reset (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 50G-1 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 24.95, 25 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 50G-2 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 24.95, 25 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 50G-3 Element Disabled, Enabled Disabled Selects between an ANSI decaying reset characteristic or DTL reset Gn 51G-4 VTS Action Selects whether 51G-4 element is blocked or made nondirectional when VTS operates Gn 51G-4 Inrush Action Selects if the 51G-4 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.5.5. 50G-1 Selects whether the DTL measured Earth fault element is enabled Gn 50G-1 Dir. Control Selects whether 50G-1 element is non-directional, forward or reverse Gn 50G-1 Setting Pickup level Gn 50G-1 Delay Sets operate delay time Gn 50G-1 VTS Action Selects whether 50G-1 element is blocked or made nondirectional when VTS operates Gn 50G-1 Inrush Action Selects if the 50G-1 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.5.6. 50G-2 Selects whether the DTL measured Earth fault element is enabled Gn 50G-2 Dir. Control Selects whether 50G-2 element is non-directional, forward or reverse Gn 50G-2 Setting Pickup level Gn 50G-2 Delay Sets operate delay time Gn 50G-2 VTS Action Selects whether 50G-2 element is blocked or made nondirectional when VTS operates Gn 50G-2 Inrush Action Selects if the 50G-2 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.5.7. 50G-3 Selects whether the DTL measured Earth fault element is enabled Unrestricted Page 26 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 50G-3 Dir. Control Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 24.95, 25 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 50G-4 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 24.95, 25 0.5 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Off, Inhibit Off Description Range Default Gn 67SEF Char Angle -95, -94 ... 94, 95 -15 deg 0.33, 0.5, 1, 1.5, 2, 2.5, 3 0.33 V Description Range Default Gn 51SEF-1 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 0.995, 1 0.2 xIn Selects whether 50G-3 element is non-directional, forward or reverse Gn 50G-3 Setting Pickup level Gn 50G-3 Delay Sets operate delay time Gn 50G-3 VTS Action Selects whether 50G-3 element is blocked or made nondirectional when VTS operates Gn 50G-3 Inrush Action Selects if the 50G-3 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.5.8. 50G-4 Selects whether the DTL measured Earth fault element is enabled Gn 50G-4 Dir. Control Selects whether 50G-4 element is non-directional, forward or reverse Gn 50G-4 Setting Pickup level Gn 50G-4 Delay Sets operate delay time Gn 50G-4 VTS Action Selects whether 50G-4 element is blocked or made nondirectional when VTS operates Gn 50G-4 Inrush Action Selects if the 50G-4 element is blocked from operating when 2nd Harmonic Inrush Detector operates 3.4.6. Sensitive E/F Maximum torque angle for sensitive earth fault elements Gn 67SEF Minimum Voltage Selects the directional elements minimum voltage, below which the element will be inhibited 3.4.6.1. 51SEF-1 Selects whether the 51SEF-1 IDMTL Sensitive Earth Fault element is enabled Gn 51SEF-1 Dir. Control Selects whether 51SEF-1 element is non-directional, forward or reverse Gn 51SEF-1 Setting Pickup level Unrestricted (c)2018 Siemens Protection Devices Limited Page 27 of 107 7SR220 Settings Guide Description Range Default Gn 51SEF-1 Char DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Description Range Default Gn 51SEF-2 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 0.995, 1 0.2 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Description Range Default Gn 51SEF-3 Element Disabled, Enabled Disabled Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51SEF-1 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51SEF-1 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51SEF-1 Min Operate Time Minimum operate time of element. Gn 51SEF-1 Follower DTL Additional definite time added after characteristic time Gn 51SEF-1 Reset Selects between an ANSI decaying reset characteristic or DTL reset Gn 51SEF-1 VTS Action Selects whether 51SEF-1 element is blocked or made nondirectional when VTS operates 3.4.6.2. 51SEF-2 Selects whether the 51SEF-2 IDMTL derived Earth Fault element is enabled Gn 51SEF-2 Dir. Control Selects whether 51SEF-2 element is non-directional, forward or reverse Gn 51SEF-2 Setting Pickup level Gn 51SEF-2 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51SEF-2 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51SEF-2 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51SEF-2 Min Operate Time Minimum operate time of element. Gn 51SEF-2 Follower DTL Additional definite time added after characteristic time Gn 51SEF-2 Reset Selects between an ANSI decaying reset characteristic or DTL reset Gn 51SEF-2 VTS Action Selects whether 51SEF-2 element is blocked or made nondirectional when VTS operates 3.4.6.3. 51SEF-3 Selects whether the 51SEF-3 IDMTL derived Earth Fault element is enabled Unrestricted Page 28 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 51SEF-3 Dir. Control Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 0.995, 1 0.2 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Description Range Default Gn 51SEF-4 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 0.995, 1 0.2 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s 0, 0.01 ... 19.99, 20 0s 0, 0.01 ... 19.99, 20 0s (ANSI) Decaying, 0 ... 59, 60 0s Off, Inhibit, Non-Dir Off Selects whether 51SEF-3 element is non-directional, forward or reverse Gn 51SEF-3 Setting Pickup level Gn 51SEF-3 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51SEF-3 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51SEF-3 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51SEF-3 Min Operate Time Minimum operate time of element. Gn 51SEF-3 Follower DTL Additional definite time added after characteristic time Gn 51SEF-3 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51SEF-3 VTS Action Selects whether 51SEF-3 element is blocked or made nondirectional when VTS operates 3.4.6.4. 51SEF-4 Selects whether the 51SEF-4 IDMTL derived Earth Fault element is enabled Gn 51SEF-4 Dir. Control Selects whether 51SEF-4 element is non-directional, forward or reverse Gn 51SEF-4 Setting Pickup level Gn 51SEF-4 Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 51SEF-4 Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 51SEF-4 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 51SEF-4 Min Operate Time Minimum operate time of element. Gn 51SEF-4 Follower DTL Additional definite time added after characteristic time Gn 51SEF-4 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn 51SEF-4 VTS Action Selects whether 51SEF-4 element is blocked or made nondirectional when VTS operates Unrestricted (c)2018 Siemens Protection Devices Limited Page 29 of 107 7SR220 Settings Guide 3.4.6.5. 50SEF-1 Description Range Default Gn 50SEF-1 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Description Range Default Gn 50SEF-2 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Description Range Default Gn 50SEF-3 Element Disabled, Enabled Disabled Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Description Range Default Gn 50SEF-4 Element Disabled, Enabled Disabled Selects whether the DTL measured Earth fault element is enabled Gn 50SEF-1 Dir. Control Selects whether 50SEF-1 element is non-directional, forward or reverse Gn 50SEF-1 Setting Pickup level Gn 50SEF-1 Delay Sets operate delay time Gn 50SEF-1 VTS Action Selects whether 50SEF-1 element is blocked or made nondirectional when VTS operates 3.4.6.6. 50SEF-2 Selects whether the DTL measured Earth fault element is enabled Gn 50SEF-2 Dir. Control Selects whether 50SEF-2 element is non-directional, forward or reverse Gn 50SEF-2 Setting Pickup level Gn 50SEF-2 Delay Sets operate delay time Gn 50SEF-2 VTS Action Selects whether 50SEF-2 element is blocked or made nondirectional when VTS operates 3.4.6.7. 50SEF-3 Selects whether the DTL measured Earth fault element is enabled Gn 50SEF-3 Dir. Control Selects whether 50SEF-3 element is non-directional, forward or reverse Gn 50SEF-3 Setting Pickup level Gn 50SEF-3 Delay Sets operate delay time Gn 50SEF-3 VTS Action Selects whether 50SEF-3 element is blocked or made nondirectional when VTS operates 3.4.6.8. 50SEF-4 Selects whether the DTL measured Earth fault element is enabled Unrestricted Page 30 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 50SEF-4 Dir. Control Non-Dir, Forward, Reverse Non-Dir 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Off, Inhibit, Non-Dir Off Description Range Default Gn 64H Element Disabled, Enabled Disabled 0.005, 0.006 ... 0.945, 0.95 0.2 xIn 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 46IT Element Disabled, Enabled Disabled 0.05, 0.06 ... 2.49, 2.5 0.25 xIn DTL, IEC-NI, IEC-VI, IEC-EI, IECLTI, ANSI-MI, ANSI-VI, ANSI-EI IEC-NI 0.025, 0.03 ... 1.595, 1.6 , 1.7 ... 4.9, 5, 6 ... 100 1 0, 0.01 ... 19.99, 20 5s (ANSI) Decaying, 0 ... 59, 60 0s Description Range Default Gn 46DT Element Disabled, Enabled Disabled 0.05, 0.06 ... 4 0.1 xIn 0, 0.01 ... 14300, 14400 0.02 s Selects whether 50SEF-4 element is non-directional, forward or reverse Gn 50SEF-4 Setting Pickup level Gn 50SEF-4 Delay Sets operate delay time Gn 50SEF-4 VTS Action Selects whether 50SEF-4 element is blocked or made nondirectional when VTS operates 3.4.7. Restricted E/F High impedance restricted earth fault current element Gn 64H Setting Pickup level Gn 64H Delay Sets operate delay time 3.4.8. NPS Overcurrent 3.4.8.1. 46IT Selects whether the 46IT IDMTL/DTL negative phase sequence current element is enabled Gn 46IT Setting Pickup level Gn 46IT Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn 46IT Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn 46IT Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 46IT Reset Selects between an ANSI decaying reset characteristic or a definite time reset 3.4.8.2. 46DT Selects whether the definite time NPS overvoltage element is enabled Gn 46DT Setting Pickup level Gn 46DT Delay Sets operate delay time Unrestricted (c)2018 Siemens Protection Devices Limited Page 31 of 107 7SR220 Settings Guide 3.4.9. Under Current Description Range Default Gn 37 U/I Guard Setting 0.05, 0.1 ... 4.95, 5 0.1 xIn Description Range Default Gn 37-1 Element Disabled, Enabled Disabled 0.05, 0.1 ... 4.95, 5 0.25 xIn 0, 0.01 ... 14300, 14400 0s No, Yes Yes All, Any All Description Range Default Gn 37-2 Element Disabled, Enabled Disabled 0.05, 0.1 ... 4.95, 5 0.25 xIn 0, 0.01 ... 14300, 14400 0s No, Yes Yes All, Any All Description Range Default Gn 37G-1 Element Disabled, Enabled Disabled 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 37G-2 Element Disabled, Enabled Disabled 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s 3.4.9.1. 37-1 Phase under current element 37-1 Gn 37-1 Setting Pickup level Gn 37-1 Delay Sets operate delay time Gn 37-1 U/I Guarded Selects whether to use the 37-1 guard element Gn 37-1 Start Option Selects whether 31-1 element operates for any phase picked up or only when all phases are picked up 3.4.9.2. 37-2 Phase under current element 37-2 Gn 37-2 Setting Pickup level Gn 37-2 Delay Sets operate delay time Gn 37-2 U/I Guarded Selects whether to use the 37-2 guard element Gn 37-2 Start Option Selects whether 31-2 element operates for any phase picked up or only when all phases are picked up 3.4.9.3. 37G-1 E/F under current element 37G-1 Gn 37G-1 Setting Pickup level Gn 37G-1 Delay Sets operate delay time 3.4.9.4. 37G-2 E/F under current element 37G-2 Gn 37G-2 Setting Pickup level Gn 37G-2 Delay Sets operate delay time Unrestricted Page 32 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 3.4.9.5. 37SEF-1 Description Range Default Gn 37SEF-1 Element Disabled, Enabled Disabled 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 37SEF-2 Element Disabled, Enabled Disabled 0.005, 0.006 ... 4.995, 5 0.2 xIn 0, 0.01 ... 14300, 14400 0s Description Range Default Gn 49 Thermal Overload Disabled, Enabled Disabled 0.1, 0.11 ... 2.99, 3 1.05 xIn 1, 1.5 ... 999.5, 1000 10 minutes Disabled, 50 ... 99, 100 Disabled Description Range Default Gn 50AFD Disabled, Enabled Disabled 1, 2,...10 2 xIn Description Range Default Gn Voltage Input Mode Ph-N, Ph-Ph Ph-N SEF under current element 37SEF-1 Gn 37SEF-1 Setting Pickup level Gn 37SEF-1 Delay Sets operate delay time 3.4.9.6. 37SEF-2 SEF under current element 37SEF-2 Gn 37SEF-2 Setting Pickup level Gn 37SEF-2 Delay Sets operate delay time 3.4.10. Thermal Selects whether the thermal overload protection element is enabled Gn 49 Overload Setting Pickup level Gn 49 Time Constant (Minutes) Thermal time constant Gn 49 Capacity Alarm Selects whether thermal capacity alarm enabled 49 Reset Therm State Control that allows thermal state to be manually reset 3.4.11. ARC Flash Detector Selects whether the ARC Flash Detector element is enabled Gn 50AFD Setting Pickup level 3.5. Voltage Protection 3.5.1. Phase U/O Voltage Selects Ph-Ph or Ph-N voltages for U/V guard element & 27/59 elements operation. Unrestricted (c)2018 Siemens Protection Devices Limited Page 33 of 107 7SR220 Settings Guide Description Range Default Gn 27/59 U/V Guard Setting 1, 1.5 ... 199.5, 200 5V Description Range Default Gn 27/59-1 Element Disabled, Enabled Disabled Under, Over Over 5, 5.5 ... 199.5, 200 80 V 0, 0.1 ... 79.9, 80 3% 0, 0.01 ... 14300, 14400 0.1 s No, Yes No No, Yes No Any, All Any Description Range Default Gn 27/59-2 Element Disabled, Enabled Disabled Under, Over Over 5, 5.5 ... 199.5, 200 80 V 0, 0.1 ... 79.9, 80 3% 0, 0.01 ... 14300, 14400 0.1 s No, Yes No No, Yes No Selects voltage level below which the guard element is applied. 3.5.2. 27/59-1 Selects whether the Under/Over voltage element stage 1 is enabled Gn 27/59-1 Operation Selects between Undervoltage and Overvoltage pickup for this element Gn 27/59-1 Setting Under or over voltage pickup level Gn 27/59-1 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 27/59-1 Delay Sets operate delay time Gn 27/59-1 U/V Guarded Selects whether U/V Guard element can block the operation of this element Gn 27/59-1 VTS Inhibit Selects whether element is blocked or not when VTS operates Gn 27/59-1 O/P Phases Selects whether element operates for any phase picked up or only when all phases are picked up 3.5.3. 27/59-2 Selects whether the Under/Over voltage element stage 2 is enabled Gn 27/59-2 Operation Selects between Undervoltage and Overvoltage pickup for this element Gn 27/59-2 Setting Under or over voltage pickup level Gn 27/59-2 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 27/59-2 Delay Sets operate delay time Gn 27/59-2 U/V Guarded Selects whether U/V Guard element can block the operation of this element Gn 27/59-2 VTS Inhibit Selects whether element is blocked or not when VTS operates Unrestricted Page 34 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 27/59-2 O/P Phases Any, All Any Description Range Default Gn 27/59-3 Element Disabled, Enabled Disabled Under, Over Under 5, 5.5 ... 199.5, 200 50 V 0, 0.1 ... 79.9, 80 3% 0, 0.01 ... 14300, 14400 0.1 s No, Yes Yes No, Yes No Any, All Any Description Range Default Gn 27/59-4 Element Disabled, Enabled Disabled Under, Over Under 5, 5.5 ... 199.5, 200 50 V 0, 0.1 ... 79.9, 80 3% 0, 0.01 ... 14300, 14400 0.1 s No, Yes Yes No, Yes No Selects whether element operates for any phase picked up or only when all phases are picked up 3.5.4. 27/59-3 Selects whether the Under/Over voltage element stage 3 is enabled Gn 27/59-3 Operation Selects between Undervoltage and Overvoltage pickup for this element Gn 27/59-3 Setting Under or over voltage pickup level Gn 27/59-3 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 27/59-3 Delay Sets operate delay time Gn 27/59-3 U/V Guarded Selects whether U/V Guard element can block the operation of this element Gn 27/59-3 VTS Inhibit Selects whether element is blocked or not when VTS operates Gn 27/59-3 O/P Phases Selects whether element operates for any phase picked up or only when all phases are picked up 3.5.5. 27/59-4 Selects whether the Under/Over voltage element stage 4 is enabled Gn 27/59-4 Operation Selects between Undervoltage and Overvoltage pickup for this element Gn 27/59-4 Setting Under or over voltage pickup level Gn 27/59-4 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 27/59-4 Delay Sets operate delay time Gn 27/59-4 U/V Guarded Selects whether U/V Guard element can block the operation of this element Gn 27/59-4 VTS Inhibit Selects whether element is blocked or not when VTS operates Unrestricted (c)2018 Siemens Protection Devices Limited Page 35 of 107 7SR220 Settings Guide Description Range Default Gn 27/59-4 O/P Phases Any, All Any Description Range Default Gn Vx 27/59 U/V Guard Setting 1, 1.5 ... 199.5, 200 5V Gn Vx 27/59 Element Disabled, Enabled Disabled Under, Over Over 5, 5.5 ... 199.5, 200 80 V 0, 0.1 ... 79.9, 80 3% 0, 0.01 ... 14300, 14400 0.1 s No, Yes No Description Range Default Gn 47-1 Element Disabled, Enabled Disabled 1, 1.5 ... 89.5, 90 20 V 0, 0.1 ... 79.9, 80 3% 0, 0.01 ... 14300, 14400 1s Description Range Default Gn 47-2 Element Disabled, Enabled Disabled 1, 1.5 ... 89.5, 90 20 V Selects whether element operates for any phase picked up or only when all phases are picked up 3.6. Vx U/O Voltage Selects whether the Under/Over voltage element for Vx is enabled Gn Vx 27/59 Operation Selects between Undervoltage and Overvoltage pickup for this element Gn Vx 27/59 Setting Under or over voltage pickup level Gn Vx 27/59 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn Vx 27/59 Delay Sets operate delay time Gn Vx 27/59 U/V Guarded 3.7. NPS Overvoltage 3.7.1. 47-1 Selects whether the definite time NPS overvoltage element is enabled Gn 47-1 Setting Pickup level Gn 47-1 Hysteresis Sets the pickup to drop-off thresholds e.g. 3% picks up at setting and drops off below 97% of setting Gn 47-1 Delay Sets operate delay time 3.7.2. 47-2 Selects whether the definite time NPS overvoltage element is enabled Gn 47-2 Setting Pickup level Unrestricted Page 36 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 47-2 Hysteresis 0, 0.1 ... 79.9, 80 3% 0, 0.01 ... 14300, 14400 0.5 s Description Range Default Gn 59N Voltage Source Vn, Vx Vn Description Range Default Gn 59NIT Element Disabled, Enabled Disabled 1, 1.5 ... 99.5, 100 5V DTL, IDMTL IDMTL 0.1, 0.2 ... 139.5, 140 1 0, 0.01 ... 19.99, 20 5s (ANSI) Decaying, 0 ... 59, 60 0s Description Range Default Gn 59NDT Element Disabled, Enabled Disabled 1, 1.5 ... 99.5, 100 5V 0, 0.01 ... 14300, 14400 0.01 s Description Range Default Gn 81 U/V Guard Setting 5, 5.5 ... 199.5, 200 5V Sets the pickup to drop-off thresholds e.g. 3% picks up at setting and drops off below 97% of setting Gn 47-2 Delay Sets operate delay time 3.8. Neutral Overvoltage Selects voltage source between calculated 3V0 (Vn) or measured 3V0 through Vx input 3.8.1. 59NIT Selects whether the inverse time neutral over voltage element is enabled Gn 59NIT Setting Pickup level Gn 59NIT Char Selects characteristic curve to be IDMTL or DTL Gn 59NIT Time Mult (IDMTL) Time multiplier (applicable to IDMTL curve but not DTL selection) Gn 59NIT Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn 59NIT Reset Selects between an instantaneous reset characteristic or a definite time reset 3.8.2. 59NDT Selects whether the definite time neutral over voltage element is enabled Gn 59NDT Setting Pickup level Gn 59NDT Delay Sets operate delay time 3.9. U/O Frequency Selects voltage level below which the guard element is applied. Unrestricted (c)2018 Siemens Protection Devices Limited Page 37 of 107 7SR220 Settings Guide 3.9.1. 81-1 Description Range Default Gn 81-1 Element Disabled, Enabled Disabled Under, Over Under 40, 40.01 ... 69.98, 69.99 49.5 Hz 0, 0.1 ... 79.9, 80 0.1 % 0, 0.01 ... 14300, 14400 1s No, Yes Yes Description Range Default Gn 81-2 Element Disabled, Enabled Disabled Under, Over Under 40, 40.01 ... 69.98, 69.99 49 Hz 0, 0.1 ... 79.9, 80 0.1 % 0, 0.01 ... 14300, 14400 0.8 s No, Yes Yes Description Range Default Gn 81-3 Element Disabled, Enabled Disabled Under, Over Under 40, 40.01 ... 69.98, 69.99 48 Hz Selects whether the Under/Over frequency element stage 1 is enabled Gn 81-1 Operation Selects between Underfrequency and Overfrequency pickup for this element Gn 81-1 Setting Under or over frequency pickup level Gn 81-1 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 81-1 Delay Sets operate delay time Gn 81-1 U/V Guarded Selects whether U/V Guard element can block the operation of this element 3.9.2. 81-2 Selects whether the Under/Over frequency element stage 2 is enabled Gn 81-2 Operation Selects between Underfrequency and Overfrequency pickup for this element Gn 81-2 Setting Under or over frequency pickup level Gn 81-2 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 81-2 Delay Sets operate delay time Gn 81-2 U/V Guarded Selects whether U/V Guard element can block the operation of this element 3.9.3. 81-3 Selects whether the Under/Over frequency element stage 3 is enabled Gn 81-3 Operation Selects between Underfrequency and Overfrequency pickup for this element Gn 81-3 Setting Under or over frequency pickup level Unrestricted Page 38 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 81-3 Hysteresis 0, 0.1 ... 79.9, 80 0.1 % 0, 0.01 ... 14300, 14400 0.6 s No, Yes Yes Description Range Default Gn 81-4 Element Disabled, Enabled Disabled Under, Over Under 40, 40.01 ... 69.98, 69.99 47.5 Hz 0, 0.1 ... 79.9, 80 0.1 % 0, 0.01 ... 14300, 14400 0.4 s No, Yes Yes Description Range Default Gn 81-5 Element Disabled, Enabled Disabled Under, Over Under 40, 40.01 ... 69.98, 69.99 47.5 Hz 0, 0.1 ... 79.9, 80 0.1 % 0, 0.01 ... 14300, 14400 0.4 s No, Yes Yes Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 81-3 Delay Sets operate delay time Gn 81-3 U/V Guarded Selects whether U/V Guard element can block the operation of this element 3.9.4. 81-4 Selects whether the Under/Over frequency element stage 4 is enabled Gn 81-4 Operation Selects between Underfrequency and Overfrequency pickup for this element Gn 81-4 Setting Under or over frequency pickup level Gn 81-4 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 81-4 Delay Sets operate delay time Gn 81-4 U/V Guarded Selects whether U/V Guard element can block the operation of this element 3.9.5. 81-5 Selects whether the Under/Over frequency element stage 5 is enabled Gn 81-5 Operation Selects between Underfrequency and Overfrequency pickup for this element Gn 81-5 Setting Under or over frequency pickup level Gn 81-5 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 81-5 Delay Sets operate delay time Gn 81-5 U/V Guarded Selects whether U/V Guard element can block the operation of this element Unrestricted (c)2018 Siemens Protection Devices Limited Page 39 of 107 7SR220 Settings Guide 3.9.6. 81-6 Description Range Default Gn 81-6 Element Disabled, Enabled Disabled Under, Over Under 40, 40.01 ... 69.98, 69.99 47.5 Hz 0, 0.1 ... 79.9, 80 0.1 % 0, 0.01 ... 14300, 14400 0.4 s No, Yes Yes Description Range Default Gn 50BF Element Disabled, Enabled Disabled 0.05, 0.055 ... 1.995, 2 0.2 xIn Gn 50BF-I4 Setting 0.005, 0.01 ... 1.995, 2 0.05 xIn Gn 50BF-1 Delay 20, 25 ... 59995, 60000 60 ms 20, 25 ... 59995, 60000 120 ms Description Range Default Gn 60VTS Element Disabled, Enabled Disabled NPS, ZPS NPS 7, 8 ... 109, 110 7V 0.05, 0.1, 0.15, 0.2, 0.25, 0.3, 0.35, 0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1 0.1 xIn Selects whether the Under/Over frequency element stage 6 is enabled Gn 81-6 Operation Selects between Underfrequency and Overfrequency pickup for this element Gn 81-6 Setting Under or over frequency pickup level Gn 81-6 Hysteresis Sets the pickup to dropoff thresholds e.g. 3% on Overlevel picks up above pickup setting and drops off below 97% of setting, 3% on Underlevel picks up below setting and drops off above 103% of setting Gn 81-6 Delay Sets operate delay time Gn 81-6 U/V Guarded Selects whether U/V Guard element can block the operation of this element 3.10. Supervision 3.10.1. CB Fail Selects whether the Circuit Breaker Fail element is enabled Gn 50BF Setting Breaker Fail Current Pickup level. If the current falls below this level then the CB is deemed to have opened and the element is reset. Delay before Circuit Breaker Fail stage 1 operates Gn 50BF-2 Delay Delay before Circuit Breaker Fail stage 2 operates 3.10.2. VT Supervision Selects whether the VT supervision element is enabled Gn 60VTS Component Selects whether NPS or ZPS quantities are used by the VT supervision element Gn 60VTS V Level above which there is a possible 1 or 2 phase VT fuse failure Gn 60VTS I Level above which a 1 or 2 phase fault condition is assumed so VTS inhibited Unrestricted Page 40 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 60VTS Vpps 1, 2 ... 109, 110 15 V 0.05, 0.1, 0.15, 0.2, 0.25, 0.3, 0.35, 0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1 0.1 xIn Level current must be above before 3 phase VTS will be issued Gn 60VTS Ipps Fault 0.05, 0.1 ... 19.95, 20 10 xIn 0.03, 0.04 ... 14300, 14400 10 s Enabled, Disabled Disabled 0, 0.1 ... 99.9, 100 2s Description Range Default Gn 60CTS Element Disabled, Enabled Disabled 0.05, 0.1, 0.15, 0.2, 0.25, 0.3, 0.35, 0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1 0.1 xIn 7, 8 ... 109, 110 10 V 0.03, 0.04 ... 14300, 14400 10 s Gn 60CTS-I Element Disabled, Enabled Disabled Gn 60CTS-I Setting 0.05, 0.1 ... 1.95, 2 0.05 xIn Gn 60CTS-I Delay 0.03, 0.04 ... 14300, 14400 10 s Description Range Default Gn 46BC U/C Guard Setting 0.05, 0.1 ... 4.95, 5 0.25 xIn Gn 46BC Element Disabled, Enabled Disabled 20, 21 ... 99, 100 20 % 0.03, 0.04 ... 14300, 14400 20 s No, Yes No Level below which there is a possible 3 phase VT fuse failure Gn 60VTS Ipps Load Level above which 3 phase fault is assumed so VTS inhibited Gn 60VTS Delay Sets operate delay time Gn 60VTF-Bus Element Selects whether the Bus VT Fail element is enabled. Element based on voltages and circuit breaker position Gn 60VTF-Bus Delay Sets operate delay time 3.10.3. CT Supervision Selects whether the CT supervision element is enabled (NPS current in the absence of NPS voltage) Gn 60CTS Inps Arm if NPS Current (Inps) is above this level Gn 60CTS Vnps Inhibit if NPS Voltage (Vnps) is above this level Gn 60CTS Delay CTS Operate delay 3.10.4. Broken Conductor Selects whether the definite time broken conductor element is enabled Gn 46BC Setting NPS Current to PPS Current ratio Gn 46BC Delay Sets operate delay time Gn 46BC U/C Guarded Unrestricted (c)2018 Siemens Protection Devices Limited Page 41 of 107 7SR220 Settings Guide 3.10.5. Trip CCT Supervision Description Range Default Gn 74TCS-1 Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Description Range Default Gn 74CCS-1 Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Disabled, Enabled Disabled 0, 0.02 ... 59.98, 60 0.4 s Description Range Default Gn 81HBL2 Element Disabled, Enabled Disabled Phase, Cross, Sum Cross 0.1, 0.11 ... 0.49, 0.5 0.2 xI Selects whether the trip circuit supervision element 74TCS-1 is enabled Gn 74TCS-1 Delay Time delay before trip circuit supervision operates Gn 74TCS-2 Selects whether the trip circuit supervision element 74TCS-2 is enabled Gn 74TCS-2 Delay Time delay before trip circuit supervision operates Gn 74TCS-3 Selects whether the trip circuit supervision element 74TCS-3 is enabled Gn 74TCS-3 Delay Time delay before trip circuit supervision operates 3.10.6. Close CCT Supervision Selects whether the trip circuit supervision element 74CCS-1 is enabled Gn 74CCS-1 Delay Time delay before trip circuit supervision operates Gn 74CCS-2 Selects whether the trip circuit supervision element 74CCS-2 is enabled Gn 74CCS-2 Delay Time delay before trip circuit supervision operates Gn 74CCS-3 Selects whether the trip circuit supervision element 74CCS-3 is enabled Gn 74CCS-3 Delay Time delay before trip circuit supervision operates 3.10.7. Inrush Detector Selects whether the phase inrush detector 81HBL2 is enabled Gn 81HBL2 Bias Selects the bias method used for magnetising inrush. Phase - Segregated, each phase blocks itself. Cross - Blocked, each phase can block the operation of other phases. Sum - Of Squares, each phase blocks itself using the square root of the sum of squares of the 2nd harmonic. Gn 81HBL2 Setting The magnetising inrush detector operates when the 2nd harmonic current exceeds a set percentage of the fundamental current Unrestricted Page 42 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 3.10.8. Load Blinder 3.10.8.1. 21LB-3P Description Range Default Gn 21LB-3P Angle +ve 5 degrees to 85 degrees 20 Degrees 5 degrees to 85 degrees 20 Degrees 1, 1.1,...50, 50.5, 51...100 Ohms 10 Ohms 1, 1.5 ...110 V 50 V 0.05, 0.1 ... 0.45, 5 0.5 xI Description Range Default Gn 21LB-1P Angle +ve 5 degrees to 85 degrees 20 Degrees 5 degrees to 85 degrees 20 Degrees 1, 1.1,...50, 50.5, 51...100 Ohms 10 Ohms 1, 1.5 ...110 V 50 V 0.05, 0.1 ... 0.45, 5 0.5 xI Description Range Default Gn 79 P/F Inst Trips Combination of ( 51-1, 51-2, 51-3, 51-4, 50-1, 50-2, 50-3, 50-4 ) -------- Combination of ( 51N-1, 51N-2, 51N-3, 51N-4, 50N-1, 50N-2, 50N3, 50N-4, 51G-1, 51G-2, 51G-3, 51G-4, 50G-1, 50G-2, 50G-3, 50G4) ---------------- Combination of ( 51SEF-1, 51SEF2, 51SEF-3, 51SEF-4, 50SEF-1, 50SEF-2, 50SEF-3, 50SEF-4 ) -------- Selects the boundary region. Gn 21LB-3P Angle -ve Selects the boundary region. Gn 21LB-3P Impedance Selects the impedance of the region. Gn 21LB-3P VPPS Sets the level of 21LB-3P VPPS setting Gn 21LB-3P INPS Sets the level of 21LB-3P INPS setting. 3.10.8.2. 21LB-1P Selects the boundary region. Gn 21LB-1P Angle -ve Selects the boundary region. Gn 21LB-1P Impedance Selects the impedance of the region. Gn 21LB-1P VPPS Sets the level of 21LB-1P VPPS setting Gn 21LB-1P IZPS Sets the level of 21LB-1P ZNPS setting. 3.11. Control & Logic 3.11.1. Autoreclose Prot'n Selects which phase fault protection elements are classed as Instantaneous elements and start an autoreclose sequence. These will be blocked from operating during Delayed autoreclose sequences. See autoreclose section of manual for detail of what elements can cause only Delayed protection to be used. Gn 79 E/F Inst Trips Selects which earth fault protection elements are classed as Instantaneous elements and start an autoreclose sequence. These will be blocked from operating during Delayed autoreclose sequences. See autoreclose section of manual for detail of what elements can cause only Delayed protection to be used. Gn 79 SEF Inst Trips Selects which sensitive earth fault protection elements are classed as Instantaneous elements and start an autoreclose sequence. These will be blocked from operating during Delayed autoreclose sequences. See autoreclose section of manual for detail of what elements can cause only Delayed protection to be used. Unrestricted (c)2018 Siemens Protection Devices Limited Page 43 of 107 7SR220 Settings Guide Description Range Default Gn 79 P/F Delayed Trips Combination of ( 51-1, 51-2, 51-3, 51-4, 50-1, 50-2, 50-3, 50-4 ) 51-1, 51-2, 51-3, 51-4, 50-1, 50-2, 50-3, 50-4 Combination of ( 51N-1, 51N-2, 51N-3, 51N-4, 50N-1, 50N-2, 50N3, 50N-4, 51G-1, 51G-2, 51G-3, 51G-4, 50G-1, 50G-2, 50G-3, 50G4) 51N-1, 51N-2, 51N-3, 51N-4, 50N-1, 50N-2, 50N-3, 50N-4, 51G-1, 51G-2, 51G-3, 51G-4, 50G-1, 50G-2, 50G-3, 50G-4 Combination of ( 51SEF-1, 51SEF2, 51SEF-3, 51SEF-4, 50SEF-1, 50SEF-2, 50SEF-3, 50SEF-4 ) 51SEF-1, 51SEF-2, 51SEF-3, 51SEF-4, 50SEF-1, 50SEF-2, 50SEF-3, 50SEF-4 Combination of ( 50-1, 50-2, 50-3, 50-4 ) ---- Combination of ( 50N-1, 50N-2, 50N-3, 50N-4, 50G-1, 50G-2, 50G3, 50G-4 ) -------- Description Range Default Gn 79 Autoreclose Disabled, Enabled Enabled 1, 2, 3, 4 1 Disabled, Enabled Disabled 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 1 0, 1 ... 599, 600 60 s 0, 1 ... 599, 600 60 s 0, 1 ... 599, 600 60 s Disabled, Enabled Enabled Selects which phase fault protection are classed as Delayed elements, any selected elements operating will start an autoreclose sequence. Gn 79 E/F Delayed Trips Selects which earth fault protection are classed as Delayed elements, any selected elements operating will start an autoreclose sequence. Gn 79 SEF Delayed Trips Selects which sensitive earth fault elements are classed as Delayed elements, any selected elements operating will start an autoreclose sequence. Gn 79 P/F HS Trips Selects which phase fault elements are classed as High Set elements, any selected elements operating will start an autoreclose sequence. Gn 79 E/F HS Trips Selects which earth fault elements are classed as High Set elements, any selected elements operating will start an autoreclose sequence. 3.11.2. Autoreclose Config If disabled then all attempts to control the AR IN/OUT status will fail and the AR will be permanently Out Of Service. When enabled the AR IN/OUT state may be controlled via the CONTROL MODE menu option, via Binary Input or via local or remote communications. Gn 79 Num Shots Selects the number of auto-reclose attempts before the Autorecloser locks out Gn 79 Retry Enable Selects whether the Retry close functionality is enabled Gn 79 Retry Attempts Selects the number of retries allowed per shot Gn 79 Retry Interval Time delay between retries Gn 79 Reclose Blocked Delay Specifies the maximum time that the Autorecloser can be blocked before proceeding to the lockout state. (NOTE: The block delay timer only starts after the Deadtime.) Gn 79 Sequence Fail Timer Time before lockout occurs on an incomplete reclose sequence. (i.e Trip & starter conditions have not been cleared after Sequence Fail Time.) Gn 79 Sequence Co-ord Selects whether Sequence co-ordination functionality is used or not. Unrestricted Page 44 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 79 Cold Load Action Off, Delayed Off Description Range Default Gn 79 P/F Prot'n Trip 1 Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 1, 2, 3, 4, 5 5 1, 2, 3, 4, 5 5 Description Range Default Gn 79 E/F Prot'n Trip 1 Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Inst Selects whether whist Cold Load is active the relay will perform only Delayed Trips or not. 3.11.2.1. P/F Shots Selects whether the first phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F Deadtime 1 Time period between the fault being cleared and the close pulse being issued Gn 79 P/F Prot'n Trip 2 Selects whether the second phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F Deadtime 2 Time period between the fault being cleared and the close pulse being issued Gn 79 P/F Prot'n Trip 3 Selects whether the third phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F Deadtime 3 Time period between the fault being cleared and the close pulse being issued Gn 79 P/F Prot'n Trip 4 Selects whether the fourth phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F Deadtime 4 Time period between the fault being cleared and the close pulse being issued Gn 79 P/F Prot'n Trip 5 Selects whether the fifth phase fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn 79 P/F HS Trips To Lockout Selects how many High Set trips are allowed before going to Lockout Gn 79 P/F Delayed Trips To Lockout Selects how many Delayed trips are allowed before going to Lockout 3.11.2.2. E/F Shots Selects whether the first earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F Deadtime 1 Time period between the fault being cleared and the close pulse being issued Gn 79 E/F Prot'n Trip 2 Selects whether the second earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Unrestricted (c)2018 Siemens Protection Devices Limited Page 45 of 107 7SR220 Settings Guide Description Range Default Gn 79 E/F Deadtime 2 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 1, 2, 3, 4, 5 5 1, 2, 3, 4, 5 5 Description Range Default Gn 79 SEF Prot'n Trip 1 Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Inst 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Inst, Delayed Delayed 0, 0.1 ... 14300, 14400 5s Time period between the fault being cleared and the close pulse being issued Gn 79 E/F Prot'n Trip 3 Selects whether the third earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F Deadtime 3 Time period between the fault being cleared and the close pulse being issued Gn 79 E/F Prot'n Trip 4 Selects whether the fourth earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F Deadtime 4 Time period between the fault being cleared and the close pulse being issued Gn 79 E/F Prot'n Trip 5 Selects whether the fifth earth fault trip is Instantaneous (Fast) or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn 79 E/F HS Trips To Lockout Selects how many High Set trips are allowed before going to Lockout Gn 79 E/F Delayed Trips To Lockout Selects how many Delayed trips are allowed before going to Lockout 3.11.2.3. SEF Shots Selects whether the first sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Deadtime 1 Time period between the fault being cleared and the close pulse being issued Gn 79 SEF Prot'n Trip 2 Selects whether the second sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Deadtime 2 Time period between the fault being cleared and the close pulse being issued Gn 79 SEF Prot'n Trip 3 Selects whether the third sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Deadtime 3 Time period between the fault being cleared and the close pulse being issued Gn 79 SEF Prot'n Trip 4 Selects whether the fourth sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Deadtime 4 Time period between the fault being cleared and the close pulse being issued Unrestricted Page 46 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn 79 SEF Prot'n Trip 5 Inst, Delayed Delayed 1, 2, 3, 4, 5 5 Description Range Default Gn 79 Extern Prot'n Trip 1 Not Blocked, Blocked Not Blocked 0, 0.1 ... 14300, 14400 5s Not Blocked, Blocked Not Blocked 0, 0.1 ... 14300, 14400 5s Not Blocked, Blocked Not Blocked 0, 0.1 ... 14300, 14400 5s Not Blocked, Blocked Not Blocked 0, 0.1 ... 14300, 14400 5s Not Blocked, Blocked Not Blocked 1, 2, 3, 4, 5 5 Description Range Default Gn 25 Sync Voltages Van, Vbn, Vcn, Vab, Vbc, Vca Vbn Gn 25 Dead Line 0 % to 150 % 20 % Gn 25 Live Line 0 % to 150 % 90 % Gn 25 Dead Bus 0 % to 150 % 20 % Gn 25 Live Bus 0 % to 150 % 90 % Gn 25 Line U/V Disabled, Enabled Enabled Gn 25 Line Undervolts 0 % to 150 % 90% Gn 25 Bus U/V Disabled, Enabled Enabled Gn 25 Bus Undervolts 0 % to 150 % 90% Gn 25 Voltage Diff Disabled, Enabled Enabled Selects whether the fifth sensitive earth fault trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn 79 SEF Delayed Trips To Lockout Selects how many Delayed trips are allowed before going to Lockout 3.11.2.4. Extern Shots Selects whether the first external trip is Instantaneous or Delayed Gn 79 Extern Deadtime 1 Time period between the fault being cleared and the close pulse being issued Gn 79 Extern Prot'n Trip 2 Selects whether the second external trip is Instantaneous or Delayed Gn 79 Extern Deadtime 2 Time period between the fault being cleared and the close pulse being issued Gn 79 Extern Prot'n Trip 3 Selects whether the third external trip is Instantaneous or Delayed Gn 79 Extern Deadtime 3 Time period between the fault being cleared and the close pulse being issued Gn 79 Extern Prot'n Trip 4 Selects whether the fourth external trip is Instantaneous or Delayed Gn 79 Extern Deadtime 4 Time period between the fault being cleared and the close pulse being issued Gn 79 Extern Prot'n Trip 5 Selects whether the fifth external trip is Instantaneous or Delayed Gn 79 Extern Trips To Lockout Selects how many external trips are allowed before going to Lockout 3.11.3. Synchronising Check Unrestricted (c)2018 Siemens Protection Devices Limited Page 47 of 107 7SR220 Settings Guide Description Range Default Gn 25 Volt Differential 0 % to 100 % 10% Gn 25 Check Sync Disabled, Enabled Enabled Gn 25 Check Sync Angle 0 Deg to 90 Deg 20 Deg Gn 25 Check Sync Slip Freq Disabled, Enabled Enabled Gn 25 Check Sync Slip 0 Hz to 2 Hz 0.05 Hz Gn 25 Check Sync Timer 0 s to 100 s 2s Gn 25 System Split Mode Phase, Slip Phase Gn 25 Split Angle 0 Deg to 180 Deg 175 Deg Gn 25 Split Slip 0 Hz to 2 Hz 0.02 Hz Gn 25 System Sync Disabled, Enabled Enabled Gn 25 System Sync Angle 0 Deg to 90 Deg 10 Deg Gn 25 System Sync Slip 0 Hz to 2 Hz 0.125 Hz Gn 25 System Sync Timer 0 s to 100 s 0.2 s Gn 25 Close On Zero Disabled, Enabled Enabled Gn 25 COZ Slip Freq 0 Hz to 2 Hz 0.125 Hz Gn 25 CB Close Time 0 ms to 900 ms 60 ms Gn 25 DAR Split Mode CS, SS, COZ, LO CS Gn 25 MC Split Mode CS, SS, COZ CS Description Range Default Gn Line Check Trip Disabled, Enabled Enabled Inst, Delayed Inst Inst, Delayed Inst Inst, Delayed Inst Not Blocked, Blocked Not Blocked 0, 0.1 ... 899, 900 10 s 0, 1 ... 599, 600 5s 0, 0.1 ... 899, 900 10 s Latch, Reset Latch 3.11.4. Manual CB Control Selects whether line check trip is enabled, if enabled no AR sequence initiated Gn P/F Line Check Trip Selects whether a phase fault line check trip is Instantaneous (Fast) or Delayed. When set to Delayed all P/F Inst Trips will be Inhibited for this shot. Gn E/F Line Check Trip Selects whether an earth fault line check trip is Instantaneous or Delayed. When set to Delayed all E/F Inst Trips will be Inhibited for this shot. Gn SEF Line Check Trip Selects whether a sensitive earth fault line check trip is Instantaneous or Delayed. When set to Delayed all SEF Inst Trips will be Inhibited for this shot. Gn Extern Line Check Trip Selects whether an external line check trip is Instantaneous (Fast) or Delayed Gn Close CB Delay Delay between a Close CB control being received and the Close CB contacts being operated to allow operator walk away. Gn Blocked Close Delay Selects the maximum time that the manual Close CB may be blocked by interlocking before the command or control is cancelled. The relay will signal "Blocked by Interlocking". Gn Open CB Delay Delay between an Open CB control being received and the Open CB contacts being operated. Gn CB Controls Latched Selects whether Binary Input triggers of Close CB and Open CB are latched. Unrestricted Page 48 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 3.11.5. Circuit Breaker Description Range Default Gn Close CB Pulse 0, 0.1 ... 19.9, 20 2s 0, 1 ... 599, 600 2s Gn Minimum LO Delay 0, 1 ... 599, 600 2s Gn Reset LO By Timer Disabled, Enabled Enabled Gn CB Control Trip Time Disabled, Enabled Enabled Gn Trip Time Alarm 0, 0.01 ... 1.99, 2 0.2 s 0, 0.005 ... 1.995, 2 0.015 s 0.01, 0.02 ... 1.99, 2 1s 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8, 1.9, 2 1s 0, 0.01, ... 1.1, 1.11 ... 2 0s Description Range Default Quick Logic Disabled, Enabled Disabled Disabled, Enabled Disabled Specifies the duration of the circuit breaker close pulse Gn Reclaim Timer The period of time after a CB has closed and remained closed before the reclosure is deemed to be successful and the AR is re-initialised. If the CB remains open at the end of the reclaim time then the AR goes to lockout. An alarm is issued when the Trip time is exceeded Gn Trip Time Adjust Adjustment to take into account any binary input delays for Trip Time Alarm Gn CB Travel Alarm Selects the maximum time that the CB should take to either Open or Close before a failure is recorded. Gn Open CB Pulse Selects the maximum time of the Open CB pulse. If the CB is not closed when this timer expires then an alarm will be raised to signify failure to close. Gn CB DBI Delay Selects the Delay before relay goes to Lockout following a simultaneous Open and Close condition indication. 3.11.6. QUICK LOGIC Enable or Disable all logic equations E1 Equation Enable or Disable logic equation E1 E1 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E1 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s Time before equation output operates, after equation satisfied E1 Drop-off Delay Time before equation output resets, after equation nolonger satisfied Unrestricted (c)2018 Siemens Protection Devices Limited Page 49 of 107 7SR220 Settings Guide Description Range Default E1 Counter Target 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Select number of times equation must be satisfied before equation output operates E1 Counter Reset Mode Select type of counter reset mode E1 Counter Reset Time Select counter reset time E2 Equation Enable or Disable logic equation E2 E2 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E2 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E2 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E2 Counter Target Select number of times equation must be satisfied before equation output operates E2 Counter Reset Mode Select type of counter reset mode E2 Counter Reset Time Select counter reset time E3 Equation Enable or Disable logic equation E3 E3 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E3 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Time before equation output operates, after equation satisfied E3 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E3 Counter Target Select number of times equation must be satisfied before equation output operates E3 Counter Reset Mode Select type of counter reset mode E3 Counter Reset Time Select counter reset time Unrestricted Page 50 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default E4 Equation Disabled, Enabled Disabled Enable or Disable logic equation E4 E4 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E4 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E4 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E4 Counter Target Select number of times equation must be satisfied before equation output operates E4 Counter Reset Mode Select type of counter reset mode E4 Counter Reset Time Select counter reset time E5 Equation Enable or Disable logic equation E5 E5 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E5 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E5 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E5 Counter Target Select number of times equation must be satisfied before equation output operates E5 Counter Reset Mode Select type of counter reset mode E5 Counter Reset Time Select counter reset time E6 Equation Enable or Disable logic equation E6 Unrestricted (c)2018 Siemens Protection Devices Limited Page 51 of 107 7SR220 Settings Guide Description Range Default E6 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E6 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E6 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E6 Counter Target Select number of times equation must be satisfied before equation output operates E6 Counter Reset Mode Select type of counter reset mode E6 Counter Reset Time Select counter reset time E7 Equation Enable or Disable logic equation E7 E7 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E7 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E7 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E7 Counter Target Select number of times equation must be satisfied before equation output operates E7 Counter Reset Mode Select type of counter reset mode E7 Counter Reset Time Select counter reset time E8 Equation Enable or Disable logic equation E8 Unrestricted Page 52 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range E8 (20 Character String) Default Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E8 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E8 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E8 Counter Target Select number of times equation must be satisfied before equation output operates E8 Counter Reset Mode Select type of counter reset mode E8 Counter Reset Time Select counter reset time E9 Equation Enable or Disable logic equation E9 E9 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E9 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E9 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E9 Counter Target Select number of times equation must be satisfied before equation output operates E9 Counter Reset Mode Select type of counter reset mode E9 Counter Reset Time Select counter reset time E10 Equation Enable or Disable logic equation E10 Unrestricted (c)2018 Siemens Protection Devices Limited Page 53 of 107 7SR220 Settings Guide Description Range Default E10 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E10 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E10 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E10 Counter Target Select number of times equation must be satisfied before equation output operates E10 Counter Reset Mode Select type of counter reset mode E10 Counter Reset Time Select counter reset time E11 Equation Enable or Disable logic equation E11 E11 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E11 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E11 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E11 Counter Target Select number of times equation must be satisfied before equation output operates E11 Counter Reset Mode Select type of counter reset mode E11 Counter Reset Time Select counter reset time E12 Equation Enable or Disable logic equation E12 Unrestricted Page 54 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range E12 (20 Character String) Default Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E12 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E12 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E12 Counter Target Select number of times equation must be satisfied before equation output operates E12 Counter Reset Mode Select type of counter reset mode E12 Counter Reset Time Select counter reset time E13 Equation Enable or Disable logic equation E13 E13 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E13 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E13 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E13 Counter Target Select number of times equation must be satisfied before equation output operates E13 Counter Reset Mode Select type of counter reset mode E13 Counter Reset Time Select counter reset time E14 Equation Enable or Disable logic equation E14 Unrestricted (c)2018 Siemens Protection Devices Limited Page 55 of 107 7SR220 Settings Guide Description Range Default E14 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E14 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E14 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E14 Counter Target Select number of times equation must be satisfied before equation output operates E14 Counter Reset Mode Select type of counter reset mode E14 Counter Reset Time Select counter reset time E15 Equation Enable or Disable logic equation E15 E15 (20 Character String) Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E15 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E15 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E15 Counter Target Select number of times equation must be satisfied before equation output operates E15 Counter Reset Mode Select type of counter reset mode E15 Counter Reset Time Select counter reset time E16 Equation Enable or Disable logic equation E16 Unrestricted Page 56 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range E16 (20 Character String) Default Specify logic equations of the form En = using the following:0123456789=Digit() = Parenthesis! = NOT operation. = AND operation^ = EXCLUSIVE OR operationE(followed by a digit) = Equation numberF (Followed by a digit) = Function Key numberI(Followed by a digit) = Binary Input numberL(Followed by a digit) = LED numberO(Followed by a digit) = output relay numberV(Followed by a digit) =Virtual Input/Output number.ExamplesMake a function key LED toggle when function key is pressed (requires E1 to drive L11 in output matrix)E1 = F3^L11 E16 Pick-up Delay 0, 0.01 ... 14300, 14400 0s 0, 0.01 ... 14300, 14400 0s 1, 2 ... 998, 999 1 Off, Multi-shot, Single-shot Off 0, 0.01 ... 14300, 14400 0s Disabled, Enabled Disabled Time before equation output operates, after equation satisfied E16 Drop-off Delay Time before equation output resets, after equation nolonger satisfied E16 Counter Target Select number of times equation must be satisfied before equation output operates E16 Counter Reset Mode Select type of counter reset mode E16 Counter Reset Time Select counter reset time E16 Equation Enable or Disable logic equation E16 Unrestricted (c)2018 Siemens Protection Devices Limited Page 57 of 107 7SR220 Settings Guide 3.12. Input Config 3.12.1. Input Matrix Description Range Default Inhibit 81HBL2 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs inhibit the 81HLB2 Inhibit Cold Load Selects which inputs inhibit the Cold Load element Inhibit 51-1 Selects which inputs inhibit the 51-1 element Inhibit 51-2 Selects which inputs inhibit the 51-2 element Inhibit 51-3 Selects which inputs inhibit the 51-3 element Inhibit 51-4 Selects which inputs inhibit the 51-4 element Inhibit 50-1 Selects which inputs inhibit the 50-1 element Inhibit 50-2 Selects which inputs inhibit the 50-2 element Inhibit 50-3 Selects which inputs inhibit the 50-3 element Inhibit 50-4 Selects which inputs inhibit the 50-4 element Inhibit 51N-1 Selects which inputs inhibit the 51N-1 element Unrestricted Page 58 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Inhibit 51N-2 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs inhibit the 51N-2 element Inhibit 51N-3 Selects which inputs inhibit the 51N-3 element Inhibit 51N-4 Selects which inputs inhibit the 51N-4 element Inhibit 50N-1 Selects which inputs inhibit the 50N-1 element Inhibit 50N-2 Selects which inputs inhibit the 50N-2 element Inhibit 50N-3 Selects which inputs inhibit the 50N-3 element Inhibit 50N-4 Selects which inputs inhibit the 50N-4 element Inhibit 51G-1 Selects which inputs inhibit the 51G-1 element Inhibit 51G-2 Selects which inputs inhibit the 51G-2 element Inhibit 51G-3 Selects which inputs inhibit the 51G-3 element Inhibit 51G-4 Selects which inputs inhibit the 51G-4 element Inhibit 50G-1 Selects which inputs inhibit the 50G-1 element Inhibit 50G-2 Selects which inputs inhibit the 50G-2 element Unrestricted (c)2018 Siemens Protection Devices Limited Page 59 of 107 7SR220 Settings Guide Description Range Default Inhibit 50G-3 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs inhibit the 50G-3 element Inhibit 50G-4 Selects which inputs inhibit the 50G-4 element Inhibit 51SEF-1 Selects which inputs inhibit the 51SEF-1 element Inhibit 51SEF-2 Selects which inputs inhibit the 51SEF-2 element Inhibit 51SEF-3 Selects which inputs inhibit the 51SEF-3 element Inhibit 51SEF-4 Selects which inputs inhibit the 51SEF-4 element Inhibit 50SEF-1 Selects which inputs inhibit the 50SEF-1 element Inhibit 50SEF-2 Selects which inputs inhibit the 50SEF-2 element Inhibit 50SEF-3 Selects which inputs inhibit the 50SEF-3 element Inhibit 50SEF-4 Selects which inputs inhibit the 50SEF-4 element Inhibit 64H Selects which inputs inhibit the 64H element Inhibit 46IT Selects which inputs inhibit the 46IT element Inhibit 46DT Selects which inputs inhibit the 46DT element Unrestricted Page 60 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Inhibit 37-1 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs inhibit the 37-1 element Inhibit 37-2 Selects which inputs inhibit the 37-2 element Inhibit 37G-1 Selects which inputs inhibit the 37G-1 element Inhibit 37G-2 Selects which inputs inhibit the 37G-2 element Inhibit 37SEF-1 Selects which inputs inhibit the 37SEF-1 element Inhibit 37SEF-2 Selects which inputs inhibit the 37SEF-2 element Inhibit 49 Selects which inputs inhibit the 49 thermal element Reset 49 Selects which inputs resets the 49 thermal model element Inhibit 27/59-1 Selects which inputs inhibit the 27/59-1 element Inhibit 27/59-2 Selects which inputs inhibit the 27/59-2 element Inhibit 27/59-3 Selects which inputs inhibit the 27/59-3 element Inhibit 27/59-4 Selects which inputs inhibit the 27/59-4 element Inhibit Vx 27/59 Selects which inputs inhibit the Vx 27/59 element Unrestricted (c)2018 Siemens Protection Devices Limited Page 61 of 107 7SR220 Settings Guide Description Range Default Inhibit 47-1 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Inhibit 60CTS-I Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Inhibit 46BC Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs inhibit the 47-1 element Inhibit 47-2 Selects which inputs inhibit the 47-2 element Inhibit 59NIT Selects which inputs inhibit the 59N IDMTL/DTL element Inhibit 59NDT Selects which inputs inhibit the 59N INST/DTL element Inhibit 81-1 Selects which inputs inhibit the 81-1 element Inhibit 81-2 Selects which inputs inhibit the 81-2 element Inhibit 81-3 Selects which inputs inhibit the 81-3 element Inhibit 81-4 Selects which inputs inhibit the 81-4 element Inhibit 81-5 Selects which inputs inhibit the 81-5 element Inhibit 81-6 Selects which inputs inhibit the 81-6 element Inhibit 60CTS Selects which inputs inhibit the CT Supervision element Selects which inputs inhibit the 46 Broken Conductor element Unrestricted Page 62 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default 74TCS-1 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs are monitoring trip circuits 74TCS-2 As Above 74TCS-3 As Above 74CCS-1 Selects which inputs are monitoring close circuits 74CCS-2 As Above 74CCS-3 As Above Trig Trip Contacts Selects which inputs will trigger the Trip contacts Inhibit 50BF Selects which inputs inhibit the 50BF element 50BF CB Faulty Selects which input bypasses the 50BF timer due to a fault CB 50BF Mech Trip Selects which input allows a mechanical trip to start the 50BF element 50BF Ext Trip Selects which inputs can also start the 50BF element Inhibit 60VTS Selects which inputs inhibit the VT Supervision element Ext Trig 60VTS Selects MCB inputs to VT Supervision element Unrestricted (c)2018 Siemens Protection Devices Limited Page 63 of 107 7SR220 Settings Guide Description Range Default Ext Reset 60VTS Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs reset the VT Supervision element Inhibit 60VTF-Bus Selects which inputs inhibit the 60VTF-Bus Supervision element Reset CB Total Trip Selects which inputs Reset the CB Total Trip count Reset CB Ph A Count Selects which inputs Reset the CB Ph A Count Reset CB Ph B Count Selects which inputs Reset the CB Ph B Count Reset CB Ph C Count Selects which inputs Reset the CB Ph C Count Reset CB E/F Count Selects which inputs Reset the CB E/F Count Reset CB Delta Trip Selects which inputs Reset the CB Delta Trip count Reset ARBlock Count Selects which inputs Reset the AR Block count Reset Freq Ops Count Selects which inputs Reset the Frequent Ops count Reset I^2t CB Wear Selects which inputs Reset the I^2t CB Wear element Trigger I^2t CB Wear Selects which inputs will cause an external trigger of the I^2t CB Wear element Reset Trip Time Selects which inputs will reset the CB trip time alarm Unrestricted Page 64 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default General Alarm 1 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs will activate the General Alarm 1 text General Alarm 2 Selects which inputs will activate the General Alarm 2 text General Alarm 3 Selects which inputs will activate the General Alarm 3 text General Alarm 4 Selects which inputs will activate the General Alarm 4 text General Alarm 5 Selects which inputs will activate the General Alarm 5 text General Alarm 6 Selects which inputs will activate the General Alarm 6 text General Alarm 7 Selects which inputs will activate the General Alarm 7 text General Alarm 8 Selects which inputs will activate the General Alarm 8 text General Alarm 9 Selects which inputs will activate the General Alarm 9 text General Alarm 10 Selects which inputs will activate the General Alarm 10 text General Alarm 11 Selects which inputs will activate the General Alarm 11 text General Alarm 12 Selects which inputs will activate the General Alarm 12 text General Alarm 13 Selects which inputs will activate the General Alarm 13 text Unrestricted (c)2018 Siemens Protection Devices Limited Page 65 of 107 7SR220 Settings Guide Description Range Default General Alarm 14 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs will activate the General Alarm 14 text General Alarm 15 Selects which inputs will activate the General Alarm 15 text General Alarm 16 Selects which inputs will activate the General Alarm 16 text General Alarm 17 Selects which inputs will activate the General Alarm 17 text General Alarm 18 Selects which inputs will activate the General Alarm 18 text General Alarm 19 Selects which inputs will activate the General Alarm 19 text General Alarm 20 Selects which inputs will activate the General Alarm 20 text CB Open Selects which inputs are connected to the circuit breaker open contacts CB Closed Selects which inputs are connected to the circuit breaker closed contacts Reset Demand Selects which inputs will reset the Demand elements. Reset Start Count Selects which inputs will reset the Start Count elements. AFD Zone 1 Flash Selects which inputs will are connected to ARC Flash Detector AFD Zone 2 Flash Selects which inputs will are connected to ARC Flash Detector Unrestricted Page 66 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default AFD Zone 3 Flash Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs will are connected to ARC Flash Detector AFD Zone 4 Flash Selects which inputs will are connected to ARC Flash Detector AFD Zone 5 Flash Selects which inputs will are connected to ARC Flash Detector AFD Zone 6 Flash Selects which inputs will are connected to ARC Flash Detector Reset AFDZone 1 Count Selects which inputs will reset ARC Flash Detector Count Reset AFDZone 2 Count Selects which inputs will reset ARC Flash Detector Count Reset AFDZone 3 Count Selects which inputs will reset ARC Flash Detector Count Reset AFDZone 4 Count Selects which inputs will reset ARC Flash Detector Count Reset AFDZone 5 Count Selects which inputs will reset ARC Flash Detector Count Reset AFDZone 6 Count Selects which inputs will reset ARC Flash Detector Count Inhibit Fault Loc Selects which inputs will Inhibit fault Locator. Close CB Selects which inputs will issue a close to the circuit breaker. Block Close CB Selects which inputs will block the manual closing of the circuit breaker. Unrestricted (c)2018 Siemens Protection Devices Limited Page 67 of 107 7SR220 Settings Guide Description Range Default Open CB Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs will issue an open to the circuit breaker. 79 Out Selects which inputs will switch the Auto-recloser out of service 79 In Selects which inputs will switch the Auto-recloser in service 79 Trip & Reclose Selects which inputs will trigger a trip & reclose 79 Trip & Lockout Selects which inputs will trigger a trip & lockout 79 Ext Trip Selects which input will start the external an Auto-relose sequence 79 Ext Pickup Selects which input should be connected to the pickup of the external elements required to start an Auto-reclose sequence 79 Block Reclose Selects which inputs will block the Auto-recloser 79 Reset Lockout Selects which inputs will force the Auto-recloser into the Lockout state 79 Line Check Selects which inputs will start the Line Check functionality of the Auto-recloser 79 Lockout Selects which inputs will force the Auto-recloser into the Lockout state 79 Override Sync Selects which inputs will start 79 Override Sync Man Override Sync Selects which inputs will start Man Override Sync Unrestricted Page 68 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Ext Start 25 Sync Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Selects which inputs will Ext Start 25 Sync Reset 25 Sync Selects which inputs will Reset 25 Sync Start 25 System Sync Selects which inputs will Start 25 System Sync Hot Line Out Selects which inputs will switch out Hot Line Working Hot Line In Selects which inputs will switch in Hot Line Working Inst Prot'n Out Selects which inputs will switch out the instantaneous protection elements Inst Prot'n In Selects which inputs will switch in the instantaneous protection elements E/F Out Selects which inputs will switch out the E/F protection elements. E/F In Selects which inputs will switch in the E/F protection elements. SEF Out Selects which inputs will switch out the SEF protection elements SEF In Selects which inputs will switch in the SEF protection elements Trigger Wave Rec Selects which inputs can trigger a waveform record Trigger Fault Rec Selects which inputs can trigger a fault record Unrestricted (c)2018 Siemens Protection Devices Limited Page 69 of 107 7SR220 Settings Guide Description Range Default Select Group 1 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Reset Energy Meters Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Select Group 2 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Switches active setting group to group 1 Switches active setting group to group 2 Select Group 3 Switches active setting group to group 3 Select Group 4 Switches active setting group to group 4 Select Group 5 Switches active setting group to group 5 Select Group 6 Switches active setting group to group 6 Select Group 7 Switches active setting group to group 7 Select Group 8 Switches active setting group to group 8 Out Of Service Mode Selects which inputs will put the relay into Out Of Service Mode Local Mode Selects which inputs will put the relay into Local Mode Remote Mode Selects which inputs will put the relay into Remote Mode Local Or Remote Mode Selects which inputs will put the relay into Local Or Remote Mode Unrestricted Page 70 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Clock Sync. Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13) ---------------------------- Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13) BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13 Combination of ( BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13) BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10, BI11, BI12, BI13 Description Range Default Open CB Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Out Of Service Mode Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Local Mode Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Remote Mode Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Local Or Remote Mode Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Selects which input is used to synchronise the real time clock Reset LEDs & O/Ps Selects which inputs will reset the latched LEDs and binary outputs Inverted Inputs Selects which inputs will be inverted Enable In Local Selects which inputs will be enabled in local mode Enable In Remote Selects which inputs will be enabled in remote mode 3.12.2. Function Key Matrix Selects which function key will Open the circuit breaker Close CB Selects which function key will Close the circuit breaker 79 In/Out Selects which function key will toggle Autoreclose In & Out 79 Trip & Reclose Selects which function key will cause the CB to trip & reclose 79 Trip & Lockout Selects which function key will cause the CB to trip & lockout Hot Line Work In/Out Selects which function key will toggle Hot Line Working In & Out E/F In/Out Selects which function key will toggle E/F protection In & Out SEF In/Out Selects which function key will toggle SEF protection In & Out Inst Prot'n In/Out Selects which function key will toggle Instantaneous protection elements In & Out Selects which inputs will put the relay into Local Or Remote Mode Unrestricted (c)2018 Siemens Protection Devices Limited Page 71 of 107 7SR220 Settings Guide Unrestricted Page 72 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 3.12.3. Binary Input Config (Variants may differ) Description Range Default Inverted Inputs Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13 ) ------------- 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s Selects which inputs pickup when voltage is removed. BI 1 Pick-up Delay Delay on pickup of DC Binary Input 1 BI 1 Drop-off Delay Delay on dropoff of DC Binary Input 1 BI 2 Pick-up Delay Delay on pickup of DC Binary Input 2 BI 2 Drop-off Delay Delay on dropoff of DC Binary Input 2 BI 3 Pick-up Delay Delay on pickup of DC Binary Input 3 BI 3 Drop-off Delay Delay on dropoff of DC Binary Input 3 BI 4 Pick-up Delay Delay on pickup of DC Binary Input 4 BI 4 Drop-off Delay Delay on dropoff of DC Binary Input 4 BI 5 Pick-up Delay Delay on pickup of DC Binary Input 5 BI 5 Drop-off Delay Delay on dropoff of DC Binary Input 5 BI 6 Pick-up Delay Delay on pickup of DC Binary Input 6 BI 6 Drop-off Delay Delay on dropoff of DC Binary Input 6 BI 7 Pick-up Delay Delay on pickup of DC Binary Input 7 BI 7 Drop-off Delay Delay on dropoff of DC Binary Input 7 BI 8 Pick-up Delay Delay on pickup of DC Binary Input 8 BI 8 Drop-off Delay Delay on dropoff of DC Binary Input 8 BI 9 Pick-up Delay Delay on pickup of DC Binary Input 9 BI 9 Drop-off Delay Delay on dropoff of DC Binary Input 9 BI 10 Pick-up Delay Delay on pickup of DC Binary Input 10 BI 10 Drop-off Delay Delay on dropoff of DC Binary Input 10 BI 11 Pick-up Delay Delay on pickup of DC Binary Input 11 BI 11 Drop-off Delay Delay on dropoff of DC Binary Input 11 Unrestricted (c)2018 Siemens Protection Devices Limited Page 73 of 107 7SR220 Settings Guide Description Range Default BI 12 Pick-up Delay 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s 0, 0.005 ... 14300, 14400 0.02 s 0, 0.005 ... 14300, 14400 0s Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13 ) 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13 Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13 ) 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13 Description Range Default Function Key 1 Text (20 Character String) Function Key 1 (20 Character String) Function Key 2 (20 Character String) Function Key 3 (20 Character String) Function Key 4 (20 Character String) Function Key 5 (20 Character String) Function Key 6 Combination of ( 1, 2, 3, 4, 5, 6 ) ------ Delay on pickup of DC Binary Input 12 BI 12 Drop-off Delay Delay on dropoff of DC Binary Input 12 BI 13 Pick-up Delay Delay on pickup of DC Binary Input 13 BI 13 Drop-off Delay Delay on dropoff of DC Binary Input 13 Enabled In Local Selects which inputs are enabled when the relay is in Operating Mode 'Local' or 'Local Or Remote' Enabled In Remote Selects which inputs are enabled when the relay is in Operating Mode 'Remote' or 'Local Or Remote' 3.12.4. Function Key Config User definable text that will be used in the HMI function key confirmation screen when Function key 1 is pressed. Function Key 2 Text User definable text that will be used in the HMI function key confirmation screen when Function key 2 is pressed. Function Key 3 Text User definable text that will be used in the HMI function key confirmation screen when Function key 3 is pressed. Function Key 4 Text User definable text that will be used in the HMI function key confirmation screen when Function key 4 is pressed. Function Key 5 Text User definable text that will be used in the HMI function key confirmation screen when Function key 5 is pressed. Function Key 6 Text User definable text that will be used in the HMI function key confirmation screen when Function key 6 is pressed. Enabled In Remote Selects which inputs are enabled when the relay is in Operating Mode 'Remote' or 'Local Or Remote' Unrestricted Page 74 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide 3.12.5. General Alarms Description Range Default General Alarm-1 (16 Character String) ALARM 1 (16 Character String) ALARM 2 (16 Character String) ALARM 3 (16 Character String) ALARM 4 (16 Character String) ALARM 5 (16 Character String) ALARM 6 (16 Character String) ALARM 7 (16 Character String) ALARM 8 (16 Character String) ALARM 9 (16 Character String) ALARM 10 (16 Character String) ALARM 11 (16 Character String) ALARM 12 (16 Character String) ALARM 13 (16 Character String) ALARM 14 (16 Character String) ALARM 15 (16 Character String) ALARM 16 (16 Character String) ALARM 17 (16 Character String) ALARM 18 (16 Character String) ALARM 19 (16 Character String) ALARM 20 Defines the text to be displayed for General Alarm 1 General Alarm-2 Defines the text to be displayed for General Alarm 2 General Alarm-3 Defines the text to be displayed for General Alarm 3 General Alarm-4 Defines the text to be displayed for General Alarm 4 General Alarm-5 Defines the text to be displayed for General Alarm 5 General Alarm-6 Defines the text to be displayed for General Alarm 6 General Alarm-7 Defines the text to be displayed for General Alarm 7 General Alarm-8 Defines the text to be displayed for General Alarm 8 General Alarm-9 Defines the text to be displayed for General Alarm 9 General Alarm-10 Defines the text to be displayed for General Alarm 10 General Alarm-11 Defines the text to be displayed for General Alarm 11 General Alarm-12 Defines the text to be displayed for General Alarm 12 General Alarm-13 Defines the text to be displayed for General Alarm 13 General Alarm-14 Defines the text to be displayed for General Alarm 14 General Alarm-15 Defines the text to be displayed for General Alarm 15 General Alarm-16 Defines the text to be displayed for General Alarm 16 General Alarm-17 Defines the text to be displayed for General Alarm 17 General Alarm-18 Defines the text to be displayed for General Alarm 18 General Alarm-19 Defines the text to be displayed for General Alarm 19 General Alarm-20 Defines the text to be displayed for General Alarm 20 Unrestricted (c)2018 Siemens Protection Devices Limited Page 75 of 107 7SR220 Settings Guide 3.13. Output Config 3.13.1. Output Matrix Description Range Default Protection Healthy Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) BO1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) Grp 1 Relays selected are energised whilst relay self-monitoring does NOT detect any hardware or software errors and DC Supply is healthy. A changeover contact or normally closed contact may be used to generate Protection Defective from this output Active Setting Grp 1 Active Setting Grp 2 Active Setting Grp 3 Active Setting Grp 4 Active Setting Grp 5 Active Setting Grp 6 Active Setting Grp 7 Active Setting Grp 8 Unrestricted Page 76 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default +ve P 3 Ph Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- -ve P 3 Ph Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- +ve Q 3 Ph Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- -ve Q 3 Ph Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 51-1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 51-1 IDMTL/DTL Overcurrent operated 51-2 51-2 IDMTL/DTL Overcurrent operated 51-3 51-3 IDMTL/DTL Overcurrent operated 51-4 51-4 IDMTL/DTL Overcurrent operated 50-1 50-1 INST/DTL Overcurrent operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 77 of 107 7SR220 Settings Guide Description Range Default 50-2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 50-2 INST/DTL Overcurrent operated 50-3 50-3 INST/DTL Overcurrent operated 50-4 50-4 INST/DTL Overcurrent operated 51N-1 51N-1 IDMTL/DTL derived Earth Fault operated 51N-2 51N-2 IDMTL/DTL derived Earth Fault operated 51N-3 51N-3 IDMTL/DTL derived Earth Fault operated 51N-4 51N-4 IDMTL/DTL derived Earth Fault operated 50N-1 50N-1 INST/DTL derived Earth Fault operated 50N-2 50N-2 INST/DTL derived Earth Fault operated Unrestricted Page 78 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default 50N-3 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 50N-3 INST/DTL derived Earth Fault operated 50N-4 50N-4 INST/DTL derived Earth Fault operated 51G-1 51G-1 IDMTL/DTL measured Earth Fault operated 51G-2 51G-2 IDMTL/DTL measured Earth Fault operated 51G-3 51G-3 IDMTL/DTL measured Earth Fault operated 51G-4 51G-4 IDMTL/DTL measured Earth Fault operated 50G-1 50G-1 INST/DTL measured Earth Fault operated 50G-2 50G-2 INST/DTL measured Earth Fault operated 50G-3 50G-3 INST/DTL measured Earth Fault operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 79 of 107 7SR220 Settings Guide Description Range Default 50G-4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) L5 50G-4 INST/DTL measured Earth Fault operated 51SEF-1 51SEF-1 IDMTL/DTL Sensitive Earth Fault operated 51SEF-2 51SEF-2 IDMTL/DTL Sensitive Earth Fault operated 51SEF-3 51SEF-3 IDMTL/DTL Sensitive Earth Fault operated 51SEF-4 51SEF-4 IDMTL/DTL Sensitive Earth Fault operated 50SEF-1 50SEF-1 INST/DTL Sensitive Earth Fault operated 50SEF-2 50SEF-2 INST/DTL Sensitive Earth Fault operated 50SEF-3 50SEF-3 INST/DTL Sensitive Earth Fault operated 50SEF-4 50SEF-4 INST/DTL Sensitive Earth Fault operated Unrestricted Page 80 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default 64H Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 64H Restricted Earth Fault element operated Cold Load Active Cold Load settings are active 46IT IDMTL/DTL NPS Overcurrent operated 46DT INST/DTL NPS Overcurrent operated 37 PhA PhA Under Current operated 37 PhB PhB Under Current operated 37 PhC PhC Under Current operated 37-1 37-1 Under Current operated 37-2 37-2 Under Current operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 81 of 107 7SR220 Settings Guide Description Range Default 37G-1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 37G-1 Under Current operated 37G-2 37G-2 Under Current operated 37SEF-1 37SEF-1 Under Current operated 37SEF-2 37SEF-2 Under Current operated 49 Trip Thermal capacity trip operated 49 Alarm Thermal capacity alarm operated 27/59-1 Under/Overvoltage stage 1 operated 27/59-2 Under/Overvoltage stage 2 operated 27/59-3 Under/Overvoltage stage 3 operated Unrestricted Page 82 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default 27/59-4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Under/Overvoltage stage 4 operated Vx 27/59 Under/Overvoltage Vx stage operated 47-1 INST/DTL NPS Overvoltage stage 1 operated 47-2 INST/DTL NPS Overvoltage stage 2 operated 59NIT Neutral Overvoltage IDMTL/DTL operated 59NDT Neutral Overvoltage INST/DTL operated 81-1 Under/Over frequency stage 1 operated 81-2 Under/Over frequency stage 2 operated 81-3 Under/Over frequency stage 3 operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 83 of 107 7SR220 Settings Guide Description Range Default 81-4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 60CTS-I Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 46BC Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Under/Over frequency stage 4 operated 81-5 Under/Over frequency stage 5 operated 81-6 Under/Over frequency stage 6 operated 60CTS CT Supervision element operated 46 Broken Conductor element operated 74TCS-1 Trip Circuit 1 fail operated 74TCS-2 Trip Circuit 2 fail operated 74TCS-3 Trip Circuit 3 fail operated Unrestricted Page 84 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default 74CCS-1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 81HBL2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- General Pickup Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Close Circuit 1 fail operated 74CCS-2 Close Circuit 2 fail operated 74CCS-3 Close Circuit 3 fail operated General Pickup operated 50BF-1 Circuit Breaker Fail stage 1 operated 50BF-2 Circuit Breaker Fail stage 2 operated 60VTS VT Supervision element operated 60VTF-Bus 60 VTF-Bus Supervision element operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 85 of 107 7SR220 Settings Guide Description Range Default 50BF PhA Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Circuit Breaker Fail Phase A 50BF PhB Circuit Breaker Fail Phase B 50BF PhC Circuit Breaker Fail Phase C 50BF EF Circuit Breaker Fail Earth Fault CB Total Trip Count Total CB trip count exceeded CB Ph A Trip Count Total CB Ph A trip count exceeded CB Ph B Trip Count Total CB Ph B trip count exceeded CB Ph C Trip Count Total CB Ph C trip count exceeded CB E/F Trip Count Total CB E/F trip count exceeded Unrestricted Page 86 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default CB Delta Trip Count Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Delta CB trip count exceeded CB Count To ARBlock Count To AR Block CB trip count exceeded CB Freq Ops Count CB Frequent Operations count exceeded I^2t CB Wear I^2t CB Wear limit exceeded Trip Time Alarm Trip Time Alarm operated CB Open Indicates that the circuit breaker is in the open position. CB Closed Indicates that the circuit breaker is in the closed position. Close CB Blocked Indicates that the Close CB control is blocked by its interlocking logic. CB Alarm Indicates the CB is either in an illegal state or is stuck neither open or closed. Unrestricted (c)2018 Siemens Protection Devices Limited Page 87 of 107 7SR220 Settings Guide Description Range Default Open CB Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Start Count Alarm Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 50AFD PhA Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Open pulse due to Manual Open being issued. Phase A Phase A element operated Phase B Phase B element operated Phase C Phase C element operated Derived E/F Derive E/F element operated Measured E/F Measured E/F element operated Sensitive E/F Sensitive E/F element operated Arc Flash Detector Phase A operated Unrestricted Page 88 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default 50AFD PhB Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 50AFD Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 1 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 2 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 3 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 3 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Arc Flash Detector Phase B operated 50AFD PhC Arc Flash Detector Phase C operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 89 of 107 7SR220 Settings Guide Description Range Default AFD Zone 4 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 4 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 5 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 5 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 6 Flash Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- AFD Zone 6 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- User Output 1 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- User Output 1 operated --User Output 32 User Output 32 operated En100 Life Raised when the En100 is communicating correctly with the Protection CPU Unrestricted Page 90 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default En100 Error Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Raised when the En100 has detected an Error IEC61850 Configured Raised when the En100 and Protection CPU are configured for IEC 61850. En100 Ch1 Link Down Raised when En100 Ch 1 Link Down En100 Ch2 Link Down Raised when En100 Ch 2 Link Down Forward P/F The Phase fault is in the forward direction. Note this output is presented EVEN when relay elements are set to be nondirectional. Reverse P/F The Phase fault is in the reverse direction. Note this output is presented EVEN when relay elements are set to be nondirectional. Forward E/F The fault is in the forward direction. Note this output is presented EVEN when relay elements are set to be nondirectional. Reverse E/F The fault is in the reverse direction. Note this output is presented EVEN when relay elements are set to be nondirectional. Forward SEF The fault is in the forward direction. Note this output is presented EVEN when relay elements are set to be nondirectional. Unrestricted (c)2018 Siemens Protection Devices Limited Page 91 of 107 7SR220 Settings Guide Description Range Default Reverse SEF Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) BO8 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- The fault is in the reverse direction. Note this output is presented EVEN when relay elements are set to be nondirectional. Manual Close CB Close pulse due to Manual close being issued 79 AR Close CB Close pulse due to auto-reclose sequence 79 Trip & Reclose Indicates the Trip & Reclose sequence being performed 79 Trip & Lockout Indicates the Trip & Lockout sequence being performed 79 Lockout Indicates the auto-recloser is in the Lockout state 79 Out Of Service Indicates the auto-recloser is out of service 79 In Service Indicates the auto-recloser is in service 79 In Progress Indicates an auto-reclose sequence is in progress Unrestricted Page 92 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default 79 Block Extern Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Man Override Sync Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 79 Override Sync Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 Live Line Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 Live bus Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Indicates that Extern for the current shot has been selected to be delayed. (This may be used to block external tripping elements in the same way as the internal protection elements are blocked to achieve Instantaneous / Delayed operation.) 79 CB Fail To Close Indicates the CB was not closed at the end of the Close Pulse 79 Close Onto Fault Indicates an element starter or trip operated during the Close Pulse 79 Successful AR Indicates that after a reclose and at the end of the Reclaim time the CB was closed and there were no auto-reclose trip elements operated. (This is issued for 2 secs) Successful Man Close Indicates that after a manual close and at the end of the Reclaim time the CB was closed and there were no autoreclose trip elements operated. (This is issued for 2 secs) Unrestricted (c)2018 Siemens Protection Devices Limited Page 93 of 107 7SR220 Settings Guide Description Range Default 25 Line U/V Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 Bus U/V Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 Diff Voltage Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 Voltage Check Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 In Sync Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 CS In Progress Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 SS In Progress Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 COZ In Progress Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- 25 System Split LO Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Unrestricted Page 94 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Hot Line Working Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Active Exp Pulse Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Active Imp Pulse Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Reactive Exp Pulse Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Indicates that Hot LineWorking functionality has been selected Inst Prot'n Out Indicates that the protection elements selected to be Instantaneous elements are switched out E/F Out Indicates that the instantaneous protection elements are switched out. SEF Out Indicates that the SEF protection elements are switched out New Wave Stored The waveform recorder has stored new information Note: this is a pulsed output New Fault Stored The fault recorder has stored new information Note: this is a pulsed output Unrestricted (c)2018 Siemens Protection Devices Limited Page 95 of 107 7SR220 Settings Guide Description Range Default Reactive Imp Pulse Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Out Of Service Mode Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Indicates the relay is in Out Of Service Mode Local Mode Indicates the relay is in Local Mode Remote Mode Indicates the relay is in Remote Mode BI 1 Operated DC Binary Input 1 has operated BI 2 Operated DC Binary Input 2 has operated BI 3 Operated DC Binary Input 3 has operated BI 4 Operated DC Binary Input 4 has operated BI 5 Operated DC Binary Input 5 has operated Unrestricted Page 96 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default BI 6 Operated Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- DC Binary Input 6 has operated BI 7 Operated DC Binary Input 7 has operated BI 8 Operated DC Binary Input 8 has operated BI 9 Operated DC Binary Input 9 has operated BI 10 Operated DC Binary Input 10 has operated BI 11 Operated DC Binary Input 11 has operated BI 12 Operated DC Binary Input 12 has operated BI 13 Operated DC Binary Input 13 has operated E1 Quick Logic equation 1 operated Unrestricted (c)2018 Siemens Protection Devices Limited Page 97 of 107 7SR220 Settings Guide Description Range Default E2 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Quick Logic equation 2 operated E3 Quick Logic equation 3 operated E4 Quick Logic equation 4 operated E5 Quick Logic equation 5 operated E6 Quick Logic equation 6 operated E7 Quick Logic equation 7 operated E8 Quick Logic equation 8 operated E9 Quick Logic equation 9 operated E10 Quick Logic equation 10 operated Unrestricted Page 98 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default E11 Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14, V1, V2, V3, V4, V5, V6, V7, V8, V9, V10, V11, V12, V13, V14, V15, V16 ) ------------------------------------------- BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 ------------------------------------------- BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 ------------------------------------------- BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 -------------- BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 -------------- Quick Logic equation 11 operated E12 Quick Logic equation 12 operated E13 Quick Logic equation 13 operated E14 Quick Logic equation 14 operated E15 Quick Logic equation 15 operated E16 Quick Logic equation 16 operated Trip Contacts Assigns Output Contact as trip contact for fault trigger Hand Reset Outputs Assigns Output Contact as hand reset contact Pickup Outputs Selects which outputs can operate because a pickup condition exists Pulsed Outputs Selects which outputs are pulsed. The pulse width is set by the Min Operate Time setting for each output 3.13.2. Binary Output Config (Variants may differ) Description Range Default Trip Contacts Combination of ( BO1, BO2, BO3, BO4, BO5, BO6, BO7, BO8, BO9, BO10, BO11, BO12, BO13, BO14 ) -------------- The Binary Outputs selected by this setting are classed as Trip contacts. (When any of these BOs operate the Trip LED is lit, CB Fail is started, if enabled, & a Fault Record is stored) Unrestricted (c)2018 Siemens Protection Devices Limited Page 99 of 107 7SR220 Settings Guide Description Range Default Hand Reset Outputs Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) -------------- 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0s 0, 0.01 ... 59, 60 0s 0, 0.01 ... 59, 60 0s 0, 0.01 ... 59, 60 0s 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s 0, 0.01 ... 59, 60 0.1 s Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) -------------- Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) -------------- Range Default Relays selected, as Hand Reset will remain latched until manually reset from front panel or via communications link or by removing DC Supply. By default relays are Self Resetting and will reset when the driving signal is removed. Min Operate Time 1 Minimum operate time of output relay if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 2 Minimum operate time of output relay 2 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 3 Minimum operate time of output relay 3 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 4 Minimum operate time of output relay 4 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 5 Minimum operate time of output relay 5 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 6 Minimum operate time of output relay 6 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 7 Minimum operate time of output relay 7 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 8 Minimum operate time of output relay 8 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 9 Minimum operate time of output relay 9 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 10 Minimum operate time of output relay 10 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 11 Minimum operate time of output relay 11 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 12 Minimum operate time of output relay 12 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 13 Minimum operate time of output relay 13 if set to self reset, if also set to be pulsed then this is the pulse width Min Operate Time 14 Minimum operate time of output relay 14 if set to self reset, if also set to be pulsed then this is the pulse width Pickup Outputs Selects which outputs can operate because a pickup condition exists Pulsed Outputs Selects which outputs are pulsed. The pulse width is set by the Min Operate Time setting for each output 3.13.3. LED Config Description Unrestricted Page 100 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Self Reset LEDs Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) 1, 9, 10, 11, 12, 13, 14 Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) -------------- Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Combination of ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 ) 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Description Range Default Gn P/F Pickups Combination of ( 51-1, 51-2, 51-3, 51-4, 50-1, 50-2, 50-3, 50-4 ) 51-1, 51-2, 51-3, 51-4, 50-1, 50-2, 50-3, 50-4 Combination of ( 51N-1, 51N-2, 51N-3, 51N-4, 50N-1, 50N-2, 50N3, 50N-4, 51G-1, 51G-2, 51G-3, 51G-4, 50G-1, 50G-2, 50G-3, 50G4) 51N-1, 51N-2, 51N-3, 51N-4, 50N-1, 50N-2, 50N-3, 50N-4, 51G-1, 51G-2, 51G-3, 51G-4, 50G-1, 50G-2, 50G-3, 50G-4 Combination of ( 51SEF-1, 51SEF2, 51SEF-3, 51SEF-4, 50SEF-1, 50SEF-2, 50SEF-3, 50SEF-4, 64H ) 51SEF-1, 51SEF-2, 51SEF-3, 51SEF-4, 50SEF-1, 50SEF-2, 50SEF-3, 50SEF-4, 64H Combination of ( 27/59-1, 27/59-2, 27/59-3, 27/59-4, Vx 27/59, 47-1, 47-2, 59NIT, 59NDT ) 27/59-1, 27/59-2, 27/59-3, 27/59-4, Vx 27/59, 47-1, 47-2, 59NIT, 59NDT Combination of ( 81-1, 81-2, 81-3, 81-4, 81-5, 81-6 ) 81-1, 81-2, 81-3, 81-4, 81-5, 81-6 Combination of ( 46IT, 46DT, 37-1, 37-2, 37G-1, 37G-2, 37SEF-1, 37SEF-2 ) 46IT, 46DT, 371, 37-2, 37G-1, 37G-2, 37SEF-1, 37SEF-2 LEDs selected, as Self Reset will automatically reset when the driving signal is removed. By default all LEDs are Hand Reset and must be manually reset either locally via the front fascia or remotely via communications. PU Self Reset LEDs LEDs selected, as Self Reset will automatically reset when the driving signal is removed. By default all PU LEDs are Self Reset. Green LEDs Selects which LEDs will be green when driven Red LEDs Selects which LEDs will be red when driven PU Green LEDs Selects which LEDs will be green when driven by a pickup PU Red LEDs Selects which LEDs will be red when driven by a pickup 3.13.4. Pickup Config When any of the selected pickups operate General Pickup is driven. Gn E/F Pickups As Above Gn SEF/REF Pickups As Above Gn Voltage Pickups As Above Gn Freq Pickups As Above Gn Misc Pickups As Above 3.14. Maintenance Unrestricted (c)2018 Siemens Protection Devices Limited Page 101 of 107 7SR220 Settings Guide 3.14.1. CB Counters Description Range Default Gn CB Total Trip Count Disabled, Enabled Disabled 0, 1 ... 9999, 10000 100 Disabled, Enabled Disabled Disabled, Enabled Disabled 0, 1 ... 9999, 10000 100 0, 1 ... 9999, 10000 100 0, 1 ... 9999, 10000 100 0, 1 ... 9999, 10000 100 Disabled, Enabled Disabled 0, 1 ... 9999, 10000 100 Disabled, Enabled Disabled 0, 1 ... 9999, 10000 100 Disabled, Enabled Disabled 0, 1 ... 9999, 10000 10 Range Default Selects whether the CB Total Trip Count counter is enabled Gn CB Total Trip Count Target Selects the number of CB trips allowed before CB Total Trip Count counter output operates Gn CB Total Trip Count Reset Resets CB Total Trip Count counter Gn CB Total Trip Manual Open Selects whether the CB Total Trip Manual Open is enabled Gn CB Phase Trip Counters Selects whether the CB Phase Trip Counters is enabled Gn CB Ph A Trip Count Target Selects the number of CB trips allowed before CB Ph A Trip Count counter output operates Gn CB Ph B Trip Count Target Selects the number of CB trips allowed before CB Ph B Trip Count counter output operates Gn CB Ph C Trip Count Target Selects the number of CB trips allowed before CB Ph C Trip Count counter output operates Gn CB E/F Trip Count Target Selects the number of CB trips allowed before CB E/F Trip Count counter output operates Gn CB Delta Trip Count Selects whether the CB Delta Trip Count counter is enabled Gn CB Delta Trip Count Target Selects the number of CB trips allowed before CB Delta Trip Count counter output operates Gn CB Delta Trip Count Reset Resets CB Delta Trip Count counter Gn CB Count To AR Block Selects whether the CB Count To AR Block counter is enabled Gn CB Count To AR Block Target Selects the number of CB trips allowed before CB Count To AR Block counter output operates. While count is above target the Autorecloser will only perform 1 x Delayed Shot and Lockout Gn CB Count To AR Block Reset Resets CB Count To AR Block counter Gn CB Freq Ops Count Selects whether the CB Frequent Operations Counter is enabled Gn CB Freq Ops Count Target Selects the number of CB trips allowed before CB Frequent Operations Counter output operates. While count is above target the Autorecloser will only perform 1 x Delayed Shot and Lockout Gn CB Freq Ops Count Reset Resets CB Frequent Operations Counter 3.14.2. I^2T CB Wear Description Unrestricted Page 102 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn I^2t Counter Disabled, Enabled Disabled 10, 11 ... 99000, 100000 10 MA^2 s 0, 0.001 ... 0.199, 0.2 0.02 s 0, 0.001 ... 0.199, 0.2 0.04 s Description Range Default Start Types(s) Power On, Expected, Unexpected All 0, ...10000 100 Description Range Default Data Log Period 5, 6, 7, 8, 9, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 5 min 1, 2 ... 23, 24 24 hrs Fixed, Peak, Rolling Fixed Description Range Default Gn P/F Trig Storage Combination of ( 51-1, 51-2, 51-3, 51-4, 50-1, 50-2, 50-3, 50-4 ) 51-1, 51-2, 51-3, 51-4, 50-1, 50-2, 50-3, 50-4 Combination of ( 51N-1, 51N-2, 51N-3, 51N-4, 50N-1, 50N-2, 50N3, 50N-4, 51G-1, 51G-2, 51G-3, 51G-4, 50G-1, 50G-2, 50G-3, 50G4) 51N-1, 51N-2, 51N-3, 51N-4, 50N-1, 50N-2, 50N-3, 50N-4, 51G-1, 51G-2, 51G-3, 51G-4, 50G-1, 50G-2, 50G-3, 50G-4 Selects whether the I^2t CB Wear monitor is enabled Gn Alarm Limit Sets limit before alarm is issued Gn Separation Time Sets the time for CB mechanism to start moving, time before contacts start to separate Gn Clearance Time Time for CB to clear fault Reset I^2t Count Reset the CB wear count 3.14.3. START COUNT Selects which type of start-up Start Count Target Selects number of times star-up has occurred before output operatest 3.15. Data Storage 3.15.1. Demand Data/Log Selects period between stored samples Clear Data Log Clear the Data Log Gn Demand Window The time window over which the Min, Max and Mean values are calculated. Gn Demand Window Type Method used to calculate Demand values. Gn Demand Reset Reset all Demand values 3.15.2. Waveform Storage Select which elements trigger a waveform record Gn E/F Trig Storage As Above Unrestricted (c)2018 Siemens Protection Devices Limited Page 103 of 107 7SR220 Settings Guide Description Range Default Gn SEF/REF Trig Storage Combination of ( 51SEF-1, 51SEF2, 51SEF-3, 51SEF-4, 50SEF-1, 50SEF-2, 50SEF-3, 50SEF-4, 64H ) 51SEF-1, 51SEF-2, 51SEF-3, 51SEF-4, 50SEF-1, 50SEF-2, 50SEF-3, 50SEF-4, 64H Combination of ( 46IT, 46DT, 37-1, 37-2, 49 Trip, 49 Alarm, 37G-1, 37G-2, 37SEF-1, 37SEF-2 ) ---------- Combination of ( 27/59-1, 27/59-2, 27/59-3, 27/59-4, Vx 27/59, 47-1, 47-2, 59NIT, 59NDT ) --------- Combination of ( 81-1, 81-2, 81-3, 81-4, 81-5, 81-6 ) ------ Combination of ( AFD-1, AFD-2, AFD-3, AFD-4, AFD-5, AFD-6) ------ 10, 20, 30, 40, 50, 60, 70, 80, 90 20 % 10 Rec x 1 Sec, 5 Rec x 2 Sec, 2 Rec x 5 Sec, 1 Rec x 10 Sec 10 Rec x 1 Sec Description Range Default Gn Max Fault Rec Time 0, 1 ... 59900, 60000 2000 ms Range Default Description Range Default Gn Active Exp Energy Unit 1kWh, 10kWh, 100kWh, 1MWh, 10MWh, 100MWh 10 kWh Gn Active Imp Energy Unit 1kWh, 10kWh, 100kWh, 1MWh, 10MWh, 100MWh 10 kWh Gn Reactive Exp Energy Unit 1kVArh, 10kVArh, 100kVArh, 1MVArh, 10MVArh, 100MVArh 10 kVArh As Above Gn Misc Current Storage As Above Gn Voltage Trig Storage As Above Gn Freq Trig Storage As Above Gn AFD Trig Storage As Above Pre-trigger Storage Select Percentage of waveform record stored before the fault is triggered Record Duration Select waveform record duration Trigger Waveform Trigger waveform storage Clear Waveforms Clear all stored waveform records 3.15.3. Fault Storage Maximum time Fault record information will be stored and classed as same fault Clear Faults Clear all stored fault records 3.15.4. Event Storage Description Clear Events Clear all stored event records 3.15.5. Energy Storage Unrestricted Page 104 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default Gn Reactive Imp Energy Unit 1kVArh, 10kVArh, 100kVArh, 1MVArh, 10MVArh, 100MVArh 10 kVArh Description Range Default Fault Locator Disabled, Enabled Disabled Line Angle 0 Deg to 90 Deg 75 Deg EF Comp Z0/Z1 Ratio 0 to 10 2.5 EF Comp Z0 Angle 0 Deg to 359 Deg 75 Deg Z+ Impedance 0.1 Ohms to 250 Ohms 10 Ohms Sec'y Z+ Per Unit Distance 0.005 Ohms to 5 Ohms 0.5 Ohm Display Units Percent, kilometres, miles Percent System Earthing Normal, Compensated Normal Gn U0/U1 Ratio 0 to 1 0.1 Gn Freq FL Inhibits 6 Bit Binary 81-1, 81-2, 81-3, 81-4, 81-5, 81-6 Gn Freq FL Inhibits 13 Bit Binary 49, 46IT, 46DT, 27/59-1, 27/59-2, 27/59-3, 27/59-4, 47-1, 47-2, 59NIT, 59NDT, 46BC, Vx 27/59 Data Log Selects whether the Data Logger is enabled 3.15.6. Fault Locator Unrestricted (c)2018 Siemens Protection Devices Limited Page 105 of 107 7SR220 Settings Guide 3.15.7. Communications Description Range Default Station Address 0, 1 ... 65533, 65534 1 OFF, IEC60870-5-103, MODBUSRTU, DNP3 IEC60870-5-103 75, 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 19200 NONE, ODD, EVEN EVEN COM1-RS485 Mode Local, Remote, Local Or Remote Remote COM2-USB Protocol IEC60870-5-103 IEC60870-5-103 COM2-USB Mode Local Local COM3 Protocol OFF, IEC60870-5-103, MODBUSRTU, DNP3 IEC60870-5-103 75, 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 19200 NONE, ODD, EVEN EVEN LIGHT OFF, LIGHT ON LIGHT OFF OFF, ON OFF COM3 Mode Local, Remote, Local Or Remote Remote COM4 Protocol OFF, IEC60870-5-103, MODBUSRTU, DNP3 OFF 75, 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 19200 NONE, ODD, EVEN EVEN LIGHT OFF, LIGHT ON LIGHT OFF OFF, ON OFF COM4 Mode Local, Remote, Local Or Remote Remote LAN Protocol OFF, IEC60870-5-103 IEC60870-5-103 Disabled, Enabled Disabled 0, 1 ... 65533, 65534 0 IEC 60870-5-103 Station Address COM1-RS485 Protocol Selects protocol to use for COM1-RS485 COM1-RS485 Baud Rate Sets the communications baud rate for COM1-RS485 COM1-RS485 Parity Selects whether parity information is used Selects protocol to use for COM2-USB Selects protocol to use for COM3 COM3 Baud Rate Sets the communications baud rate for COM3 COM3 Parity Selects whether parity information is used COM3 Line Idle Selects the communications line idle sense COM3 Data Echo Enables echoing of data from RX port to TX port when operating relays in a Fibre Optic ring configuration Selects protocol to use for COM4 COM4 Baud Rate Sets the communications baud rate for COM4 COM4 Parity Selects whether parity information is used COM4 Line Idle Selects the communications line idle sense COM4 Data Echo Enables echoing of data from RX port to TX port when operating relays in a Fibre Optic ring configuration Selects protocol to use for LAN port DNP3 Unsolicited Events Allows unsolicited event support in the relay. When Enabled, unsolicited event transmission can be controlled by the Master. When Disabled, Master requests are ignored. DNP3 Destination Address The address of the master to which unsolicited events will be sent. Unrestricted Page 106 of 107 (c) 2013 Siemens Protection Devices Limited 7SR220 Settings Guide Description Range Default DNP3 Application Timeout 5, 6 ... 299, 300 10 s The address of the master to which unsolicited events will be sent. Unrestricted (c)2018 Siemens Protection Devices Limited Page 107 of 107 7SR210 Non-Directional Relay 7SR220 Directional Relay Performance Specification Unrestricted The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Performance Specification Document Release History This document is issue 2017/12 The list of revisions up to and including this issue is: 2011/05 First issue. 2011/08 Typographical revisions and added data. 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/05 Amended data and reference to EATS 48-4, classes ESI 1 and ESI 2 removed. 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. Software Revision History 2011/05 2435H85008R7a-7a (7SR210) First Release 2435H85009R7a-7a (7SR220) 2013/01 2435H85008R7c-7b (7SR210) 2435H85009R7c-7b (7SR220) 2014/06 2435H85008R7f-7d (7SR210) 2435H85009R7f-7d (7SR220) 2015/06 2435H85008R8a-7f (7SR210) 2435H85009R8a-7f (7SR220) 2016/02 2435H85008R8b-7f (7SR210) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Added Fault Locator feature and Check Sync feature. Fault data transmitted over 103. Additional communications data, control features, meters. Added Power Factor Meters, Load Blinding feature, Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. 2435H85009R8b-7f (7SR220) 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Unrestricted Page 2 of 68 Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing, 67SEF Compensated Network, 67SEF Wattmetric. Increased I/O. Event Data on LCD. (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification Contents Software Revision History ................................................................................................................ 2 Section 1: Common Functions ......................................................................................................... 8 1.1 General ................................................................................................................................ 8 1.1.1 CE Conformity ......................................................................................................... 8 1.1.2 Reference ................................................................................................................ 8 1.1.3 Dimensions .............................................................................................................. 8 1.1.4 Weights ................................................................................................................... 9 1.2 Energising Quantities ......................................................................................................... 10 1.2.1 Auxiliary Power Supply .......................................................................................... 10 1.2.2 AC Current............................................................................................................. 11 1.2.3 AC Voltage ............................................................................................................ 12 1.2.4 Binary (Digital) Outputs .......................................................................................... 13 1.2.5 Binary (Digital) Inputs ............................................................................................. 14 1.3 Functional Performance ..................................................................................................... 15 1.3.1 Instrumentation ...................................................................................................... 15 1.3.2 USB Data Communication Interface ....................................................................... 15 1.3.3 Fibre Optic Serial Data Communication Interface (Optional Rear Mounted Port) ..... 15 1.3.4 RS485 Data Communication Interface (Standard Rear Port) .................................. 15 1.3.5 RS485 Data Communication Interface (Optional Rear Mounted Port) ..................... 15 1.3.6 RS232 Data Communication Interface (Optional Rear Mounted Port) ..................... 15 1.3.7 Fibre Optic Ethernet Data Communication Interface (IEC 61850 Option) ................ 16 1.3.8 Electrical Ethernet Data Communication Interface (IEC 61850 Option) ................... 16 1.3.9 Real Time Clock .................................................................................................... 16 1.4 Environmental Performance ............................................................................................... 17 1.4.1 General.................................................................................................................. 17 1.4.2 Emissions .............................................................................................................. 18 1.4.3 Immunity ................................................................................................................ 18 1.4.4 Mechanical ............................................................................................................ 20 Section 2: Protection Functions..................................................................................................... 21 2.1 27/59 Phase Under/Over Voltage ....................................................................................... 21 2.1.2 Reference .............................................................................................................. 21 2.1.3 Operate and Reset Level ....................................................................................... 21 2.1.4 Operate and Reset Time ........................................................................................ 21 2.2 27/59 Vx Under/Over Voltage ............................................................................................. 22 2.2.1 Reference .............................................................................................................. 22 2.2.2 Operate and Reset Level ....................................................................................... 22 2.2.3 Operate and Reset Time ........................................................................................ 22 2.3 32 Power............................................................................................................................ 23 2.3.1 Reference .............................................................................................................. 23 2.3.2 Operate and Reset Level ....................................................................................... 23 2.3.3 Operate and Reset Time ........................................................................................ 23 2.3.4 Operate Threshold ................................................................................................. 23 2.4 32S Sensitive Power .......................................................................................................... 24 2.4.1 Reference .............................................................................................................. 24 2.4.2 Operate and Reset Level ....................................................................................... 24 2.4.3 Operate and Reset Time ........................................................................................ 24 2.4.4 Operate Threshold ................................................................................................. 24 2.5 37 Undercurrent ................................................................................................................. 25 2.5.1 Reference .............................................................................................................. 25 2.5.2 Operate and Reset Level ....................................................................................... 25 2.5.3 Operate and Reset Time ........................................................................................ 25 2.6 37G & 37SEF Undercurrent................................................................................................ 26 2.6.1 Reference .............................................................................................................. 26 2.6.2 Operate and Reset Level ....................................................................................... 26 Unrestricted (c) 2013 Siemens Protection Devices Limited Page 3 of 68 7SR21 & 7SR22 Performance Specification 2.6.3 Operate and Reset Time ........................................................................................ 26 2.7 46NPS Negative Phase Sequence Overcurrent .................................................................. 27 2.7.1 Reference (46DT) .................................................................................................. 27 2.7.2 Operate and Reset Level (46DT)............................................................................ 27 2.7.3 Operate and Reset Time (46DT) ............................................................................ 27 2.7.4 Reference (46IT).................................................................................................... 27 2.7.5 Operate and Reset Time (46IT).............................................................................. 28 2.8 47 Negative Phase Sequence Voltage................................................................................ 29 2.8.1 Reference (47)....................................................................................................... 29 2.8.2 Operate and Reset Level (47) ................................................................................ 29 2.8.3 Operate and Reset Time (47)................................................................................. 29 2.9 49 Thermal Overload.......................................................................................................... 30 2.9.1 Reference .............................................................................................................. 30 2.9.2 Operate and Reset Level ....................................................................................... 30 2.9.3 Operate and Reset Time ........................................................................................ 30 2.10 50 Instantaneous Overcurrent ............................................................................................ 32 2.10.1 Reference .............................................................................................................. 32 2.10.2 Operate and Reset Level ....................................................................................... 32 2.10.3 Operate and Reset Time ........................................................................................ 32 2.11 50G Instantaneous Measured Earth Fault........................................................................... 33 2.11.1 Reference .............................................................................................................. 33 2.11.2 Operate and Reset Level ....................................................................................... 33 2.11.3 Operate and Reset Time ........................................................................................ 33 2.12 50N Instantaneous Derived Earth Fault .............................................................................. 34 2.12.1 Reference .............................................................................................................. 34 2.12.2 Operate and Reset Level ....................................................................................... 34 2.12.3 Operate and Reset Time ........................................................................................ 34 2.13 50SEF Instantaneous Sensitive Earth Fault ........................................................................ 35 2.13.1 Reference .............................................................................................................. 35 2.13.2 Operate and Reset Level ....................................................................................... 35 2.13.3 Operate and Reset Time ........................................................................................ 35 2.14 51 Time Delayed Overcurrent ............................................................................................. 36 2.14.1 Reference .............................................................................................................. 36 2.14.2 Operate and Reset Level ....................................................................................... 36 2.14.3 Operate and Reset Time ........................................................................................ 37 2.15 51G Time Delayed Measured Earth Fault ........................................................................... 41 2.15.1 Reference .............................................................................................................. 41 2.15.2 Operate and Reset Level ....................................................................................... 41 2.15.3 Operate and Reset Time ........................................................................................ 42 2.16 51N Time Delayed Derived Earth Fault............................................................................... 43 2.16.1 Reference .............................................................................................................. 43 2.16.2 Operate and Reset Level ....................................................................................... 43 2.16.3 Operate and Reset Time ........................................................................................ 44 2.17 51SEF Time Delayed Sensitive Earth Fault ........................................................................ 45 2.17.1 Reference .............................................................................................................. 45 2.17.2 Operate and Reset Level ....................................................................................... 45 2.17.3 Operate and Reset Time ........................................................................................ 46 2.18 51V Voltage Controlled Overcurrent (Ph-Ph) ...................................................................... 47 2.18.1 Reference .............................................................................................................. 47 2.18.2 Operate and Reset Level ....................................................................................... 47 2.19 55 Power Factor ................................................................................................................. 48 2.19.1 Reference .............................................................................................................. 48 2.19.2 Operate and Reset Level ....................................................................................... 48 2.19.3 Operate and Reset Time ........................................................................................ 48 2.19.4 Operate Threshold ................................................................................................. 48 2.20 59N Neutral Voltage Displacement ..................................................................................... 49 2.20.1 Reference (59NDT)................................................................................................ 49 Unrestricted Page 4 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.20.2 Operate and Reset Level (59NDT) ......................................................................... 49 2.20.3 Operate and Reset Time (59NDT).......................................................................... 49 2.20.4 Reference (59NIT) ................................................................................................. 49 2.20.5 Operate and Reset Level (59NIT)........................................................................... 50 2.20.6 Operate and Reset Time (59NIT) ........................................................................... 50 2.21 64H Restricted Earth Fault Protection................................................................................. 51 2.21.1 Reference .............................................................................................................. 51 2.21.2 Operate and Reset Level ....................................................................................... 51 2.21.3 Operate and Reset Time ........................................................................................ 51 2.22 67/67N Directional Overcurrent & Earth Fault ..................................................................... 52 2.22.1 Reference .............................................................................................................. 52 2.22.2 Operate Angle ....................................................................................................... 52 2.22.3 Operate Threshold ................................................................................................. 52 2.22.4 Operate and Reset Time ........................................................................................ 52 2.23 Directional SEF Wattmetric................................................................................................. 53 2.23.1 Reference .............................................................................................................. 53 2.23.2 Operate and Reset Level ....................................................................................... 53 2.23.3 Operate and Reset Time ........................................................................................ 53 2.24 81 Under/Over Frequency .................................................................................................. 54 2.24.1 Reference .............................................................................................................. 54 2.24.2 Operate and Reset Level ....................................................................................... 54 2.24.3 Operate and Reset Time ........................................................................................ 54 2.25 50 AFD ARC Flash Detector............................................................................................... 55 (Refer to 7XG31 Technical Manual for performance characteristics) .......................................... 55 2.25.1 Reference .............................................................................................................. 55 2.25.2 Operate and Reset Level ....................................................................................... 55 2.25.3 Operate and Reset Time ........................................................................................ 55 Section 3: Supervision Functions .................................................................................................. 56 3.1 46BC & 46BC U/C Broken Conductor................................................................................. 56 3.1.1 Reference .............................................................................................................. 56 3.1.2 Operate and Reset Level ....................................................................................... 56 3.1.3 Operate and Reset Time ........................................................................................ 56 3.2 50BF & 50BF-I4 Circuit Breaker Fail ................................................................................... 57 3.2.1 Reference .............................................................................................................. 57 3.2.2 Operate and Reset Level ....................................................................................... 57 3.2.3 Operate and Reset Time ........................................................................................ 57 3.3 60CTS & CTS-I Current Transformer Supervision............................................................... 58 3.3.1 Reference .............................................................................................................. 58 3.3.2 Current & Voltage Threshold .................................................................................. 58 3.3.3 Operate and Reset Time ........................................................................................ 58 3.4 60VTS Voltage Transformer Supervision ............................................................................ 59 3.4.1 Reference .............................................................................................................. 59 3.4.2 Operate and Reset Level ....................................................................................... 59 3.4.3 Operate and Reset Time ........................................................................................ 60 3.5 74TCS Trip Circuit Supervision........................................................................................... 61 3.5.1 Reference .............................................................................................................. 61 3.5.2 Operate and Reset Time ........................................................................................ 61 3.6 81HBL2 Inrush Detector ..................................................................................................... 62 3.6.1 Reference .............................................................................................................. 62 3.6.2 Operate and Reset Level ....................................................................................... 62 3.6.3 Operate and Reset Time ........................................................................................ 62 3.7 81HBL5 Over Fluxing Detector ........................................................................................... 63 3.7.1 Reference .............................................................................................................. 63 3.7.2 Operate and Reset Level ....................................................................................... 63 3.7.3 Operate and Reset Time ........................................................................................ 63 3.8 Load Blinder (21LB - 3P) ................................................................................................... 64 3.8.1 Reference .............................................................................................................. 64 Unrestricted (c) 2013 Siemens Protection Devices Limited Page 5 of 68 7SR21 & 7SR22 Performance Specification 3.8.2 Operate Level ........................................................................................................ 64 3.8.3 Operate Angle ....................................................................................................... 64 3.9 Load Blinder (21LB - 1P) ................................................................................................... 65 3.9.1 Reference .............................................................................................................. 65 3.9.2 Operate Level ........................................................................................................ 65 3.9.3 Operate Angle ....................................................................................................... 65 Section 4: Control Functions.......................................................................................................... 66 4.1 Check Synchronising.......................................................................................................... 66 4.1.1 Reference .............................................................................................................. 66 4.1.2 Live/Dead Line/Bus Detector Elements .................................................................. 66 4.1.3 Line and Bus Undervoltage Elements..................................................................... 67 4.1.4 Voltage Difference ................................................................................................. 67 4.1.5 General Autoreclose Timers................................................................................... 67 4.1.6 CS/SS/COZ Line and Bus Phase Angle Difference ................................................ 67 4.1.7 CS/SS/COZ Slip Frequency ................................................................................... 67 4.1.8 CS/SS Timer.......................................................................................................... 67 4.1.9 Split Angle Detector ............................................................................................... 68 4.1.10 Split Slip Frequency Detector ................................................................................. 68 4.2 Live/Dead........................................................................................................................... 68 4.2.1 Reference .............................................................................................................. 68 4.2.2 Live/Dead Detector Elements ................................................................................. 68 Unrestricted Page 6 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification List of Figures Figure 2-1 Figure 2-2 Figure 2-3 Figure 2-4 Thermal Overload Protection Curves ............................................................................. 31 IEC IDMTL Curves (Time Multiplier = 1) ........................................................................ 38 ANSI IDMTL Operate Curves (Time Multiplier = 1)......................................................... 39 ANSI IDMTL Reset Curves (Time Multiplier = 1) ............................................................ 40 Unrestricted (c) 2013 Siemens Protection Devices Limited Page 7 of 68 7SR21 & 7SR22 Performance Specification Section 1: Common Functions 1.1 General 1.1.1 CE Conformity This product is CE compliant to relevant EU directives. 1.1.2 Reference This product complies with IEC 60255-3, IEC 60255-6 and IEC 60255-12. 1.1.2.1 Accuracy Reference Conditions This product has been tested under the following conditions, unless specifically stated otherwise. Parameter Value Auxiliary supply Nominal AC Current Nominal Frequency Nominal Ambient temperature 20 C 1.1.3 Dimensions Parameter Width Value E6 case 155.5 mm E8 case 207.5 mm E12 case 311.5 mm Height 177 mm Depth behind panel, including clearance for: Wiring 241.5 mm Fibre Optic 286.5 mm Ethernet enclosure 259.5 mm Depth below Ethernet variant for cables 75 mm Projection (from front of panel) 31 mm See appropriate case outline and panel drilling drawing, as specified in Diagrams and Parameters document, for complete dimensional specifications. Unrestricted Page 8 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 1.1.4 Weights Hardware Model 7SR2102 7SR2103 7SR2104 7SR2105 7SR2106 7SR2202 7SR2203 7SR2204 7SR2205 7SR2206 Typical Net Weight (kg) 4.2 4.6 4.8 8.4 8.4 4.8 4.9 5.3 8.4 8.4 NB: For relays supplied with additional (optional) communication interface devices, please add an additional 0.165 kg to the figures in the above table. For relays supplied with Ethernet interface (optional) please add 0.1 kg to the figures in the above table. Unrestricted (c) 2013 Siemens Protection Devices Limited Page 9 of 68 7SR21 & 7SR22 Performance Specification 1.2 Energising Quantities 1.2.1 Auxiliary Power Supply Nominal Operating Range MLFB Code (column 9) 30 V DC, 48 V DC, 110 V DC, 220 V DC 24 V DC to 290 V DC VAUX 1.2.1.1 24 V DC to 250 V DC 24 V DC to 290 V DC 100 V AC to 230 V AC 88 V AC to 242 V AC A, B M, N Burden (24 V DC to 250 V DC, 100 V AC to 230 V AC) PSU Attribute Watts (DC) Voltage (V) 24 48 60 110 125 220 250 Quiescent Relay (inc. PROT HEALTHY LED) 6.0 5.8 5.8 5.5 5.5 5.4 5.5 LCD backlight on 1.4 1.3 1.2 1.2 1.2 1.2 1.2 Per LED (Red) 0.04 0.03 0.03 0.03 0.03 0.03 0.03 Per LED (Yellow) 0.08 0.06 0.06 0.06 0.06 0.06 0.06 Per Binary Output 0.35 0.3 0.3 0.3 0.3 0.28 0.28 Optional IEC61850 2.6 2.5 2.4 2.4 2.4 2.4 2.4 Attribute VA (AC) Voltage (V) 100 110 115 120 200 230 Quiescent Relay (inc. PROT HEALTHY LED) 10.0 10.0 10.0 10.5 12.0 14.0 LCD backlight on 2.5 2.5 2.5 2.6 3.0 3.2 Per LED (Red) 0.06 0.06 0.06 0.06 0.06 0.07 Per LED (Yellow) 0.10 0.12 0.10 0.10 0.10 0.12 Per Binary Output 0.6 0.6 0.6 0.6 0.6 0.6 Optional IEC61850 5.0 5.0 5.0 5.0 4.5 4.5 1.2.1.2 Burden (30 V DC, 48 V DC, 110 V DC, 220 V DC) PSU Attribute 30 V DC 48 V DC 110 V DC 220 V DC Value Quiescent (typical) 6.0 W Quiescent (back light) 7.0 W Quiescent (typical) 5.5 W Quiescent (back light) 6.5 W Quiescent (typical) 6.5 W Quiescent (back light) 7.5 W Quiescent (typical) 7.5 W Quiescent (back light) 8.5 W Unrestricted Page 10 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 1.2.1.3 Operational Features Attribute Value 0% Dip Withstand Period Dip Immunity Acquisition Period Comments 100 ms 5 minutes Typical time after switch on to attain claimed immunity to dips NOTE: Dips in supply that fall below the minimum voltage for a period greater than the 0% Dip Withstand Period, will invoke a relay reset. During conditions of auxiliary input voltage variations which are not described (1) in section 1.4.3.1, the relay may enter a safety protection mode where a power supply shutdown occurs. This condition is designed to protect the power supply from damage as well as prevent internal relay faults from developing into dangerous situations. Once the relay has entered this safety mode, it may be necessary to reduce the auxiliary input voltage to zero volts for up to 30 seconds before re-application of the auxiliary supply will cause the relay to power up and operate normally. (1) Using fuses as on/off switches or allowing batteries to run at very low cell voltages for extended periods and then attempting to re-charge them are examples of such auxiliary supply conditions. 1.2.2 AC Current Nominal Measuring Range In 1 A, 5 A Phase and earth 80 x In fn 50 Hz, 60 Hz 47 Hz to 62 Hz Sample Rate 32 cycles / sec @ 50 Hz Note. 1 A and 5 A nominal inputs are user selectable on each model. Unrestricted (c) 2013 Siemens Protection Devices Limited Page 11 of 68 7SR21 & 7SR22 Performance Specification 1.2.2.1 Burden Value - Phase and Earth Attribute AC Burden 1.2.2.2 1A 5A 0.1 VA 0.3 VA Thermal Withstand Overload Current Overload Period Phase and Earth 1A 5A Continuous 3.0 xIn 10 minutes 3.5 xIn 5 minutes 4.0 xIn 3 minutes 5.0 xIn 2 minutes 6.0 xIn 3 seconds 57.7 A 202 A 2 seconds 70.7 A 247 A 1 second 100 A 350 A 1 cycle 700 A 2500 A 1.2.3 AC Voltage Nominal Operating Range Vn 63.5 V, 110 V 40 V rms to 160 V rms fn 50 Hz, 60 Hz 47 Hz to 62 Hz 1.2.3.1 Burden Attribute Value AC Burden 0.1 VA at 110 V Unrestricted Page 12 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 1.2.4 Binary (Digital) Outputs Contact rating to IEC 60255-0-2 Attribute Value Carry continuously 5 A AC or DC Make and carry (L/R 40 ms and V 300 V) Break ( 5 A and 300 V) for 0.5 s 20 A AC or DC for 0.2 s 30 A AC or DC AC resistive 1250 VA AC inductive 250 VA at p.f. 0.4 DC resistive 75 W DC inductive 30 W at L/R 40ms 50 W at L/R 10 ms Contact Operate / Release Time 7 ms / 3 ms Minimum number of operations 1000 at maximum load Minimum recommended load 0.5 W at minimum of 10 mA or 5 V Unrestricted (c) 2013 Siemens Protection Devices Limited Page 13 of 68 7SR21 & 7SR22 Performance Specification 1.2.5 Binary (Digital) Inputs Nominal VBI 1.2.5.1 Operating Range 19 V DC 17 V DC (minimum) to 290 V DC 88 V DC 74 V DC (minimum) to 290 V DC Performance Attribute Maximum DC current for operation Value VBI = 19 V 1.5 mA VBI = 88 V 1.5 mA Reset/Operate voltage ratio 90 % Response time < 7 ms Response time when programmed to energise an output relay contact (i.e. includes output relay operation) < 20 ms Sample Rate Every 5 ms The binary inputs are isolated from earth potential. They have a low minimum operate current and may be set for high speed operation. Where a binary input is both used to influence a control function (e.g. provide a tripping function) and it is considered to be susceptible to mal-operation due to capacitive currents, the external circuitry can be modified to provide immunity to such disturbances. To achieve immunity from AC interference, a BI pick-up delay of typically one-cycle can be applied. Unrestricted Page 14 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 1.3 Functional Performance 1.3.1 Instrumentation Instrument Value Reference Typical accuracy I Current 0.1In to 2.0In 1 % or 1 % In V Voltage 0.1Vn to 1.2Vn 1 % or 1 % Vn Power, real and apparent V = Vn, I 0.1 xIn, pf 0.8 3 % Pn, where Pn = Vn x In Power factor V = Vn, I 0.1 xIn, pf 0.8 0.05 pf 1.3.2 USB Data Communication Interface Attribute Value Physical layer Electrical Connectors USB-Type B 1.3.3 Fibre Optic Serial Data Communication Interface (Optional Rear Mounted Port) Attribute Value Physical layer Fibre-optic Connectors STTM (BFOC/2.5) Recommended fibre 62.5/125 mm glass fibre with ST connector Optical Wavelength 820 nm Launch power (into recommended fibre) -16 dBm Receiver sensitivity -24 dBm 1.3.4 RS485 Data Communication Interface (Standard Rear Port) Attribute Value Physical layer Electrical Connectors 4 mm Ring Crimp 1.3.5 RS485 Data Communication Interface (Optional Rear Mounted Port) Attribute Value Physical layer Electrical Connectors 4-way Plug 1.3.6 RS232 Data Communication Interface (Optional Rear Mounted Port) Attribute Value Physical layer Electrical Connectors 9-way D-plug Unrestricted (c) 2013 Siemens Protection Devices Limited Page 15 of 68 7SR21 & 7SR22 Performance Specification 1.3.7 Fibre Optic Ethernet Data Communication Interface (IEC 61850 Option) Attribute Value Physical layer Fibre-optic Connectors Duplex LC 100BaseF in acc. With IEEE802.3 Recommended fibre 62.5/125 mm glass fibre with Duplex-LC connector Transmission Speed 100 MBits/s Optical Wavelength 1300 nm Bridgeable distance 2 km 1.3.8 Electrical Ethernet Data Communication Interface (IEC 61850 Option) Attribute Value Physical layer Electrical Connectors RJ45 100BaseF in acc. With IEEE802.3 Transmission Speed 100 MBits/s Test Voltage (with regard to socket) 500 VAC 50 Hz Bridgeable distance 20 m 1.3.9 Real Time Clock 1.3.9.1 Internal Clock The specification below applies only while no external synchronisation signal (e.g. IRIG-B, IEC 60870-5-103) is being received. Attribute Value Accuracy (- 10 oC to + 55 oC) 1.3.9.2 100 ppm IRIG-B (Inter Range Instrumentation Group)-B Attribute Value Connector BNC Signal Type IRIG-B 120, 122 or 123 Applied signal level minimum 3 V, maximum 6 V, peak-to-peak Signal : carrier ratio 3:1 Impedance 4 kOhm *Cable impedance is irrelevant. The cable does not need to have a termination resistor fitted. Unrestricted Page 16 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 1.4 Environmental Performance 1.4.1 General 1.4.1.1 Temperature IEC 60068-2-1, IEC 60068-2-2 Type Level Operating range - 10 C to + 55 C Storage range - 25 C to + 70 C 1.4.1.2 Humidity IEC 60068-2-30, IEC 60068-2-78 Type Level Operational test (Indoor) 56 days at +40 C and 95 % relative humidity (r.h.) Operational test (Outdoor) 6 cycles at 24 h between +25 C (97% r.h.) and +55 C (93% r.h.) 1.4.1.3 Transient Overvoltage IEC 60255-5 Type Level Between all terminals and earth, or between any two independent circuits 5.0 kV, 1.2/50 ms 0.5j 1.4.1.4 Insulation IEC 60255-5 Type Level Between any terminal and earth Between independent circuits Across normally open contacts 1.4.1.5 2.5 kV AC RMS for 1 min 1.0 kV AC RMS for 1 min IP Ratings Type Installed with cover on Installed with cover removed Level IP 51 from front of relay IP 10 from rear of relay IP 20 from front of relay IP 10 from rear of relay Unrestricted (c) 2013 Siemens Protection Devices Limited Page 17 of 68 7SR21 & 7SR22 Performance Specification 1.4.2 Emissions IEC 60255-25 1.4.2.1 Radiated Radio Frequency Type Limits at 10 m, Quasi-peak 30 MHz to 230 MHz 40 dB(mV/m) 230 MHz to 10000 MHz 47 dB(mV/m) 1.4.2.2 Conducted Radio Frequency Limits Type Quasi-peak Average 0.15 MHz to 0.5 MHz 79 dB(mV) 66 dB(mV) 0.5 MHz to 30 MHz 73 dB(mV) 60 dB(mV) 1.4.3 1.4.3.1 Immunity Auxiliary DC Supply Variation Quantity Value Allowable superimposed ac component 12 % of DC voltage Allowable breaks/dips in supply (collapse to zero from nominal voltage) 20 ms 1.4.3.2 High Frequency Disturbance IEC 60255-22-1 Class III Type Level Common (longitudinal) mode 2.5 kV Series (transverse) mode 1.0 kV 1.4.3.3 Variation 5% Electrostatic Discharge IEC 60255-22-2 Class IV Type Level Variation Contact discharge 8.0 kV 5% Type Level Variation 80 MHz to 1000 MHz 10 V/m 5% 1.4.3.4 Radiated Immunity IEC 60255-22-3 Class III Unrestricted Page 18 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 1.4.3.5 Fast Transients IEC 60255-22-4 Class A (2002) Type Level Variation 5/50 ns 2.5 kHz repetitive 4 kV 5% Level Variation 4.0 kV 10 % or 1 mA 2.0 kV 10 % or 1 mA 1.0 kV No Data Loss 1.0 kV 10 % or 1 mA 1.0 kV* 10 % or 1 mA 1.4.3.6 Surge Immunity IEC 60255-22-5; IEC 61000-4-5 Type Analogue Inputs. Line to Earth. Case, Aux Power & I/O. Line to Earth. RS485 Comms Port. Line to Earth. Analogue Inputs. Line to Line. Case, Aux Power & I/O. Line to Line. * Note: 45 ms pick-up delay for DTL applied to binary inputs 1.4.3.7 Conducted Radio Frequency Interference IEC 60255-22-6 Type Level Variation 0.15 MHz to 80 MHz 10 V 5% 1.4.3.8 Magnetic Field with Power Frequency IEC 61000-4-8 level 5 100 A/m, (0.126 mT) continuous 1000 A/m, (1.26 mT) for 3 s 50 Hz Unrestricted (c) 2013 Siemens Protection Devices Limited Page 19 of 68 7SR21 & 7SR22 Performance Specification 1.4.4 1.4.4.1 Mechanical Vibration (Sinusoidal) IEC 60255-21-1 Class I Type Level Vibration response 0.5 gn Vibration endurance 1.0 gn 1.4.4.2 Variation 5% Shock and Bump IEC 60255-21-2 Class I Type Level Shock response 5 gn, Shock withstand 15 gn, 11 ms Bump test 10 gn, 16 ms 1.4.4.3 Variation 11 ms 5% Seismic IEC 60255-21-3 Class I Type Level Variation Seismic response 1 gn 5% 1.4.4.4 Mechanical Classification Type Durability Unrestricted Page 20 of 68 Level > 106 operations (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification Section 2: Protection Functions 2.1 27/59 Phase Under/Over Voltage 2.1.2 Reference Parameter Value Vs Setting 5, 5.5...199.5, 200 V hyst Hysteresis setting 0, 0.1... 80.0 % td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 2.1.3 Vop Operate and Reset Level Attribute Value Operate level 100 % Vs, 1 % or 0.25 V Reset level Overvoltage = (100 % - hyst) x Vop, 1 % or 0.25 V Undervoltage = (100 % + hyst) x Vop, 1 % or 0.25 V 1% Repeatability Variation 2.1.4 -10 C to +55 C fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute tbasicE Element basic operate time Value Overvoltage Undervoltage top 5% Switched from 0 to 1.1 x Vs: 73 ms 10 ms Switched from 0 to 2.0 xVs: 63 ms 10 ms 1.1 to 0.5 xVs: 58 ms 10 ms Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Disengaging time < 80 ms Unrestricted (c) 2013 Siemens Protection Devices Limited Page 21 of 68 7SR21 & 7SR22 Performance Specification 2.2 27/59 Vx Under/Over Voltage 2.2.1 Reference Parameter Setting Value 5, 5.5...199.5, 200 V Vs Guard Guard Setting 1, 1.5, ...199.5, 200 V hyst Hysteresis setting 0, 0.1... 80.0 % td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s Vs 2.2.2 Vop Operate and Reset Level Attribute Value Operate level 100 % Vs, 1 % or 0.25 V Reset level Overvoltage = (100 % - hyst) x Vop, 1 % or 0.25 V Undervoltage = (100 % + hyst) x Vop, 1 % or 0.25 V 1% Repeatability Variation 2.2.3 -10 C to +55 C fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute tbasicE Element basic operate time Value Overvoltage Undervoltage top 5% Switched from 0 to 1.1 xVs: 73 ms 10 ms Switched from 0 to 2.0 xVs: 63 ms 10 ms 1.1 to 0.5 xVs: 58 ms 10 ms Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Disengaging time < 80 ms Unrestricted Page 22 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.3 32 Power 2.3.1 Reference Parameter Value Ss 32-n Setting 0.05...2 x Sn td 32-n Delay setting 0.00 ... 14400 s 2.3.2 Sop Operate and Reset Level Attribute Value Operate level 100 % Ss, 5% or 2% Sn Reset level Variation 2.3.3 Over-power 95 % Sop Under-power 105 % Sop -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute Value Over-power 1.1 x Ss: 60 ms 10 ms tbasic Element basic operate time top Operate time following delay tbasic + td, 1 % or 10ms Disengaging time < 40 ms Under-power 2.3.4 2.0 x Ss: 45 ms 10ms 0.5 x Ss: 30 ms 10ms Operate Threshold Attribute Minimum levels for operation Value I 2.5 % In V 2.5% Vn Unrestricted (c) 2013 Siemens Protection Devices Limited Page 23 of 68 7SR21 & 7SR22 Performance Specification 2.4 32S Sensitive Power 2.4.1 Reference Ss Parameter 32S-n Setting Value 0.005...2 x Sn td 32S-n Delay setting 0.00 ... 14400 s 2.4.2 Sop Operate and Reset Level Attribute Value Operate level 100 % Ss, 5% or 2% Sn Reset level Variation 2.4.3 Over-power 95 % Sop Under-power 105 % Sop -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute tbasicE Element basic operate time Value Over-power Under-power top 2.4.4 1.1 x Ss: 60 ms 10 ms 2.0 x Ss: 45 ms 10ms 0.5 x Ss: 30 ms 10ms Operate time following delay tbasic + td, 1 % or 10ms Disengaging time < 40 ms Operate Threshold Attribute Minimum levels for operation Unrestricted Page 24 of 68 Value I 2.5 % In V 2.5% Vn (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.5 37 Undercurrent 2.5.1 Reference Parameter Value Is Setting 0.05, 0.10...5.0 xIn td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s Is 37-n U/I Guard Setting 0.05, 0.10...5.0 xIn 2.5.2 Iop Operate and Reset Level Attribute Value Operate level 100 % Is, 5 % or 1% In Reset level 105 % Iop Repeatability 1% Variation 2.5.3 -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute Value tbasic Element basic operate time 1.1 to 0.5 xIs: 35 ms, 10ms top Operate time following delay tbasic + td, 1 % or 10ms Repeatability 1 % or 10ms Overshoot time < 40 ms Disengaging time < 60 ms Unrestricted (c) 2013 Siemens Protection Devices Limited Page 25 of 68 7SR21 & 7SR22 Performance Specification 2.6 37G & 37SEF Undercurrent 2.6.1 Reference Parameter Value Is Setting 0.005, 0.10...5.0 xIn td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 2.6.2 Iop Operate and Reset Level Attribute Value Operate level 100 % Is, 5 % or 1% In Reset level 105 % Iop or Iop 0.1 % In Repeatability 1% Variation 2.6.3 -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute Value tbasic Element basic operate time 1.1 to 0.5 xIs: 35 ms, 10 ms top Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Overshoot time < 40 ms Disengaging time < 60 ms Unrestricted Page 26 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.7 46NPS Negative Phase Sequence Overcurrent 2.7.1 Reference (46DT) Parameter Value Is Setting 0.05, 0.06... 4.0xIn td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 2.7.2 Iop Operate and Reset Level (46DT) Attribute Value Operate level 100 % Is, 5 % or 1% In Reset level 95 % Iop Repeatability 1% Transient overreach (X/R 100) -5 % Variation 2.7.3 -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5% Operate and Reset Time (46DT) Attribute Value Switched from 0 to 2 xIs: 40 ms, 10 ms tbasic Element basic operate time top Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Overshoot time <40 ms Disengaging time < 60 ms 2.7.4 Switched from 0 to 5 xIs: 30 ms, 10 ms Reference (46IT) Parameter Value char Characteristic setting IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL Tm Time Multiplier setting 0.025, 0.050 ... 1.6 Is Setting 0.05, 0.06... 2.5xIn I Applied Current (for operate time) IDMTL 2 to 20 x Is td Delay setting 0, 0.01... 20 s tres Reset setting ANSI DECAYING, 0, 1... 60 s Unrestricted (c) 2013 Siemens Protection Devices Limited Page 27 of 68 7SR21 & 7SR22 Performance Specification Operate and Reset Level (46IT) Iop Attribute Value Operate level 105 % Is, 4 % or 1% In Reset level 95 % Iop Repeatability 1% Variation 2.7.5 -10 C to +55 C fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time (46IT) Attribute Value Starter operate time ( 2xIs) 35 ms, 10 ms char = IEC-NI, IEC-VI, IEC-EI, IEC-LTI top 5% Operate time char = ANSI-MI, ANSI-VI, ANSI-EI char = DTL t op = ANSI DECAYING tres [] -1 for char = e t op = e e e Tm , 5 % or 50 ms, IEC-NI : IEC-VI : IEC-EI : IEC-LTI : A [IsI ]P u + B u Tm , 5 % or 50 ms, u -1 u td, 1 % or 20 ms R [ ] I 2 Is -1 Tm , 5 % or 50 ms, for char = ANSI-MI : R = 4.85 ANSI-VI : R = 21.6 ANSI-EI : R = 29.1 tres, 1 % or 20 ms Repeatability 1 % or 20 ms Overshoot time < 40 ms Disengaging time < 60 ms Unrestricted Page 28 of 68 K = 0.14, a = 0.02 K = 13.5, a = 1.0 K = 80.0, a = 2.0 K = 120.0, a = 1.0 for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02 ANSI-VI : A = 19.61, B = 0.491, P = 2.0 ANSI-EI : A = 28.2, B = 0.1217, P = 2.0 tres = Reset time K I a Is (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.8 47 Negative Phase Sequence Voltage 2.8.1 Reference (47) Parameter Value Vs Setting 1, 1.5... 90 V Hyst. Hysteresis 0, 0.1... 80 % td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 2.8.2 Vop Operate and Reset Level (47) Attribute Value Operate level 100 % Vs, 2 % or 0.5 V Reset level (100 % - Hyst.) x Vop 1% or 0.25 V Repeatability 1% Variation 2.8.3 -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5% Operate and Reset Time (47) Attribute Value 0 to 2 xVs, 80 ms, 20 ms tbasic Element basic operate time top Operate time following delay tbasic + td, 2 % or 20 ms Repeatability 1 % or 20 ms Overshoot time < 40 ms Disengaging time < 60 ms 0 to 10 xVs, 55 ms, 20 ms Unrestricted (c) 2013 Siemens Protection Devices Limited Page 29 of 68 7SR21 & 7SR22 Performance Specification 2.9 49 Thermal Overload 2.9.1 Reference Parameter Value Is Overload setting 0.10, 0.11... 3 xIn t Time constant setting 1, 1.5... 1000 min 2.9.2 Iol Operate and Reset Level Attribute Value Overload level 100 % Is, 5 % or 1% In Reset level 95 % Iol Repeatability 1% Variation 2.9.3 top -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute Value Overload trip operate time i I 2 - I 2P u t = t ln i 2 2y i I - (k I B ) 5 % or 100 ms, (For I s range 0.3 xI n to 3 xI n) where I P = prior current Repeatability Unrestricted Page 30 of 68 100 ms (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 100000 10000 t = 1000 mins 1000 Time (sec) t = 100 mins 100 t = 10 mins 10 t = 1 min 1 0.1 0 1 2 3 4 5 6 7 8 9 10 Current (multiple of setting) Figure 2-1 Thermal Overload Protection Curves Unrestricted (c) 2013 Siemens Protection Devices Limited Page 31 of 68 7SR21 & 7SR22 Performance Specification 2.10 50 Instantaneous Overcurrent 2.10.1 Reference Parameter Value Is Setting 0.05, 0.06... 25, 25.5... 50 xIn i Applied Current (for operate time) td Delay setting Current switched from below Is to 2x Is Current switched from below Is to 5x Is 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 2.10.2 Operate and Reset Level Iop Attribute Value Operate level 100 % Is, 5 % or 1% In Reset level 95 % Iop Repeatability 1% Transient overreach (X/R 100) -5 % Variation -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % 2.10.3 Operate and Reset Time Attribute Value Switched from 0 to 2x Is: 40 ms, 10 ms tbasic Element basic operate time top Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Overshoot time < 40 ms Disengaging time < 50 ms Unrestricted Page 32 of 68 Switched from 0 to 5x Is: 30 ms, 10 ms (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.11 50G Instantaneous Measured Earth Fault 2.11.1 Reference Parameter Value Is Setting 0.005, 0.006... 25 xIn i Applied Current (for operate time) From below Is to 2x Is & from below Is to 5x Is td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 2.11.2 Operate and Reset Level Iop Attribute Value Operate level 100 % Is, 5 % or 1% In Reset level 95 % Iop Repeatability 1% Transient overreach (X/R 100) -5 % Variation -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % 2.11.3 Operate and Reset Time Attribute Value Switched from 0 to 2x Is: 35 ms, 10 ms tbasic Element basic operate time top Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Overshoot time < 40 ms Disengaging time < 50 ms Switched from 0 to 5x Is: 25 ms, 10 ms Unrestricted (c) 2013 Siemens Protection Devices Limited Page 33 of 68 7SR21 & 7SR22 Performance Specification 2.12 50N Instantaneous Derived Earth Fault 2.12.1 Reference Parameter Value Is Setting 0.05, 0.06... 25, 25.5... 50 xIn td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 2.12.2 Operate and Reset Level Iop Attribute Value Operate level 100 % Is, 5 % or 1% In Reset level 95 % Iop Repeatability 1% Transient overreach (X/R 100) -5 % Variation -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % 2.12.3 Operate and Reset Time Attribute Value Switched from 0 to 2x Is: 40 ms, 10 ms tbasic Element basic operate time top Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Overshoot time < 40 ms Disengaging time < 50 ms Unrestricted Page 34 of 68 Switched from 0 to 5x Is: 30 ms, 10 ms (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.13 50SEF Instantaneous Sensitive Earth Fault 2.13.1 Reference Parameter Value Is Setting 0.005, 0.006... 5.0 xIn td Delay setting 0.00, 0.01... 20.0, 20.1 .. 100.0, 101....1000, 1010 ... 10000 , 10100 ... 14400 I Applied current (for operate time) 5 xIs 2.13.2 Operate and Reset Level Iop Attribute Value Operate level 100 % Is, 5 % or 1% In Reset level 95 % Iop 5 % or 0.1% In Repeatability 1% Transient overreach (X/R 100) -5 % -10 C to +55 C Variation fnom - 3 Hz to fnom + 2 Hz harmonics to fcutoff 5% 5% 2.13.3 Operate and Reset Time Attribute Value Switched from 0 to 0 to 2x Is: 35 ms, 10 ms tbasic Element basic operate time top Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Overshoot time < 40 ms Disengaging time < 50 ms Variation fnom - 3 Hz to fnom + 2 Hz Switched from 0 to 0 to 5x Is: 25 ms, 10 ms 5% Unrestricted (c) 2013 Siemens Protection Devices Limited Page 35 of 68 7SR21 & 7SR22 Performance Specification 2.14 51 Time Delayed Overcurrent 2.14.1 Reference Parameter Value Is Setting 0.05, 0.06... 2.5 xIn char Characteristic setting Tm Time Multiplier setting 0.025, 0.05... 1.6 td Delay setting 0, 0.01... 20 s tres Reset setting ANSI DECAYING, 0, 1... 60 s I IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL Applied Current IDMTL 2 to 20 x ls (for operate time) DTL 5 x Is 2.14.2 Operate and Reset Level Iop Attribute Value Operate level 105 % Is, 4 % or 1 % In Reset level 95 % Iop Repeatability 1% Variation - 10 C to + 55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Unrestricted Page 36 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.14.3 Operate and Reset Time Attribute Value Starter operate time ( 2xIs) 20 ms, 20 ms char = IEC-NI, IEC-VI, IEC-EI, IEC-LTI top Operate time char = ANSI-MI, ANSI-VI, ANSI-EI char = DTL t op = [IsI ]a -1 for char = e t op = e e e ANSI DECAYING tres Tm , 5 % or 30 ms, IEC-NI : IEC-VI : IEC-EI : IEC-LTI : A [IsI ]P K = 0.14, a = 0.02 K = 13.5, a = 1.0 K = 80.0, a = 2.0 K = 120.0, a = 1.0 u + B u Tm , 5 % or 30 ms, u -1 u for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02 ANSI-VI : A = 19.61, B = 0.491, P = 2.0 ANSI-EI : A = 28.2, B = 0.1217, P = 2.0 td, 1 % or 20ms t res = Reset time K R [ IsI ]2 - 1 Tm , 5 % or 30 ms, for char = ANSI-MI : R = 4.85 ANSI-VI : R = 21.6 ANSI-EI : R = 29.1 tres, 1 % or 20 ms Repeatability 1 % or 20 ms Overshoot time < 40 ms Disengaging time < 50 ms Figure 2.2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1. Figure 2.3 and Figure 2.4 show the ANSI operate and reset curves. These operate times apply to non-directional characteristics. Where directional control is applied then the directional element operate time should be added to give total maximum operating time. Unrestricted (c) 2013 Siemens Protection Devices Limited Page 37 of 68 7SR21 & 7SR22 Performance Specification 1000 100 Time (sec) 10 Long Time Inverse Normal Inverse 1 Very Inverse Extremely Inverse 0.1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 Current (multiples of setting) Figure 2-2 Unrestricted Page 38 of 68 IEC IDMTL Curves (Time Multiplier = 1) (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 1000 100 Time (sec) 10 Moderately Inverse 1 Very Inverse Extremely Inverse 0.1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 Current (multiples of setting) Figure 2-3 ANSI IDMTL Operate Curves (Time Multiplier = 1) Unrestricted (c) 2013 Siemens Protection Devices Limited Page 39 of 68 7SR21 & 7SR22 Performance Specification 1000 500 100 50 Extremely Inverse Very Inverse Time (sec) 10 5 Moderately Inverse 1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Current (multiples of setting) Figure 2-4 Unrestricted Page 40 of 68 ANSI IDMTL Reset Curves (Time Multiplier = 1) (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.15 51G Time Delayed Measured Earth Fault 2.15.1 Reference Parameter Value Is Setting 0.005, 0.006... 1.0 xIn Char Characteristic setting Tm Time Multiplier setting 0.025, 0.05... 1.6 td Delay setting (DTL) 0, 0.01... 20 s tres Reset setting ANSI DECAYING, 0, 1... 60 s I Applied current (for operate time) IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL IDMTL 2 to 20 xIs DTL 5 xIs 2.15.2 Operate and Reset Level Iop Attribute Value Operate level 105 % Is, 4 % or 1% In Reset level 95 % Iop Repeatability 1% Variation -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5% Unrestricted (c) 2013 Siemens Protection Devices Limited Page 41 of 68 7SR21 & 7SR22 Performance Specification 2.15.3 Operate and Reset Time Attribute Value Starter operate time ( 2 xIs) 20 ms, 20 ms char = IEC-NI, IEC-VI, IEC-EI, IEC-LTI top Operate time char = ANSI-MI, ANSI-VI, ANSI-EI char = DTL t op = [IsI ]a -1 for char = e t op = e e e ANSI DECAYING tres Tm , 5 % or 30 ms, IEC-NI : IEC-VI : IEC-EI : IEC-LTI : A [IsI ]P K = 0.14, a = 0.02 K = 13.5, a = 1.0 K = 80.0, a = 2.0 K = 120.0, a = 1.0 u + B u Tm , 5 % or 30 ms, u -1 u for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02 ANSI-VI : A = 19.61, B = 0.491, P = 2.0 ANSI-EI : A = 28.2, B = 0.1217, P = 2.0 td, 1 % or 20 ms t res = Reset time K R [ IsI ]2 - 1 Tm , 5 % or 30 ms, for char = ANSI-MI : R = 4.85 ANSI-VI : R = 21.6 ANSI-EI : R = 29.1 tres, 1 % or 20 ms Repeatability 1 % or 20 ms Overshoot time < 40 ms Disengaging time < 50 ms Figure 2-2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1. Figure 2-3 and Figure 2-4 show the ANSI operate and reset curves respectively. These operate times apply to non-directional characteristics. Where directional control is applied then the directional element operate time should be added to give total maximum operating time. Unrestricted Page 42 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.16 51N Time Delayed Derived Earth Fault 2.16.1 Reference Parameter Value Is Setting 0.05, 0.06... 2.5 xIn char Characteristic setting Tm Time Multiplier setting 0.025, 0.05... 1.6 td Delay setting 0, 0.01... 20 s tres Reset setting ANSI DECAYING, 0, 1... 60 s IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL 2.16.2 Operate and Reset Level Iop Attribute Value Operate level 105 % Is, 4 % or 1% In Reset level 95 % Iop Repeatability 1% Variation - 10 C to + 55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Unrestricted (c) 2013 Siemens Protection Devices Limited Page 43 of 68 7SR21 & 7SR22 Performance Specification 2.16.3 Operate and Reset Time Attribute Value Starter operate time ( 2 xIs) 20 ms, 20 ms char = IEC-NI, IEC-VI, IEC-EI, IEC-LTI top Operate time char = ANSI-MI, ANSI-VI, ANSI-EI char = DTL t op = [IsI ]a -1 for char = e t op = e e e ANSI DECAYING tres Tm , 5 % or 30 ms, IEC-NI : IEC-VI : IEC-EI : IEC-LTI : A [IsI ]P K = 0.14, a = 0.02 K = 13.5, a = 1.0 K = 80.0, a = 2.0 K = 120.0, a = 1.0 u + B u Tm , 5 % or 30 ms, u -1 u for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02 ANSI-VI : A = 19.61, B = 0.491, P = 2.0 ANSI-EI : A = 28.2, B = 0.1217, P = 2.0 td, 1 % or 20 ms t res = Reset time K R [ IsI ]2 - 1 Tm , 5 % or 30 ms, for char = ANSI-MI : R = 4.85 ANSI-VI : R = 21.6 ANSI-EI : R = 29.1 tres, 1 % or 20 ms Repeatability 1 % or 20 ms Overshoot time < 40 ms Disengaging time < 50 ms Figure 2-2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1. Figure 2-3 and Figure 2-4 show the ANSI operate and reset curves respectively. These operate times apply to non-directional characteristics. Where directional control is applied then the directional element operate time should be added to give total maximum operating time. Unrestricted Page 44 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.17 51SEF Time Delayed Sensitive Earth Fault 2.17.1 Reference Parameter Value Is Setting 0.005, 0.006...1 xIn char Characteristic setting Tm Time multiplier 1.0 td Delay setting 0.00...20.00 s tres Reset setting DECAYING, 0, 1...60 s I Applied current (for operate time) IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL IDMTL 2 to 20xIs DTL 5 xIs 2.17.2 Operate and Reset Level Iop Attribute Value Operate level 105 % Is, 4 % or 1% In Reset level 95 % Iop 4 % or 1% In Repeatability 1% -10 C to +55 C Variation fnom - 3 Hz to fnom + 2 Hz 5% 5% harmonics to fcutoff Unrestricted (c) 2013 Siemens Protection Devices Limited Page 45 of 68 7SR21 & 7SR22 Performance Specification 2.17.3 Operate and Reset Time Attribute Value Starter operate time 20 ms, 20 ms t op = char = IEC-NI, IEC-VI, IEC-EI, IEC-LTI top Operate time char = ANSI-MI, ANSI-VI, ANSI-EI, char = DTL [] for char = e t op = e e e Reset time tres DECAYING -1 Tm , 5 % or 30 ms, IEC-NI : IEC-VI : IEC-EI : IEC-LTI : A [IsI ]P u + B u Tm , 5 % or 30 ms, u -1 u td, 1 % or tcycle R [ IsI ]2 - 1 Tm , 5 % or 30 ms, for char = ANSI-MI : R = 4.85 ANSI-VI : R = 21.6 ANSI-EI : R = 29.1 tres, 1 % or 20 ms Repeatability 1 % or 20 ms Overshoot time < 40 ms Disengaging time < 50 ms Variation fnom - 3 Hz to fnom + 2 Hz K = 0.14, a = 0.02 K = 13.5, a = 1.0 K = 80.0, a = 2.0 K = 120.0, a = 1.0 for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02 ANSI-VI : A = 19.61, B = 0.491, P = 2.0 ANSI-EI : A = 28.2, B = 0.1217, P = 2.0 t res = char = ANSI and tres = DECAYING K I a Is 5% harmonics to fcutoff Figure 2-2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1. Figure 2-3 and Figure 2-4 show the ANSI operate and reset curves. These operate times apply to non-directional characteristics. Where directional control is applied then the directional element operate time should be added to give total maximum operating time. Unrestricted Page 46 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.18 51V Voltage Controlled Overcurrent (Ph-Ph) 2.18.1 Reference Parameter Value Vs Setting 5, 5.5...199.5, 200 V m Multiplier 0.25, 0.3...0.95, 1 Is Setting 1 xIn 2.18.2 Operate and Reset Level Vop Attribute Value Operate level 100 % Vs, 1 % or 0.25 V Reset level 105 % Vop Repeatability 1% -10 C to +55 C Variation fnom - 3 Hz to fnom + 2 Hz 5% 5% harmonics to fcutoff Operate and Reset Time As per Phase Fault Shaped Characteristic Element (ANSI 51). Where Pickup Level = Is for Voltage > Vs Pickup Level = (Is x m) for Voltage < Vs Unrestricted (c) 2013 Siemens Protection Devices Limited Page 47 of 68 7SR21 & 7SR22 Performance Specification 2.19 55 Power Factor 2.19.1 Reference PFs Parameter 55-n Setting Value 0.05...0.99 td 55-n Delay setting 0.00 ... 14400 s 2.19.2 Operate and Reset Level PFop Attribute Value Operate Level PFs 0.05 Reset Level Under PF PFop + 0.02 Over PF PFop - 0.02 0.05 Repeatability Variation -10 C to +55 C 0.05 fnom - 3 Hz to fnom + 2 Hz 0.05 2.19.3 Operate and Reset Time Attribute Value tbasic Element basic operate time 70 ms top Operate time following delay tbasic + td, 1 % or 10ms Disengaging time < 80 ms 2.19.4 Operate Threshold Attribute Minimum levels for operation Unrestricted Page 48 of 68 Value I 2.5 % In V 2.5% Vn (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.20 59N Neutral Voltage Displacement 2.20.1 Reference (59NDT) Parameter Value Vs Setting 1, 1.5... 100 V td Delay setting 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 2.20.2 Operate and Reset Level (59NDT) Vop Attribute Value Operate level 100 % Vs, 2 % or 0.5 V Reset level 95 % Vop or 0.25 V Repeatability 1% Variation -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5% 2.20.3 Operate and Reset Time (59NDT) Attribute Value Switched from 0 to 1.5 xVs, 76 ms, 20 ms tbasic Element basic operate time top Operate time following delay tbasic + td, 1 % or 20 ms Repeatability 1 % or 20 ms Overshoot time < 40 ms Disengaging time < 50 ms Switched from 0 to 10 xVs, 63 ms, 20 ms 2.20.4 Reference (59NIT) Parameter Value M Multiplier setting 0.1, 0.2... 10, 10.5... 140 Vs Setting 1, 1.5... 100 V td Delay setting 0, 0.01... 20 s tres Reset setting 0, 1...60 s Unrestricted (c) 2013 Siemens Protection Devices Limited Page 49 of 68 7SR21 & 7SR22 Performance Specification 2.20.5 Operate and Reset Level (59NIT) Vop Attribute Value Operate level 105 % Vs, 2 % or 0.5 V Reset level 95 % Vop or 0.25 V Repeatability 1% Variation -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5% 2.20.6 Operate and Reset Time (59NIT) tbasic top Attribute Value Starter operate time ( 2xVs) 65 ms, 20 ms Operate time Reset Time char = IDMTL t op = M [ ]- 1 3V0 Vs , 5 % or 65 ms char = DTL td, 1 % or 40 ms char = IDMTL tres, 5 % or 65 ms char = DTL tres, 1 % or 40 ms Repeatability 1 % or 20 ms Overshoot time < 40 ms Disengaging time < 50 ms Unrestricted Page 50 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.21 64H Restricted Earth Fault Protection 2.21.1 Reference Parameter Value Is Setting 0.005, 0.006... 0.95 xIn td Delay setting 0.00, 0.01... 20.0, 20.1... 100.0, 101....1000, 1010 ... 10000 , 10100 ... 14400 s 2.21.2 Operate and Reset Level Iop Attribute Value Operate level 100 % Is, 5 % or 1 % xIn Reset level 95 % Iop, 5 % or 0.1 % xIn Repeatability 1% Transient overreach (X/R 100) -5 % Variation -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % 2.21.3 Operate and Reset Time Attribute Value tbasic Element basic operate time top Operate time following delay tbasic + td, 1% or 10 ms Repeatability 1% or 10 ms Overshoot time < 40 ms Disengaging time < 50 ms Unrestricted (c) 2013 Siemens Protection Devices Limited Page 51 of 68 7SR21 & 7SR22 Performance Specification 2.22 67/67N Directional Overcurrent & Earth Fault 2.22.1 Reference Parameter Value us Angle setting -95...+95 I Applied current In V Applied voltage 110 V phase-phase (63.5 V phase-earth) 2.22.2 Operate Angle CA Attribute Value Characteristic angle (I with respect to V) us , 5 forward CA - 85 5 to CA + 85 5 reverse (CA - 180) - 85 5 to (CA - 180) + 85 5 10C to +55C 5 fnom - 3 Hz to fnom + 2 Hz 5 Operating angle Variation in characteristic angle 2.22.3 Operate Threshold Attribute Minimum levels for operation Value I (p/f) > 5 % In I (e/f) > 10 % In V (p/f) >1V V (e/f) >1V 2.22.4 Operate and Reset Time Attribute Value Operate time typically 25 < 40 ms at characteristic angle Reset time typically < 65 ms at characteristic angle Unrestricted Page 52 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.23 Directional SEF Wattmetric 2.23.1 Reference Parameter Value Po Setting 0.05, 0.10,... 20.0 xInxW (Where In = 1A or 5A ) I Applied current @ In = 1A 10mA...5A V Applied voltage 10V...200V q Angle <87.5deg CA 67SEF Char Angle (qc) 0 f Nominal 50/60Hz 2.23.2 Operate and Reset Level Pop Attribute Value Operate level 100 % Po, 25 % or 25mW Reset level 95 % Pop Variation -10 C to +55 C 5% 2.23.3 Operate and Reset Time tbasic Attribute Value Element basic operate time <50ms Repeatability 1 % or 10ms Unrestricted (c) 2013 Siemens Protection Devices Limited Page 53 of 68 7SR21 & 7SR22 Performance Specification 2.24 81 Under/Over Frequency 2.24.1 Reference Parameter Value Fs Setting 40, 40.01... 69.99 Hz Hyst Hysteresis setting 0, 0.1... 80 % td Delay setting 0.00, 0.01... 20.0, 20.1... 100.0, 101....1000, 1010 ... 10000 , 10100 ... 14400 s 2.24.2 Operate and Reset Level Fop Attribute Value Operate level 100 % Fs, 10 mHz Reset level overfrequency (100 % - hyst) xFop, 10 mHz underfrequency (100 % + hyst) xFop, 10 mHz 1% Repeatability Variation - 10 C to + 55 C 5% 2.24.3 Operate and Reset Time Attribute Element basic operate time tbasic top Value overfrequency Typically < 110 ms Maximum < 150 ms (for ROCOF between 0.1 underfrequency and 5.0 Hz/sec) Typically < 110 ms Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Disengaging time < 100 ms Unrestricted Page 54 of 68 Maximum < 150 ms (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 2.25 50 AFD ARC Flash Detector (Refer to 7XG31 Technical Manual for performance characteristics) 2.25.1 Reference 50 AFD Parameter Value Setting 1, 2,...10 xIn 2.25.2 Operate and Reset Level Iop Attribute Value Operate level 100 % Is, 10 % Transient overreach (X/R 100) -30 % Reset level 95 % Iop Repeatability 5% 2.25.3 Operate and Reset Time Attribute Value tbasic 50AFD Overcurrent operate time 10 ms - 16 ms top AFD Zone operate time (Flash & 50AFD) 15 ms - 25 ms Repeatability 10 ms Disengaging time < 50 ms Unrestricted (c) 2013 Siemens Protection Devices Limited Page 55 of 68 7SR21 & 7SR22 Performance Specification Section 3: Supervision Functions 3.1 46BC & 46BC U/C Broken Conductor 3.1.1 Reference Parameter tf 3.1.2 Value Setting (NPS to PPS ratio) 20...100 % U/C Guard setting 0.05, 0.1 ... 4.95, 5 Delay setting 0.02...1000 s Operate and Reset Level Attribute Icurr Operate level 100 % Iset 5 % Reset level 90 % Icurr , 5 % Repeatability 1% - 10 C to + 55 C Variation fnom - 3 Hz to fnom + 2 Hz harmonics to fcutoff 3.1.3 Value 5% 5% Operate and Reset Time Attribute tbasic Value Basic operate time 1x In to 0 A 40 ms Operate time tf + tbasic, 1 % or 20 ms Repeatability 1 % or 20 ms Variation fnom - 3 Hz to fnom + 2 Hz harmonics to fcutoff Unrestricted Page 56 of 68 5% (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 3.2 50BF & 50BF-I4 Circuit Breaker Fail 3.2.1 Reference Parameter Value Is 50BF Setting 0.050, 0.055... 2.0 xIn Is 50BF-I4 Setting 0.005, 0.01... 2.0 xIn tCBF1 Stage 1 Delay setting 20, 25... 60000ms tCBF2 Stage 2 Delay setting 20, 25... 60000ms 3.2.2 Operate and Reset Level Attribute Value Iop Operate level 100 % Is, 5 % or 1% In Ireset Reset level <100 % Iop, 5 % or 1% In Repeatability 1% Variation -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % 3.2.3 Operate and Reset Time tbasic top Attribute Value Element basic operate time < 20 ms Stage 1 tCBF1, 1 % or 20 ms Stage 2 tCBF2, 1 % or 20 ms Repeatability 1 % or 20 ms Overshoot < 2 x 20 ms Disengaging time < 30 ms Unrestricted (c) 2013 Siemens Protection Devices Limited Page 57 of 68 7SR21 & 7SR22 Performance Specification 3.3 60CTS & CTS-I Current Transformer Supervision 3.3.1 Reference Parameter Value Ithresh Current Threshold 0.05, 0.1... 1 xIn Vthresh Voltage Threshold 7, 8... 110V td Delay setting 0.03, 0.04...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s CTS-I Ithresh Current Threshold 0.05, 0.1... 2 xIn 3.3.2 Iop Vop Current & Voltage Threshold Attribute Value CT failed current level 100 % Ithresh, 5% or 1% In Reset level 90 % Iop, 5% or 1% In CT failed voltage level 100 % Vthresh, 2% or 0.5 V Reset level 110 % Vop, 2 % or 0.5 V Repeatability 1% -10 C to +55 C Variation fnom - 3 Hz to fnom + 2 Hz harmonics to fcutoff 3.3.3 tbasic 5% 5% Operate and Reset Time Attribute Value Basic operate time 30 ms 20ms Operate time tbasic, 1 % or 20ms Repeatability 1 % or 20ms Unrestricted Page 58 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 3.4 60VTS Voltage Transformer Supervision 3.4.1 Reference Parameter Value Vnps Vnps Level 7, 8 ... 110 V Inps Inps Level 0.05, 0.1 ... 1 x In Ipps Ipps Load Level 0.05, 0.1 ... 1 x In IFpps Ipps Fault Level 0.05, 0.1 ... 20 x In Vpps Vpps Level 1, 2 ... 110 V td 60VTS Delay 0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010... 10000, 10100... 14400 s 3.4.2 VNPSop VPPSop INPSblk IPPSblk IPPSload Operate and Reset Level Attribute Value Voltage NPS operate level 100 % Vnps, 5 % Vn Voltage NPS reset level 90 % VNPSop, 5 % Vn Voltage PPS operate level 100 % Vpps, 5 % Vn Voltage PPS reset level 110 % VPPSop, 5 % Vn Current NPS operate level 100 % Inps, 5 % xIn Current NPS reset level 90 % INPSblk, 5 % xIn Current PPS operate level 100 % IFpps, 5 % xIn Current PPS reset level 90 % IPPSblk, 5 % xIn Current PPS operate level 100 % Ipps, 5 % xIn Current PPS reset level 90 % IPPSload, 5 % xIn Repeatability 1% -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5% Variation Unrestricted (c) 2013 Siemens Protection Devices Limited Page 59 of 68 7SR21 & 7SR22 Performance Specification 3.4.3 tbasic Operate and Reset Time Attribute Value Basic operate time 0V to 2 x Vs 32 ms 10 ms Operate time tbasic, 1 % or 10 ms Repeatability 1 % or 10 ms Unrestricted Page 60 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 3.5 74TCS Trip Circuit Supervision 3.5.1 Reference td 3.5.2 Parameter Value Delay setting 0, 0.02...60 s Operate and Reset Time Attribute Value tbasic Element basic operate time 25 ms 20 ms top Operate time following delay tbasic + td, 1 % or 10 ms Repeatability 1 % or 10 ms Variation - 10 C to + 55 C 5% fnom - 3 Hz to fnom + 2 Hz 5% Unrestricted (c) 2013 Siemens Protection Devices Limited Page 61 of 68 7SR21 & 7SR22 Performance Specification 3.6 81HBL2 Inrush Detector 3.6.1 Reference Parameter Value Setting I (Ratio of 2nd Harmonic current to 0.10, 0.11... 0.5 Fundamental component current) 3.6.2 Iop Operate and Reset Level Attribute Value Operate level 100 % I, 4 % or 1 % In Reset level 100 % Iop, 4 % or 1 % In Repeatability 1% Variation 3.6.3 tbasic - 10 C to + 55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute Value Element basic operate time Will pick-up before operation of any protection element due to magnetic inrush Reset Time Will operation until drop-off of any protection element due to magnetic inrush Unrestricted Page 62 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 3.7 81HBL5 Over Fluxing Detector 3.7.1 Reference Parameter Value Setting I (Ratio of 5th Harmonic current to 0.10, 0.11... 0.5 Fundamental component current) 3.7.2 Iop Operate and Reset Level Attribute Value Operate level 100 % I, 4 % or 1% In Reset level 100 % Iop, 4 % or 1% In Repeatability 1% Variation 3.7.3 tbasic -10 C to +55 C 5% fnom - 3 Hz to fnom + 2 Hz 5 % Operate and Reset Time Attribute Value Element basic operate time Will pick-up before operation of any protection element due to overfluxing Reset Time Will operation until drop-off of any protection element due to overfluxing Unrestricted (c) 2013 Siemens Protection Devices Limited Page 63 of 68 7SR21 & 7SR22 Performance Specification 3.8 Load Blinder (21LB - 3P) 3.8.1 Reference Parameter Value Angle + ve setting 5 Deg to 85 Deg Angle - ve setting 5 Deg to 85 Deg Z Impedance 1 Ohm to 100 Ohms Vpps Vpps Level 1 V to 110 V Inps Inps Level 0.05 xIn to 5 xIn 3.8.2 Operate Level Attribute Value VPPS Voltage PPS operate level 100 % Vs, 2 % or 0.5 V INPS Current NPS operate level 100 % Is, 5 % or 1% In Impedance 100 % Zs, 5 % or 0.1 Repeatability 1% 3.8.3 Operate Angle Attribute Value forward (21LB-3P Angle +ve) 5 to (21LB-3P Angle -ve) 5 reverse (180 - 21LB-3P Angle +ve) 5 to (180 + 21LB-3P Angle -ve) 5 Operating angle Unrestricted Page 64 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 3.9 Load Blinder (21LB - 1P) 3.9.1 Reference Parameter Value Angle + ve setting 5 Deg to 85 Deg Angle - ve setting 5 Deg to 85 Deg Z Impedance 1 Ohm to 100 Ohms Vpps Vpps Level 1 V to 110 V Izps Izps Level 0.05 xIn to 5 xIn 3.9.2 VPPS IZPS 3.9.3 Operate Level Attribute Value Voltage PPS operate level 100 % Vs, 2 % or 0.5 V Voltage PPS reset level 110 % VPPSop, 5 % Vn Current ZPS operate level 100 % Is, 5 % or 1% In Impedance 100 % Zs, 5 % or 0.1 Repeatability 1% Operate Angle Attribute Value forward (21LB-1P Angle +ve) 5 to (21LB-1P Angle -ve) 5 reverse (180 - 21LB-1P Angle +ve) 5 to (180 + 21LB-1P Angle -ve) 5 Operating angle Unrestricted (c) 2013 Siemens Protection Devices Limited Page 65 of 68 7SR21 & 7SR22 Performance Specification Section 4: Control Functions 4.1 Check Synchronising 4.1.1 Reference Parameter Value Vnom Nominal Voltage 40-160 V fn Nominal Frequency 50/60 Hz Vlive Live Setting 10 % - 150 % Vdead Dead Setting 10 % - 150 % Vsl Line Voltage Setting 10 % - 150 % Vsb Bus Voltage Setting 10 % - 150 % Vdiff Voltage Differential Setting 5 % - 95 % cs CS Angle 1 - 90 ss SS Angle 1 - 90 fcoz COZ Slip 30 mHz - 250 mHz fcs CS Slip Freq 20 mHz - 250 mHz fss SS Slip Freq 10 mHz - 250 mHz tcs CS Timer 0-100 s tss SS Timer 0-1 s fsps Split Slip 20 mHz - 250 mHz tdlc/tdbc DLC/DBC Delays 0-60 s tcw Sync Close Window 1 s - 1200 s 4.1.2 Vlive,act Live/Dead Line/Bus Detector Elements Attribute Value Live operate level 100 % Vlive, 1 % Vn Live reset level Vdead,act, 1 % Vn Vdead,act Dead operate level 100 % Vdead, 1 % Vn Dead reset level Vlive,act, 1 % Vn Repeatability 1% Variation -10 C to +55 C 5% fnom 5 % 1% Unrestricted Page 66 of 68 (c) 2013 Siemens Protection Devices Limited 7SR21 & 7SR22 Performance Specification 4.1.3 Vline Vbus Line and Bus Undervoltage Elements Attribute Value Operate level 100 % Vsl, 1 % Vn Reset level Vline + 4 % Operate level 100 % Vsb, 1 % Vn Reset level Vbus + 4 % Repeatability 1% Variation 4.1.4 Vop 4.1.5 -10 C to +55 C 5% fnom 5 % 1% Voltage Difference Attribute Value Operate level 100 % Vdiff, 1 % Vn Reset level Vop - 4 % Repeatability 2% General Autoreclose Timers Attribute Value tbasic Element basic operate time 20 ms 20 ms top tdlc/tdbc/tcw top + tbasic 1% Repeatability 20 ms 4.1.6 qop 4.1.7 fop 4.1.8 CS/SS/COZ Line and Bus Phase Angle Difference Attribute Value Operate angle qdiff, 1 Reset angle qop, 1 Repeatability 1 CS/SS/COZ Slip Frequency Attribute Value Operate frequency fslip, 10 mHz Reset frequency fop, - 10 mHz Repeatability 10 mHz CS/SS Timer Attribute Value top Operate time 1 , + 20 ms Note: minimum synchronising time following restoration of voltage from a dead condition is 320 ms. Unrestricted (c) 2013 Siemens Protection Devices Limited Page 67 of 68 7SR21 & 7SR22 Performance Specification 4.1.9 qop Split Angle Detector Attribute Value Operate angle qsplit, 1 4.1.10 Split Slip Frequency Detector fop Attribute Value Operate frequency fslip, 10 mHz Reset frequency fop, - 10 mHz Repeatability 10 mHz 4.2 Live/Dead 4.2.1 Reference Parameter Value Vs Setting (ABC side) 5, 5.5...200 V Vs Setting (XYZ side) 5, 5.5...120 V 4.2.2 Vlive,act Live/Dead Detector Elements Attribute Value Live operate level 100 % Vlive, 1 % Vn Live reset level Vdead,act, 1 % Vn Vdead,act Dead operate level 100 % Vdead, 1 % Vn Dead reset level Vlive,act, 1 % Vn Repeatability 1% Variation -10 C to +55 C 5% fnom 5 % 1% Unrestricted Page 68 of 68 (c) 2013 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Data Communications Definitions Overcurrent Relay Document Release History This document is issue 2017/07. The list of revisions up to and including this issue is: Date 2017/07 Description Addition of increases I/O and 32Power, 32S Sensitive Power, Frequency. The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2017 Siemens Protection Devices Limited 7SR220 Technical Manual Chapter 4 - Page 2 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Contents 1. Introduction ............................................................................................................... 5 2. Physical Connection ................................................................................................. 7 2.1 Introduction ......................................................................................................................................... 7 2.2 USB Interface (COM2)........................................................................................................................ 8 2.3 RS485 Interface (COM1) .................................................................................................................... 8 2.4 Serial Fibre Optic Interface (COM3 & COM4) .................................................................................... 10 2.5 Optional Rear RS485 (COM3) .......................................................................................................... 13 2.6 Optional Rear RS232 (COM3) .......................................................................................................... 14 2.7 Optional Rear EN100 Ethernet Module (COM3) ................................................................................ 16 3. IEC 60870-5-103 Definitions .................................................................................. 19 3.1 Introduction ....................................................................................................................................... 19 3.2 Cause of Transmission ..................................................................................................................... 20 3.3 Application Service Data Unit (ASDU) Type ...................................................................................... 21 3.4 Point List .......................................................................................................................................... 22 3.4.1 Event Function (FUN) & Information (INF) Numbers............................................................. 22 3.4.2 Measurands ........................................................................................................................ 32 3.4.3 Disturbance Recorder Actual Channel (ACC) Numbers ........................................................ 33 4. MODBUS Definitions .............................................................................................. 35 4.1 Introduction ....................................................................................................................................... 35 4.2 MODBUS Register Data Types ......................................................................................................... 36 4.2.1 FLOAT_IEEE_754 ............................................................................................................... 36 4.2.2 FP_32BITS_3DP ................................................................................................................. 37 4.2.3 UINT32 ............................................................................................................................... 37 4.2.4 UINT16 ............................................................................................................................... 37 4.2.5 EVENT ................................................................................................................................ 38 4.2.6 EVENTCOUNT.................................................................................................................... 39 4.2.7 TIME_METER ..................................................................................................................... 39 4.2.8 STR32 & STR64 ................................................................................................................. 39 4.2.9 BITSTRING ......................................................................................................................... 39 4.3 Point List .......................................................................................................................................... 41 4.3.1 Coils (Read Write Binary values) ......................................................................................... 41 4.3.2 Inputs (Read Only Binary values) ........................................................................................ 42 4.3.3 Input Registers (Read Only Registers) ................................................................................. 49 4.3.4 Holding Registers (Read Write Registers) ............................................................................ 52 5. DNP3 Definitions .................................................................................................... 53 5.1 Device Profile ................................................................................................................................... 53 5.2 Implementation Table........................................................................................................................ 56 5.3 Point List .......................................................................................................................................... 62 5.3.1 Binary Input Points .............................................................................................................. 62 5.3.2 Double Bit Input Points........................................................................................................ 70 5.3.3 Binary Output Status Points and Control Relay Output Blocks .............................................. 71 5.3.4 Counters ............................................................................................................................. 77 5.3.5 Analog Inputs ...................................................................................................................... 79 5.4 Additional Settings ............................................................................................................................ 83 6. Not Applicable ........................................................................................................ 85 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 3 of 96 7SR220 Technical Manual 7. IEC61850 Protocol Support .................................................................................... 87 7.1 Introduction ...................................................................................................................................... 87 8. Serial Modems ........................................................................................................89 8.1 Introduction ...................................................................................................................................... 89 8.2 Connecting a Modem to the Relay(s) ............................................................................................... 89 8.3 Setting the Remote Modem .............................................................................................................. 89 8.4 Connecting to the Remote Modem ................................................................................................... 89 9. Not Applicable ........................................................................................................91 10. Glossary................................................................................................................93 Appendix 1 .................................................................................................................. 95 List of Figures Fig. 2-1 Communication to Front USB Port ......................................................................................................... 8 Fig. 2-2 Communication to Multiple Devices using RS485 (Standard Port) ......................................................... 10 Fig. 2-3 Communication to Multiple Devices using Fibre-optic Ring Network....................................................... 13 Fig. 2-4 Communication to Multiple Devices from Control System and Laptop using Fibre-optic Star Network ...... 13 Fig. 2-5 Additional (Optional) Rear RS485 + IRIG-B Connection to a PC ........................................................... 14 Fig. 2-6 Additional (Optional) Rear RS232 + IRIG-B Connection to a PC ........................................................... 15 Fig. 2-7 RS232 Data Comms Pin Connections .................................................................................................. 15 Fig. 2-8 EN100 Ethernet Module ....................................................................................................................... 17 Fig. A1 Operating Mode Table .......................................................................................................................... 95 Chapter 4 - Page 4 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 1. Introduction This section describes how to use the Communication Interface with a control system or interrogating computer. The interface is compatible with control and automation systems using industry standard communications protocols DNP3 , IEC 60870-5-103 , IEC 61850 and MODBUS-RTU. Note, not all protocols are available on all devices. Reydisp Evolution or Reydisp Manager Software is available, for computers running Microsoft WindowsTM, to connect to devices to provide operational information, post-fault analysis, setting interrogation and editing facilities etc. Configuration software can be downloaded from our website http://www.siemens.com/energy. This section specifies connection details and lists the information available through the individual protocols. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 5 of 96 7SR220 Technical Manual Chapter 4 - Page 6 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 2. Physical Connection 2.1 Introduction The relay provides one "Front" USB communication interface (Com2) located on the fascia and one RS485 (Com1) located on the "Rear" as standard. An additional module may be fitted as an ordering option to provide extra rear serial port(s) or two Ethernet channels. Modules are available for serial fibre optic, RS232 and RS485. These modules provide one (Com3) or two (Com3 and Com4) additional ports. The optional EN100 Ethernet module, available in optical and electrical versions, supports the IEC 61850 protocol and Reydisp access through the network (LAN port) interface. A detailed description of the ports is given below. COM1-RS485: This port can be used for IEC60870-5-103, MODBUS-RTU or DNP3 communications to a substation SCADA or integrated control system or for engineer remote access. This port can also be used for connection to Reydisp software. COM2-USB: This port is used for IEC60870-5-103 (default setting) communication with the Reydisp software. An ASCII protocol is also available through this port, the main use of this protocol is to allow the Relay firmware to be updated via the front connection. MODBUS-RTU or the optional DNP3 protocols are also available. COM3: Where fitted, an additional rear serial fibre optic, RS232 or RS485 port. This port can be used for IEC60870-5-103, MODBUS-RTU or DNP3 communications to a substation SCADA or integrated control system or for engineer remote access. This port can also be used for connection to Reydisp software. COM4: As COM3. COM3-LAN: When the Ethernet module is fitted, in addition to IEC61850 a LAN connection is provided to allow the Reydisp software to connect to the Relay via the network. This port only supports the IEC60870-5-103 protocol. Any or all serial ports can be mapped to the IEC60870-5-103, DNP3 or MODBUS-RTU protocol at any one time, protocols available will depend upon relay model. The optional ethernet port uses IEC 61850 protocol and can also provide an IEC 60870-5-103 protocol connection to Reydisp. Any port not required can be disabled by setting its protocol to OFF. When connecting to Reydisp Evolution software the protocol for the relevant port should be set to IEC60870-5-103. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 7 of 96 7SR220 Technical Manual 2.2 USB Interface (COM2) The USB communication port is connected using a standard USB cable with a type B connection to the relay and type A to the PC. The PC will require a suitable USB driver to be installed; this will be carried out automatically when the Reydisp software is installed. When the Reydisp software is running with the USB cable connected to a device an additional connection is shown. Connections to these devices are not shown when they are not connected. The USB communication interface on the relay is labelled Com 2 and its associated settings are located in the Data communications menu. When connecting to Reydisp using this connection the default settings can be used without the need to first change any settings. Access to the communication settings for the USB port is only available from the relay front fascia via the key pad setting menu COMMUNICATIONS MENU. Setting Name COM2-USB Protocol Range/Options OFF IEC60870-5-103 MODBUS-RTU ASCII Default Setting Notes Reydisp software requires IEC60870-5-103. IEC60870-5-103 DNP3 COM2-USB Station Address 0 - 254 for IEC60870-5-103 1 - 247 for Modbus RTU 0 - 65534 for DNP3.0 COM2-USB Mode Local Local or Remote Remote An address within the range of the relevant protocol must be given to identify the relay. Each relay in a network must have a unique address. 0 Refer to Appendix 1, page 95, for further explanation Local USB Type A Socket on PC USB Type B Socket on Device Local Engineer Access Fig. 2-1 Communication to Front USB Port 2.3 RS485 Interface (COM1) The 2-wire RS485 communication port is located on the rear of the relay and can be connected using a suitable RS485 120 Ohm screened twisted pair cable. Chapter 4 - Page 8 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions The RS485 electrical connection can be used in a single or multi-drop configuration. The RS485 master must support and use the Auto Device Enable (ADE) feature. The last device in the connection must be terminated correctly in accordance with the master device driving the connection. This can be done via the internal 120 ohm terminating resistor, which can be connected between 14 (A) and 18 (B) by fitting an external wire loop between terminals 18 and 20 on the power supply module. The polarity of the signal terminals is marked as A and B in line with the RS485 standard. The polarity is that when the bus is in the quiescent state and no communication is taking place, the B terminal is more positive than A. This can be used to identify the polarity of any equipment to be connected, typically measured at each terminal in turn to ground. Connection of the device to a termination network at the end of the bus will also be to suit the quiescent state as shown in the diagram below. The polarity marking is often found to be reversed or marked as +/- on other equipment so care is required. If the devices are connected in reverse, communication to all devices will be disturbed but no damage will occur. If problems are experienced during commissioning, the connections should be tried in reverse. The maximum number of relays that can be connected to the bus is 64. The RS485 data comms link will be broken for that particular relay element if it is withdrawn from the case but the chain of communication to the other relays is maintained. The following settings, on the COMMUNICATIONS MENU, must be configured when using the RS485 interface. Setting Name COM1-RS485 Protocol COM1-RS485 Station Address COM1-RS485 Baud Rate COM1-RS485 Parity COM1-RS485 Mode Range/Options OFF IEC60870-5-103 MODBUS-RTU DNP3 0 - 254 for IEC60870-5-103 1 - 247 for Modbus RTU 0 - 65534 for DNP3.0 75 110 150 300 600 1200 2400 4800 9600 19200 38400 NONE ODD Default IEC60870-5-103 (c) 2017 Siemens Protection Devices Limited Notes The protocol used to communicate on the standard RS485 connection. 0 An address within the range of the relevant protocol must be given to identify the relay. Each relay in a network must have a unique address. 19200 The baud rate set on all of the relays connected to the control system must be the same as the one set on the master device. EVEN The parity set on all of the relays connected to the control system must be the same and in accordance with the master device. EVEN Local Local or Remote Remote Setting Remote Refer to Appendix 1, page 95, for further explanation Chapter 4 - Page 9 of 96 7SR220 Technical Manual Rear terminals To Control System Rear terminals 14 16 18 RS485 Screened twisted pair RS485 Screened twisted pair 14 16 18 14 16 18 20 Ext Wire loop (terminating resistance) added where permanent drive from master station available To Control System 16 18 20 Term. 14 A B 20 RS485 Sc 18 Term. 14 A 16 20 Term. B 18 RS485 Sc 16 B 14 A Sc RS 485 Twisted pair Cable RS485 Bus Termination Polarity 5V B A Sc Fig. 2-2 Communication to Multiple Devices using RS485 (Standard Port) 2.4 Serial Fibre Optic Interface (COM3 & COM4) When connecting via the optional fibre optic interface the selection of fibre-optic cable is important. Fibres must be terminated with STTM (BFOC/2.5) connectors. The recommended type is 62.5/125m glass fibre. Communication distances over 1 km are achievable using this type of fibre. A budget loss calculation should be made for all installations. The following table gives the launch power and receiver sensitivity of each of the fibre optic communication ports on the Relay when used with specific fibre optic types. Tx Launch Power (dB) Fibre Type RX Receive Sensitivity (dB) Max Min Min Max 62.5/125m -11.7 -15.7 -24 -9.2 1mm Polymer -6.4 -10.4 -24 -9.2 200m PCS -2.8 -6.8 -24 -9.2 Factors to be considered when calculating fibre-optic transmission distances: * Transmitter launch power. * Attenuation, based on light frequency, fibre material and fibre diameter. (Consult fibre manufacturers' data for actual values of fibre attenuation). * Number of intermediate connectors and splices. Fibre cables are supplied on reels of finite length which may necessitate additional jointing. Typical losses at connectors are 0.5-1.0dB each. This allows for normal age related deterioration. Typical losses at splices are <0.3dB. (Consult fibre manufacturers' data for actual values). Chapter 4 - Page 10 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions * Receiver sensitivity. The light power at the receiver must be above the sensitivity of the receiver in order that effective communication can occur. * A 3dB safety margin is usually allowed after the budget calculation is performed. Following installation and prior to putting into service the actual losses should be measured for each fibre using a calibrated light source and meter. Measured and calculated values can be compared. The following table can be used to record budget calculations: A Launch power B Fibre Type C Loss (dB/km) dB/km D Length km E Total fibre loss (CxD) dB F No. of Splices G Loss at each splice dB H Total loss at splices (FxG) dB I No. of connectors J Loss per connector dB K Total loss at connectors (IxJ) dB L Total losses (E+H+K) dB M Receive power budget (A-L) dB N Safety Margin dB O Device Receive Sensitivity dB dB The following settings, on the COMMUNICATIONS MENU, must be configured when using the fibre Optic Com3 interface. Setting Name COM3 Protocol COM3 Station Address Range/Options OFF IEC60870-5-103 MODBUS-RTU DNP3 0 - 254 for IEC60870-5-103 1 - 247 for Modbus RTU 0 - 65534 for DNP3.0 Default IEC60870-5-103 600 1200 2400 4800 Baud Rate 9600 19200 38400 57600 115200 COM3 Parity NONE ODD EVEN (c) 2017 Siemens Protection Devices Limited Notes The protocol used to communicate on the standard RS485 connection. 0 An address within the range of the relevant protocol must be given to identify the relay. Each relay in a network must have a unique address. 19200 The baud rate set on all of the relays connected to the control system must be the same as the one set on the master device. EVEN The parity set on all of the relays connected to the control system must be the same and in accordance with the master device. 75 110 150 300 COM3 Setting Chapter 4 - Page 11 of 96 7SR220 Technical Manual Setting Name Range/Options COM3 Line Idle LIGHT ON LIGHT OFF COM3 ON OFF Data Echo#1 Setting Notes Sets the fibre optic line idle state. LIGHT OFF Set to ON when relays are connected in a fibre-optic ring configuration. OFF Local Local or Remote Remote COM3 Mode Default Refer to Appendix 1, page 95, for further explanation Remote The following settings, on the COMMUNICATIONS MENU, must be configured when using the fibre Optic Com4 interface Setting Name Range/Options OFF IEC60870-5-103 MODBUS-RTU COM4 Protocol Default IEC60870-5-103 DNP3 COM4 Station Address 0 - 254 for IEC60870-5-103 1 - 247 for Modbus RTU 0 - 65534 for DNP3.0 75 110 150 300 600 1200 2400 4800 COM4 Baud Rate NONE ODD EVEN COM4 Line Idle LIGHT ON LIGHT OFF COM4 ON OFF #1 Data Echo COM4 Mode Local Local or Remote Remote Notes The protocol used to communicate on the standard RS485 connection. 0 An address within the range of the relevant protocol must be given to identify the relay. Each relay in a network must have a unique address. 19200 The baud rate set on all of the relays connected to the control system must be the same as the one set on the master device. EVEN The parity set on all of the relays connected to the control system must be the same and in accordance with the master device. 9600 19200 38400 COM4 Parity Setting LIGHT OFF OFF Remote Sets the fibre optic line idle state. Set to ON when relays are connected in a fibre-optic ring configuration. Refer to Appendix 1, page 95, for further explanation #1 In ring mode, echo = on, the whole fibre optic data comms link will be interrupted if the relay element is withdrawn from the case. Chapter 4 - Page 12 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Rx Rx Tx Tx RS232 to Fibre Optic Converter RS232 straight through cable Computer or Control System USB or 9 pin male D connector Tx Rx Rx Tx 62.5/125m fibre optic with ST connectors 25 pin male D connector Fig. 2-3 Communication to Multiple Devices using Fibre-optic Ring Network To Control System 7SG24 Sigma 1 Tx Master Rx Rx Rx Tx Tx Tx Rx Tx Rx Tx Rx RS232 straight through cable Tx Rx Computer or Control System USB or 9 pin male D connector Rx 62.5/125m fibre optic with ST connectors Tx 25 pin male D connector Fig. 2-4 Communication to Multiple Devices from Control System and Laptop using Fibre-optic Star Network 2.5 Optional Rear RS485 (COM3) The following settings, on the COMMUNICATIONS MENU, must be configured when using the electrical 2-wire RS485 Com3 interface. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 13 of 96 7SR220 Technical Manual Setting Name COM3 Protocol Range/Options OFF IEC60870-5-103 MODBUS-RTU Default Setting The protocol used to communicate on the standard RS485 connection. IEC60870-5-103 DNP3 COM3 Station Address 0 - 254 for IEC60870-5-103 1 - 247 for Modbus RTU 0 - 65534 for DNP3.0 0 An address within the range of the relevant protocol must be given to identify the relay. Each relay in a network must have a unique address. 19200 The baud rate set on all of the relays connected to the control system must be the same as the one set on the master device. EVEN The parity set on all of the relays connected to the control system must be the same and in accordance with the master device. 75 110 150 300 COM3 600 1200 2400 4800 Baud Rate 9600 19200 38400 57600 115200 COM3 Parity NONE ODD EVEN COM3 Line Idle LIGHT ON LIGHT OFF COM3 ON OFF Data Echo#1 COM3 Mode LIGHT OFF OFF Local Local or Remote Remote Notes LIGHT OFF Not applicable for RS 485 or RS 232 option, set to OFF. OFF Not applicable for RS 485 or RS 232 option, set to OFF. Refer to Appendix 1, page 95, for further explanation Remote 7SR24 COMMS MODULE IRIG-B COM3 RS485 Screened twisted pair GND TERM USB or 9 pin male D connector Laptop computer B A RS232 straight through cable Fig. 2-5 Additional (Optional) Rear RS485 + IRIG-B Connection to a PC 2.6 Optional Rear RS232 (COM3) The following settings, on the COMMUNICATIONS MENU, must be configured when using the electrical RS232 Com3 interface. Chapter 4 - Page 14 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Setting Name COM3 Protocol COM3 Station Address Range/Options OFF IEC60870-5-103 MODBUS-RTU DNP3 0 - 254 for IEC60870-5-103 1 - 247 for Modbus RTU 0 - 65534 for DNP3.0 Default Setting The protocol used to communicate on the standard RS485 connection. IEC60870-5-103 0 An address within the range of the relevant protocol must be given to identify the relay. Each relay in a network must have a unique address. 19200 The baud rate set on all of the relays connected to the control system must be the same as the one set on the master device. EVEN The parity set on all of the relays connected to the control system must be the same and in accordance with the master device. 75 110 150 300 COM3 600 1200 2400 4800 Baud Rate 9600 19200 38400 57600 115200 COM3 Parity NONE ODD EVEN COM3 Line Idle LIGHT ON LIGHT OFF COM3 ON OFF Data Echo#1 COM3 Mode LIGHT OFF OFF Local Local or Remote Remote Notes LIGHT OFF Not applicable for RS 485 or RS 232 option, set to OFF. OFF Not applicable for RS 485 or RS 232 option, set to OFF. Remote Refer to Appendix 1, page 95, for further explanation 7SR24 COMMS MODULE IRIG-B COM3 USB or 9 pin male D connector Laptop computer RS232 cross-over cable or RS232 to USB converter cable Fig. 2-6 Additional (Optional) Rear RS232 + IRIG-B Connection to a PC Pin Relay Function 1 Not Connected 2 Receive Data (RXD) 3 Transmit Data (TXD) (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 15 of 96 7SR220 Technical Manual Pin Relay Function 4 Output Supply +5V 50mA 5 Signal Ground (GND) 6 Output Supply +5V 50mA 7 Linked to 8 (volts free) 8 Linked to 7 (volts free) 9 Output Supply +5V 50mA Fig. 2-7 RS232 Data Comms Pin Connections 2.7 Optional Rear EN100 Ethernet Module (COM3) The optional ethernet interface is primarily provided for support of IEC 61850 Protocol. Support for IEC 60870-5-103 is also provided over this interface to allow connection with Reydisp Evolution and Reydisp Manager Software for interrogation, editing and download of relay settings and other data. Ordering options are available with two RJ45 electrical connectors or with two duplex LC fibre optic connectors. Setting Name LAN Protocol Range/Options OFF IEC60870-5-103 Default Setting IEC60870-5-103 Notes Sets the protocol used to communicate on the LAN port. If this setting is set to off, access to relay data using Reydisp Evolution and Reydisp Manager Software via the Ethernet interface is not available. Connections to the optional EN100 Ethernet module are made on the rear underside of the relay. Connections are made to either RJ45 sockets (electrical) or Duplex LC (fibre optic) connectors. Fibre cables should be 62.5/125m (or 50/125m) multimode with LC connectors. The two types of EN100 module work slightly differently. The optical version contains an Ethernet switch to control the two channels. The switch will manage data from either channel as an Ethernet switch would in a network. The electrical version connects through one channel until it detects a break in the data traffic. After a delay it will swap to the other channel to try and re-establish communication. Either method can be thought of as providing for redundancy. While a 61850 session is established, an operator can simultaneously connect to the device via Reydisp Evolution or a web browser through the EN100 module. Configuration of 61850 communication is via the Reydisp Manager software package. Chapter 4 - Page 16 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Ethernet - EN100-E Ethernet - EN100-O Ch 1 Ch 2 Ch 1 LED yellow LED yellow LED green Ch 2 LED green EN100 Module - RJ45 Interface EN100 Module - Duplex-LC Interface Green LED (Physical Link) Off - No link On - Link present Yellow LED (Activity) Off - No traffic On/flashing - Traffic Fig. 2-8 EN100 Ethernet Module (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 17 of 96 7SR220 Technical Manual Chapter 4 - Page 18 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 3. IEC 60870-5-103 Definitions 3.1 Introduction This section describes the IEC 60870-5-103 protocol implementation in the relays. This protocol is used for the communication with Reydisp software and can also be used for communication with a suitable control system. The control system or local PC acts as the master in the system with the relay operating as a slave responding to the master's commands. The implementation provides event information, time synchronising, commands and measurands and also supports the transfer of disturbance records. This protocol can be set to use any or all of the relays hardware interfaces (USB, Fibre Optic, RS232, RS485 and Ethernet) where fitted and is the standard protocol used by the USB port. The relay can communicate simultaneously on all ports regardless of protocol used. The Station Address of the port being used must be set to a suitable address within the range 0 - 254 to enable communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 19 of 96 7SR220 Technical Manual 3.2 Cause of Transmission The cause of transmission (COT) column of the "Information Number and Function" table lists possible causes of transmission for these frames. The following abbreviations are used: Abbreviation Description SE spontaneous event T test mode GI general interrogation Loc local operation Rem remote operation Ack command acknowledge Nak Negative command acknowledge Note: Events listing a GI cause of transmission can be raised and cleared; other events are raised only. Chapter 4 - Page 20 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 3.3 Application Service Data Unit (ASDU) Type The Application Service Data Unit (ASDU) column of the "Information Number and Function" table lists the possible ASDUs returned for a point. ASDU # Description 1 Time tagged message (monitor direction) 2 Time tagged message (relative time) (monitor direction) 3.1 Measurands I 4 Time-tagged measurands with relative time 5 Identification message 6 Time synchronisation 7 General Interrogation Initialization 9 Measurands II 20 General command (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 21 of 96 7SR220 Technical Manual 3.4 Point List The following sub-sections contain tables listing the data points available via the IEC60870-5-103 protocol. The information shown below is the default configuration. The information shown below is the default configuration. 3.4.1 Event Function (FUN) & Information (INF) Numbers The following Event EVT and INF numbers apply to this device. FUN INF Description ASDU COT 1 SE, GI 60 4 Remote Mode 60 5 Out Of Service Mode 60 6 Local Mode 60 7 Local & Remote 60 12 Control Received 1 SE 60 13 Command Received 1 SE 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 60 128 Cold Start 1 SE 60 129 Warm Start 1 SE 60 130 Re-Start 1 SE 60 131 Expected Restart 1 SE, GI 60 132 Unexpected Restart 1 SE, GI 60 133 Reset Start Count 60 135 Trigger Storage 1 SE 60 136 Clear Waveform Records 1 SE 60 137 Clear Fault Records 1 SE 60 138 Clear Event Records 1 SE 60 140 Demand metering reset 60 170 General Alarm 1 1 SE, GI 60 171 General Alarm 2 1 SE, GI 60 172 General Alarm 3 1 SE, GI 60 173 General Alarm 4 1 SE, GI 60 174 General Alarm 5 1 SE, GI 60 175 General Alarm 6 1 SE, GI 60 176 General Alarm 7 1 SE, GI 60 177 General Alarm 8 1 SE, GI 60 178 General Alarm 9 1 SE, GI 60 179 General Alarm 10 1 SE, GI 60 180 General Alarm 11 1 SE, GI 60 181 General Alarm 12 1 SE, GI 60 182 Quick Logic E1 1 SE, GI 60 183 Quick Logic E2 1 SE, GI Chapter 4 - Page 22 of 96 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak (c) 2017 Siemens Protection Devices Limited FUN Chapter 4 - Data Communications Definitions Description ASDU COT INF 60 184 Quick Logic E3 1 SE, GI 60 185 Quick Logic E4 1 SE, GI 60 186 Quick Logic E5 1 SE, GI 60 187 Quick Logic E6 1 SE, GI 60 188 Quick Logic E7 1 SE, GI 60 189 Quick Logic E8 1 SE, GI 60 190 Quick Logic E9 1 SE, GI 60 191 Quick Logic E10 1 SE, GI 60 192 Quick Logic E11 1 SE, GI 60 193 Quick Logic E12 1 SE, GI 60 194 Quick Logic E13 1 SE, GI 60 195 Quick Logic E14 1 SE, GI 60 196 Quick Logic E15 1 SE, GI 60 197 Quick Logic E16 1 SE, GI 61 1 General Alarm 13 1 SE, GI 61 2 General Alarm 14 1 SE, GI 61 3 General Alarm 15 1 SE, GI 61 4 General Alarm 16 1 SE, GI 61 5 General Alarm 17 1 SE, GI 61 6 General Alarm 18 1 SE, GI 61 7 General Alarm 19 1 SE, GI 61 8 General Alarm 20 1 SE, GI 70 5 Binary Input 5 1 SE, GI 70 6 Binary Input 6 1 SE, GI 70 7 Binary Input 7 1 SE, GI 70 8 Binary Input 8 1 SE, GI 70 9 Binary Input 9 1 SE, GI 70 10 Binary Input 10 1 SE, GI 70 11 Binary Input 11 1 SE, GI 70 12 Binary Input 12 1 SE, GI 70 13 Binary Input 13 1 SE, GI 75 1 Virtual Input 1 1 SE, GI 75 2 Virtual Input 2 1 SE, GI 75 3 Virtual Input 3 1 SE, GI 75 4 Virtual Input 4 1 SE, GI 75 5 Virtual Input 5 1 SE, GI 75 6 Virtual Input 6 1 SE, GI 75 7 Virtual Input 7 1 SE, GI 75 8 Virtual Input 8 1 SE, GI 75 9 Virtual Input 9 1 SE, GI 75 10 Virtual Input 10 1 SE, GI 75 11 Virtual Input 11 1 SE, GI 75 12 Virtual Input 12 1 SE, GI 75 13 Virtual Input 13 1 SE, GI 75 14 Virtual Input 14 1 SE, GI 75 15 Virtual Input 15 1 SE, GI 75 16 Virtual Input 16 1 SE, GI 80 1 Binary Output 1 1 SE, GI (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 23 of 96 7SR220 Technical Manual FUN Description INF ASDU COT 20 Ack, Nak 80 2 Binary Output 2 80 3 Binary Output 3 80 4 Binary Output 4 80 5 Binary Output 5 80 6 Binary Output 6 80 7 Binary Output 7 80 8 Binary Output 8 80 9 Binary Output 9 80 10 Binary Output 10 80 11 Binary Output 11 80 12 Binary Output 12 80 13 Binary Output 13 80 14 Binary Output 14 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 90 1 LED 1 1 SE, GI 90 2 LED 2 1 SE, GI 90 3 LED 3 1 SE, GI 90 4 LED 4 1 SE, GI 90 5 LED 5 1 SE, GI 90 6 LED 6 1 SE, GI 90 7 LED 7 1 SE, GI 90 8 LED 8 1 SE, GI 90 9 LED 9 1 SE, GI 90 10 LED 10 1 SE, GI 90 11 LED 11 1 SE, GI 90 12 LED 12 1 SE, GI 90 13 LED 13 1 SE, GI 90 14 LED 14 1 SE, GI 90 15 LED 15 1 SE, GI 90 16 LED 16 1 SE, GI 91 1 LED PU 1 1 SE, GI 91 2 LED PU 2 1 SE, GI 91 3 LED PU 3 1 SE, GI 91 4 LED PU 4 1 SE, GI 91 5 LED PU 5 1 SE, GI 91 6 LED PU 6 1 SE, GI Chapter 4 - Page 24 of 96 (c) 2017 Siemens Protection Devices Limited FUN Chapter 4 - Data Communications Definitions Description ASDU COT INF 91 7 LED PU 7 1 SE, GI 91 8 LED PU 8 1 SE, GI 91 9 LED PU 9 1 SE, GI 91 10 LED PU 10 1 SE, GI 91 11 LED PU 11 1 SE, GI 91 12 LED PU 12 1 SE, GI 91 13 LED PU 13 1 SE, GI 91 14 LED PU 14 1 SE, GI 91 15 LED PU 15 1 SE, GI 1 SE, GI 91 16 LED PU 16 160 2 Reset FCB 5 SE 160 3 Reset CU 5 SE 160 4 Start/Restart 5 SE 160 5 Power On 1 SE, GI 1 SE, GI 160 16 Auto-reclose active 160 19 LED Reset 160 22 Settings changed 160 23 Setting G1 selected 160 24 Setting G2 selected 160 25 Setting G3 selected 160 26 Setting G4 selected 160 27 Binary Input 1 1 SE, GI 160 28 Binary Input 2 1 SE, GI 160 29 Binary Input 3 1 SE, GI 160 30 Binary Input 4 1 SE, GI 160 36 Trip Circuit Fail 1 SE, GI 160 38 VT Fuse Failure 1 SE, GI 160 51 Earth Fault Forward/Line 2 SE, GI 160 52 Earth Fault Reverse/Busbar 2 SE, GI 160 64 Start/Pick-up L1 2 SE, GI 160 65 Start/Pick-up L2 2 SE, GI 160 66 Start/Pick-up L3 2 SE, GI 160 67 Start/Pick-up N 2 SE, GI 160 68 General Trip 2 SE 160 69 Trip L1 2 SE 160 70 Trip L2 2 SE 160 71 Trip L3 2 SE 160 73 Fault Impedance 1 SE 160 74 Fault Forward/Line 2 SE, GI 160 75 Fault Reverse/Busbar 2 SE, GI 160 84 General Start/Pick-up 2 SE, GI 160 85 Breaker Failure 2 SE (c) 2017 Siemens Protection Devices Limited 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak Chapter 4 - Page 25 of 96 7SR220 Technical Manual FUN INF Description ASDU COT 160 90 Trip I> 2 SE 160 91 Trip I>> 2 SE 160 92 Trip In> 2 SE 93 Trip In>> 2 SE 160 160 128 CB on by auto reclose 1 SE 183 10 51-1 2 SE, GI 183 11 50-1 2 SE, GI 183 12 51N-1 2 SE, GI 183 13 50N-1 2 SE, GI 183 14 51G-1 2 SE, GI 183 15 50G-1 2 SE, GI 183 16 51-2 2 SE, GI 183 17 50-2 2 SE, GI 183 18 51N-2 2 SE, GI 183 19 50N-2 2 SE, GI 183 20 51G-2 2 SE, GI 183 21 50G-2 2 SE, GI 183 22 51-3 2 SE, GI 183 23 50-3 2 SE, GI 183 24 51N-3 2 SE, GI 183 25 50N-3 2 SE, GI 183 26 51G-3 2 SE, GI 183 27 50G-3 2 SE, GI 183 28 51-4 2 SE, GI 183 29 50-4 2 SE, GI 183 30 51N-4 2 SE, GI 183 31 50N-4 2 SE, GI 183 32 51G-4 2 SE, GI 183 33 50G-4 2 SE, GI 183 34 50BF Stage 2 2 SE, GI 183 35 49-Alarm 2 SE, GI 183 36 49-Trip 2 SE, GI 183 40 60 CTS 2 SE, GI 183 41 51SEF-1 2 SE, GI 183 42 50SEF-1 2 SE, GI 183 43 51SEF-2 2 SE, GI 183 44 50SEF-2 2 SE, GI 183 45 51SEF-3 2 SE, GI 183 46 50SEF-3 2 SE, GI 183 47 51SEF-4 2 SE, GI 183 48 50SEF-4 2 SE, GI 183 49 SEF Out 183 50 46IT 2 SE, GI 183 51 46DT 2 SE, GI 183 52 64H 2 SE, GI 183 53 E/F Out 183 56 50BF Stage 1 Chapter 4 - Page 26 of 96 2 SE, GI 20 Ack, Nak 2 SE, GI 20 Ack, Nak 2 SE, GI (c) 2017 Siemens Protection Devices Limited FUN Chapter 4 - Data Communications Definitions Description ASDU COT INF 183 60 47-1 2 SE, GI 183 61 47-2 2 SE, GI 183 62 37-1 2 SE, GI 183 63 37-2 2 SE, GI 183 64 37G-1 2 SE, GI 183 65 37G-2 2 SE, GI 183 66 37SEF-1 2 SE, GI 183 67 37SEF-2 2 SE, GI 183 70 46BC 2 SE, GI 183 81 27/59-1 2 SE, GI 183 82 27/59-2 2 SE, GI 183 83 27/59-3 2 SE, GI 183 84 27/59-4 2 SE, GI 183 85 59NIT 2 SE, GI 183 86 59NDT 2 SE, GI 183 87 Vx27/59 2 SE, GI 183 90 81-1 2 SE, GI 183 91 81-2 2 SE, GI 183 92 81-3 2 SE, GI 183 93 81-4 2 SE, GI 183 94 81-5 2 SE, GI 183 95 81-6 2 SE, GI 183 96 81HBL2 1 SE, GI 183 100 CB Alarm 1 SE, GI 183 101 Trip Circuit Fail 1 2 SE, GI 183 102 Trip Circuit Fail 2 2 SE, GI 183 103 Trip Circuit Fail 3 2 SE, GI 183 110 Setting G5 selected 183 111 Setting G6 selected 183 112 Setting G7 selected 183 113 Setting G8 selected 183 114 Close CB Failed 1 SE, GI 183 115 Open CB Failed 1 SE, GI 183 116 Reclaim 1 SE, GI 183 117 Lockout 1 SE, GI 183 119 Successful DAR Close 1 SE 183 120 Successful Man Close 1 SE 183 121 HotLine Working 183 122 Inst Protection Out 183 123 CB Total Trip Count 1 SE, GI 183 124 CB Delta Trip Count 1 SE, GI 183 125 CB Count To AR Block 1 SE, GI (c) 2017 Siemens Protection Devices Limited 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak Chapter 4 - Page 27 of 96 7SR220 Technical Manual FUN INF Description ASDU COT 1 SE 183 126 Reset CB Total Trip Count 183 127 Reset CB Delta Trip Count 183 128 Reset CB Count To AR Block 183 129 I^2t CB Wear 183 130 Reset I^2t CB Wear 183 131 79 AR In progress 1 SE, GI 183 132 CB Frequent Ops Count 1 SE, GI 183 133 Reset CB Frequent Ops Count 183 136 CB On By Manual Close 1 SE 183 137 CB on by auto reclose 1 SE, GI 183 140 Cold Load Active 1 SE, GI 183 141 P/F Inst Protection Inhibited 1 SE, GI 183 142 E/F Inst Protection Inhibited 1 SE, GI 183 143 SEF Inst Protection Inhibited 1 SE, GI 183 144 Ext Inst Protection Inhibited 1 SE, GI 183 163 Trip Time Alarm 183 164 Close Circuit Fail 1 2 SE, GI 183 165 Close Circuit Fail 2 2 SE, GI 183 166 Close Circuit Fail 3 2 SE, GI 183 167 Close Circuit Fail 2 SE, GI 183 168 Distance To Fault 1 SE 183 169 Distance To Fault Percent 1 SE 183 170 Fault Reactance 1 SE 183 171 60 CTS-I 2 SE, GI 183 172 Act Energy Exp 4 SE 183 173 Act Energy Imp 4 SE 183 174 React Energy Exp 4 SE 183 175 React Energy Imp 4 SE 183 176 Reset Energy Meters 183 177 Active Exp Meter Reset 1 SE 183 178 Active Imp Meter Reset 1 SE 183 179 Reactive Exp Meter Reset 1 SE 183 180 Reactive Imp Meter Reset 1 SE 183 181 CB Total Trip Count 4 SE 183 182 CB Delta Trip Count 4 SE 183 183 CB Count To AR Block 4 SE 183 184 CB Freq Ops Count 4 SE 183 198 25 Check Sync 1 SE, GI 183 199 25 System Sync 1 SE, GI 183 200 25 Close On Zero 1 SE, GI 183 201 25 System Split 1 SE, GI 183 202 25 Live Line 1 SE, GI 183 203 25 Live Bus 1 SE, GI Chapter 4 - Page 28 of 96 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE, GI 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 1 SE 20 Ack, Nak (c) 2017 Siemens Protection Devices Limited FUN Chapter 4 - Data Communications Definitions Description ASDU COT INF 183 204 25 Line U/V 1 SE, GI 183 205 25 Bus U/V 1 SE, GI 183 206 25 Voltage Dif > 1 SE, GI 183 207 25 CS Slip Freq > 1 SE, GI 183 208 25 SS Slip Freq > 1 SE, GI 183 209 25 COZ Slip Freq > 1 SE, GI 183 210 25 In Sync 1 SE, GI 183 211 25 CS In Progress 1 SE, GI 183 212 25 SS In Progress 1 SE, GI 183 213 25 COZ In Progress 1 SE, GI 183 214 25 System Split LO 1 SE, GI 183 215 60VTF-Bus 1 SE, GI 183 217 Man Override Sync 183 218 79 Override Sync 183 219 Dead Line Close 1 SE, GI 183 220 Dead Bus Close 1 SE, GI 183 221 Wattmetric Po> 1 SE, GI 183 222 37-PhA 2 SE, GI 183 223 37-PhB 2 SE, GI 183 224 37-PhC 2 SE, GI 183 231 50BF-PhA 2 SE, GI 183 232 50BF-PhB 2 SE, GI 183 233 50BF-PhC 2 SE, GI 183 234 50BF-EF 2 SE, GI 183 235 79 Last Trip Lockout 2 SE, GI 183 237 CB DBI 1 SE, GI 183 238 CB Travelling 1 SE, GI 183 239 In Fault Current 4 SE 183 240 Ia Fault Current 4 SE 183 241 Ib Fault Current 4 SE 183 242 Ic Fault Current 4 SE 183 243 Ig Fault Current 4 SE 183 244 Isef Fault Current 4 SE 183 245 Va Fault Voltage 4 SE 183 246 Vb Fault Voltage 4 SE 183 247 Vc Fault Voltage 4 SE 183 249 60 CTS-I-PhA 2 SE, GI 183 250 60 CTS-I-PhB 2 SE, GI 183 251 60 CTS-I-PhC 2 SE, GI 183 252 Trip PhA 2 SE, GI 183 253 Trip PhB 2 SE, GI 183 254 Trip PhC 2 SE, GI 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 185 9 CB Phase A Trip Count 4 SE 185 10 CB Phase B Trip Count 4 SE 185 11 CB Phase C Trip Count 4 SE 185 12 CB E/F Trip Count 4 SE (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 29 of 96 7SR220 Technical Manual FUN INF Description ASDU COT 185 37 27/59 PhA 2 SE, GI 185 38 27/59 PhB 2 SE, GI 185 39 27/59 PhC 2 SE, GI 185 43 General Trip 2 SE, GI 185 44 32-1 1 SE, GI 185 45 32-2 1 SE, GI 185 46 32S-1 1 SE, GI 185 47 32S-2 1 SE, GI 185 48 55-1 1 SE, GI 49 55-2 1 SE, GI 185 185 171 User Output 1 1 SE, GI 185 172 User Output 2 1 SE, GI 185 173 User Output 3 1 SE, GI 185 174 User Output 4 1 SE, GI 185 175 User Output 5 1 SE, GI 185 176 User Output 6 1 SE, GI 185 177 User Output 7 1 SE, GI 185 178 User Output 8 1 SE, GI 185 179 User Output 9 1 SE, GI 185 180 User Output 10 1 SE, GI 185 181 User Output 11 1 SE, GI 185 182 User Output 12 1 SE, GI 185 183 User Output 13 1 SE, GI 185 184 User Output 14 1 SE, GI 185 185 User Output 15 1 SE, GI 185 186 User Output 16 1 SE, GI 185 187 User Output 17 1 SE, GI 185 188 User Output 18 1 SE, GI 185 189 User Output 19 1 SE, GI 185 190 User Output 20 1 SE, GI 185 191 User Output 21 1 SE, GI 185 192 User Output 22 1 SE, GI 185 193 User Output 23 1 SE, GI 185 194 User Output 24 1 SE, GI 185 195 User Output 25 1 SE, GI 185 196 User Output 26 1 SE, GI 185 197 User Output 27 1 SE, GI 185 198 User Output 28 1 SE, GI 185 199 User Output 29 1 SE, GI 185 200 User Output 30 1 SE, GI 185 201 User Output 31 1 SE, GI 185 202 User Output 32 1 SE, GI 185 238 E/F In 185 239 SEF In 185 241 Start Count Alarm 1 SE, GI 185 242 21LB-3P Fwd 1 SE, GI 185 243 21LB-3P Rev 1 SE, GI Chapter 4 - Page 30 of 96 2 SE, GI 20 Ack, Nak 2 SE, GI 20 Ack, Nak (c) 2017 Siemens Protection Devices Limited FUN Chapter 4 - Data Communications Definitions Description ASDU COT INF 185 244 21LB-1P Fwd 1 SE, GI 185 245 21LB-1P Rev 1 SE, GI 185 246 81HBL5 1 SE, GI 186 1 50AFD PhA 1 SE, GI 186 2 50AFD PhB 1 SE, GI 186 3 50AFD PhC 1 SE, GI 186 4 50AFD 1 SE, GI 186 5 AFD Zone 1 Flash 1 SE, GI 186 6 AFD Zone 1 1 SE, GI 186 7 AFD Zone 2 Flash 1 SE, GI 186 8 AFD Zone 2 1 SE, GI 186 9 AFD Zone 3 Flash 1 SE, GI 186 10 AFD Zone 3 1 SE, GI 186 11 AFD Zone 4 Flash 1 SE, GI 186 12 AFD Zone 4 1 SE, GI 186 13 AFD Zone 5 Flash 1 SE, GI 186 14 AFD Zone 5 1 SE, GI 186 15 AFD Zone 6 Flash 1 SE, GI 186 16 AFD Zone 6 1 SE, GI 186 17 AFD Zone1 Count 4 SE 186 18 AFD Zone2 Count 4 SE 186 19 AFD Zone3 Count 4 SE 186 20 AFD Zone4 Count 4 SE 186 21 AFD Zone5 Count 4 SE 186 22 AFD Zone6 Count 4 SE 200 1 CB 1 200 6 CB 1 Opened 200 7 CB 1 Closed 200 150 User SP Command 1 200 151 User SP Command 2 200 152 User SP Command 3 200 153 User SP Command 4 200 154 User SP Command 5 200 155 User SP Command 6 200 156 User SP Command 7 200 157 User SP Command 8 200 158 User DP Command 1 (c) 2017 Siemens Protection Devices Limited 1 SE 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE, GI 20 Ack, Nak 1 SE Chapter 4 - Page 31 of 96 7SR220 Technical Manual FUN Description INF ASDU COT 20 Ack, Nak 1 SE 200 159 User DP Command 2 200 160 User DP Command 3 200 161 User DP Command 4 200 162 User DP Command 5 200 163 User DP Command 6 200 164 User DP Command 7 200 165 User DP Command 8 200 200 CB 1 Trip & Reclose 200 201 CB 1 Trip & Lockout 200 255 Blocked By Interlocking 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE 20 Ack, Nak 1 SE, GI 255 0 General Interrogation (GI) Initiation 7 Init. GI 255 0 General Interrogation (GI) End 8 End of GI 255 0 Time Synchronisation Time 6 Synch. 3.4.2 Measurands The following Measurand EVT and INF numbers apply to this device. FUN INF Description ASDU COT Measurand IL1,2,3, VL1,2,3, P, Q, F, VL1-2,L2-3,L3-1 --IL1 (2.4x) (Window 1%) IL2 (2.4x) (Window 1%) Cyclic Refresh rate 5 seconds or value 9 change greater than Window x %. IL3 (2.4x) (Window 1%) VL1 (1.2x) (Window 1%) 183 148 VL2 (1.2x) (Window 1%) VL3 (1.2x) (Window 1%) P (2.4x) (Window 1%) Q (2.4x) (Window 1%) F (1.2x) (Window 0.1%) VL1-2 (1.2x) (Window 1%) VL2-3 (1.2x) (Window 1%) VL3-1 (1.2x) (Window 1%) Measurand Power W 1,2,3, Power VAr1,2,3, Power Factor1,2,3, --- 183 149 W1 (2.4x) (Window 1%) W2 (2.4x) (Window 1%) W3 (2.4x) (Window 1%) Chapter 4 - Page 32 of 96 Cyclic Refresh rate 5 9 seconds or value change greater (c) 2017 Siemens Protection Devices Limited FUN Chapter 4 - Data Communications Definitions Description ASDU COT INF VAr1 (2.4x) (Window 1%) VAr2 (2.4x) (Window 1%) VAr3 (2.4x) (Window 1%) PF1 (1.2x) (Window 1%) PF2 (1.2x) (Window 1%) than Window x %. PF3 (1.2x) (Window 1%) 183 216 Measurand Vx, Bus Freq, Phase Diff, Diff Volts and Slip Freq --Vx (1.2x) (Window 0%) Bus Freq (1.2x) (Window 0%) Phase Diff (1.2x) (Window 0%) Diff Volts (1.2x) (Window 0%) Slip Freq (1.2x) (Window 0%) --Note - Phase difference is stored as -1 to +1 as a multiple of 180deg nominal Cyclic Refresh rate 5 seconds or value 9 change greater than Window x %. Measurand Max Ia,b,c, Van,bn,cn, P, Q, Vab,bc,ca --Ia Max (2.4x) (Window 1%) Ib Max (2.4x) (Window 1%) Ic Max (2.4x) (Window 1%) Van Max1 (1.2x) (Window 1%) Vbn Max2 (1.2x) (Window 1%) 183 236 Vcn Max3 (1.2x) (Window 1%) P Max (2.4x) (Window 1%) Q Max (2.4x) (Window 1%) Vab Max (1.2x) (Window 1%) Vbc Max (1.2x) (Window 1%) Vca Max (1.2x) (Window 1%) Cyclic Refresh rate 5 seconds or value 9 change greater than Window x %. --Voltages only supported on 7SR1915/6 3.4.3 Disturbance Recorder Actual Channel (ACC) Numbers The following Disturbance Recorder channel numbers apply to this device. FUN ACC Description 182 1 V1 182 2 V2 182 3 V3 182 4 Vx 182 5 Ia 182 6 Ib 182 7 Ic 182 8 Ig1 182 9 Ig2 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 33 of 96 7SR220 Technical Manual Chapter 4 - Page 34 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 4. MODBUS Definitions 4.1 Introduction This section describes the MODBUS-RTU protocol implementation in the relays. This protocol is used for communication with a suitable control system. This protocol can be set to use any or all of the relays hardware interfaces (USB, Fibre Optic, RS232 and RS485) where fitted. The relay can communicate simultaneously on all ports regardless of protocol used. The Station Address of the port being used must be set to a suitable address within the range 1 - 247 to enable communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting. Communication via MODBUS over Ethernet requires external devices. Please refer to the documents TCPIP Catalogue Sheet and TCPIP Interface Technical Guidance Notes for more information. Definitions with shaded area are not available on all relay models. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 35 of 96 7SR220 Technical Manual 4.2 MODBUS Register Data Types 4.2.1 FLOAT_IEEE_754 The float data type conforms to the IEEE 754 floating point definition. This specifies that 32 bits of data will be formatted as a sign bit in the most significant bit (MSB) followed by an 8 bit exponent then a 23 bit mantissa, down to the least significant bit (LSB). MSB LSB Sign Exponent Mantissa FLOAT_IEEE_754 IN DETAIL The exponent is an 8 bit unsigned integer. To allow for negative exponents, it is offset by 127. Therefore the actual exponent is e - 127. The following table shows a detailed layout of the exponent. 27 26 25 24 23 22 21 20 128 64 32 16 8 4 2 1 The mantissa contains the fractional part of a number normalized to the form 1.xyz i.e. in this instance xyz. The mantissa represents the binary fraction of a number; therefore the MSB represents 2-1 (or 1/21 ) and its LSB 2-23 (or 1/223). The following table shows a detailed layout of the mantissa. 1 1 1 1 1 1 1 21 22 23 24 221 222 223 0.5 0.25 0.125 0.0625 4.768e-7 2.384e-7 1.192e-7 As an example 1,000,000 would be represented as follows (hex 49742400). 4 0 1 9 0 0 1 0 7 0 1 0 1 4 1 1 0 2 1 0 0 0 0 4 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 This calculates out as: Sign = +1 Exponent = 100100102 = 128 + 16 + 2 = 146, subtract 127 = 19. 1 1 + Mantissa = 1 + 21 1 + 22 1 + 23 25 = 1 + 213 1 + 210 213 7433 4096 + 2048 + 1024 + 256 + 8 + 1 = 1 + 1 + 213 = 1.907348632 Therefore Sign * 2Exponent * Mantissa = 1 * 219 * 1.907348632 = 1000000 FLOAT_IEEE_754 & MODBUS In this MODBUS implementation the 32 bit float is stored in 2 16 registers in Big-Endian format. As an example, if we take the hex representation of 1,000,000 as a float (from above) we have 49742400h. Assume this is stored in the registers 30001 and 30002, it would look as follows. Address 30001 Chapter 4 - Page 36 of 96 Value 4974 (c) 2017 Siemens Protection Devices Limited Address Chapter 4 - Data Communications Definitions Value 30002 2400 On reception these two registers should be interpreted in the correct order as IEEE754 floating point representation. 4.2.2 FP_32BITS_3DP The FP_32BITS_3DP is a 32 bit integer fixed point value, containing 3 decimal places of information. It is used to send a real value to 3 decimal places as an integer. For example, if the value in a device is 123.456 it will be sent as 123456. As it is an integer, negative numbers are sent as 2's complement. FP_32BITS_3DP & MODBUS In this MODBUS implementation the 32 bit value is stored in 2 16 registers in Big-Endian format. As an example, if we take the hex representation of 123456, we have 1E240h. Assume this is stored in the registers 30001 and 30002, it would look as follows: Address Value 30001 1 30002 E240 On reception these two registers should be interpreted in the correct order as a 32 bit integer. 4.2.3 UINT32 The UINT32 is a signed 32 bit integer. As it is an integer, negative numbers are sent as 2's complement. UINT32 & MODBUS In this MODBUS implementation the 32 bit value is stored in 2 16 bit registers in Big-Endian format. As an example, if we take the hex representation of -123456, in 2's complement, we have FFFE1DC0h. Assume this is stored in the registers 30001 and 30002, it would look as follows: Address Value 30001 FFFE 30002 1DC0 On reception these two registers should be interpreted in the correct order as a 32 bit integer. 4.2.4 UINT16 The UINT16 is a signed 16 bit integer. As it is an integer, negative numbers are sent as 2's complement. UINT16 & MODBUS In this MODBUS implementation the 16 bit value is stored in a 16 bit register in Big-Endian format. As an example, if we take the hex representation of 5678 we have 162Eh. Assume this is stored in the register 30001, it would look as follows: Address 30001 Value 162E On reception this register should be interpreted as a 16 bit integer. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 37 of 96 7SR220 Technical Manual Truncation Calculations are performed as 32 bit. The 16 bit value is the lowest 16 bits of the 32 bit value. Therefore, when values overflow the returned value is the lowest 16 bits of the calculated value. For Example, if the value is 85400 = 14D98h, the value returned would be the lowest 16 bits = 4D98h which equals 19864. 4.2.5 EVENT MODBUS does not define a method for extracting events; therefore a private method has been defined based on that defined by IEC60870-5-103. The EVENT register contains the earliest event record available. The event record is 8 registers (16 bytes) of information, whose format is described below. When this record has been read it will be replaced by the next available record. Event records must be read completely; therefore the quantity value must be set to 8 before reading. Failing to do this will result in an exception code 2. If no event record is present the exception code 2 will be returned. The EVENT register should be polled regularly by the master for events. The EVENTCOUNT register can be checked periodically to determine how many events are stored. The format of the event record is defined by the zero byte. It signifies the type of record which is used to decode the event information. The zero byte can be one of the following. Format The format of the event record is defined by the zero byte. It signifies the type of record which is used to decode the event information. The zero byte can be one of the following. Type Description 1 Event 2 Event with Relative Time 4 Measurand Event with Relative Time The following table describes the fields in the event record. Key Description FUN Function Type, as defined for IEC870-5-103. INF Information Number, as defined for IEC870-5-103. DPI Measurand Event with Relative Time, values 1 = OFF, 2 = ON. ms L Time Stamp Milliseconds low byte. ms H Time Stamp Milliseconds high byte. Mi Time Stamp Minutes (MSB = invalid, time not set > 23 hours). Ho Time Stamp Hours (MSB = Summer time flag). RT L Relative Time low byte. RT H Relative Time high byte. F# L Fault Number low byte. F# H Fault Number high byte. Meas Measurand format R32.23, sent least significant byte first. The following tables show the fields in the different event records as they are returned. Byte Content 0 1 1 0 2 3 FUN INF 4 DPI 5 0 6 0 7 0 8 0 9 0 10 0 11 0 12 13 14 15 ms L ms H Mi Ho Event Type 1 Format. Chapter 4 - Page 38 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Byte 0 1 Content 2 0 2 3 4 FUN INF 5 6 DPI RT L 7 RT H 8 9 10 11 12 13 14 15 0 0 0 ms L ms H Mi Ho 8 9 10 11 12 13 14 15 0 0 0 0 ms L ms H Mi Ho F# L F# H Event Type 2 Format. Byte 0 1 Content 4 0 2 3 4 5 FUN INF 7 6 Meas Event Type 4 Format. 4.2.6 EVENTCOUNT The EVENTCOUNT register contains the current number of events in the relay's event buffer. On reception this register should be interpreted as a 16 bit integer. 4.2.7 TIME_METER The TIME_METER register contains the device's time. The time must be read or written in one step; therefore the quantity should be 4 registers. Failing to do this will result in an exception code 2. The time format is 8 bytes as follows. The following table describes the fields in the time. Key Description ms L Time Stamp Milliseconds low byte. ms H Time Stamp Milliseconds high byte. Mi Time Stamp Minutes (MSB = invalid, time not set > 23 hours). Ho Time Stamp Hours (MSB = Summer time flag). Da Time Stamp Days. Mo Time Stamp Months. Ye L Time Stamp Years low byte. Ye H Time Stamp Years high byte (Not Used). The following table shows the fields in the time as they are returned. Byte Content 0 1 ms L ms H 2 3 4 5 Mi Ho Da Mo 6 7 Ye L Ye H Time Format. 4.2.8 STR32 & STR64 4.2.9 BITSTRING A Bit-String (or Bit-Array) is a method of compactly storing a number of bits of data. In this instance we store up to 16 bit values, for example the states of binary inputs, in a single 16 bit register. The first bit value is stored in the Least Significant Bit (LSB) of the register. The 16th value would be in the Most Significant Bit (MSB). Bit values can only be zero or one. Any unused bits will be set to zero. BITSTRING & MODBUS (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 39 of 96 7SR220 Technical Manual In this MODBUS implementation the 16 bit value is stored in a 16 bit register in Big-Endian format. As an example, assume bits 1, 3, 9 and 12 are set. The binary representation of this would be 00001001000001012 giving a hex representation of 0905h. Assume this is stored in the register 30001, it would look as follows: Address 30001 Value 0905 On reception this register should be interpreted as a 16 bit integer. Chapter 4 - Page 40 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 4.3 Point List The information shown below is the default configuration. 4.3.1 Coils (Read Write Binary values) Address Description 00001 Binary Output 1 00002 Binary Output 2 00003 Binary Output 3 00004 Binary Output 4 00005 Binary Output 5 00006 Binary Output 6 00007 Binary Output 7 00008 Binary Output 8 00009 Binary Output 9 00010 Binary Output 10 00011 Binary Output 11 00012 Binary Output 12 00013 Binary Output 13 00014 Binary Output 14 00101 Setting G1 selected 00102 Setting G2 selected 00103 Setting G3 selected 00104 Setting G4 selected 00105 Setting G5 selected 00106 Setting G6 selected 00107 Setting G7 selected 00108 Setting G8 selected 00109 CB 1 00112 Auto-reclose active 00113 HotLine Working 00114 E/F Out 00115 SEF Out 00116 Inst Protection Out 00155 Remote Mode 00156 Out Of Service Mode 00157 Local Mode 00158 Local & Remote 00159 Man Override Sync 00160 79 Override Sync 00165 Reset Start Count 00180 CB 1 Opened 00181 CB 1 Closed 00200 User SP Command 1 00201 User SP Command 2 00202 User SP Command 3 00203 User SP Command 4 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 41 of 96 7SR220 Technical Manual Address Description 00204 User SP Command 5 00205 User SP Command 6 00206 User SP Command 7 00207 User SP Command 8 00208 User DP Command 1 00209 User DP Command 2 00210 User DP Command 3 00211 User DP Command 4 00212 User DP Command 5 00213 User DP Command 6 00214 User DP Command 7 00215 User DP Command 8 4.3.2 Inputs (Read Only Binary values) Address Description 10001 Binary Input 1 10002 Binary Input 2 10003 Binary Input 3 10004 Binary Input 4 10005 Binary Input 5 10006 Binary Input 6 10007 Binary Input 7 10008 Binary Input 8 10009 Binary Input 9 10010 Binary Input 10 10011 Binary Input 11 10012 Binary Input 12 10013 Binary Input 13 10102 Remote Mode 10103 Out Of Service Mode 10104 Local Mode 10105 Local & Remote 10110 General Trip 10111 Trip Circuit Fail 10112 Start/Pick-up L1 10113 Start/Pick-up L2 10114 Start/Pick-up L3 10115 General Start/Pick-up 10116 VT Fuse Failure 10117 Earth Fault Forward/Line 10118 Earth Fault Reverse/Busbar 10119 Start/Pick-up N 10120 Fault Forward/Line 10121 Fault Reverse/Busbar 10122 51-1 10123 50-1 10124 51N-1 Chapter 4 - Page 42 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Description Address 10125 50N-1 10126 51G-1 10127 50G-1 10128 51-2 10129 50-2 10130 51N-2 10131 50N-2 10132 51G-2 10133 50G-2 10134 51-3 10135 50-3 10136 51N-3 10137 50N-3 10138 51G-3 10139 50G-3 10140 51-4 10141 50-4 10142 51N-4 10143 50N-4 10144 51G-4 10145 50G-4 10146 50BF Stage 2 10147 49-Alarm 10148 49-Trip 10149 60 CTS 10150 46IT 10151 46DT 10152 47-1 10153 47-2 10154 46BC 10155 27/59-1 10156 27/59-2 10157 27/59-3 10158 27/59-4 10159 59NIT 10160 59NDT 10161 81-1 10162 81-2 10163 81-3 10164 81-4 10165 81-5 10166 81-6 10167 64H 10168 37-1 10169 37-2 10170 Vx27/59 10171 Auto-reclose active 10172 CB on by auto reclose (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 43 of 96 7SR220 Technical Manual Address Description 10173 Reclaim 10174 Lockout 10175 HotLine Working 10176 Inst Protection Out 10177 CB Total Trip Count 10178 CB Delta Trip Count 10179 CB Count To AR Block 10180 I^2t CB Wear 10181 79 AR In progress 10182 Cold Load Active 10183 E/F Out 10184 P/F Inst Protection Inhibited 10185 E/F Inst Protection Inhibited 10186 SEF Inst Protection Inhibited 10187 Ext Inst Protection Inhibited 10202 51SEF-1 10203 50SEF-1 10204 51SEF-2 10205 50SEF-2 10206 51SEF-3 10207 50SEF-3 10208 51SEF-4 10209 50SEF-4 10210 SEF Out 10211 Trip Circuit Fail 1 10212 Trip Circuit Fail 2 10213 Trip Circuit Fail 3 10214 CB Total Trip Count 10215 CB Delta Trip Count 10216 CB Count To AR Block 10217 CB Frequent Ops Count 10218 I^2t CB Wear 10219 CB 1 Opened 10220 CB 1 Closed 10283 Close Circuit Fail 1 10284 Close Circuit Fail 2 10285 Close Circuit Fail 3 10286 Close Circuit Fail 10290 General Alarm 1 10291 General Alarm 2 10292 General Alarm 3 10293 General Alarm 4 10294 General Alarm 5 10295 General Alarm 6 10296 General Alarm 7 10297 General Alarm 8 10298 General Alarm 9 10299 General Alarm 10 10300 General Alarm 11 Chapter 4 - Page 44 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Description Address 10301 General Alarm 12 10302 Quick Logic E1 10303 Quick Logic E2 10304 Quick Logic E3 10305 Quick Logic E4 10306 Quick Logic E5 10307 Quick Logic E6 10308 Quick Logic E7 10309 Quick Logic E8 10310 Quick Logic E9 10311 Quick Logic E10 10312 Quick Logic E11 10313 Quick Logic E12 10314 Quick Logic E13 10315 Quick Logic E14 10316 Quick Logic E15 10317 Quick Logic E16 10334 60 CTS-I 10335 81HBL2 10336 37G-1 10337 37G-2 10338 37SEF-1 10339 37SEF-2 10352 25 System Split 10353 25 Live Line 10354 25 Live Bus 10355 25 Line U/V 10356 25 Bus U/V 10357 25 Voltage Dif > 10358 25 CS Slip Freq > 10359 25 SS Slip Freq > 10360 25 COZ Slip Freq > 10361 25 In Sync 10362 25 CS In Progress 10363 25 SS In Progress 10364 25 COZ In Progress 10365 25 System Split LO 10366 60VTF-Bus 10367 50BF Stage 1 10368 Wattmetric Po> 10369 37-PhA 10370 37-PhB 10371 37-PhC 10378 50BF-PhA 10379 50BF-PhB 10380 50BF-PhC 10381 50BF-EF 10383 60 CTS-I-PhA (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 45 of 96 7SR220 Technical Manual Address Description 10384 60 CTS-I-PhB 10385 60 CTS-I-PhC 10390 Trip PhA 10391 Trip PhB 10392 Trip PhC 10401 27/59 PhA 10402 27/59 PhB 10403 27/59 PhC 10410 CB Alarm 10411 General Alarm 13 10412 General Alarm 14 10413 General Alarm 15 10414 General Alarm 16 10415 General Alarm 17 10416 General Alarm 18 10417 General Alarm 19 10418 General Alarm 20 10501 Virtual Input 1 10502 Virtual Input 2 10503 Virtual Input 3 10504 Virtual Input 4 10505 Virtual Input 5 10506 Virtual Input 6 10507 Virtual Input 7 10508 Virtual Input 8 10509 Virtual Input 9 10510 Virtual Input 10 10511 Virtual Input 11 10512 Virtual Input 12 10513 Virtual Input 13 10514 Virtual Input 14 10515 Virtual Input 15 10516 Virtual Input 16 10601 LED 1 10602 LED 2 10603 LED 3 10604 LED 4 10605 LED 5 10606 LED 6 10607 LED 7 10608 LED 8 10609 LED 9 10610 LED 10 10611 LED 11 10612 LED 12 10613 LED 13 10614 LED 14 10615 LED 15 10616 LED 16 Chapter 4 - Page 46 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Description Address 10701 LED PU 1 10702 LED PU 2 10703 LED PU 3 10704 LED PU 4 10705 LED PU 5 10706 LED PU 6 10707 LED PU 7 10708 LED PU 8 10709 LED PU 9 10710 LED PU 10 10711 LED PU 11 10712 LED PU 12 10713 LED PU 13 10714 LED PU 14 10715 LED PU 15 10716 LED PU 16 10800 Cold Start 10801 Warm Start 10802 Re-Start 10803 Power On 10804 Expected Restart 10805 Unexpected Restart 10806 Reset Start Count 10900 User SP Command 1 10901 User SP Command 2 10902 User SP Command 3 10903 User SP Command 4 10904 User SP Command 5 10905 User SP Command 6 10906 User SP Command 7 10907 User SP Command 8 10908 User DP Command 1 10909 User DP Command 2 10910 User DP Command 3 10911 User DP Command 4 10912 User DP Command 5 10913 User DP Command 6 10914 User DP Command 7 10915 User DP Command 8 10916 32-1 10917 32-2 10918 32S-1 10919 32S-2 10920 55-1 10921 55-2 11020 User Output 1 11021 User Output 2 11022 User Output 3 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 47 of 96 7SR220 Technical Manual Address Description 11023 User Output 4 11024 User Output 5 11025 User Output 6 11026 User Output 7 11027 User Output 8 11028 User Output 9 11029 User Output 10 11030 User Output 11 11031 User Output 12 11032 User Output 13 11033 User Output 14 11034 User Output 15 11035 User Output 16 11036 User Output 17 11037 User Output 18 11038 User Output 19 11039 User Output 20 11040 User Output 21 11041 User Output 22 11042 User Output 23 11043 User Output 24 11044 User Output 25 11045 User Output 26 11046 User Output 27 11047 User Output 28 11048 User Output 29 11049 User Output 30 11050 User Output 31 11051 User Output 32 11071 E/F In 11072 SEF In 11073 CB DBI 11074 CB Travelling 11075 Close CB Failed 11076 Open CB Failed 11077 Start Count Alarm 11078 50AFD PhA 11079 50AFD PhB 11080 50AFD PhC 11081 50AFD 11082 AFD Zone 1 Flash 11083 AFD Zone 1 11084 AFD Zone 2 Flash 11085 AFD Zone 2 11086 AFD Zone 3 Flash 11087 AFD Zone 3 11088 AFD Zone 4 Flash 11089 AFD Zone 4 11090 AFD Zone 5 Flash Chapter 4 - Page 48 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Description Address 11091 AFD Zone 5 11092 AFD Zone 6 Flash 11093 AFD Zone 6 11094 21LB-3P Fwd 11095 21LB-3P Rev 11096 21LB-1P Fwd 11097 21LB-1P Rev 11098 81HBL5 4.3.3 Input Registers (Read Only Registers) Address Description Format Mult Description 30001 Event Count EVENTCOUNT 0.000000 Events Counter 30002 Event EVENT 0.000000 8 Registers 30010 Vab Primary FP_32BITS_3DP 1.000000 Vab V 30012 Vbc Primary FP_32BITS_3DP 1.000000 Vbc V 30014 Vca Primary FP_32BITS_3DP 1.000000 Vca V 30016 Va Primary FP_32BITS_3DP 1.000000 Va V 30018 Vb Primary FP_32BITS_3DP 1.000000 Vb V 30020 Vc Primary FP_32BITS_3DP 1.000000 Vc V 30022 Va Secondary FP_32BITS_3DP 1.000000 Va V 30024 Vb Secondary FP_32BITS_3DP 1.000000 Vb V 30026 Vc Secondary FP_32BITS_3DP 1.000000 Vc V 30034 Vab Nominal FP_32BITS_3DP 1.000000 Vab Degrees 30036 Vbc Nominal FP_32BITS_3DP 1.000000 Vbc Degrees 30038 Vca Nominal FP_32BITS_3DP 1.000000 Vca Degrees 30040 Va Nominal FP_32BITS_3DP 1.000000 Va Degrees 30042 Vb Nominal FP_32BITS_3DP 1.000000 Vb Degrees 30044 Vc Nominal FP_32BITS_3DP 1.000000 Vc Degrees 30048 Vzps FP_32BITS_3DP 1.000000 Vzps V 30050 Vpps FP_32BITS_3DP 1.000000 Vpps V 30052 Vnps FP_32BITS_3DP 1.000000 Vnps V 30054 Vzps FP_32BITS_3DP 1.000000 Vzps Degrees 30056 Vpps FP_32BITS_3DP 1.000000 Vpps Degrees 30058 Vnps FP_32BITS_3DP 1.000000 Vnps Degrees 30060 Frequency FP_32BITS_3DP 1.000000 Frequency Hz 30064 Ia Primary FP_32BITS_3DP 1.000000 Ia A 30066 Ib Primary FP_32BITS_3DP 1.000000 Ib A 30068 Ic Primary FP_32BITS_3DP 1.000000 Ic A 30070 Ia Secondary FP_32BITS_3DP 1.000000 Ia A 30072 Ib Secondary FP_32BITS_3DP 1.000000 Ib A 30074 Ic Secondary FP_32BITS_3DP 1.000000 Ic A 30076 Ia Nominal FP_32BITS_3DP 1.000000 Ia xIn 30078 Ib Nominal FP_32BITS_3DP 1.000000 Ib xIn 30080 Ic Nominal FP_32BITS_3DP 1.000000 Ic xIn 30082 Ia Nominal FP_32BITS_3DP 1.000000 Ia Degrees 30084 Ib Nominal FP_32BITS_3DP 1.000000 Ib Degrees (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 49 of 96 7SR220 Technical Manual Address Description Format Mult Description 30086 Ic Nominal FP_32BITS_3DP 1.000000 Ic Degrees 30088 In Primary FP_32BITS_3DP 1.000000 In A 30090 In Secondary FP_32BITS_3DP 1.000000 In A 30092 In Nominal FP_32BITS_3DP 1.000000 In xInom 30094 Ig Primary FP_32BITS_3DP 1.000000 Ig A 30096 Ig Secondary FP_32BITS_3DP 1.000000 Ig A 30098 Ig Nominal FP_32BITS_3DP 1.000000 Ig xInom 30100 Izps Nominal FP_32BITS_3DP 1.000000 Izps xIn 30102 Ipps Nominal FP_32BITS_3DP 1.000000 Ipps xIn 30104 Inps Nominal FP_32BITS_3DP 1.000000 Inps xIn 30106 Izps Nominal FP_32BITS_3DP 1.000000 Izps Degrees 30108 Ipps Nominal FP_32BITS_3DP 1.000000 Ipps Degrees 30110 Inps Nominal FP_32BITS_3DP 1.000000 Inps Degrees 30112 Active Power A FP_32BITS_3DP 0.000001 A Phase W 30114 Active Power B FP_32BITS_3DP 0.000001 B Phase W 30116 Active Power C FP_32BITS_3DP 0.000001 C Phase W 30118 P (3P) FP_32BITS_3DP 0.000001 3 Phase W 30120 Reactive Power A FP_32BITS_3DP 0.000001 Phase A VAr 30122 Reactive Power B FP_32BITS_3DP 0.000001 Phase B VAr 30124 Reactive Power C FP_32BITS_3DP 0.000001 Phase C VAr 30126 Q (3P) FP_32BITS_3DP 0.000001 3 Phase VAr 30128 Apparent Power A FP_32BITS_3DP 0.000001 Phase A VA 30130 Apparent Power B FP_32BITS_3DP 0.000001 Phase B VA 30132 Apparent Power C FP_32BITS_3DP 0.000001 Phase C VA 30134 S (3P) FP_32BITS_3DP 0.000001 3 Phase VA 30136 Power Factor A FP_32BITS_3DP 1.000000 Phase A 30138 Power Factor B FP_32BITS_3DP 1.000000 Phase B 30140 Power Factor C FP_32BITS_3DP 1.000000 Phase C 30142 Power Factor(3P) FP_32BITS_3DP 1.000000 3 Phase 30144 Act Energy Exp UINT32 1.000000 Act Energy Exp 30146 Act Energy Imp UINT32 1.000000 Act Energy Imp 30148 React Energy Exp UINT32 1.000000 React Energy Exp 30150 React Energy Imp UINT32 1.000000 React Energy Imp 30152 Thermal Status Ph A UINT16 1.000000 Thermal Status Ph A % 30153 Thermal Status Ph B UINT16 1.000000 Thermal Status Ph B % 30154 Thermal Status Ph C UINT16 1.000000 Thermal Status Ph C % 30167 Fault Records UINT16 1.000000 Fault Records 30168 Event Records UINT16 1.000000 Event Records 30169 Waveform Records UINT16 1.000000 Waveform Records 30170 Vab Secondary FP_32BITS_3DP 1.000000 Vab V 30172 Vbc Secondary FP_32BITS_3DP 1.000000 Vbc V 30174 Vca Secondary FP_32BITS_3DP 1.000000 Vca V 30176 Vn Primary FP_32BITS_3DP 1.000000 Vn V 30178 Vn Secondary FP_32BITS_3DP 1.000000 Vn V 30180 Vn Secondary FP_32BITS_3DP 1.000000 Vn Degrees 30182 Vx Primary FP_32BITS_3DP 1.000000 Vx V 30184 Vx Secondary FP_32BITS_3DP 1.000000 Vx V 30186 Vx Secondary FP_32BITS_3DP 1.000000 Vx Degrees 30193 I Phase A Max FP_32BITS_3DP 1.000000 Ia Max Demand Chapter 4 - Page 50 of 96 (c) 2017 Siemens Protection Devices Limited Address Description Chapter 4 - Data Communications Definitions Format Mult Description 30195 I Phase B Max FP_32BITS_3DP 1.000000 Ib Max Demand 30197 I Phase C Max FP_32BITS_3DP 1.000000 Ic Max Demand 30199 P 3P Max FP_32BITS_3DP 0.000001 Power Max Demand 30201 Q 3P Max FP_32BITS_3DP 0.000001 VARs Max Demand 30203 Ig Max FP_32BITS_3DP 1.000000 Ig Max Demand 30207 Isef Primary FP_32BITS_3DP 1.000000 Isef A 30209 Isef Secondary FP_32BITS_3DP 1.000000 Isef A 30211 Isef Nominal FP_32BITS_3DP 1.000000 Isef xInom 30213 Fault Distance Percent FP_32BITS_3DP 1.000000 Fault Distance Percent 30215 Fault Reactance FP_32BITS_3DP 1.000000 Fault Reactance 30241 CB Total Trip Count UINT32 1.000000 CB Total Trip Count 30243 CB Delta Trip Count UINT32 1.000000 CB Delta Trip Count 30245 CB Count To AR Block UINT32 1.000000 CB Count to AR Block 30247 CB Frequent Ops Count UINT32 1.000000 CB Frequent Ops Count 30293 Bus Freq FP_32BITS_3DP 1.000000 Vx Frequency 30295 Phase Diff FP_32BITS_3DP 1.000000 25 Phase Diff 30297 Slip Freq FP_32BITS_3DP 1.000000 25 Slip Freq 30299 Voltage Diff FP_32BITS_3DP 1.000000 25 Voltage Diff 30301 Ia Last Trip FP_32BITS_3DP 1.000000 Ia Fault 30303 Ib Last Trip FP_32BITS_3DP 1.000000 Ib Fault 30305 Ic Last Trip FP_32BITS_3DP 1.000000 Ic Fault 30307 Va Last Trip FP_32BITS_3DP 1.000000 Va Fault 30309 Vb Last Trip FP_32BITS_3DP 1.000000 Vb Fault 30311 Vc Last Trip FP_32BITS_3DP 1.000000 Vc Fault 30313 In Last Trip FP_32BITS_3DP 1.000000 In Fault 30315 Ig Last Trip FP_32BITS_3DP 1.000000 Ig Fault 30317 Isef Last Trip FP_32BITS_3DP 1.000000 Isef Fault 30319 V Phase A Max FP_32BITS_3DP 1.000000 Va Max Demand 30321 V Phase B Max FP_32BITS_3DP 1.000000 Vb Max Demand 30323 V Phase C Max FP_32BITS_3DP 1.000000 Vc Max Demand 30325 V Phase AB Max FP_32BITS_3DP 1.000000 Vab Max Demand 30327 V Phase BC Max FP_32BITS_3DP 1.000000 Vbc Max Demand 30329 V Phase CA Max FP_32BITS_3DP 1.000000 Vca Max Demand 30331 CB Ph A Trip Count UINT32 1.000000 CB Phase A Trip Count 30333 CB Ph B Trip Count UINT32 1.000000 CB Phase B Trip Count 30335 CB Ph C Trip Count UINT32 1.000000 CB Phase C Trip Count 30337 CB E/F Trip Count UINT32 1.000000 CB EF Trip Count 30341 LED1-n BITSTRING 0.000000 Led 1-16 status 30342 LED1-n BITSTRING 0.000000 Led 17-32 status 30343 INP1-n BITSTRING 0.000000 Input 1-16 status 30344 INP1-n BITSTRING 0.000000 Input 17-32 status 30345 OUT1-n BITSTRING 0.000000 Output 1-16 status 30346 OUT1-n BITSTRING 0.000000 Output 17-32 status 30347 VRT1-n BITSTRING 0.000000 Virtual 1-16 status 30348 VRT1-n BITSTRING 0.000000 Virtual 17-32 status 30349 EQN1-n BITSTRING 0.000000 Equation 1-16 status 30350 EQN1-n BITSTRING 0.000000 Equation 17-32 status 30352 Fault Distance Perunit FP_32BITS_3DP 1.000000 Fault Distance Perunit (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 51 of 96 7SR220 Technical Manual Address Description Format Mult Description 30354 CB Wear A FP_32BITS_3DP 0.000001 CB Wear A 30356 CB Wear B FP_32BITS_3DP 0.000001 CB Wear B 30358 CB Wear C FP_32BITS_3DP 0.000001 CB Wear C 30360 CB Wear A Remaining FP_32BITS_3DP 1.000000 CB Wear A Remaining 30362 CB Wear B Remaining FP_32BITS_3DP 1.000000 CB Wear B Remaining 30364 CB Wear C Remaining FP_32BITS_3DP 1.000000 CB Wear C Remaining 30366 CB Wear Minimum FP_32BITS_3DP 1.000000 CB Wear Minimum 30380 StartCount FP_32BITS_3DP 1.000000 Start Count 30382 Start Count Target FP_32BITS_3DP 1.000000 Start Count Target 30392 Active Setting Group UINT16 1.000000 Active Setting Group 30400 Frequency Max FP_32BITS_3DP 1.000000 Frequency Max 30402 S 3P Max FP_32BITS_3DP 0.000010 S 3P Max 30444 Sec Active Power A FP_32BITS_3DP 1.000000 Secondary A Phase W 30446 Sec Active Power B FP_32BITS_3DP 1.000000 Secondary B Phase W 30448 Sec Active Power C FP_32BITS_3DP 1.000000 Secondary C Phase W 30450 Sec P (3P) FP_32BITS_3DP 1.000000 Secondary 3 Phase W 30452 Sec Reactive Power A FP_32BITS_3DP 1.000000 Secondary Phase A VAr 30454 Sec Reactive Power B FP_32BITS_3DP 1.000000 Secondary Phase B VAr 30456 Sec Reactive Power C FP_32BITS_3DP 1.000000 Secondary Phase C VAr 30458 Sec Q (3P) FP_32BITS_3DP 1.000000 Secondary 3 Phase VAr 30460 Sec Apparent Power A FP_32BITS_3DP 1.000000 Secondary Phase A VA 30462 Sec Apparent Power B FP_32BITS_3DP 1.000000 Secondary Phase B VA 30464 Sec Apparent Power C FP_32BITS_3DP 1.000000 Secondary Phase C VA 30466 Sec S (3P) FP_32BITS_3DP 1.000000 Secondary 3 Phase VA 30468 CB Trip Time Meter FP_32BITS_3DP 1.000000 CB Trip Time 30482 PF 3P Max FP_32BITS_3DP 1.000000 Power Factor 3 Phase Max 4.3.4 Holding Registers (Read Write Registers) Address Description 40001 Time Chapter 4 - Page 52 of 96 Format TIME_METER Mult Description 0.000000 Time (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 5. DNP3 Definitions 5.1 Device Profile The following table provides a "Device Profile Document" in the standard format defined in the DNP 3.0 Subset Definitions Document. While it is referred to in the DNP 3.0 Subset Definitions as a "Document," it is in fact a table, and only a component of a total interoperability guide. The table, in combination with the Implementation Table provided in Section 5.2 (beginning on page 56), and the Point List Tables provided in Section 5.3 (beginning on page 62), should provide a complete configuration/interoperability guide for communicating with a device implementing the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library. DNP V3.0 DEVICE PROFILE DOCUMENT (Also see the DNP 3.0 Implementation Table in Section 5.2, beginning on page 56). Vendor Name: Siemens Protection Devices Ltd. Device Name: 7SR220, using the Triangle MicroWorks, Inc. DNP3 Slave Source Code Library, Version 3. Device Function: Master Slave Highest DNP Level Supported: For Requests: Level 3 For Responses: Level 3 Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table): For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and 28 (index) are supported. Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers 00 or 01. Output Event Object 11 is supported. Maximum Data Link Frame Size (octets): Transmitted: 256 Received: 256 Maximum Application Fragment Size (octets): Transmitted: 2048 Received: 2048 Maximum Data Link Re-tries: None Fixed (3) Configurable from 0 to 65535 (Default 3) Maximum Application Layer Re-tries: None Configurable Requires Data Link Layer Confirmation: Never Always Sometimes Configurable as: Never, Only for multi-frame messages, or Always Requires Application Layer Confirmation: Never Always When reporting Event Data (Slave devices only) When sending multi-fragment responses (Slave devices only) Sometimes Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages." Timeouts while waiting for: Data Link Confirm: None Fixed at Variable Configurable (2sec) Complete Appl. Fragment: None Fixed at Variable Configurable Application Confirm: None Fixed at Variable Configurable (10sec) Complete Appl. Response: None Fixed at Variable Configurable Others: Transmission Delay, (Configurable, default 0 sec) Select/Operate Arm Timeout, (Configurable, default 5 sec) Need Time Interval, (Configurable, default 30 minutes) (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 53 of 96 7SR220 Technical Manual DNP V3.0 DEVICE PROFILE DOCUMENT (Also see the DNP 3.0 Implementation Table in Section 5.2, beginning on page 56). Unsolicited Notification Delay, (Configurable, default 5 seconds) Unsolicited Response Retry Delay, (Configurable (between 3 - 9), default 5 seconds) Unsolicited Offline Interval, (Configurable, default 30 seconds) Binary Change Event Scan Period, (Polled, Not Applicable) Double Bit Change Event Scan Period, (Polled - Not Applicable) Analog Change Event Scan Period, (Polled - Not Applicable) Counter Change Event Scan Period, (Polled - Not Applicable) Frozen Counter Change Event Scan Period, (Polled - Not Applicable) String Change Event Scan Period, (Unsupported - Not Applicable) Virtual Terminal Event Scan Period, (Unsupported - Not Applicable) Sends/Executes Control Operations: WRITE Binary Outputs Never Always Sometimes Configurable SELECT/OPERATE Never Always Sometimes Configurable DIRECT OPERATE Never Always Sometimes Configurable DIRECT OPERATE - NO ACK Never Always Sometimes Configurable Count > 1 Never Always Sometimes Configurable Pulse On Never Always Sometimes Configurable Pulse Off Never Always Sometimes Configurable Latch On Never Always Sometimes Configurable Latch Off Never Always Sometimes Configurable Queue Never Always Sometimes Configurable Clear Queue Never Always Sometimes Configurable Attach explanation if "Sometimes" or "Configurable" was checked for any operation. Reports Binary Input Change Events when no specific variation requested: Never Only time-tagged Only non-time-tagged Configurable to send one or the other Reports time-tagged Binary Input Change Events when no specific variation requested: Never Binary Input Change With Time Binary Input Change With Relative Time Configurable Sends Unsolicited Responses: Never Configurable Only certain objects Sometimes (attach explanation) ENABLE/DISABLE UNSOLICITED Function codes supported Sends Static Data in Unsolicited Responses: Never When Device Restarts When Status Flags Change No other options are permitted. Default Counter Object/Variation: No Counters Reported Configurable Default Object Default Variation: Point-by-point list attached Counters Roll Over at: No Counters Reported Configurable (attach explanation) 16 Bits 32 Bits Other Value: Point-by-point list attached Sends Multi-Fragment Responses: Yes No Configurable Sequential File Transfer Support: Chapter 4 - Page 54 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions DNP V3.0 DEVICE PROFILE DOCUMENT (Also see the DNP 3.0 Implementation Table in Section 5.2, beginning on page 56). File Transfer Support Yes No Append File Mode Yes No Custom Status Code Strings Yes No Permissions Field Yes No File Events Assigned to Class Yes No File Events Send Immediately Yes No Multiple Blocks in a Fragment Yes No Max Number of Files Open (c) 2017 Siemens Protection Devices Limited 0 Chapter 4 - Page 55 of 96 7SR220 Technical Manual 5.2 Implementation Table The following table identifies which object variations, function codes, and qualifiers the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library supports in both request messages and in response messages. For static (nonchange-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always responded. In the table below, text shaded as 00, 01 (start stop) indicates Subset Level 3 functionality (beyond Subset Level 2). In the table below, text shaded as 07, 08 (limited qty) indicates functionality beyond Subset Level 3. REQUEST (Library will parse) OBJECT RESPONSE (Library will respond with) Function Codes (dec) Qualifier Codes (hex) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) Binary Input Change - Any Variation 1 (read) 06 (no range, or all) 07, 08 (limited qty) 1 Binary Input Change without Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 2 2 (default see note 1) Binary Input Change with Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 2 3 Binary Input Change with Relative Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 3 0 Double Bit Input - Any Variation 1 (read) 22 (assign class) 3 1 (default see note 1) Double Bit Input 1 (read) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 1) 3 2 Double Bit Input with Status 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 1) 4 0 Double Bit Input Change - Any Variation 1 (read) 06 (no range, or all) 07, 08 (limited qty) 4 1 Double Bit Input Change without Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 4 2 Double Bit Input Change with Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 4 3 (default see note 1) Double Bit Input Change with Relative Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 10 0 Binary Output - Any Variation 1 (read) 22 (assign class) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) Object Number Variation Description Function Codes (dec) Qualifier Codes (hex) 1 0 Binary Input - Any Variation 1 (read) 22 (assign class) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 1 1 Binary Input 1 (read) 1 2 (default see note 1) Binary Input with Status 2 0 2 Chapter 4 - Page 56 of 96 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions REQUEST (Library will parse) OBJECT Object Number 10 Variation 1 Description Binary Output Function Codes (dec) Qualifier Codes (hex) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 2 (write) 00, 01 (start-stop) RESPONSE (Library will respond with) Function Codes (dec) Qualifier Codes (hex) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 10 2 (default see note 1) Binary Output Status 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 11 0 Binary Output Change - Any Variation 1 (read) 06 (no range, or all) 07, 08 (limited qty) 11 1 Binary Output Change without Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 11 2 (default see note 1) Binary Output Change with Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 12 0 Control Relay Output Block 22 (assign class) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 12 1 Control Relay Output Block 3 (select) 4 (operate) 5 (direct op) 6 (dir. op, noack) 17, 28 (index) 129 (response) echo of request 12 2 Pattern Control Block 3 (select) 4 (operate) 5 (direct op) 6 (dir. op, noack) 7 (limited quantity) 129 (response) echo of request 00, 01 (start-stop) 129 (response) echo of request 12 3 Pattern Mask 3 (select) 4 (operate) 5 (direct op) 6 (dir. op, noack) 13 0 Binary Output Command Event - Any Variation 1 (read) 06 (no range, or all) 07, 08 (limited qty) 13 1 (default see note 1) Binary Output Command Event without Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 13 2 Binary Output Command Event with Time 1 (read) 06 (no range, or all) 07, 08 (limited qty) 1 (read) 22 (assign class) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 7 (freeze) 8 (freeze noack) 9 (freeze clear) 10 (frz. cl. noack) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 20 0 Binary Counter - Any Variation 129 (response) 130 (unsol. resp) 129 (response) 130 (unsol. resp) 129 (response) 130 (unsol. resp) 17, 28 (index) 17, 28 (index) 17, 28 (index) 129 (response) 130 (unsol. resp) 17, 28 (index) 20 1 32-Bit Binary Counter (with Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 20 2 16-Bit Binary Counter (with Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 20 3 32-Bit Delta Counter (with Flag) 20 4 16-Bit Delta Counter (with Flag) 20 5 (default see note 1) 32-Bit Binary Counter (without Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 57 of 96 7SR220 Technical Manual REQUEST (Library will parse) OBJECT RESPONSE (Library will respond with) Object Number Variation Description Function Codes (dec) Qualifier Codes (hex) Function Codes (dec) Qualifier Codes (hex) 20 6 16-Bit Binary Counter (without Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 20 7 32-Bit Delta Counter (without Flag) 20 8 16-Bit Delta Counter (without Flag) 21 0 Frozen Counter - Any Variation 1 (read) 22 (assign class) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 21 1 32-Bit Frozen Counter (with Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 21 2 16-Bit Frozen Counter (with Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 21 3 32-Bit Frozen Delta Counter (with Flag) 21 4 16-Bit Frozen Delta Counter (with Flag) 21 5 32-Bit Frozen Counter (without Time Of Freeze) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 21 6 16-Bit Frozen Counter (without Time Of Freeze) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 21 7 32-Bit Frozen Delta Counter (with Time Of Freeze) 21 8 16-Bit Frozen Delta Counter (with Time Of Freeze) 21 9 (default see note 1) 32-Bit Frozen Counter (without Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 21 10 16-Bit Frozen Counter (without Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 21 11 32-Bit Frozen Delta Counter (without Flag) 21 12 16-Bit Frozen Delta Counter (without Flag) 22 0 Counter Change Event - Any Variation 1 (read) 06 (no range, or all) 07, 08 (limited qty) 22 1 (default see note 1) 32-Bit Counter Change Event (without Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 22 2 16-Bit Counter Change Event (without Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 22 3 32-Bit Delta Counter Change Event (without Time) 22 4 16-Bit Delta Counter Change Event (without Time) 22 5 32-Bit Counter Change Event (with Time) 1 (read) 129 (response) 130 (unsol. resp) 17, 28 (index) 22 6 16-Bit Counter Change Event (with Time) 1 (read) 129 (response) 130 17, 28 (index) Chapter 4 - Page 58 of 96 06 (no range, or all) 07, 08 (limited qty) 06 (no range, or all) 07, 08 (limited qty) (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions REQUEST (Library will parse) OBJECT Object Number Variation Description Function Codes (dec) Qualifier Codes (hex) RESPONSE (Library will respond with) Function Codes (dec) Qualifier Codes (hex) (unsol. resp) 22 7 32-Bit Delta Counter Change Event (with Time) 22 8 16-Bit Delta Counter Change Event (with Time) 23 0 Frozen Counter Event (Variation 0 is used to request default variation) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 23 1 (default see note 1) 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 17, 28 (index) 23 2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 17, 28 (index) 23 3 32-Bit Frozen Delta Counter Event 23 4 16-Bit Frozen Delta Counter Event 23 5 32-Bit Frozen Counter Event (with Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 23 6 32-Bit Frozen Counter Event (with Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 23 7 32-Bit Frozen Delta Counter Event (with Time) 23 8 16-Bit Frozen Delta Counter Event (with Time) 30 0 Analog Input - Any Variation 1 (read) 22 (assign class) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 30 2 (default see note 1) 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 30 3 32-Bit Analog Input (without Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 30 4 16-Bit Analog Input (without Flag) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 30 5 short floating point 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 30 6 long floating point 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 31 0 Frozen Analog Input - Any Variation 31 1 32-Bit Frozen Analog Input 31 2 16-Bit Frozen Analog Input 31 3 32-Bit Frozen Analog Input (with Time of freeze) 31 4 16-Bit Frozen Analog Input (with Time of freeze) 31 5 32-Bit Frozen Analog Input (without Flag) 31 6 16-Bit Frozen Analog Input (without Flag) (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 59 of 96 7SR220 Technical Manual REQUEST (Library will parse) OBJECT RESPONSE (Library will respond with) Function Codes (dec) Qualifier Codes (hex) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 3 32Bit-Analog Change Event (with Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 4 (default see note 1) 16Bit-Analog Change Event (with Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 32 5 short floating point Analog Change Event (without Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 32 6 long floating point Analog Change Event (without Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 32 7 short floating point Analog Change Event (with Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 32 8 long floating point Analog Change Event (with Time) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 130 (unsol. resp) 17, 28 (index) 33 0 Frozen Analog Event - Any Variation 33 1 32-Bit Frozen Analog Event (without Time) 33 2 16-Bit Frozen Analog Event (without Time) 33 3 32-Bit Frozen Analog Event (with Time) 33 4 16-Bit Frozen Analog Event (with Time) 33 5 Short Floating Point Frozen Analog Event 33 6 Long Floating Point Frozen Analog Event 33 7 Extended Floating Point Frozen Analog Event 34 0 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 2 (write) 00, 01 (start-stop) 07, 08 (limited qty) 17, 27, 28 (index) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) 2(write) 00, 01 (start-stop) 07, 08 (limited qty) 17, 27, 28 (index) 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 129 (response) 00, 01 (start-stop) 17, 28 (index - see note 2) Object Number Variation Description Function Codes (dec) Qualifier Codes (hex) 32 0 Analog Change Event - Any Variation) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 32 1 32Bit-Analog Change Event (without Time) 1 (read) 32 2 16Bit-Analog Change Event (without Time) 32 32 34 34 34 Analog Input Deadband (Variation 0 is used to request default variation) 1 16 bit Analog Input Deadband 2 (default see note 1) 3 32 bit Analog Input Deadband Short Floating Point Analog Input Deadband Chapter 4 - Page 60 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Object Number Variation RESPONSE (Library will respond with) REQUEST (Library will parse) OBJECT Description Function Codes (dec) Qualifier Codes (hex) Function Codes (dec) 17, 27, 28 (index) 50 0 Time and Date 50 3 Time and Date Last Recorded Time 51 1 Time and Date CTO 51 2 Unsynchronized Time and Date CTO 52 1 Time Delay Coarse 52 2 Time Delay Fine 60 60 0 1 Class 0 Data 60 2 00, 01 (start-stop) 07, 08 (limited qty) 17, 27, 28 (index) 1 (read) 07, 08 (limited qty) 2 (write) 00, 01 (start-stop) 07, 08 (limited qty) 17, 27, 28 (index) 2 (write) 07 (limited qty) Time and Date 1 (default see note 1) 50 2 (write) 60 80 3 4 1 129 (response) 129 (response) 130 (unsol. resp) 129 (response) 130 (unsol. resp) 129 (response) 129 (response) 07 (limited qty = 1) (limited qty = 1) (limited qty = 1) (limited qty = 1) (limited qty = 1) Not Defined Class 1 Data 1 (read) 06 (no range, or all) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 20 (enbl. unsol.) 21 (dab. unsol.) 22 (assign class) 1 (read) 60 Qualifier Codes (hex) Class 2 Data Class 3 Data 20 (enbl. unsol.) 21 (dab. unsol.) 22 (assign class) No Object (function code only) No Object (function code only) 06 (no range, or all) 07, 08 (limited qty) 06 (no range, or all) 1 (read) 06 (no range, or all) 07, 08 (limited qty) 20 (enbl. unsol.) 21 (dab. unsol.) 22 (assign class) 06 (no range, or all) 1 (read) 00, 01 (start-stop) 2 (write)(see note 3) 00 (startstop) index=7 Internal Indications No Object (function code only) No Object (function code only) 06 (no range, or all) 129 (response) 00, 01 (start-stop) 13 (cold restart) 14 (warm restart) 23 (delay meas.) 24 (record current time) Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Default variations are configurable; however, default settings for the configuration parameters are indicated in the table above. Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.) Note 3: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7). (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 61 of 96 7SR220 Technical Manual 5.3 Point List The tables below identify all the default data points provided by the implementation of the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library. This protocol can be set to use any or all of the relays hardware interfaces (USB, Fibre Optic, RS232 and RS485) where fitted. The relay can communicate simultaneously on all ports regardless of protocol used. The Station Address of the port being used must be set to a suitable address within the range 0 - 65534 to enable communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting. Communication via DNP3 over Ethernet requires external devices. Please refer to the documents TCPIP Catalogue Sheet and TCPIP Interface Technical Guidance Notes for more information. The information shown below is the default configuration. 5.3.1 Binary Input Points The default binary input event buffer size is set to allow 100 events. Binary inputs are by default returned in a class zero interrogation. Note, not all points listed here apply to all builds of devices. Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 1 Binary Input 1 0,2 2 2 2 Binary Input 2 0,2 2 2 3 Binary Input 3 0,2 2 2 4 Binary Input 4 0,2 2 2 5 Binary Input 5 0,2 2 2 6 Binary Input 6 0,2 2 2 7 Binary Input 7 0,2 2 2 8 Binary Input 8 0,2 2 2 9 Binary Input 9 0,2 2 2 10 Binary Input 10 0,2 2 2 11 Binary Input 11 0,2 2 2 12 Binary Input 12 0,2 2 2 13 Binary Input 13 0,2 2 2 35 Remote Mode 0,2 2 2 36 Out Of Service Mode 0,2 2 2 37 Local Mode 0,2 2 2 38 Local & Remote 0,2 2 2 40 General Trip 0,2 2 2 41 Trip Circuit Fail 0,2 2 2 42 Start/Pick-up L1 0,2 2 2 43 Start/Pick-up L2 0,2 2 2 Point Index Description Chapter 4 - Page 62 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 44 Start/Pick-up L3 0,2 2 2 45 General Start/Pick-up 0,2 2 2 46 VT Fuse Failure 0,2 2 2 47 Earth Fault Forward/Line 0,2 2 2 48 Earth Fault Reverse/Busbar 0,2 2 2 49 Start/Pick-up N 0,2 2 2 50 Fault Forward/Line 0,2 2 2 51 Fault Reverse/Busbar 0,2 2 2 52 51-1 0,2 2 2 53 50-1 0,2 2 2 54 51N-1 0,2 2 2 55 50N-1 0,2 2 2 56 51G-1 0,2 2 2 57 50G-1 0,2 2 2 58 51-2 0,2 2 2 59 50-2 0,2 2 2 60 51N-2 0,2 2 2 61 50N-2 0,2 2 2 62 51G-2 0,2 2 2 63 50G-2 0,2 2 2 64 60 CTS 0,2 2 2 65 46IT 0,2 2 2 66 46DT 0,2 2 2 67 47-1 0,2 2 2 68 47-2 0,2 2 2 69 46BC 0,2 2 2 70 27/59-1 0,2 2 2 71 27/59-2 0,2 2 2 72 27/59-3 0,2 2 2 73 27/59-4 0,2 2 2 74 59NIT 0,2 2 2 75 59NDT 0,2 2 2 76 81-1 0,2 2 2 77 81-2 0,2 2 2 78 81-3 0,2 2 2 79 81-4 0,2 2 2 80 Auto-reclose active 0,2 2 2 81 CB on by auto reclose 0,2 2 2 82 Reclaim 0,2 2 2 83 Lockout 0,2 2 2 84 81-5 0,2 2 2 Point Index Description (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 63 of 96 7SR220 Technical Manual Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 85 81-6 0,2 2 2 86 51-3 0,2 2 2 87 50-3 0,2 2 2 88 51N-3 0,2 2 2 89 50N-3 0,2 2 2 90 51G-3 0,2 2 2 91 50G-3 0,2 2 2 92 51-4 0,2 2 2 93 50-4 0,2 2 2 94 51N-4 0,2 2 2 95 50N-4 0,2 2 2 96 51G-4 0,2 2 2 97 50G-4 0,2 2 2 98 Cold Load Active 0,2 2 2 99 E/F Out 0,2 2 2 100 P/F Inst Protection Inhibited 0,2 2 2 101 E/F Inst Protection Inhibited 0,2 2 2 102 SEF Inst Protection Inhibited 0,2 2 2 103 Ext Inst Protection Inhibited 0,2 2 2 117 51SEF-1 0,2 2 2 118 50SEF-1 0,2 2 2 119 51SEF-2 0,2 2 2 120 50SEF-2 0,2 2 2 121 51SEF-3 0,2 2 2 122 50SEF-3 0,2 2 2 123 51SEF-4 0,2 2 2 124 50SEF-4 0,2 2 2 125 SEF Out 0,2 2 2 126 Trip Circuit Fail 1 0,2 2 2 127 Trip Circuit Fail 2 0,2 2 2 128 Trip Circuit Fail 3 0,2 2 2 129 CB Total Trip Count 0,2 2 2 130 CB Delta Trip Count 0,2 2 2 131 CB Count To AR Block 0,2 2 2 132 CB Frequent Ops Count 0,2 2 2 133 I^2t CB Wear 0,2 2 2 207 Close Circuit Fail 1 0,2 2 2 208 Close Circuit Fail 2 0,2 2 2 209 Close Circuit Fail 3 0,2 2 2 210 Close Circuit Fail 0,2 2 2 211 50BF Stage 1 0,2 2 2 212 50BF Stage 2 0,2 2 2 Point Description Index Chapter 4 - Page 64 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 213 49-Alarm 0,2 2 2 214 49-Trip 0,2 2 2 215 64H 0,2 2 2 216 Vx27/59 0,2 2 2 217 37-1 0,2 2 2 218 37-2 0,2 2 2 219 CB Alarm 0,2 2 2 225 General Alarm 1 0,2 2 2 226 General Alarm 2 0,2 2 2 227 General Alarm 3 0,2 2 2 228 General Alarm 4 0,2 2 2 229 General Alarm 5 0,2 2 2 230 General Alarm 6 0,2 2 2 231 General Alarm 7 0,2 2 2 232 General Alarm 8 0,2 2 2 233 General Alarm 9 0,2 2 2 234 General Alarm 10 0,2 2 2 235 General Alarm 11 0,2 2 2 236 General Alarm 12 0,2 2 2 237 Quick Logic E1 0,2 2 2 238 Quick Logic E2 0,2 2 2 239 Quick Logic E3 0,2 2 2 240 Quick Logic E4 0,2 2 2 241 Quick Logic E5 0,2 2 2 242 Quick Logic E6 0,2 2 2 243 Quick Logic E7 0,2 2 2 244 Quick Logic E8 0,2 2 2 245 Quick Logic E9 0,2 2 2 246 Quick Logic E10 0,2 2 2 247 Quick Logic E11 0,2 2 2 248 Quick Logic E12 0,2 2 2 249 Quick Logic E13 0,2 2 2 250 Quick Logic E14 0,2 2 2 251 Quick Logic E15 0,2 2 2 252 Quick Logic E16 0,2 2 2 269 60 CTS-I 0,2 2 2 270 81HBL2 0,2 2 2 271 37G-1 0,2 2 2 272 37G-2 0,2 2 2 273 Wattmetric Po> 0,2 2 2 274 37-PhA 0,2 2 2 Point Index Description (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 65 of 96 7SR220 Technical Manual Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 275 37-PhB 0,2 2 2 276 37-PhC 0,2 2 2 283 50BF-PhA 0,2 2 2 284 50BF-PhB 0,2 2 2 285 50BF-PhC 0,2 2 2 286 50BF-EF 0,2 2 2 287 79 Last Trip Lockout 0,2 2 2 288 60 CTS-I-PhA 0,2 2 2 289 60 CTS-I-PhB 0,2 2 2 290 60 CTS-I-PhC 0,2 2 2 291 Trip PhA 0,2 2 2 292 Trip PhB 0,2 2 2 293 Trip PhC 0,2 2 2 302 27/59 PhA 0,2 2 2 303 27/59 PhB 0,2 2 2 304 27/59 PhC 0,2 2 2 310 General Alarm 13 0,2 2 2 311 General Alarm 14 0,2 2 2 312 General Alarm 15 0,2 2 2 313 General Alarm 16 0,2 2 2 314 General Alarm 17 0,2 2 2 315 General Alarm 18 0,2 2 2 316 General Alarm 19 0,2 2 2 317 General Alarm 20 0,2 2 2 330 32-1 0,2 2 2 331 32-2 0,2 2 2 332 32S-1 0,2 2 2 333 32S-2 0,2 2 2 334 55-1 0,2 2 2 335 55-2 0,2 2 2 373 37SEF-1 0,2 2 2 374 37SEF-2 0,2 2 2 387 25 System Split 0,2 2 2 388 25 Live Line 0,2 2 2 389 25 Live Bus 0,2 2 2 390 25 Line U/V 0,2 2 2 391 25 Bus U/V 0,2 2 2 392 25 Voltage Dif > 0,2 2 2 393 25 CS Slip Freq > 0,2 2 2 394 25 SS Slip Freq > 0,2 2 2 395 25 COZ Slip Freq > 0,2 2 2 396 25 In Sync 0,2 2 2 Point Index Description Chapter 4 - Page 66 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 397 25 CS In Progress 0,2 2 2 398 25 SS In Progress 0,2 2 2 399 25 COZ In Progress 0,2 2 2 400 25 System Split LO 0,2 2 2 401 60VTF-Bus 0,2 2 2 411 Setting G1 selected 0,2 2 2 412 Setting G2 selected 0,2 2 2 413 Setting G3 selected 0,2 2 2 414 Setting G4 selected 0,2 2 2 415 Setting G5 selected 0,2 2 2 416 Setting G6 selected 0,2 2 2 417 Setting G7 selected 0,2 2 2 418 Setting G8 selected 0,2 2 2 420 79 AR In progress 0,2 2 2 422 HotLine Working 0,2 2 2 425 Inst Protection Out 0,2 2 2 427 CB 1 0,2 2 2 434 Man Override Sync 0,2 2 2 435 79 Override Sync 0,2 2 2 501 Virtual Input 1 0,2 2 2 502 Virtual Input 2 0,2 2 2 503 Virtual Input 3 0,2 2 2 504 Virtual Input 4 0,2 2 2 505 Virtual Input 5 0,2 2 2 506 Virtual Input 6 0,2 2 2 507 Virtual Input 7 0,2 2 2 508 Virtual Input 8 0,2 2 2 509 Virtual Input 9 0,2 2 2 510 Virtual Input 10 0,2 2 2 511 Virtual Input 11 0,2 2 2 512 Virtual Input 12 0,2 2 2 513 Virtual Input 13 0,2 2 2 514 Virtual Input 14 0,2 2 2 515 Virtual Input 15 0,2 2 2 516 Virtual Input 16 0,2 2 2 601 LED 1 0,2 2 2 602 LED 2 0,2 2 2 603 LED 3 0,2 2 2 604 LED 4 0,2 2 2 605 LED 5 0,2 2 2 606 LED 6 0,2 2 2 Point Index Description (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 67 of 96 7SR220 Technical Manual Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 607 LED 7 0,2 2 2 608 LED 8 0,2 2 2 609 LED 9 0,2 2 2 610 LED 10 0,2 2 2 611 LED 11 0,2 2 2 612 LED 12 0,2 2 2 613 LED 13 0,2 2 2 614 LED 14 0,2 2 2 615 LED 15 0,2 2 2 616 LED 16 0,2 2 2 701 LED PU 1 0,2 2 2 702 LED PU 2 0,2 2 2 703 LED PU 3 0,2 2 2 704 LED PU 4 0,2 2 2 705 LED PU 5 0,2 2 2 706 LED PU 6 0,2 2 2 707 LED PU 7 0,2 2 2 708 LED PU 8 0,2 2 2 709 LED PU 9 0,2 2 2 710 LED PU 10 0,2 2 2 711 LED PU 11 0,2 2 2 712 LED PU 12 0,2 2 2 713 LED PU 13 0,2 2 2 714 LED PU 14 0,2 2 2 715 LED PU 15 0,2 2 2 716 LED PU 16 0,2 2 2 801 Binary Output 1 0,2 2 2 802 Binary Output 2 0,2 2 2 803 Binary Output 3 0,2 2 2 804 Binary Output 4 0,2 2 2 805 Binary Output 5 0,2 2 2 806 Binary Output 6 0,2 2 2 807 Binary Output 7 0,2 2 2 808 Binary Output 8 0,2 2 2 809 Binary Output 9 0,2 2 2 810 Binary Output 10 0,2 2 2 811 Binary Output 11 0,2 2 2 812 Binary Output 12 0,2 2 2 813 Binary Output 13 0,2 2 2 814 Binary Output 14 0,2 2 2 871 Cold Start 0,2 2 2 872 Warm Start 0,2 2 2 Point Index Description Chapter 4 - Page 68 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 873 Re-Start 0,2 2 2 874 Power On 0,2 2 2 875 Expected Restart 0,2 2 2 876 Unexpected Restart 0,2 2 2 877 Reset Start Count 0,2 2 2 890 CB 1 Opened 0,2 2 2 891 CB 1 Closed 0,2 2 2 900 User SP Command 1 0,2 2 2 901 User SP Command 2 0,2 2 2 902 User SP Command 3 0,2 2 2 903 User SP Command 4 0,2 2 2 904 User SP Command 5 0,2 2 2 905 User SP Command 6 0,2 2 2 906 User SP Command 7 0,2 2 2 907 User SP Command 8 0,2 2 2 1010 User Output 1 0,2 2 2 1011 User Output 2 0,2 2 2 1012 User Output 3 0,2 2 2 1013 User Output 4 0,2 2 2 1014 User Output 5 0,2 2 2 1015 User Output 6 0,2 2 2 1016 User Output 7 0,2 2 2 1017 User Output 8 0,2 2 2 1018 User Output 9 0,2 2 2 1019 User Output 10 0,2 2 2 1020 User Output 11 0,2 2 2 1021 User Output 12 0,2 2 2 1022 User Output 13 0,2 2 2 1023 User Output 14 0,2 2 2 1024 User Output 15 0,2 2 2 1025 User Output 16 0,2 2 2 1026 User Output 17 0,2 2 2 1027 User Output 18 0,2 2 2 1028 User Output 19 0,2 2 2 1029 User Output 20 0,2 2 2 1030 User Output 21 0,2 2 2 1031 User Output 22 0,2 2 2 1032 User Output 23 0,2 2 2 1033 User Output 24 0,2 2 2 1034 User Output 25 0,2 2 2 1035 User Output 26 0,2 2 2 Point Index Description (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 69 of 96 7SR220 Technical Manual Binary Input Points Static (Steady-State) Object Number: 1 (Packed Format) Change Event Object Number: 1 (w/o Time) Static Variation reported when variation 0 requested: 1 (Binary Input w/o status) or 2 (Binary Input with status) Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time) or 2 (Binary Input Change with Absolute Time) or 3 (Binary Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 1 Default Variation Event Object 2 1036 User Output 27 0,2 2 2 1037 User Output 28 0,2 2 2 1038 User Output 29 0,2 2 2 1039 User Output 30 0,2 2 2 1040 User Output 31 0,2 2 2 1041 User Output 32 0,2 2 2 1061 E/F In 0,2 2 2 1062 SEF In 0,2 2 2 1063 CB DBI 0,2 2 2 1064 CB Travelling 0,2 2 2 1065 Close CB Failed 0,2 2 2 1066 Open CB Failed 0,2 2 2 1067 Start Count Alarm 0,2 2 2 1068 50AFD PhA 0,2 2 2 1069 50AFD PhB 0,2 2 2 1070 50AFD PhC 0,2 2 2 1071 50AFD 0,2 2 2 1072 AFD Zone 1 Flash 0,2 2 2 1073 AFD Zone 1 0,2 2 2 1074 AFD Zone 2 Flash 0,2 2 2 1075 AFD Zone 2 0,2 2 2 1076 AFD Zone 3 Flash 0,2 2 2 1077 AFD Zone 3 0,2 2 2 1078 AFD Zone 4 Flash 0,2 2 2 1079 AFD Zone 4 0,2 2 2 1080 AFD Zone 5 Flash 0,2 2 2 1081 AFD Zone 5 0,2 2 2 1082 AFD Zone 6 Flash 0,2 2 2 1083 AFD Zone 6 0,2 2 2 1084 21LB-3P Fwd 0,2 2 2 1085 21LB-3P Rev 0,2 2 2 1086 21LB-1P Fwd 0,2 2 2 1087 21LB-1P Rev 0,2 2 2 1088 81HBL5 0,2 2 2 Point Index Description 5.3.2 Double Bit Input Points The default double bit input event buffer size is set to allow 100 events. Double bit inputs are by default returned in a class zero interrogation. Note, not all points listed here apply to all builds of devices. Chapter 4 - Page 70 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Double Bit Input Points Static (Steady-State) Object Number: 3 Change Event Object Number: 4 Static Variation reported when variation 0 requested: 1 (Double Bit Input w/o status) or 2 (Double Bit Input with status) Change Event Variation reported when variation 0 requested: 1 (Double Bit Input Change w/o Time) or 2 (Double Bit Input Change with Absolute Time) or 3 (Double Bit Input Change with Relative Time) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 3 Default Variation Event Object 4 0,2 1 3 10 User DP Command 1 0,2 1 3 11 User DP Command 2 0,2 1 3 12 User DP Command 3 0,2 1 3 13 User DP Command 4 0,2 1 3 14 User DP Command 5 0,2 1 3 15 User DP Command 6 0,2 1 3 16 User DP Command 7 0,2 1 3 17 User DP Command 8 0,2 1 3 Point Index Description 0 CB 1 5.3.3 Binary Output Status Points and Control Relay Output Blocks The following table lists both the Binary Output Status Points (Object 10) and the Control Relay Output Blocks (Object 12). While Binary Output Status Points are included here for completeness, they are not often polled by DNP 3.0 Masters. Binary Output Status points are not recommended to be included in class 0 polls. As an alternative, it is recommended that "actual" status values of Control Relay Output Block points be looped around and mapped as Binary Inputs. (The "actual" status value, as opposed to the "commanded" status value, is the value of the actuated control. For example, a DNP control command may be blocked through hardware or software mechanisms; in this case, the actual status value would indicate the control failed because of the blocking. Looping Control Relay Output Block actual status values as Binary Inputs has several advantages: * it allows actual statuses to be included in class 0 polls, * it allows change event reporting of the actual statuses, which is a more efficient and time-accurate method of communicating control values, * and it allows reporting of time-based information associated with controls, including any delays before controls are actuated, and any durations if the controls are pulsed. The default select/control buffer size is large enough to hold 10 of the largest select requests possible. Binary outputs are by default NOT returned in a class zero interrogation. Note, not all points listed here apply to all builds of devices. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 71 of 96 7SR220 Technical Manual Binary Output Status Points Static (Steady-State) Object Number: 10 Change Event Object Number: 11 Control Relay Output Blocks (CROB) Object Number: 12 Binary Output Command Event Object Number: 13 Static Variation reported when variation 0 requested: 1 (Binary Output w/o status) or 2 (Binary Output with status) Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time) or 2 (Binary Output Event with Time) Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time) or 2 (Command Status with Time) Default Variation Event Object 11 Default Command Event Object 13 Assigned Class (1, 2, 3 or none) Default Variation Command Event Object 13 2 2 0 1 Pulse On Latch On Pulse On Close 0 2 2 0 1 Pulse On Latch On Pulse On Close 3 RL 3 0 2 2 0 1 Pulse On Latch On Pulse On Close 4 RL 4 0 2 2 0 1 Pulse On Latch On Pulse On Close 5 RL 5 0 2 2 0 1 Pulse On Latch On Pulse On Close 6 RL 6 0 2 2 0 1 Pulse On Latch On Pulse On Close 7 RL 7 0 2 2 0 1 Pulse On Latch On Pulse On Close 8 RL 8 0 2 2 0 1 Pulse On Latch On Pulse On Close 9 RL 9 0 2 2 0 1 Pulse On Latch On Pulse On Close 10 RL 10 0 2 2 0 1 Pulse On Latch On Pulse On Close 11 RL 11 0 2 2 0 1 Pulse On Latch On Pulse On Close 12 RL 12 0 2 2 0 1 Pulse On Latch On Pulse On Close 13 RL 13 0 2 2 0 1 Pulse On Latch On Pulse On Close 14 RL 14 0 2 2 0 1 Pulse On Latch On Pulse On Close 0 2 2 0 1 Pulse On Latch On Pulse On Close Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 10 1 RL 1 0 2 RL 2 Point Index 33 Description LED reset, write only location. Chapter 4 - Page 72 of 96 CROB Supported Operations Default CROB Operations (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Binary Output Status Points Static (Steady-State) Object Number: 10 Change Event Object Number: 11 Control Relay Output Blocks (CROB) Object Number: 12 Binary Output Command Event Object Number: 13 Static Variation reported when variation 0 requested: 1 (Binary Output w/o status) or 2 (Binary Output with status) Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time) or 2 (Binary Output Event with Time) Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time) or 2 (Command Status with Time) Default Variation Event Object 11 Default Command Event Object 13 Assigned Class (1, 2, 3 or none) Default Variation Command Event Object 13 2 2 0 1 Pulse On Latch On Latch On Close 0 2 2 0 1 Pulse On Latch On Latch On Close 36 Settings Group 3 0 2 2 0 1 Pulse On Latch On Latch On Close 37 Settings Group 4 0 2 2 0 1 Pulse On Latch On Latch On Close 38 Settings Group 5 0 2 2 0 1 Pulse On Latch On Latch On Close 39 Settings Group 6 0 2 2 0 1 Pulse On Latch On Latch On Close 40 Settings Group 7 0 2 2 0 1 Pulse On Latch On Latch On Close 41 Settings Group 8 0 2 2 0 1 Pulse On Latch On Latch On Close 1 Pulse On Pulse Off Latch On Latch Off Close Trip Pulse On Pulse Off Latch On Latch Off 1 Pulse On Pulse Off Latch On Latch Off Close Trip Pulse On Pulse Off Latch On Latch Off 1 Pulse On Pulse Off Latch On Latch Off Close Trip Pulse On Pulse Off Latch On Latch Off 1 Pulse On Pulse Off Latch On Latch Off Pulse On Pulse Off Latch On Latch Off Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 10 34 Settings Group 1 0 35 Settings Group 2 Point Index Description 42 Auto-reclose on/off 43 Hot Line Working on/off 44 E/F Out on/off 45 SEF Out on/off 0 0 0 0 (c) 2017 Siemens Protection Devices Limited 2 2 2 2 2 2 2 2 0 0 0 0 CROB Supported Operations Default CROB Operations Chapter 4 - Page 73 of 96 7SR220 Technical Manual Binary Output Status Points Static (Steady-State) Object Number: 10 Change Event Object Number: 11 Control Relay Output Blocks (CROB) Object Number: 12 Binary Output Command Event Object Number: 13 Static Variation reported when variation 0 requested: 1 (Binary Output w/o status) or 2 (Binary Output with status) Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time) or 2 (Binary Output Event with Time) Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time) or 2 (Command Status with Time) Point Index Description Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 10 Default Variation Event Object 11 Default Command Event Object 13 Assigned Class (1, 2, 3 or none) Default Variation Command Event Object 13 CROB Supported Operations Default CROB Operations Close Trip 46 Inst Protection off/on 0 2 2 0 1 Pulse On Pulse Off Latch On Latch Off Close Trip Pulse On Pulse Off Latch On Latch Off 48 Reset CB Total Trip Count, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 49 Reset CB Delta Trip Count, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 50 Reset CB Count To AR Block, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 51 Reset CB Frequent Ops Count, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 0 2 2 0 1 Pulse On Latch On Pulse On Close 53 Reset I^2t CB Wear 54 CB 1 0 2 2 0 1 Pulse On Pulse Off Latch On Latch Off Close Trip Pulse On Pulse Off Latch On Latch Off 55 CB 1 Trip & Reclose, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 56 CB 1 Trip & Lockout, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 59 Demand metering reset, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 87 Reset Energy Meters 0 2 2 0 1 Pulse On Latch On Pulse On Close 88 Remote mode 0 2 2 0 1 Pulse On Latch On Pulse On Close 89 Service mode 0 2 2 0 1 Pulse On Latch On Pulse On Close Chapter 4 - Page 74 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Binary Output Status Points Static (Steady-State) Object Number: 10 Change Event Object Number: 11 Control Relay Output Blocks (CROB) Object Number: 12 Binary Output Command Event Object Number: 13 Static Variation reported when variation 0 requested: 1 (Binary Output w/o status) or 2 (Binary Output with status) Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time) or 2 (Binary Output Event with Time) Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time) or 2 (Command Status with Time) Default Variation Event Object 11 Default Command Event Object 13 Assigned Class (1, 2, 3 or none) Default Variation Command Event Object 13 2 2 0 1 Pulse On Latch On Pulse On Close 2 2 0 1 Pulse On Latch On Pulse On Close 1 Pulse On Pulse Off Latch On Latch Off Close Trip Pulse On Pulse Off Latch On Latch Off Pulse On Pulse Off Latch On Latch Off Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 10 90 Local mode 0 91 Local & Remote 0 Point Index Description 92 Man Override Sync on/off 0 2 2 0 CROB Supported Operations Default CROB Operations 93 79 Override Sync on/off 0 2 2 0 1 Pulse On Pulse Off Latch On Latch Off Close Trip Reset CB Phase A Trip 94 Count, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 95 Reset CB Phase B Trip Count, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 96 Reset CB Phase C Trip Count, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 97 Reset CB EF Trip Count, write only location. 0 2 2 0 1 Pulse On Latch On Pulse On Close 98 Reset Start Count (Action) 0 2 2 0 1 Pulse On Pulse On Latch On Latch On Close 99 User SP Command 1. 0 2 2 0 1 Pulse On Latch On Pulse On Close 100 User SP Command 2. 0 2 2 0 1 Pulse On Latch On Pulse On Close 101 User SP Command 3. 0 2 2 0 1 Pulse On Latch On Pulse On Close 102 User SP Command 4. 0 2 2 0 1 Pulse On Latch On Pulse On Close (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 75 of 96 7SR220 Technical Manual Binary Output Status Points Static (Steady-State) Object Number: 10 Change Event Object Number: 11 Control Relay Output Blocks (CROB) Object Number: 12 Binary Output Command Event Object Number: 13 Static Variation reported when variation 0 requested: 1 (Binary Output w/o status) or 2 (Binary Output with status) Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time) or 2 (Binary Output Event with Time) Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time) or 2 (Command Status with Time) Default Variation Event Object 11 Default Command Event Object 13 Assigned Class (1, 2, 3 or none) Default Variation Command Event Object 13 2 2 0 1 Pulse On Latch On Pulse On Close 0 2 2 0 1 Pulse On Latch On Pulse On Close 105 User SP Command 7. 0 2 2 0 1 Pulse On Latch On Pulse On Close 106 User SP Command 8. 0 2 2 0 1 Pulse On Latch On Pulse On Close 1 Pulse On Pulse Off Latch On Pulse On Latch Off Pulse Off Close Trip 1 Pulse On Pulse Off Latch On Pulse On Latch Off Pulse Off Close Trip 1 Pulse On Pulse Off Latch On Pulse On Latch Off Pulse Off Close Trip 1 Pulse On Pulse Off Latch On Pulse On Latch Off Pulse Off Close Trip 1 Pulse On Pulse Off Latch On Pulse On Latch Off Pulse Off Close Trip 1 Pulse On Pulse Off Latch On Pulse On Latch Off Pulse Off Close Trip Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 10 103 User SP Command 5. 0 104 User SP Command 6. Point Index Description 107 User DP Command 1. 108 User DP Command 2. 109 User DP Command 3. 110 User DP Command 4. 111 User DP Command 5. 112 User DP Command 6. Chapter 4 - Page 76 of 96 0 0 0 0 0 0 2 2 2 2 2 2 2 2 2 2 2 2 0 0 0 0 0 0 CROB Supported Operations Default CROB Operations (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Binary Output Status Points Static (Steady-State) Object Number: 10 Change Event Object Number: 11 Control Relay Output Blocks (CROB) Object Number: 12 Binary Output Command Event Object Number: 13 Static Variation reported when variation 0 requested: 1 (Binary Output w/o status) or 2 (Binary Output with status) Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time) or 2 (Binary Output Event with Time) Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time) or 2 (Command Status with Time) Point Index Description 113 User DP Command 7. Default Change Event Assigned Class (1, 2, 3 or none) 0 Default Variation Static Object 10 2 Default Variation Event Object 11 2 Default Command Event Object 13 Assigned Class (1, 2, 3 or none) 0 Default Variation Command Event Object 13 CROB Supported Operations Default CROB Operations 1 Pulse On Pulse Off Latch On Pulse On Latch Off Pulse Off Close Trip 114 User DP Command 8. 0 2 2 0 1 Pulse On Pulse Off Latch On Pulse On Latch Off Pulse Off Close Trip 115 CB-1 Open 0 2 2 0 1 Pulse On Pulse On Latch On Latch On Close 116 CB-1 Close 0 2 2 0 1 Pulse On Pulse On Latch On Latch On Close 1 Pulse On Pulse Off Latch On Latch Off Close Trip Pulse On Pulse Off Latch On Latch Off Pulse On Pulse Off Latch On Latch Off 126 E/F In on/off 127 SEF In on/off 128 Reset Hrs In Service, write only location. 0 2 2 0 0 2 2 0 1 Pulse On Pulse Off Latch On Latch Off Close Trip 0 2 2 0 1 Pulse On Latch On Pulse On Close 5.3.4 Counters The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function is performed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point. The default Binary Counter and Frozen Counter event buffer sizes are set to 30. The "Default Deadband," and the "Default Change Event Assigned Class" columns are used to represent the absolute amount by which the point must change before a Counter change event will be generated, and once generated in which class poll (1, 2, 3, or none) will the change event be reported. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 77 of 96 7SR220 Technical Manual The default counter event buffer size is set 30. The counter event mode is set to Most Recent, only most recent event for each point is stored. Counters are by default returned in a class zero interrogation. Note, not all points listed here apply to all builds of devices. Counters Static (Steady-State) Object Number: 20 Change Event Object Number: 22 Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag) or 2 (16-Bit Counter with Flag) or 5 (32-Bit Counter w/o Flag) or 6 (16-Bit Counter w/o Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Event with Flag) or 2 (16-Bit Counter Event with Flag) or 5 (32-Bit Counter Event with Flag and Time) or 6 (16-Bit Counter Event with Flag and Time) Frozen Counters Static (Steady-State) Object Number: 21 Change Event Object Number: 23 Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag) or 2 (16-Bit Frozen Counter with Flag) or 5 (32-Bit Frozen Counter with Flag and Time) or 6 (16-Bit Frozen Counter with Flag and Time) or 9 (32-Bit Frozen Counter w/o Flag) or 10 (16-Bit Frozen Counter w/o Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event with Flag) or 2 (16-Bit Frozen Counter Event with Flag) or 5 (32-Bit Frozen Counter Event with Flag and Time) or 6 (16-Bit Frozen Counter Event with Flag and Time) Frozen Counter Default Variation Static Object 21 Default Variation Event Object 23 0,2 9 1 1 0,2 9 1 1 1 0,2 9 1 5 1 1 0,2 9 1 0,3 5 1 1 0,2 9 1 0,3 5 1 1 0,2 9 1 1 0,2 9 1 0,2 9 1 Default Variation Static Object 20 Default Variation Event Object 22 0 Waveform Records 0,3 5 1 1 1 Fault Records 0,3 5 1 2 Event Records 0,3 5 3 Data Log Records 0,3 5 StartCount 6 Start Count Target Point Index Description 7 Active Setting Group 0,3 5 1 Is Resettable Default Change Event Assigned Class (1, 2, 3 or none) Default Change Event Assigned Class (1, 2, 3 or none) Deadband IsFreezable Counter 11 CB Total Trip Count 0,3 5 1 1 12 CB Ph A Trip Count 0,3 5 1 1 0,2 9 1 13 CB Ph B Trip Count 0,3 5 1 1 0,2 9 1 14 CB Ph C Trip Count 0,3 5 1 1 0,2 9 1 15 CB E/F Trip Count 0,3 5 1 1 0,2 9 1 16 CB Delta Trip Count 0,3 5 1 1 0,2 9 1 17 CB Count To AR Block 0,3 5 1 1 0,2 9 1 18 CB Frequent Ops Count 0,3 5 1 1 0,2 9 1 21 E1 Counter 0,3 5 1 1 0,2 9 1 22 E2 Counter 0,3 5 1 1 0,2 9 1 23 E3 Counter 0,3 5 1 1 0,2 9 1 24 E4 Counter 0,3 5 1 1 0,2 9 1 Chapter 4 - Page 78 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Counters Static (Steady-State) Object Number: 20 Change Event Object Number: 22 Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag) or 2 (16-Bit Counter with Flag) or 5 (32-Bit Counter w/o Flag) or 6 (16-Bit Counter w/o Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Event with Flag) or 2 (16-Bit Counter Event with Flag) or 5 (32-Bit Counter Event with Flag and Time) or 6 (16-Bit Counter Event with Flag and Time) Frozen Counters Static (Steady-State) Object Number: 21 Change Event Object Number: 23 Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag) or 2 (16-Bit Frozen Counter with Flag) or 5 (32-Bit Frozen Counter with Flag and Time) or 6 (16-Bit Frozen Counter with Flag and Time) or 9 (32-Bit Frozen Counter w/o Flag) or 10 (16-Bit Frozen Counter w/o Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event with Flag) or 2 (16-Bit Frozen Counter Event with Flag) or 5 (32-Bit Frozen Counter Event with Flag and Time) or 6 (16-Bit Frozen Counter Event with Flag and Time) Counter Default Variation Static Object 20 Default Variation Event Object 22 25 E5 Counter 0,3 5 1 1 26 E6 Counter 0,3 5 1 27 E7 Counter 0,3 5 28 E8 Counter 0,3 29 E9 Counter Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 21 Default Variation Event Object 23 0,2 9 1 1 0,2 9 1 1 1 0,2 9 1 5 1 1 0,2 9 1 0,3 5 1 1 0,2 9 1 30 E10 Counter 0,3 5 1 1 0,2 9 1 31 E11 Counter 0,3 5 1 1 0,2 9 1 32 E12 Counter 0,3 5 1 1 0,2 9 1 33 E13 Counter 0,3 5 1 1 0,2 9 1 34 E14 Counter 0,3 5 1 1 0,2 9 1 1 0,2 9 1 1 0,2 9 1 Point Index Description 35 E15 Counter 36 E16 Counter 0,3 0,3 5 5 1 1 Is Resettable IsFreezable Default Change Event Assigned Class (1, 2, 3 or none) Deadband Frozen Counter 5.3.5 Analog Inputs The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit variations of Analog Inputs, Analog Output Control Blocks, and Analog Output Statuses are transmitted through DNP as signed numbers. The "Default Deadband," and the "Default Change Event Assigned Class" columns are used to represent the absolute amount by which the point must change before an Analog change event will be generated, and once generated in which class poll (1, 2, 3, or none) will the change event be reported. The default analog input event buffer size is set 30. The analog input event mode is set to Most Recent, only most recent event for each point is stored. Analog inputs are by default returned in a class zero interrogation. Note, not all points listed here apply to all builds of devices. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 79 of 96 7SR220 Technical Manual Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Analog Input Deadband: 34 Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag) or 2 (16-Bit Analog Input with Flag) or 3 (32-Bit Analog Input w/o Flag) or 4 (16-Bit Analog Input w/o Flag) or 5 (Single Precision, floating point Analog Input with Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time) or 2 (16-Bit Analog Input w/o Time) or 3 (32-Bit Analog Input with Time) or 4 (16-Bit Analog Input with Time) or 5 (Single Precision, floating point Analog Input w/o Time) or 7 (Single Precision, floating point Analog Input with Time) Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit) or 2 (32-Bit) or 3 (Single Precision, floating point) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 30 Default Variation Event Object 32 0 Frequency 0,3 2 4 100.000 1.000 1 Vab Primary 0,3 2 4 0.010 100.000 2 Vbc Primary 0,3 2 4 0.010 100.000 3 Vca Primary 0,3 2 4 0.010 100.000 4 Va Primary 0,3 2 4 0.010 100.000 5 Vb Primary 0,3 2 4 0.010 100.000 6 Vc Primary 0,3 2 4 0.010 100.000 7 Va Secondary 0,3 2 4 10.000 1.000 8 Vb Secondary 0,3 2 4 10.000 1.000 9 Vc Secondary 0,3 2 4 10.000 1.000 21 Vzps 0,3 2 4 10.000 1.000 22 Vpps 0,3 2 4 10.000 1.000 23 Vnps 0,3 2 4 10.000 1.000 31 Ia Primary 0,3 2 4 1.000 100.000 32 Ib Primary 0,3 2 4 1.000 100.000 33 Ic Primary 0,3 2 4 1.000 100.000 34 Ia Secondary 0,3 2 4 100.000 0.100 35 Ib Secondary 0,3 2 4 100.000 0.100 36 Ic Secondary 0,3 2 4 100.000 0.100 37 Ia Nominal 0,3 2 4 100.000 0.100 38 Ib Nominal 0,3 2 4 100.000 0.100 39 Ic Nominal 0,3 2 4 100.000 0.100 43 In Primary 0,3 2 4 1.000 100.000 44 In Secondary 0,3 2 4 100.000 0.100 45 In Nominal 0,3 2 4 100.000 0.100 46 Ig Primary 0,3 2 4 1.000 100.000 47 Ig Secondary 0,3 2 4 1000.000 0.100 48 Ig Nominal 0,3 2 4 1000.000 0.100 51 Izps Nominal 0,3 2 4 100.000 0.100 52 Ipps Nominal 0,3 2 4 100.000 0.100 53 Inps Nominal 0,3 2 4 100.000 0.100 57 Active Power A 0,3 2 4 0.000 1000000.000 58 Active Power B 0,3 2 4 0.000 1000000.000 Point Index Description Chapter 4 - Page 80 of 96 Default Multiplier Default Deadband (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Analog Input Deadband: 34 Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag) or 2 (16-Bit Analog Input with Flag) or 3 (32-Bit Analog Input w/o Flag) or 4 (16-Bit Analog Input w/o Flag) or 5 (Single Precision, floating point Analog Input with Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time) or 2 (16-Bit Analog Input w/o Time) or 3 (32-Bit Analog Input with Time) or 4 (16-Bit Analog Input with Time) or 5 (Single Precision, floating point Analog Input w/o Time) or 7 (Single Precision, floating point Analog Input with Time) Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit) or 2 (32-Bit) or 3 (Single Precision, floating point) Point Index Description Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 30 Default Variation Event Object 32 Default Multiplier Default Deadband 59 Active Power C 0,3 2 4 0.000 1000000.000 60 P (3P) 0,3 2 4 0.000 1000000.000 61 Reactive Power A 0,3 2 4 0.000 1000000.000 62 Reactive Power B 0,3 2 4 0.000 1000000.000 63 Reactive Power C 0,3 2 4 0.000 1000000.000 64 Q (3P) 0,3 2 4 0.000 1000000.000 65 Apparent Power A 0,3 2 4 0.000 1000000.000 66 Apparent Power B 0,3 2 4 0.000 1000000.000 67 Apparent Power C 0,3 2 4 0.000 1000000.000 68 S (3P) 0,3 2 4 0.000 1000000.000 71 Power Factor A 0,3 2 4 1000.000 0.100 72 Power Factor B 0,3 2 4 1000.000 0.100 73 Power Factor C 0,3 2 4 1000.000 0.100 74 Power Factor(3P) 0,3 2 4 1000.000 0.100 75 Act Energy Exp 0,3 1 3 1.000 Disabled 76 Act Energy Imp 0,3 1 3 1.000 Disabled 77 React Energy Exp 0,3 1 3 1.000 Disabled 78 React Energy Imp 0,3 1 3 1.000 Disabled 81 Thermal Status Ph A 0,1 4 4 100.000 1.000 82 Thermal Status Ph B 0,1 4 4 100.000 1.000 83 Thermal Status Ph C 0,1 4 4 100.000 1.000 95 Active Setting Group 0,3 2 4 1.000 1.000 99 Vab Secondary 0,3 2 4 10.000 1.000 100 Vbc Secondary 0,3 2 4 10.000 1.000 101 Vca Secondary 0,3 2 4 10.000 1.000 102 Vn Primary 0,3 2 4 0.010 100.000 103 Vn Secondary 0,3 2 4 10.000 1.000 105 Vx Primary 0,3 2 4 0.010 100.000 106 Vx Secondary 0,3 2 4 10.000 1.000 108 I Phase A Max 0,3 2 4 1.000 100.000 109 I Phase B Max 0,3 2 4 1.000 100.000 110 I Phase C Max 0,3 2 4 1.000 100.000 111 P 3P Max 0,3 2 4 0.000 1000000.000 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 81 of 96 7SR220 Technical Manual Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Analog Input Deadband: 34 Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag) or 2 (16-Bit Analog Input with Flag) or 3 (32-Bit Analog Input w/o Flag) or 4 (16-Bit Analog Input w/o Flag) or 5 (Single Precision, floating point Analog Input with Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time) or 2 (16-Bit Analog Input w/o Time) or 3 (32-Bit Analog Input with Time) or 4 (16-Bit Analog Input with Time) or 5 (Single Precision, floating point Analog Input w/o Time) or 7 (Single Precision, floating point Analog Input with Time) Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit) or 2 (32-Bit) or 3 (Single Precision, floating point) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 30 Default Variation Event Object 32 112 Q 3P Max 0,3 2 4 0.000 1000000.000 113 Ig Max 0,3 2 4 1.000 100.000 115 Isef Primary 0,3 2 4 1.000 10.000 116 Isef Secondary 0,3 2 4 1000.000 0.050 117 Isef Nominal 0,3 2 4 1000.000 0.050 118 Fault Distance Percent 0,3 2 4 100.000 Disabled 119 Fault Reactance 0,3 2 4 1000.000 Disabled 135 CB Total Trip Count 0,3 1 3 1.000 1.000 136 CB Delta Trip Count 0,3 1 3 1.000 1.000 137 CB Count To AR Block 0,3 1 3 1.000 1.000 138 CB Frequent Ops Count 0,3 1 3 1.000 1.000 162 Phase Diff 0,3 2 4 100.000 1.000 163 Slip Freq 0,3 2 4 100.000 1.000 164 Voltage Diff 0,3 2 4 100.000 1.000 165 Ia Last Trip 0,3 1 3 1.000 Disabled 166 Ib Last Trip 0,3 1 3 1.000 Disabled 167 Ic Last Trip 0,3 1 3 1.000 Disabled 168 Va Last Trip 0,3 1 3 1.000 Disabled 169 Vb Last Trip 0,3 1 3 1.000 Disabled 170 Vc Last Trip 0,3 1 3 1.000 Disabled 171 In Last Trip 0,3 1 3 1.000 Disabled 172 Ig Last Trip 0,3 1 3 1.000 Disabled 173 Isef Last Trip 0,3 1 3 1.000 Disabled 174 V Phase A Max 0,3 2 4 0.010 100.000 175 V Phase B Max 0,3 2 4 0.010 100.000 176 V Phase C Max 0,3 2 4 0.010 100.000 177 V Phase AB Max 0,3 2 4 0.010 100.000 178 V Phase BC Max 0,3 2 4 0.010 100.000 179 V Phase CA Max 0,3 2 4 0.010 100.000 180 CB Ph A Trip Count 0,3 1 3 1.000 1.000 181 CB Ph B Trip Count 0,3 1 3 1.000 1.000 182 CB Ph C Trip Count 0,3 1 3 1.000 1.000 183 CB E/F Trip Count 0,3 1 3 1.000 1.000 184 CB Wear A 0,3 1 3 0.000 1000000.000 Point Index Description Chapter 4 - Page 82 of 96 Default Multiplier Default Deadband (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Analog Input Deadband: 34 Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag) or 2 (16-Bit Analog Input with Flag) or 3 (32-Bit Analog Input w/o Flag) or 4 (16-Bit Analog Input w/o Flag) or 5 (Single Precision, floating point Analog Input with Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time) or 2 (16-Bit Analog Input w/o Time) or 3 (32-Bit Analog Input with Time) or 4 (16-Bit Analog Input with Time) or 5 (Single Precision, floating point Analog Input w/o Time) or 7 (Single Precision, floating point Analog Input with Time) Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit) or 2 (32-Bit) or 3 (Single Precision, floating point) Default Change Event Assigned Class (1, 2, 3 or none) Default Variation Static Object 30 Default Variation Event Object 32 185 CB Wear B 186 CB Wear C 0,3 1 3 0.000 1000000.000 0,3 1 3 0.000 1000000.000 187 CB Wear A Remaining 0,3 1 3 1.000 1.000 188 CB Wear B Remaining 0,3 1 3 1.000 1.000 189 CB Wear C Remaining 0,3 1 3 1.000 1.000 190 CB Wear Minimum 0,3 1 3 1.000 1.000 191 Fault Distance Perunit 0,3 5 7 0.001 1.000 196 Frequency Max 0,3 2 4 100.000 1.000 197 S 3P Max 0,3 2 4 0.000 1000000.000 318 Sec Active Power A 0,3 2 4 1.000 10.000 319 Sec Active Power B 0,3 2 4 1.000 10.000 320 Sec Active Power C 0,3 2 4 1.000 10.000 321 Sec P (3P) 0,3 2 4 1.000 10.000 322 Sec Reactive Power A 0,3 2 4 1.000 10.000 323 Sec Reactive Power B 0,3 2 4 1.000 10.000 324 Sec Reactive Power C 0,3 2 4 1.000 10.000 325 Sec Q (3P) 0,3 2 4 1.000 10.000 326 Sec Apparent Power A 0,3 2 4 1.000 10.000 327 Sec Apparent Power B 0,3 2 4 1.000 10.000 328 Sec Apparent Power C 0,3 2 4 1.000 10.000 329 Sec S (3P) 0,3 2 4 1.000 10.000 330 CB Trip Time Meter 0,3 2 4 1000.000 0.010 337 PF 3P Max 0,3 2 4 1000.000 0.100 Point Index Description Default Multiplier Default Deadband 5.4 Additional Settings The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are common to all ports using this protocol. Setting Name Unsolicited Mode Range/Options DISABLED, ENABLED (c) 2017 Siemens Protection Devices Limited Default DISABLED Setting As Required Notes Setting is only visible when any port Protocol is set to DNP3. Chapter 4 - Page 83 of 96 7SR220 Technical Manual Setting Name Range/Options Destination Address DNP3 Application Timeout 0 - 65534 5, 6 ... 299, 300 Chapter 4 - Page 84 of 96 Default 0 10s Setting Notes As Required Setting is only visible when DNP3 Unsolicited Events set to Enabled. As Required Setting is only visible when any port Protocol is set to DNP3. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 6. Not Applicable This section intentionally left blank. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 85 of 96 7SR220 Technical Manual Chapter 4 - Page 86 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 7. IEC61850 Protocol Support 7.1 Introduction The relay can optionally be provided with IEC61850 comms. For further details refer to the following publications: * Model Implementation Conformance Statement (MICS) * Protocol Implementation Conformance Statement (PICS) * Protocol Implementation Extra Information for Testing (PIXIT) (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 87 of 96 7SR220 Technical Manual Chapter 4 - Page 88 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 8. Serial Modems 8.1 Introduction The communications interface has been designed to allow data transfer via modems. A suitable Modem can be connected directly to the Relay's serial interface, for example RS232, RS485 or fibre-optic port where fitted. 8.2 Connecting a Modem to the Relay(s) RS232C defines devices as being either Data Terminal Equipment (DTE) e.g. computers, or data Communications Equipment (DCE), e.g. modems, where one is designed to be connected to the other. The optional RS232 port of the Relay is wired as a DTE device and can therefore be connected directly to a Modem. The 7XV5652 RS232 fibre-optic converter is wired as a DCE device, the same as a Modem. Where two DCE devices e.g. the modem and the fibre-optic converter are being connected together a null terminal connector is required which switches various control lines. The fibre-optic converter is then connected to the relay Network Tx to Relay Rx and Network Rx to Relay Tx. 8.3 Setting the Remote Modem The exact settings of the modem are dependent on the type of modem. Although most modems support the basic Hayes "AT" command format, different manufacturers use different commands for the same functions. In addition, some modems use DIP switches to set parameters, others are entirely software configured. Before applying settings, the modem's factory default settings should be applied, to ensure it is in a known state. Several factors must be considered to allow remote dialling to the relays. The first is that the modem at the remote end must be configured as auto answer. This will allow it to initiate communications with the relays. Next, the user should set the data configuration at the local port, i.e. baud rate and parity, so that communication will be at the same rate and format as that set on the relay and the error correction is disabled. Auto-answer usually requires two parameters to be set. The auto-answer setting should be switched on and the number of rings after which it will answer. The Data Terminal Ready (DTR) settings should be forced on. This tells the modem that the device connected to it is ready to receive data. The parameters of the modem's RS232C port are set to match those set on the relay, set baud rate and parity to be the same as the settings on the relay and number of data bits to be 8 and stop bits 1. Note, although the device may be able to communicate with the modem at, for example, 19200 bps, the modem may only be able to transmit over the telephone lines at 14400 bps. Therefore, a baud rate setting on which the modem can transmit should be chosen. In the above example, a baud rate of 9600 should be chosen. As the modems are required to be transparent, simply passing on the data sent from the controller to the device and vice versa, error correction and buffering is turned off. Finally, the settings selected for configuration should be stored in the modem's memory for power on defaults. 8.4 Connecting to the Remote Modem Once the remote modem has been configured correctly, it should be possible to make connection to the relay. Where a "dial-up" modem system is installed the settings on the remote modem are fixed so the local modem should negotiate with it on connection, choosing suitable matching settings. Where this is not possible the local modem should be set with settings equivalent to those of the remote modem as described above. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 89 of 96 7SR220 Technical Manual Chapter 4 - Page 90 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 9. Not Applicable This section intentionally left blank. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 91 of 96 7SR220 Technical Manual Chapter 4 - Page 92 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions 10. Glossary Baud Rate Data transmission speed. Bit The smallest measure of computer data. Bits Per Second (bps) Measurement of data transmission speed. Data Bits A number of bits containing the data. Sent after the start bit. Data Echo When connecting relays in an optical ring architecture, the data must be passed from one relay to the next, therefore when connecting in this method all relays must have the Data Echo ON. EN100 Siemens' Ethernet communications module supporting IEC61850, available in optical and electrical versions. Ethernet A computer networking technology. Full-Duplex Asynchronous Communications Communications in two directions simultaneously. Half-Duplex Asynchronous Communications Communications in two directions, but only one at a time. Hayes "AT" Modem command set developed by Hayes Microcomputer products, Inc. LAN Local Area Network. A computer network covering a small geographic area. LC Fibre optic connector type designed by Lucent Technologies, Inc. Line Idle Determines when the device is not communicating if the idle state transmits light. Modem MOdulator / DEModulator device for connecting computer equipment to a telephone line. Parity Method of error checking by counting the value of the bits in a sequence, and adding a parity bit to make the outcome, for example, even. Parity Bit Bit used for implementing parity checking. Sent after the data bits. RS232C Serial Communications Standard. Electronic Industries Association Recommended Standard Number 232, Revision C. RS485 Serial Communications Standard. Electronic Industries Association Recommended Standard Number 485. (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 93 of 96 7SR220 Technical Manual Start Bit Bit (logical 0) sent to signify the start of a byte during data transmission. Stop Bit Bit (logical 1) sent to signify the end. USB Universal Serial Bus standard for the transfer of data. WAN Wide Area Network. A computer network covering a large geographic area. Chapter 4 - Page 94 of 96 (c) 2017 Siemens Protection Devices Limited Chapter 4 - Data Communications Definitions Appendix 1 The operating mode of the device is set via the setting, or through a command sent to a communications port. There are four options; Local, Remote, Local or Remote and Service. The following table illustrates whether a function is Enabled () or Disabled () in each mode. Operation Mode Function Local Remote Out of Service Com1 when Com1-Mode = Local when Com1-Mode = Remote Com2 (USB) when Com2-Mode = Local when Com2-Mode = Remote Com3 when Com3-Mode = Local when Com3-Mode = Remote when Com4-Mode = Local when Com4-Mode = Remote Fascia (Control Mode) Function Key (n) when F Key(n) Mode = Remote Binary Input (n) when BI (n) Mode = Local when BI (n) Mode = Remote Binary Outputs IEC DNP3 IEC DNP3 MODBUS Com1 when Com1-Mode = Local when Com1-Mode = Remote Com2 (USB) when Com2-Mode = Local when Com2-Mode = Remote Com3 when Com3-Mode = Local when Com3-Mode = Remote Com4 when Com4-Mode = Local when Com4-Mode = Remote Fascia Waveform Records Event Records Fault Information Setting Information Control Com4 Reporting Spontaneous General Interrogation Change Settings Historical Information Fig. A1 Operating Mode Table (c) 2017 Siemens Protection Devices Limited Chapter 4 - Page 95 of 96 7SR220 Technical Manual Siemens Protection Devices Ltd. (SPDL) P.O. Box 8 Hebburn Tyne and Wear NE31 1TZ United Kingdom For enquiries please contact our Customer Support Centre Tel.: +49 180/524 8437 (24hrs) Fax.: +49 180/524 2471 E-Mail:support.ic@siemens.com www.siemens.com/reyrolle Template Revision 17. Chapter 4 - Page 96 of 96 (c) 2017 Siemens Protection Devices Limited 7SR210 Non-Directional Relay 7SR220 Directional Relay Installation Guide Unrestricted The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Document Release History This document is issue 2018/10. The list of revisions up to and including this issue is: 2011/05 First issue 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions amended drawings and added data. Updated in line with software release. 2015/07 Amended drawings. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/11 Redundancy added to electrical ethernet interface 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. 2018/05 Amended RS485 connection diagrams. 2018/07 Addition of Disposal information 2018/10 Addition of check sync diagram Software Revision History 2011/05 2435H85008R7a-7a (7SR210) First Release 2435H85009R7a-7a (7SR220) 2013/01 2435H85008R7c-7b (7SR210) 2435H85009R7c-7b (7SR220) 2014/06 2435H85008R7f-7d (7SR210) 2435H85009R7f-7d (7SR220) 2015/06 2435H85008R8a-7f (7SR210) 2435H85009R8a-7f (7SR220) 2016/02 2435H85008R8b-7f (7SR210) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Added Fault Locator feature and Check Sync feature. Fault data transmitted over 103. Additional communications data, control features, meters. Added Power Factor Meters, Load Blinding feature, Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. 2435H85009R8b-7f (7SR220) 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Unrestricted Page 2 of 36 Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing, 67SEF Compensated Network, 67SEF Wattmetric. Increased I/O. Event Data on LCD. (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Table of Contents Document Release History ............................................................................................................... 2 Software Revision History ................................................................................................................ 2 Section 1: Installation ....................................................................................................................... 5 1.1 Unpacking, Storage and Handling ........................................................................................ 5 1.2 Recommended Mounting Position ........................................................................................ 5 1.3 Wiring .................................................................................................................................. 5 1.4 Earthing ............................................................................................................................... 5 1.5 Ancillary Equipment.............................................................................................................. 5 Section 2: Equipment Operating Conditions ................................................................................... 6 2.1 Current Transformer Circuits ................................................................................................ 6 2.2 External Resistors ................................................................................................................ 6 2.3 Fibre Optic Communication .................................................................................................. 6 2.4 Front Cover .......................................................................................................................... 6 2.5 Disposal ............................................................................................................................... 6 2.5.1 Environmental Protection Hints ................................................................................ 6 Section 3: Dimensions and Panel Fixings ....................................................................................... 8 3.1 Relay Dimensions and Weight .............................................................................................. 8 3.2 Fixings ............................................................................................................................... 11 3.2.1 Crimps ................................................................................................................... 11 3.2.2 Panel Fixings ......................................................................................................... 11 3.2.3 Fibre Optic Connectors .......................................................................................... 11 3.2.4 Connectors Ethernet Option ................................................................................... 11 Section 4: Rear Terminal Drawings................................................................................................ 12 4.1 E6 Case ............................................................................................................................. 12 4.2 E8 Case ............................................................................................................................. 14 4.3 E12 Case ........................................................................................................................... 16 Section 5: Connection/Wiring/Diagrams ........................................................................................ 19 5.1 Wiring Diagram: 7SR21 OC/EF Relay ................................................................................ 19 5.2 Wiring Diagram: 7SR22 Directional OC/EF Relay ............................................................... 20 Section 6: Data Comms Connections ............................................................................................ 21 6.1 Standard RS485 Connections ............................................................................................ 21 6.2 IRIG-B Connections ........................................................................................................... 21 6.3 Additional (Optional) Fibre Optic Connections..................................................................... 22 6.4 Additional (Optional) RS485 Connections ........................................................................... 23 6.5 Additional (Optional) RS232 Connections ........................................................................... 23 6.6 Additional (Optional) Ethernet Connection for IEC 61850 .................................................... 24 6.7 Ethernet Network Redundancy IEC 61850.......................................................................... 25 6.7.1 RSTP - Rapid Spanning Tree Protocol .................................................................. 26 6.7.2 PRP - Parallel Redundancy Protocol ..................................................................... 26 6.7.3 HSR - High Availability Seamless Redundancy Protocol ........................................ 28 Section 7: Connection Diagrams.................................................................................................... 29 7.1 Typical Connection: 7SR22 Directional OC/EF and REF..................................................... 29 7.2 Typical Connection: 7SR22 Directional OC/EF and NVD .................................................... 30 7.3 Typical Connection: 7SR22 Directional OC/EF and NVD .................................................... 31 7.4 Typical Connection: 7SR22 Directional OC/EF and NVD .................................................... 32 7.5 Typical Connection: 7SR22 Directional OC and EF ............................................................ 33 7.6 Typical Connection: 7SR22 Connected to VTs and Capacitor Cone Unit ............................ 34 Unrestricted (c)2018 Siemens Protection Devices Limited Page 3 of 36 7SR210 & 7SR220 Installation Guide 7.7 Typical Connection: 7SR22 Voltage Transformer Configurations for Check Synchronisation35 7.8 Voltage Transformer Configurations ................................................................................... 36 LIST OF FIGURES Figure 3.1-1 Overall Dimensions (mm) and panel Drilling for Size E6 Epsilon case .............................. 8 Figure 3.1-2 Overall Dimensions (mm) and Panel Drilling for Size E8 Epsilon Case............................. 9 Figure 3.1-3 Overall Dimensions (mm) and Panel Drilling for Size E12 Epsilon Case ......................... 10 Figure 4.1-1 E6 Standard Comms (USB Front Port, Rear RS485) (See Note 2)................................. 12 Figure 4.1-2 E6 Standard + Additional Comms (IRIG-B, 2 x F.O. (ST Connectors)) (See Note 2) .......................................................................................................................... 12 Figure 4.1-3 E6 Standard + Additional Comms (IRIG B + RS485) (See Note 2) ................................. 13 Figure 4.1-4 E6 Standard + Additional Comms (IRIG B + RS232) (See Note 2) ................................ 13 Figure 4.2-1 E8 Standard Comms (USB Front Port, Rear RS485) (See Note 2)................................. 14 Figure 4.2-2 E8 Standard + Additional Comms (IRIG B, 2 x F.O. (ST Connectors)) (See Note 2) .......................................................................................................................... 14 Figure 4.2-3 E8 Standard + Additional Comms (IRIG B + RS485) (See Note 2) ................................. 15 Figure 4.2-4 E8 Standard + Additional Comms (IRIG B + RS232) (See Note 2) ................................. 15 Figure 4.3-1 E12 Standard + Additional Comms (IRIG B, 2 x F.O. (ST Connectors)) (See Note 2) .......................................................................................................................... 16 Figure 4.3-2 E12 Standard + Additional Comms (IRIG B + RS485) (See Note 2) ............................... 16 Figure 4.3-3 E12 Standard + Additional Comms (IRIG B + RS232) (See Note 2) ............................... 17 Figure 4.3-4 E12 Standard + Additional Comms (RS485 + Ethernet (x2)) (See Note 2) ..................... 17 Figure 4.3-5 Standard Comms + Additional Ethernet Ports (RJ45 shown, Duplex LC Fibre Optic similar) ................................................................................................................. 18 Figure 5.1-1 Connection Diagram for 7SR21 Relay ........................................................................... 19 Figure 5.2-1 Connection Diagram for 7SR22 Relay ........................................................................... 20 Figure 6.1-1 RS485 Data Comms Connections Between Relays ....................................................... 21 Figure 6.3-1 Data Comms to Multiple Devices Using 7SG24 and F.O. Star Network .......................... 22 Figure 6.3-2 Data Comms to Multiple Devices Using 7SG24 and F.O. Ring Network ......................... 22 Figure 6.4-1 RS485 Data Comms Connections Between Relays ....................................................... 23 Figure 6.5-1 RS232 Data Comms Pin Connections ........................................................................... 23 Figure 6.6-1 Ethernet connection for IEC 61850 (star connection) ..................................................... 24 Figure 6.6-2 Ethernet connection for IEC 61850 (ring connection) ..................................................... 24 Figure 6.7-1 EN100 Redundancy Availability ..................................................................................... 25 Figure 7.1-1 7SR22 Applied to Transformer Incomer ......................................................................... 29 Figure 7.2-1 7SR22 Applied to Transformer Incomer Including HV NVD Protection......................... 30 Figure 7.3-1 7SR22 Applied to Feeder Including NVD Protection....................................................... 31 Figure 7.4-1 7SR22 Applied to Feeder .............................................................................................. 32 Figure 7.5-1 7SR22 Applied to Feeder - No Zero Sequence Voltage Source ..................................... 33 Figure 7.6-1 7SR22 Applied to Feeder with Capacitor Cones Fitted................................................... 34 Figure 7.7-1 7SR22 Applied to Check Synchronisation ...................................................................... 35 Figure 7.7-1 7SR22 VT Connections ................................................................................................. 36 Unrestricted Page 4 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Section 1: Installation 1.1 Unpacking, Storage and Handling On receipt remove the relay from the container in which it was received and inspect it for obvious damage. It is recommended that the relay not be removed from its case. If damage has been sustained a claim should be immediately be made against the carrier, also inform Siemens Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this manual. When not required for immediate use, the relay should be returned to its original carton and stored in a clean, dry place. The relay contains static sensitive devices, which are susceptible to damage due to static discharge. The relay's electronic circuits are protected from damage by static discharge when the relay is housed in its case. There can be no requirement to disassemble any relay, since there are no user serviceable parts in the relay. If any modules have been tampered with, then the guarantee will be invalidated. Siemens Protection Devices Limited reserves the right to charge for any subsequent repairs. 1.2 Recommended Mounting Position The relay uses a liquid crystal display (LCD) which is used in the programming and for operation. The LCD has a vertical viewing angle of 30 and is back-lit. However, the best viewing position is at eye level, and this is particularly important given its control features. The relay should be mounted on the circuit breaker (or protection panel) to allow the operator the best access to the relay functions. 1.3 Wiring The product should be wired according to the scheme requirements, with reference to the appropriate wiring diagram. Refer to the appropriate Diagrams and Parameters document for a cross-reference of wiring diagrams and models. 1.4 Earthing Terminal 28 of the PSU (Power Supply Unit) should be solidly earthed by a direct connection to the panel earth. The Relay case earth stud connection should be connected to terminal 28 of the PSU. It is normal practice to additionally 'daisy chain' together the case (safety) earths of all the Relays installed in a panel to prevent earth current loops posing a risk to personnel. 1.5 Ancillary Equipment The relay can be interrogated locally or remotely. For local interrogation a portable PC with suitable version of MS Windows (2000 SP4 or XP SP2)and Reydisp EvolutionTM s/w (Latest Version available 32 bit) using USB port situated on front of the relay. Unrestricted (c)2018 Siemens Protection Devices Limited Page 5 of 36 7SR21 & 7SR22 - Installation Guide Section 2: Equipment Operating Conditions 2.1 ! ! ! Current Transformer Circuits The secondary circuit of a live CT must not be open circuited. Non-observance of this precaution can result in injury to personnel or damage to equipment. 2.2 External Resistors Where external resistors are fitted to relays, these may present a danger of electric shock or burns, if touched. 2.3 Fibre Optic Communication Where fibre optic communication devices are fitted, these should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device. 2.4 ! ! Front Cover The front cover provides additional securing of the relay element within the case. The relay cover should be in place during normal operating conditions. 2.5 Disposal The Relay should be disposed of in a manner which does not provide a threat to health or the environment. All laws and regulations specific to the country of disposal should be adhered to. 2.5.1 Environmental Protection Hints Disposal of Old Equipment and Batteries (Applicable only for European Union and Countries with a Recycling System) The disposal of our products and possible recycling of their components after decommissioning has to be carried out by an accredited recycling company, or the products/components must be taken to applicable collection points. Such disposal activities must comply with all local laws, guidelines and environmental specifications of the country in which the disposal is done. For the European Union the sustainable disposal of electronic scrap is defined in the respective regulation for "waste electrical and electronic equipment" (WEEE). The crossed-out wheelie bin on the products, packaging and/or accompanying documents means that used electrical and electronic products and batteries must not be mixed with normal household waste. According to national legislation, penalties may be charged for incorrect disposal of such waste. Unrestricted Page 6 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide By disposing of these products correctly you will help to save valuable resources and prevent any potential negative effects on human health and the environment. NOTE: Our products and batteries must not be disposed of as household waste. For disposing batteries it is necessary to observe the local national/international directives. Disposal of Mobile Storage Devices (e.g. USB Sticks and Memory Cards) When disposing of/transferring mobile storage devices, using the format or delete functions only changes the file management information and does not completely delete the data from your mobile storage device. When disposing of or transferring a mobile storage device, Siemens strongly recommends physically destroying it or completely deleting data from the mobile storage device by using a commercially available computer data erasing software. REACH/RoHS Declaration You can find our current REACH/RoHS declarations at: https://www.siemens.com/global/en/home/products/energy/ecotransparency/ecotransparency-downloads.html NOTE: You can find more information about activities and programs to protect the climate at the EcoTransparency website: https://www.siemens.com/global/en/home/products/energy/ecotransparency.html Unrestricted (c)2018 Siemens Protection Devices Limited Page 7 of 36 7SR21 & 7SR22 - Installation Guide Section 3: Dimensions and Panel Fixings 3.1 Relay Dimensions and Weight Relays are supplied in the modular size E6, E8 or E12 The following drawings are available which give panel cut-out and mounting details. Typical when fitted 130 216.5 SIDE VIEW Case Earth connection 75 mm MIN CLEARANCE FOR ETHERNET COMMS WIRING 10 PANEL CUT-OUT 159 168 150 31 151.5 11 MINIMUM CLEARANCES: 25mm FOR TERMINAL WIRING 45mm FOR ETHERNET COMMS MODULE 70mm FOR F/O COMMS CABLE Diameter 3.6 - 4 holes (see note) 155.5 177 Case Earth connection FRONT VIEW TOP VIEW Optional ethernet comms module See note 2 FRONT NOTE: THE 3.6 HOLES ARE FOR M4 THREAD FORMING (TRILOBULAR) SCREWS. THESE ARE SUPPLIED AS STANDARD AND ARE SUITABLE FOR USE IN FERROUS / ALUMINIUM PANELS 1.6mm THICK AND ABOVE. FOR OTHER PANELS, HOLES TO BE M4 CLEARANCE (TYPICALLY 4.5 DIAMETER) AND RELAYS MOUNTED USING M4 MACHINE SCREWS, NUTS AND LOCKWASHERS (SUPPLIED IN PANEL FIXING KIT). 2) ACCESS CLEARANCE REQUIRED FOR OPTIONAL ETHERNET COMMS MODULE RETAINING SCREW Figure 3.1-1 Overall Dimensions (mm) and panel Drilling for Size E6 Epsilon case Unrestricted Page 8 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Typical when fitted 182 216.5 SIDE VIEW Case Earth connection 75 mm MIN CLEARANCE FOR ETHERNET COMMS WIRING 9.75 PANEL CUT-OUT 159 168 201.5 31 151.5 11 MINIMUM CLEARANCES: 25mm FOR TERMINAL WIRING 45mm FOR ETHERNET COMMS MODULE 70mm FOR F/O COMMS CABLE Diameter 3.6 - 4 holes (see note) Optional ethernet comms module 207.5 177 Case Earth connection FRONT VIEW TOP VIEW See note 2 FRONT NOTE: THE 3.6 HOLES ARE FOR M4 THREAD FORMING (TRILOBULAR) SCREWS. THESE ARE SUPPLIED AS STANDARD AND ARE SUITABLE FOR USE IN FERROUS / ALUMINIUM PANELS 1.6mm THICK AND ABOVE. FOR OTHER PANELS, HOLES TO BE M4 CLEARANCE (TYPICALLY 4.5 DIAMETER) AND RELAYS MOUNTED USING M4 MACHINE SCREWS, NUTS AND LOCKWASHERS (SUPPLIED IN PANEL FIXING KIT). 2) ACCESS CLEARANCE REQUIRED FOR OPTIONAL ETHERNET COMMS MODULE RETAINING SCREW Figure 3.1-2 Overall Dimensions (mm) and Panel Drilling for Size E8 Epsilon Case Unrestricted (c)2018 Siemens Protection Devices Limited Page 9 of 36 7SR21 & 7SR22 - Installation Guide Figure 3.1-3 Overall Dimensions (mm) and Panel Drilling for Size E12 Epsilon Case Hardware Model 7SR2102 7SR2103 7SR2104 7SR2105 7SR2106 7SR2202 7SR2203 7SR2204 7SR2205 7SR2206 Typical Net Weight (kg) 4.2 4.6 4.8 8.4 8.4 4.8 4.9 5.3 8.4 8.4 NB: For relays supplied with additional (optional) communication interface devices, please add an additional 0.165 kg to the figures in the above table. For relays supplied with Ethernet EN100 interface (optional) please add 0.1 kg to the figures in the above table. Unrestricted Page 10 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide 3.2 Fixings 3.2.1 Crimps Ring tongued crimps with 90 bend are recommended. 3.2.2 Panel Fixings Typical mounting screw kit per Relay Consists of 4 off M4x10 mm Screws 4 off M4 Nuts 4 off M4 Lock Washers Typical rear terminal block fixing kit (1 kit per terminal block fitted to relay) consists of: 28 x M4, 8 mm Screws 28 x M4 Lock Washers 3.2.3 Fibre Optic Connectors The relay has Fibre-Optic STTM (BFOC/2.5) bayonet connectors fitted when specified. 3.2.4 Connectors Ethernet Option The relay has RJ45 connectors for electrical Ethernet and Duplex LC Fibre Optic connectors for optical Ethernet. Unrestricted (c)2018 Siemens Protection Devices Limited Page 11 of 36 7SR21 & 7SR22 - Installation Guide Section 4: Rear Terminal Drawings 4.1 E6 Case B A Figure 4.1-1 E6 Standard Comms (USB Front Port, Rear RS485) (See Note 2) Figure 4.1-2 E6 Standard + Additional Comms (IRIG-B, 2 x F.O. (ST Connectors)) (See Note 2) Notes 1) Recommended terminations are pre-insulated & must be crimped using approved tooling. 2) RS485 (block "B" terms 14, 16, 18, 20) connections to this communication facility is by screened, twisted pair cable. On site when wiring other facilities ensure that these terminals are not obscured by other wiring runs. Cable should be RS485 compliant. Unrestricted Page 12 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Figure 4.1-3 E6 Standard + Additional Comms (IRIG B + RS485) (See Note 2) Figure 4.1-4 E6 Standard + Additional Comms (IRIG B + RS232) (See Note 2) Unrestricted (c)2018 Siemens Protection Devices Limited Page 13 of 36 7SR21 & 7SR22 - Installation Guide 4.2 E8 Case C B A Figure 4.2-1 E8 Standard Comms (USB Front Port, Rear RS485) (See Note 2) Figure 4.2-2 E8 Standard + Additional Comms (IRIG B, 2 x F.O. (ST Connectors)) (See Note 2) Unrestricted Page 14 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Figure 4.2-3 E8 Standard + Additional Comms (IRIG B + RS485) (See Note 2) Figure 4.2-4 E8 Standard + Additional Comms (IRIG B + RS232) (See Note 2) Unrestricted (c)2018 Siemens Protection Devices Limited Page 15 of 36 7SR21 & 7SR22 - Installation Guide 4.3 E12 Case Figure 4.3-1 E12 Standard + Additional Comms (IRIG B, 2 x F.O. (ST Connectors)) (See Note 2) Figure 4.3-2 E12 Standard + Additional Comms (IRIG B + RS485) (See Note 2) Unrestricted Page 16 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Figure 4.3-3 E12 Standard + Additional Comms (IRIG B + RS232) (See Note 2) Figure 4.3-4 E12 Standard + Additional Comms (RS485 + Ethernet (x2)) (See Note 2) Unrestricted (c)2018 Siemens Protection Devices Limited Page 17 of 36 7SR21 & 7SR22 - Installation Guide Figure 4.3-5 Standard Comms + Additional Ethernet Ports (RJ45 shown, Duplex LC Fibre Optic similar) Notes 1) Recommended terminations are pre-insulated & must be crimped using approved tooling. 2) RS485 (block "B" terminals 14, 16, 18, 20 and optional COMMS MODULE) connections are by screened, twisted pair cable. Ensure that these terminals are not obscured by other wiring runs. Cable should be RS485 compliant. Unrestricted Page 18 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Section 5: Connection/Wiring/Diagrams 5.1 Wiring Diagram: 7SR21 OC/EF Relay Figure 5.1-1 Connection Diagram for 7SR21 Relay Unrestricted (c)2018 Siemens Protection Devices Limited Page 19 of 36 7SR21 & 7SR22 - Installation Guide Wiring Diagram: 7SR22 Directional OC/EF Relay RS485 5.2 Figure 5.2-1 Connection Diagram for 7SR22 Relay Unrestricted Page 20 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Section 6: Data Comms Connections 6.1 Standard RS485 Connections The standard RS485 communication port is located on terminal block 2 at the rear of the relay and can be connected using a suitable RS485 120 Ohm screened twisted pair cable. The RS485 electrical connection can be used in a single or multi-drop configuration. The RS485 master must support and use the Auto Device Enable (ADE) feature. The last device in the connection must be terminated correctly in accordance with the master driving the connection. A terminating resistor is fitted in each relay, when required this is connected in circuit using an external wire loop between terminals 18 and 20 of the power supply module. Up to 64 relays can be connected to the RS485 bus. The RS485 data communications link with a particular relay will be broken if the relay element is withdrawn from the case, all other relays will still communicate. Figure 6.1-1 RS485 Data Comms Connections Between Relays 6.2 IRIG-B Connections A BNC plug is provided on the optional additional communication interface modules to connect a co-axial cable carrying IRIG-B time synchronisation signals. Ensure that the stub length is minimised by connecting the teeconnector directly to the rear of the relay. A suitable co-axial cable would be type RG58 50 Ohms. Unrestricted (c)2018 Siemens Protection Devices Limited Page 21 of 36 7SR21 & 7SR22 - Installation Guide 6.3 Additional (Optional) Fibre Optic Connections Rear Com ports 3 and 4 comprise Fibre-Optic STTM (BFOC/2.5) bayonet connectors-4 per product. 62.5 / 125 m glass fibre is recommended for all distances. When installing fibre, ensure that the fibres' bend radii comply with the recommended minimum for the fibre usedtypically 50 mm is acceptable. To Control System 7SG24 Tx Master Rx Rx Rx Tx Tx Tx Rx Tx Rx Tx RS232 straight Through cable Rx Tx Rx Computer or Control System USB or 9 pin male D connector Rx 62.5/125 m fibre optic with ST connectors Tx 25 pin male D connector Figure 6.3-1 Data Comms to Multiple Devices Using 7SG24 and F.O. Star Network Figure 6.3-2 Data Comms to Multiple Devices Using 7SG24 and F.O. Ring Network The F.O. data communications link with a particular relay will be broken if the relay element is withdrawn from the case, all other relays will still communicate. Unrestricted Page 22 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide 6.4 Additional (Optional) RS485 Connections The additional (optional) RS485 communication port is located at the rear of the relay and can be connected using a suitable RS485 120 Ohm screened twisted pair cable. The RS485 electrical connection can be used in a single or multi-drop configuration. The RS485 master must support and use the Auto Device Enable (ADE) feature. The last device in the connection must be terminated correctly in accordance with the master device driving the connection. The relays are fitted with an internal terminating resistor which can be connected between the A and B by fitting an external wire loop between terminals 18 and 20 on the power supply module. Figure 6.4-1 RS485 Data Comms Connections Between Relays 6.5 Additional (Optional) RS232 Connections The additional (optional) RS232 (9 pin plug) (DTE) communication port is located at the rear of the relay and can be connected using a suitable RS232 cable. Where there is a requirement for multi-drop RS232 connection, a suitable device to facilitate this should be obtained. Pin 1 2 3 4 5 6 7 8 9 Relay Function Not Connected Receive Data (RXD) Transmit Data (TXD) Input Supply +5 V Signal Ground (GND) Input Supply +5 V Linked to 8 (volts free) Linked to 7 (volts free) Output Supply +5 V 50 mA Figure 6.5-1 RS232 Data Comms Pin Connections Unrestricted (c)2018 Siemens Protection Devices Limited Page 23 of 36 7SR21 & 7SR22 - Installation Guide 6.6 Additional (Optional) Ethernet Connection for IEC 61850 Rear Ethernet Comms port Ch 1 and Ch 2 comprises Duplex LC 100BaseF in acc. With IEEE802.3 Fibre- Optic or RJ45 100BaseF in acc. With IEEE802.3 electrical connectors. When installing fibre, ensure that the fibres' bend radii comply with the recommended minimum for the fibre usedtypically 50 mm is acceptable, 62.5/125 mm glass fibre with Duplex-LC connector recommended for all distances. Figure 6.6-1 Ethernet connection for IEC 61850 (star connection) Figure 6.6-2 Ethernet connection for IEC 61850 (ring connection) Unrestricted Page 24 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide 6.7 Ethernet Network Redundancy IEC 61850 The EN100+ module is used on current Reyrolle devices (from 7SR21/22 hardware /DD) to provide Ethernet/IEC61850 functionality. The RJ45 electrical EN100+ supports PRP redundancy protocols. The DuplexLC Optical EN100+ also supports RSTP and HSR redundancy protocols. Earlier 7SR21/22 (/CC) devices were manufactured with the EN100 (not EN100+) module and the electrical version cannot support redundancy. The optical version can support redundancy if firmware is updated. Earlier devices do not support the EN100+ module cannot be updated by simply exchanging the EN100 module. All current 7SR21/22 IEC61850 variants are delivered with the EN100+ (Plus) module and firmware 4.24 or later. The EN100 module firmware can be updated by connecting to the relay via the rear Ethernet port. For more information on connecting to the relay via the Ethernet port, please see the Reydisp Manager User guide. Depending on the EN100 module type and Firmware version, the following protocol options are available: Interface Type Electrical RJ45 EN100+ Optical EN100+ Electrical RJ45 EN100+ Optical EN100+ Electrical RJ45 EN100 Optical EN100 Electrical RJ45 EN100 Optical EN100 EN100 Firmware 4.21and later 4.21and later 4.08 or earlier 4.08 or earlier 4.21and later 4.21and later 4.08 or earlier 4.08 or earlier Line Mode u u u u u u u u RSTP u u u u u u u u Switch Mode OSM PRP u u u u u u u u u u u u u u u u HSR u u u u u u u u Figure 6.7-1 EN100 Redundancy Availability Unrestricted (c)2018 Siemens Protection Devices Limited Page 25 of 36 7SR21 & 7SR22 - Installation Guide 6.7.1 RSTP - Rapid Spanning Tree Protocol RSTP is a redundancy protocol with a minimal response time that has been standardized in IEEE-802.1D (2004). The reconfiguration time depend on the topology and start at 50 ms. RSTP need to be enabled on the device within Reydisp Manager (See Reydisp Manager user guide). Network rings with up to 30 devices is possible. Figure: 6.7.1-1 RSTP Ethernet Network Ring Configuration 6.7.2 PRP - Parallel Redundancy Protocol The HSR redundancy protocol according to the IEC 62439-3 standard is based on double transmission of message frames over ring-topology networks in both directions. In the case of an error, the message frame will be transmitted without any delay. No reconfiguration time is necessary for the network, as is the case for RSTP. PRP need to be enabled on the device within Reydisp Manager (See Reydisp Manager user guide). Unrestricted Page 26 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Figure: 6.7.2-1 PRP Ethernet Network Configuration Unrestricted (c)2018 Siemens Protection Devices Limited Page 27 of 36 7SR21 & 7SR22 - Installation Guide 6.7.3 HSR - High Availability Seamless Redundancy Protocol The HSR redundancy protocol according to the IEC 62439-3 standard is based on double transmission of message frames over ring-topology networks in both directions. In the case of an error, the message frame will be transmitted without any delay. No reconfiguration time is necessary for the network. HSR needs to be enabled on the device within Reydisp Manager (See Reydisp Manager user guide). Network rings with up to 50 devices is possible. Figure: 6.7.3-1 HSR Ethernet Network Ring Configuration Unrestricted Page 28 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide Section 7: Connection Diagrams 7.1 Typical Connection: 7SR22 Directional OC/EF and REF P1 S1 L1 P1 P2 S2 S1 S2 L2 L3 S1 S2 S1 S2 P2 1 3 1A 1A 2 5A I5 IL1 (IA) (ISEF) 20 4 5 1A 6 7 17 18 5A 19 5A IL2 (IB) VL1 (VA) 21 VL2 (VB) 23 VL3 (VC) 25 22 8 9 1A 10 11 5A IL3 (IC) 12 13 1A 14 15 5A I4 (IG) 16 V4 (VX) A 24 26 27 28 B C NOTES 1) CT circuits are shown connected to 1 A tap - use alternative tap for 5 A rated CTs. 2) CT and Earth connections are typical only. 3) Application shows use of I5 as an REF input with external stabilising and voltage limiting resistor. 4) Phase Voltage Config:-VanVbnVcn Figure 7.1-1 7SR22 Applied to Transformer Incomer Unrestricted (c)2018 Siemens Protection Devices Limited Page 29 of 36 7SR21 & 7SR22 - Installation Guide 7.2 Typical Connection: 7SR22 Directional OC/EF and NVD Figure 7.2-1 7SR22 Unrestricted Page 30 of 36 Applied to Transformer Incomer Including HV NVD Protection (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide 7.3 L1 Typical Connection: 7SR22 Directional OC/EF and NVD L2 L3 P1 1 1A 1A IL1 (IA) 2 3 P2 S1 4 S2 5 5A 18 5A 19 20 1A IL2 (IB) 6 7 I5 (ISEF) 17 5A VL1 (VA) 21 VL2 (VB) 23 VL3 (VC) 25 22 8 9 1A 10 11 IL3 (IC) 5A 12 13 1A 14 15 I4 (IG) 5A 16 V4 (VX) A 24 26 27 28 B C VL VN NOTES 1) CT circuits are shown connected to 1 A tap - use alternative tap for 5 A rated CTs. 2) CT and Earth connections are typical only. 3) Application shows use of V4 as an NVD input. 4) Star Connected VT: Phase Voltage Config:-Van,Vbn,Vcn Figure 7.3-1 7SR22 Applied to Feeder Including NVD Protection Unrestricted (c)2018 Siemens Protection Devices Limited Page 31 of 36 7SR21 & 7SR22 - Installation Guide 7.4 Typical Connection: 7SR22 Directional OC/EF and NVD L1 L2 L3 P1 1 1A 1A 3 S1 S2 5A 5 7 17 18 5A 19 20 4 1A IL2 (IB) 6 P2 I5 (ISEF) IL1 (IA) 2 5A VL1 (VA) 21 VL2 (VB) 23 VL3 (VC) 25 22 8 9 1A IL3 (IC) 10 11 5A 12 13 1A 14 15 I4 (IG) 5A 16 V4 (VX) A 24 26 27 28 B C VL 3Vo VN NOTES 1) CT circuits are shown connected to 1 A tap - use alternative tap for 5 A rated CTs. 2) CT and Earth connections are typical only. 3) Voltage Config:-Vab, Vbc, 3V0 Figure 7.4-1 7SR22 Applied to Feeder Unrestricted Page 32 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide 7.5 Typical Connection: 7SR22 Directional OC and EF L1 L2 L3 P1 1 2 3 S1 1A 1A 5A IL1 (IA) I5 (ISEF) 5 7 19 1A 6 P2 18 5A 20 4 S2 17 5A IL2 (IB) VL1 (VA) 21 VL2 (VB) 23 VL3 (VC) 25 22 8 9 1A 10 11 5A IL3 (IC) 12 13 1A 14 15 5A 16 I4 (IG) V4 (VX) A 24 26 27 28 B C A B C NOTES 1) CT circuits are shown connected to 1 A tap - use alternative tap for 5 A rated CTs. 2) CT and Earth connections are typical only. 3) Vee Connected VT: Phase Voltage Config:-Va,Vb,Vc 4) DEF elements must be NPS polarised (Vo polarising not applicable) Figure 7.5-1 7SR22 Applied to Feeder - No Zero Sequence Voltage Source Unrestricted (c)2018 Siemens Protection Devices Limited Page 33 of 36 7SR21 & 7SR22 - Installation Guide 7.6 Typical Connection: 7SR22 Connected to VTs and Capacitor Cone Unit L1 L2 L3 P1 1 1A 1A 3 S1 I5 (ISEF) IL1 (IA) 2 5A 5 7 19 1A 6 P2 18 5A 20 4 S2 17 IL2 (IB) 5A VL1 (VA) 21 VL2 (VB) 23 VL3 (VC) 25 22 8 9 1A 10 11 IL3 (IC) 5A 12 13 1A 14 15 I4 (IG) 5A 16 V4 (VX) A 24 26 27 28 B C A B C Capacitor Cones Adaptor Unit NOTES 1) CT circuits are shown connected to 1 A tap - use alternative tap for 5 A rated CTs. 2) CT and Earth connections are typical only. 3) Vee Connected VT: Phase Voltage Config:-Va,Vb,Vc 4) DEF elements must be NPS polarised (Vo polarising not applicable) 5) V4 used for NVD input Figure 7.6-1 7SR22 Applied to Feeder with Capacitor Cones Fitted Unrestricted Page 34 of 36 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Installation Guide 7.7 Typical Connection: 7SR22 Voltage Transformer Configurations for Check Synchronisation Relay Voltage Configuration Vbn line, Vbn bus, Description Connection 25 Check Sync, A A B C B C N n N n a a b b c A21 c V Line A22 A27 V Bus A28 Vab line, Vab bus, 25 Check Sync, A A B C B C N n N n a a b b c A21 c V Line A22 A27 V Bus A28 Figure 7.7-1 7SR22 Applied to Check Synchronisation Unrestricted (c)2018 Siemens Protection Devices Limited Page 35 of 36 7SR21 & 7SR22 - Installation Guide 7.8 Voltage Transformer Configurations Relay Voltage Configuration Setting Van, Vbn, Vcn Description Connection 67 & 67N & 67G 47, 27/59 & 81 Phase - Neutral Phase - Phase Calculated NPS ZPS Va, Vb, Vc 67 67N (NPS polarising) 47, 27/59 & 81 Phase - Phase Calculated NPS Vab, Vbc, 3V0 67 & 67N & 67G 47, 59N, 27/59 & 81 Phase - Neutral Calculated Phase - Phase Phase Vca Calculated NPS ZPS Figure 7.8-1 7SR22 VT Connections Unrestricted Page 36 of 36 (c)2018 Siemens Protection Devices Limited 7SR21 Non-Directional Relay 7SR22 Directional Relay Commissioning & Maintenance Guide The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Document Release History This document is issue 2017/12. The list of revisions up to and including this issue is: 2011/05 First issue 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions, drawing amendments and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. Software Revision History 2011/05 2435H85008R7a-7a (7SR210) First Release 2435H85009R7a-7a (7SR220) 2013/01 2435H85008R7c-7b (7SR210) 2435H85009R7c-7b (7SR220) 2014/06 2435H85008R7f-7d (7SR210) 2435H85009R7f-7d (7SR220) 2015/06 2435H85008R8a-7f (7SR210) 2435H85009R8a-7f (7SR220) 2016/02 2435H85008R8b-7f (7SR210) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Added Fault Locator feature and Check Sync feature. Fault data transmitted over 103. Additional communications data, control features, meters. Added Power Factor Meters, Load Blinding feature, Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. 2435H85009R8b-7f (7SR220) 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Page 2 of 82 Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing, 67SEF Compensated Network, 67SEF Wattmetric. Increased I/O. Event Data on LCD. (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Contents Document Release History ............................................................................................................... 2 Software Revision History ................................................................................................................ 2 Contents ............................................................................................................................................ 3 Section 1: Common Functions ......................................................................................................... 6 1.1 Overview.............................................................................................................................. 6 1.2 Before Testing...................................................................................................................... 6 1.2.1 Safety ...................................................................................................................... 6 1.2.2 Sequence of Tests ................................................................................................... 6 1.2.3 Test Equipment........................................................................................................ 7 1.2.4 Precautions.............................................................................................................. 7 1.2.5 Applying Settings ..................................................................................................... 7 1.3 Tests .................................................................................................................................... 9 1.3.1 Inspection ................................................................................................................ 9 1.3.2 Secondary Injection Tests ........................................................................................ 9 1.3.3 Primary Injection Tests............................................................................................. 9 1.3.4 Putting into Service .................................................................................................. 9 1.4 AC Energising Quantities ................................................................................................... 10 1.5 Binary Inputs ...................................................................................................................... 11 1.6 Binary Outputs ................................................................................................................... 12 1.7 Relay Case Shorting Contacts ............................................................................................ 13 Section 2: Protection Functions..................................................................................................... 14 2.1 Phase Directional Polarity Check........................................................................................ 15 2.1.1 2 out of 3 logic ....................................................................................................... 16 2.2 Phase Overcurrent (67/50,67/51) ....................................................................................... 17 2.2.1 Definite Time Overcurrent. (50) .............................................................................. 18 2.2.2 Inverse Time Overcurrent. (51) .............................................................................. 18 2.3 Voltage Controlled Overcurrent (51V) ................................................................................. 20 2.4 Cold Load (51c).................................................................................................................. 22 2.4.1 Inverse Time Overcurrent. (51C) ............................................................................ 23 2.1 Arc Flash Detection (50AFD) .............................................................................................. 25 2.2 Directional Earth Fault Polarity Check (67N) ....................................................................... 26 2.3 Derived Earth Fault (67/50N, 67/51N)................................................................................. 27 2.3.1 Directional Polarity ................................................................................................. 28 2.3.2 Definite Time Overcurrent..(50N)............................................................................ 28 2.3.3 Inverse Time Overcurrent. (51N) ............................................................................ 28 2.4 Measured Earth fault (67/50G,67/51G) ............................................................................... 31 2.4.1 Directional Polarity ................................................................................................. 32 2.4.2 Definite Time Overcurrent..(67/50G)....................................................................... 32 2.4.3 Inverse Time Overcurrent. (67/51G) ....................................................................... 32 2.5 Sensitive Earth fault (67/50S,67/51S) ................................................................................. 35 2.5.1 Directional Polarity ................................................................................................. 36 2.5.2 Definite Time Overcurrent. (50SEF) ....................................................................... 36 2.5.3 Inverse Time Overcurrent. (51SEF)........................................................................ 36 2.6 Restricted Earth fault. (64H) ............................................................................................... 39 2.7 Negative Phase Sequence Overcurrent (46NPS)................................................................ 41 2.7.1 Definite Time NPS Overcurrent. (46DT) ................................................................. 42 2.7.2 Inverse Time NPS Overcurrent. (46IT) ................................................................... 42 (c) 2013 Siemens Protection Devices Limited Page 3 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.8 Undercurrent. (37) .............................................................................................................. 44 2.9 Thermal Overload (49) ....................................................................................................... 46 2.10 Over/Under Voltage............................................................................................................ 48 2.10.1 Phase Under/Over Voltage. (27/59) ....................................................................... 48 2.10.2 Undervoltage Guard (27/59UVG) ........................................................................... 50 2.10.3 Vx Under/Over Voltage. (Vx 27/59) ........................................................................ 51 2.10.4 NPS Overvoltage (47) ............................................................................................ 53 2.10.5 Neutral Overvoltage (59N) ..................................................................................... 55 2.10.6 Definite Time (59NDT) ........................................................................................... 55 2.10.7 Inverse Time (59NIT) ............................................................................................. 56 2.10.8 Element Blocking ................................................................................................... 56 2.10.9 Under/Over Frequency (81) ................................................................................... 57 2.11 Power (32) ......................................................................................................................... 59 2.12 Sensitive Power (32S) ........................................................................................................ 61 2.13 Power Factor (55) .............................................................................................................. 63 Section 3: Supervision Functions .................................................................................................. 65 3.1 CB Fail. (50BF) .................................................................................................................. 65 3.2 Voltage Transformer Supervision. (60VTS)......................................................................... 67 3.2.1 1 or 2 Phase VT fail ............................................................................................... 68 3.2.2 3 Phase VT fail ...................................................................................................... 68 3.3 Current Transformer Supervision. (60CTS)......................................................................... 69 3.3.1 Element Blocking ................................................................................................... 70 3.4 Broken Conductor. (46BC) ................................................................................................. 71 3.4.1 Element Blocking ................................................................................................... 72 3.5 Load Blinder (21)................................................................................................................ 73 3.5.1 Determining Load Blinder Regions (21LB).............................................................. 75 3.5.2 Determining Trip Level ........................................................................................... 76 3.6 Trip Circuit Supervision. (74TCS) ....................................................................................... 77 3.7 Magnetising Inrush Detector. (81HBL) ................................................................................ 78 3.1 Over Fluxing Detector. (81HBL5)........................................................................................ 79 Section 4: Control & Logic Functions ............................................................................................ 80 4.1 Autoreclose (79) ................................................................................................................. 80 4.2 Quick Logic ........................................................................................................................ 80 Section 5: Testing and Maintenance .............................................................................................. 81 5.1 Periodic Tests .................................................................................................................... 81 5.2 Maintenance ...................................................................................................................... 81 5.3 Troubleshooting ................................................................................................................. 82 Page 4 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide List of Figures Figure 2.1-1 Directional Phase Fault Boundary System Angles ................................................... 16 Figure 2.2-1 Phase Overcurrent ..................................................................................................... 17 Figure 2.3-1 Voltage Controlled Overcurrent................................................................................. 20 Figure 2.4-1 Cold Load ................................................................................................................... 22 Figure 2.4-2 Cold Load Logic diagram........................................................................................... 23 Figure 2.1-1 Arc Flash Detection .................................................................................................... 25 Figure 2.5-1 Directional Earth Fault Boundary System Angles .................................................... 26 Figure 2.6-1 Derived Earth Fault .................................................................................................... 27 Figure 2.7-1 Measured Earth Fault ................................................................................................. 31 Figure 2.8-1 Sensitive Earth Fault .................................................................................................. 35 Figure 2.9-1 Restricted Earth Fault ................................................................................................ 39 Figure 2.10-1 Negative Phase Sequence Overcurrent .............................................................. 41 Figure 2.11-1 Undercurrent ........................................................................................................ 44 Figure 2.12-1 Thermal Overload ................................................................................................ 46 Figure 2.13-1 Phase Under/Over Voltage .................................................................................. 48 Figure 2.13-2 Vx Under/Over Voltage ........................................................................................ 51 Figure 2.13-3 NPS Overvoltage.................................................................................................. 53 Figure 2.13-4 Neutral Overvoltage ............................................................................................. 55 Figure 2.13-5 Under/Over Frequency ........................................................................................ 57 Figure 2.11-1 Power ................................................................................................................... 59 Figure 2.12-1 Sensitive Power ................................................................................................... 61 Figure 2.13-1 Power Factor ........................................................................................................ 63 Figure 3.1-1 CB Fail ........................................................................................................................ 65 Figure 3.2-1 Voltage Transformer Supervision.............................................................................. 67 Figure 3.3-1 Current Transformer Supervision.............................................................................. 69 Figure 3.4-1 Broken Conductor ...................................................................................................... 71 Figure 3.5-1 Load Blinder (21) ........................................................................................................ 73 Figure 3.5-2 Load Blinder (21) Boundary Points ........................................................................... 74 Figure 3.6-1 Trip Circuit Supervision ............................................................................................. 77 Figure 3.7-1 Magnetising Inrush Detector ..................................................................................... 78 Figure 3.1-1 Magnetising Inrush Detector ..................................................................................... 79 (c) 2013 Siemens Protection Devices Limited Page 5 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Section 1: Common Functions 1.1 Overview Commissioning tests are carried out to prove: a) Equipment has not been damaged in transit. b) Equipment has been correctly connected and installed. c) Prove characteristics of the protection and settings which are based on calculations. d) Confirm that settings have been correctly applied. e) To obtain a set of test results for future reference. 1.2 Before Testing 1.2.1 Safety The commissioning and maintenance of this equipment should only be carried out by skilled personnel trained in protective relay maintenance and capable of observing all the safety precautions and regulations appropriate to this type of equipment and also the associated primary plant. Ensure that all test equipment and leads have been correctly maintained and are in good condition. It is recommended that all power supplies to test equipment be connected via a Residual Current Device (RCD), which should be located as close to the supply source as possible. The choice of test instrument and test leads must be appropriate to the application. Fused instrument leads should be used when measurements of power sources are involved, since the selection of an inappropriate range on a multi-range instrument could lead to a dangerous flashover. Fused test leads should not be used where the measurement of a current transformer (C.T.) secondary current is involved, the failure or blowing of an instrument fuse or the operation of an instrument cut-out could cause the secondary winding of the C.T. to become an open circuit. Open circuit secondary windings on energised current transformers are a hazard that can produce high voltages dangerous to personnel and damaging to equipment, test procedures must be devised so as to eliminate this risk. 1.2.2 Sequence of Tests If other equipment is to be tested at the same time, then such testing must be co-ordinated to avoid danger to personnel and equipment. When cabling and wiring is complete, a comprehensive check of all terminations for tightness and compliance with the approved diagrams must be carried out. This can then be followed by the insulation resistance tests, which if satisfactory allows the wiring to be energised by either the appropriate supply or test supplies. When primary injection tests are completed satisfactorily, all remaining systems can be functionally tested before the primary circuit is energised. Some circuits may require further tests before being put on load. Protection relay testing will require access to the protection system wiring diagrams; relay configuration information and protection settings. The following sequence of tests is loosely based on the arrangement of the relay menu structure. A test log based on the actual tests completed should be recorded for each relay tested. The `Description of Operation' section of this manual provides detailed information regarding the operation of each function of the relay. Page 6 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 1.2.3 Test Equipment Required test equipment is: 1. Secondary injection equipment with integral time interval meter 2. Primary injection equipment 3. A d.c. supply with nominal voltage within the working range of the relay's d.c. auxiliary supply rating 4. A d.c. supply with nominal voltage within the working range of the relay's d.c. binary input rating 5. Other equipment as appropriate to the protection being commissioned - this will be specified in the product specific documentation. The secondary injection equipment should be appropriate to the protection functions to be tested. Additional equipment for general tests and for testing the communications channel is: Portable PC with appropriate interface equipment: 6. Portable PC with appropriate interface equipment. 7. Printer to operate from the above PC (Optional). Use of PC to facilitate testing The functions of Reydisp Evolution (see Settings Guide) can be used during the commissioning tests to assist with test procedures or to provide documentation recording the test and test parameters. One method is to clear both the waveform and event records before each test is started, then, after the test upload from the relay the settings, events and waveform files generated as a result of application of the test. These can then be saved off to retain a comprehensive record of that test. Relay settings files can be prepared on the PC (offline) or on the relay before testing commences. These settings should be saved for reference and compared with the settings at the end of testing to check that errors have not been introduced during testing and that any temporary changes to settings to suit the test process are returned to the required service state. A copy of the Relay Settings as a Rich Text Format (.rtf) file suitable for printing or for record purposes can be produced from Reydisp as follows. From the File menu select Save As, change the file type to Export Default/Actual Setting (.RTF) and input a suitable filename. When testing is completed the event and waveform records should be cleared and the settings file checked to ensure that the required in-service settings are being applied. 1.2.4 Precautions Before electrical testing commences the equipment should be isolated from the current and voltage transformers. The current transformers should be short-circuited in line with the local site procedure. The tripping and alarm circuits should also be isolated where practical. The provision and use of secondary injection test sockets on the panel simplifies the isolation and test procedure. Ensure that the correct auxiliary supply voltage and polarity is applied. See the relevant scheme diagrams for the relay connections. Check that the nominal secondary current rating of the current and voltage transformers has been correctly set in the System Config. menu of the relay. 1.2.5 Applying Settings The relay settings for the particular application should be applied before any secondary testing occurs. If they are not available then the relay has default settings that can be used for pre-commissioning tests. Note that the tripping and alarm contacts for any function must be programmed correctly before any scheme tests are carried out. Relays feature multiple settings groups, only one of which is active at a time. In applications where more than one settings group is to be used it may be necessary to test the relay in more than one configuration. Note. One group may be used as a `Test' group to hold test-only settings that can be used for regular maintenance testing, eliminating the need for the Test Engineer to interfere with the actual in-service settings in the normally active group. This Test group may also be used for functional testing where it is necessary to disable or change settings to facilitate testing. When using settings groups it is important to remember that the relay need not necessarily be operating according to the settings that are currently being displayed. (c) 2013 Siemens Protection Devices Limited Page 7 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide There is an `active settings group' on which the relay operates and an `edit/view settings group' which is visible on the display and which can be altered. This allows the settings in one group to be altered from the relay fascia while the protection continues to operate on a different unaffected group. The `Active Settings Group' and the `Edit Settings Group' are selected in the `System Configuration Menu'. The currently Active Group and the group currently Viewed are shown at the top of the display in the Settings display screen. If the View Group is not shown at the top of the display, this indicates that the setting is common to all groups. CT/VT ratio, I/O mapping and other settings which are directly related to hardware are common to all groups. If the relay is allowed to trip during testing then the instruments display will be interrupted and replaced by the `Trip Alert' screen which displays fault data information. If this normal operation interferes with testing then this function can be temporarily disabled for the duration of testing by use of the Trip Alert Enabled/Disabled setting in the System Config Menu. After applying a settings change to the relay, which may involve a change to the indication and output contacts, the TEST/RESET key should be pressed to ensure any existing indication and output is correctly cleared. Page 8 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 1.3 1.3.1 Tests Inspection Ensure that all connections are tight and correct to the relay wiring diagram and the scheme diagram. Record any deviations. Check that the relay is correctly programmed and that it is fully inserted into the case. Refer to `Settings Guide' for information on programming the relay. 1.3.2 Secondary Injection Tests Select the required relay configuration and settings for the application. Isolate the auxiliary D.C. supplies for alarm and tripping from the relay and remove the trip and inter-trip links. Carry out injection tests for each relay function, as described in this document For all high current tests it must be ensured that the test equipment has the required rating and stability and that the relay is not stressed beyond its thermal limit. 1.3.3 Primary Injection Tests Primary injection tests are essential to check the ratio and polarity of the transformers as well as the secondary wiring. Note. If the current transformers associated with the protection are located in power transformer bushings it may not be possible to apply test connections between the current transformer and the power transformer windings. Primary injection is needed, however, to verify the polarity of the CTs. In these circumstances primary current must be injected through the associated power transformer winding. It may be necessary to short circuit another winding in order to allow current to flow. During these primary injection tests the injected current is likely to be small due to the impedance of the transformer. 1.3.4 Putting into Service After tests have been performed satisfactorily the relay should be put back into service as follows:Remove all test connections. Replace all secondary circuit fuses and links, or close m.c.b. Ensure the Protection Healthy LED is on, steady, and that all LED indications are correct. If necessary press CANCEL until the Relay Identifier screen is displayed, then press TEST/RESET to reset the indication LEDs. The relay meters should be checked in Instruments Mode with the relay on load. The relay settings should be downloaded to a computer and a printout of the settings produced. The installed settings should then be compared against the required settings supplied before testing began. Automated setting comparison can be carried out by Reydisp using the Compare Settings Groups function in the Edit menu. Any modified settings will be clerly highlighted. (c) 2013 Siemens Protection Devices Limited Page 9 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 1.4 AC Energising Quantities Voltage and current measurement for each input channel is displayed in the Instrumentation Mode sub-menus, each input should be checked for correct connection and measurement accuracy by single phase secondary injection at nominal levels. Ensure that the correct instrument displays the applied signal within limits of the Performance Specification. Applied Current IA IB IC Applied Voltage IG ISEF VA/VAB VB/VBC VC/VCB VX Secondary Primary Apply 3P balanced Current and Voltage at nominal levels and ensure that the measured Zero Phase Sequence and Negative Phase Sequence quantities are approximately zero. ZPS NPS Voltage Current Page 10 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 1.5 Binary Inputs The operation of the binary input(s) can be monitored on the `Binary Input Meters' display shown in `Instruments Mode'. Apply the required supply voltage onto each binary input in turn and check for correct operation. Depending on the application, each binary input may be programmed to perform a specific function; each binary should be checked to prove that its mapping and functionality is as set as part of the Scheme Operation tests. Where the pick-up timers associated with a binary input are set these delays should be checked either as part of the scheme logic or individually. To check a binary pick-up time delay, temporarily map the binary to an output relay that has a normally open contact. This can be achieved in the Output Matrix sub-menu by utilising the BI n Operated settings. Use an external timer to measure the interval between binary energisation and closure of the output contacts. Similarly, to measure the drop-off delay, map to an output relay that has a normally closed contact, time the interval between binary de-energisation and closure of the output contacts. Note. The time measured will include an additional delay, typically less than 20 ms, due to the response time of the binary input hardware, software processing time and the operate time of the output relay. BI Tested DO Delay Measured PU Delay Measured Notes (method of initiation) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 (c) 2013 Siemens Protection Devices Limited Page 11 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 1.6 Binary Outputs A minimum of six output relays are provided. Two of these have change over contacts, BO2 & BO3, one has a normally closed contact, BO1 and the remainder have normally open contacts. Care should be observed with regard to connected devices when forcing contacts to operate for test purposes. Short duration energisation can cause contact failure due to exceeding the break capacity when connected to inductive load such as electrically reset trip relays. Close each output relay in turn from the Reydisp Evolution PC programme, Relay - Control - Close output relay. This function will energise the output for its minimum operate time. This time is specified in the Output Config Binary Output Config menu for each output relay and may be too short to measure with a continuity tester. An alternative method of energising an output permanently so that wiring can be checked is to temporarily map the relay being tested to the `Protection Healthy' signal in the Output Matrix, as this signal is permanently energised the mapped relay will be held energised, normally open contacts will be closed and vice versa. BO Checked Notes (method of test) 1NC 2NO 2NC 3NO 3NC 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Page 12 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 1.7 Relay Case Shorting Contacts CT inputs and terminals B25-B26 (Relay Withdrawn Alarm) are fitted with case mounted shorting contacts which provide a closed contact when the relay is withdrawn from the case. The operation of these contacts should be checked. CT Shorting contacts checked Relay Withdrawn Alarm Checked (c) 2013 Siemens Protection Devices Limited Page 13 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Section 2: Protection Functions This section details the procedures for testing each protection function of the 7SR21 & 7SR22 relays. These tests are carried out to verify the accuracy of the protection pick-ups and time delays at setting and to confirm correct operation of any associated input and output functionality. The exact model type must be checked to confirm the functions available in each type. Guidance for calculating test input quantities is given in the relevant test description where required. In many cases it may be necessary to disable some functions during the testing of other functions, this prevents any ambiguity caused by the operation of multiple functions from one set of input quantities. The `Function Config' Menu provides a convenient high level point at which all elements of a particular function can be Enabled/Disabled to suit testing. The `Config' tab in `Reydisp Evolution' can be used to `Enable/Disable' individual elements. Note that this screen disables functions by applying setting changes to the relay and that any changes must be sent to the relay to take effect and settings must be returned to their correct value after testing. O O O O O O O O O O O O O O O O O O O O Measured E/F O Sensitive E/F O O O O Undercurrent O O O O O O O Phase U/O voltage NPS Overvoltage U/O Frequency CB Fail O O Restricted E/F Thermal Inrush Detector O Trip cct Supervision O Derived E/F NPS Overcurrent Broken Conductor O CT supervision O VT Supervision O CB Fail O U/O Frequency O NPS Overvoltage Thermal O O O Phase U/O voltage Undercurrent O Restricted E/F O Sensitive E/F O Measured E/F O Derived E/F NPS Overcurrent Phase Overcurrent Voltage Cont O/C Cold Load Cold Load Under Test Voltage Cont O/C Function Phase Overcurrent The table below indicates functions where function conflicts may occur during testing, consideration should be given to disabling functions to avoid interference. O O O O O O O O O O Broken Conductor Trip cct Supervision Inrush Detector O O O O O O O O VT Supervision CT supervision O O O O O O O Any LED can be assigned to be a General Pickup LED in the Output Matrix menu and can be used to assess operation of functions during testing if other functions are disabled or if the setting allocating General Pickup is temporarily modified. Voltage inputs may not be required for testing of non-directional Overcurrent elements but it may be advantageous to apply balanced 3 phase nominal rated voltage to the VT inputs during testing to avoid inadvertent operation of other functions. Particular care should be taken when testing overcurrent functions that the thermal rating of the current inputs is not exceeded. Page 14 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide It should be considered that where several overlapping elements are used simultaneously, the overall protection operate time may be dependent on the operation of different individual elements at the various levels of applied current or voltage. The resulting composite characteristic may be tested by enabling all of the relevant applicable elements or the element operations can be separated or disabled and tested individually. All relay settings should be checked before testing begins. It is recommended that the relay settings are extracted from the relay using Reydisp Evolution software and a copy of these settings is stored for reference during and after testing. It may be necessary to disable some protection functions during the testing of other functions to allow unambiguous results to be obtained. Care must be taken to reset or re-enable any settings that have been temporarily altered during the testing before the relay can be put into service. At the end of testing the relay settings should be compared to the file extracted at the start to ensure that errors have not been introduced. 2.1 Phase Directional Polarity Check If the relay has Directional Overcurrent elements, the common direction polarising can be checked independently from the individual overcurrent elements and their settings. In the INSTRUMENTS MODE display, indication is provided in the DIRECTIONAL METERS menu which displays current direction under P/F Dir as forward or reverse based on the output states of the directional elements, i.e. whether they see forward current, reverse current or neither for each pole with respect to the 67 Char Angle setting in the Phase Overcurrent menu. This display and the equivalent Measured and Calculated Earth Fault direction meters can be used as an aid to commissioning testing. 1. Check the direction of each pole in turn by connecting to the appropriate terminals. The table below shows the polarising quantity for each pole. Connections for Directional Polarity Overcurrent pole Polarising voltage Phase A VBC Phase B VCA Phase C VAB 2. Inject single phase rated current and apply single phase-phase rated voltage at the Char Angle (MTA) phase angle setting, to each phase in turn. For each pole, monitor the directional display in the instrument menu and check that indication of forward current (FWD) is displayed. To achieve the required forward Characteristic Angle, the phase angle of the current should be greater than that of the polarising voltage by the angle setting. 3. Repeat all of the above with the current connections reversed. Indication should now be given of reverse (REV) current flow. Phase A B C Forward FWD FWD FWD Reverse REV REV REV Apply balanced 3 phase rated voltage and current with Vbc voltage as a 0deg reference and Ia at the characteristic angle. Increase current phase angle until the `Fwd' indication is extinguished. Record this angle in the table below (Forward lead DO). Continue to increase/decrease the angle until the instrument reads `Rev'. Record the angle (Reverse lead PU). Reduce the current angle until the 'Rev' extinguishes (Reverse lead DO). and the `Fwd' subsequently returns (Forward lead PU), recording the angles. Repeat the above tests, starting from the Characteristic Angle, but reducing the current phase angle to record the directional boundaries in the opposite (lag) direction. The recorded angle should be the angle at which the phase current leads the phase-phase polarising voltage. This measurement is greatly simplified if the polarising reference voltage is set to 0deg and the current phase angle is measured with respect to this reference. Alternatively, the instrument can be checked at the 4 points marked a,b,c & d on Figure 2-1 only. (c) 2013 Siemens Protection Devices Limited Page 15 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Forward Lag (point C) Pick-up MTA Reverse Lead (point A) Drop-off Pick-up MTA-85 Lead(point B) Drop-off MTA+85 Pick-up MTA-85 Drop-off Lag (point D) Pick-up Drop-off MTA-85 Phase A Phase B Phase C VA a +900 +600 A With balanced 3-phase system quantities: IA FWD B Adjust the phase angle of the currents relative to the voltages: +300 b 0 Verify directional pick-up and drop off at points A, B, C and D 0 0 +180 VBC Alternatively, Verify correct directional indication at points a, b, c and d (C.A +750, +950, -750, -950) c +210 0 C REV VC +2400 d +270 Figure 2.1-1 4. D VB 0 Directional Phase Fault Boundary System Angles With the instrument reading `Fwd' or `Rev', reduce the voltage until the element resets. Record the minimum phase-phase operate voltage. Minimum Voltage Setting 2.1.1 Measured 2 out of 3 logic Ensure that at least 1 Phase Overcurrent element is set to Directional. Apply balanced nominal voltage. Apply current at a level above on phase A only at the characteristic angle for forward operation, normally 45 lagging. Ensure no Directional Phase Overcurrent element operation occurs. Note that non-directional Phase Overcurrent and Non-direction Earth Fault elements may operate unless disabled. Repeat the test with Phase A current as above but also with equal current in the B phase at 180 to that in the A phase. 1 phase current No 50/51-n Operation Page 16 of 82 2 phase current 50/51-n operation (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.2 Phase Overcurrent (67/50,67/51) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 ADF 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 ADF 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 ADF 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.2-1 Phase Overcurrent Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) for directional elements. Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 51V, 51c, 46, 49, 50BF, 79 Map Pickup LED: 51-n/50-n - Self Reset Other protection functions may overlap with these functions during testing, it may be useful to disable some functions to avoid ambiguity. It should be particularly noted that if the function is enabled, the 51C Cold Load settings may modify the normal 50-n and 51-n settings if the CB is open during testing. Voltage inputs may not be required for this function if the Phase Overcurrent functions are not directional but it may be advantageous to apply balanced 3 phase nominal rated voltage to the VT inputs during testing to avoid inadvertent operation of other functions. Particular care should be taken when testing overcurrent functions that the thermal rating of the current inputs is not exceeded. (c) 2013 Siemens Protection Devices Limited Page 17 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.2.1 Definite Time Overcurrent. (50) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, and check operation. Apply 2x setting current if possible and record operating time. Phase Dir. Is (Amps) DTL (sec) P.U. Current Amps Operate Time 2 x Is Tol Tol IL1(IA) IL2(IB) IL3(IC) Check correct indication, trip output, alarm contacts, waveform record. 2.2.2 Inverse Time Overcurrent. (51) It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. Gradually increase current until Pickup LED operates. Apply 2x setting current and record operating time, Apply 5x setting current and record operating time. Compare to calculated values for operating times Gradually reduce current until the element drops off and record the level. P.U. D.O. & TIMING TESTS Ph. Dir Char. Curve Is (A) TM Operate Current P.U. D.O. Tol (Amps) (Amps) Operate Time 2 x Is 5 x Is Tol (sec) (sec) IL1(IA) IL2(IB) IL3(IC) Calculated Timing values in seconds for TM =1.0 Curve 2 xIs 5 xIs IEC-NI 10.03 4.28 IEC-VI 13.50 3.38 IEC-EI 26.67 3.33 IEC-LTI 120.00 30.00 ANSI-MI 3.80 1.69 ANSI-VI 7.03 1.31 ANSI-EI 9.52 1.30 Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a Follower DTL applied. Page 18 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 1.1.1.1 Element Blocking The Phase Overcurrent elements can be blocked by Binary Input Inhibit, VT Supervision and Inrush Detector operation, as well as 79 Autoreclose settings for Inst/Delayed. The Characteristic can be modified by Cold Load (51-n only) and Voltage Controlled Overcurrent and can be made non-directional by VT Supervision. This functionality should be checked. Element BI Inhibits VTS action Inrush Detector 79 Autoreclose 51-1 51-2 51-3 51-4 50-1 50-2 50-3 50-4 . 2.1.1.1 ANSI Reset If the element is configured as an ANSI characteristic, it may have an ANSI (decaying) reset delay applied. If ANSI reset is selected for an IEC characteristic element, the reset will be instantaneous. ANSI reset times from operated condition to fully reset are as follows for zero applied current and Time multiplier (TM) = 1.0. The reset curve characteristic type and TM is defined by the operating characteristic. Curve Fully operated to reset with Zero current applied & TM=1 (secs) ANSI-MI 4.85 ANSI-VI 21.6 ANSI-EI 29.1 Apply current in the following sequence, a) 2x setting for a time to ensure element operation, b) Zero current for the reset time above (xTM), c) 2x setting for a time to ensure element operation. Check that the second operation (c) is similar to the first (a) and in line with the expected operate time for the element at this current level. Repeat the test with the reset time (b) reduced to 50% of the previous value. Ensure that the second operate time (c) is 50% of the first (a) operate time. Operate time (expected) Reset time (calculated) Operate time (measured) 50% Reset Time (calculated) First test (c) 50% operate time (calculated) 50% operate time (measured) Second Test (c) Check correct indication, trip output, alarm contacts, waveform record. (c) 2013 Siemens Protection Devices Limited Page 19 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.3 Voltage Controlled Overcurrent (51V) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.3-1 Voltage Controlled Overcurrent OC Phase Control Voltage IL1 (IA), IL2 (IB), IL3 (IC), IL1(IA) V12(VAB) Disable: 51c, 46, 37, 49, 50BF, 79 IL2(IB) V23(VBC) Map Pickup LED: 51-n/50-n - Self Reset IL3(IC) V31(VCA) Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: Shaped Phase Overcurrent elements 51-n should be tested for pick-up and timing before this function is tested. The General Pickup LED can be used to assess operation of this function if other functions are disabled or if the setting allocating General Pickup is temporarily modified. Apply nominal 3 phase balanced voltage. Apply 3 phase balanced current at a level below the normal 51-n setting but above the effective 51V-n setting. Ensure that the thermal rating of the relay is not exceeded. Gradually reduce the voltage until the a-b voltage is less than the Voltage setting. Pickup LED operation can be used to confirm the Voltage setting. If the 51V-n current setting is above the continuous rating of the relay an alternative procedure should be used, apply test current in short duration shots with applied voltage being gradually reduced for each subsequent shot. Apply nominal 3 phase balanced voltage. Reduce the voltage such that the a-b voltage is 110 % of the Voltage setting. Page 20 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Gradually increase the a-b phase current or balanced 3P current until Pickup LED operates. Confirm result of Phase O/C test above. Reduce the applied voltage to a level such that V12(VAB) phase-phase voltage is less than 90 % of the setting. Gradually increase the I12(IAB) phase-phase current until Pickup LED operates. Note that these elements may be set as directional. If this is the case, the phase angle of the current must be set with respect to the voltage to produce operation of the elements. Voltage Setting (V, p-p) I Setting Multiplier Measured (V, p-p) Calculated PU Measured Tolerance 51-1 Pickup 51-2 Pickup 51-3 Pickup 51-4 Pickup 1.1.1.1 Element Blocking The Voltage Controlled Overcurrent function can be set to Inhibit for VT Supervision operation. This functionality should be checked. Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase 3P current until the element operates at its full setting, i.e. 51V settings are not used. Element VTS action 51-1 51-2 51-3 51-4 Check correct indication, trip output, alarm contacts. (c) 2013 Siemens Protection Devices Limited Page 21 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.4 Cold Load (51c) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.4-1 Cold Load Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) for directional elements Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 51V, 46, 49, 50BF, 79 Map Pickup LED:. 51-n - Self Reset The CB must be open for more than the Cold Load Pick-up Time to allow testing of this function. It may be convenient to reduce this setting to suit the test procedure. If the CB is open throughout the tests, the Cold Load protection settings can be tested provided that the current is not allowed to fall below the level of the Reduced Current Level for more than the Reduced Current Time during testing. It may be convenient to set the Reduced Current setting to Disabled for the duration of the test. The Cold Load Active output is provided and can be used as an indication during testing. Page 22 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Figure 2.4-2 Cold Load Logic diagram Ensure that the Cold load active is not raised. This can be reset by CB closed for more than the Cold Load Dropoff Time or current less than the Reduced Current Level for greater than the Reduced Current Time. Check the Cold Load Pick-up Delay by applying or simulating CB Open. Measure the time delay before Cold Load Active is raised. Apply current above the Reduced Current Level if this functionality is Enabled before applying CB Closed. Measure the time for Cold Load Active to reset. 2.4.1 Inverse Time Overcurrent. (51C) It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. Gradually increase current until Pickup LED operates. Apply 2x setting current and record operating time. Apply 5x setting current and record operating time. Compare to calculated values for operating times (c) 2013 Siemens Protection Devices Limited Page 23 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide P.U. D.O. & TIMING TESTS Ph. Dir Char. (NI EI VI LTI, DTL) Operate Current Is (A) TM P.U. (Amps) D.O. (Amps) Operate Time Tol 2 x Is (sec) 5 x Is (sec) Tol IL1(IA) IL2(IB) IL3(IC) Calculated Timing values in seconds for TM =1.0 Curve 2 xIs 5 xIs IEC-NI 10.03 4.28 IEC-VI 13.50 3.38 IEC-EI 26.67 3.33 IEC-LTI 120.00 30.00 ANSI-MI 3.80 1.69 ANSI-VI 7.03 1.31 ANSI-EI 9.52 1.30 Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a Follower DTL applied. 1.1.1.1 ANSI Reset If the element is configured as an ANSI characteristic, it may have a reset delay applied. If ANSI reset is selected for an IEC characteristic element, the reset will be instantaneous. ANSI reset times from operated condition to fully reset are as follows for zero applied current and TM = 1.0. The reset curve characteristic type and TM is defined by the operating characteristic. Curve Fully operated to reset with Zero current applied & TM=1 (secs) ANSI-MI 4.85 ANSI-VI 21.6 ANSI-EI 29.1 Apply current in the following sequence, a) 2x setting for a time to ensure element operation, b) Zero current for the reset time above (xTM), c) 2x setting for a time to ensure element operation. Check that the second operation (c) is similar to the first (a) and in line with the expected operate time for the element at this current level. Repeat the test with the reset time (b) reduced to 50 % of the previous value. Ensure that the second operate time (c) is 50 % of the first (a) operate time. Operate time (expected) Reset time (calculated) Operate time (measured) 50 % Reset Time (calculated) 50 % operate time (calculated) 50 % operate time (measured) Check correct indication, trip output, alarm contacts, waveform record. Page 24 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.1 Arc Flash Detection (50AFD) IL1 (IA) IL2 (IB) IL3 (IC) I4 (IG) I5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 46 BC 46 NPS (x2) 60 CTS 60 VTS 67/ 50/51N (x4) 51c 81 HBL 2/5N 37G (x2) 37 50 BF 67/ 50/51G (x4) 37 50 BF 67/ 50/51S (x4) (ISEF) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 47 (x2) 32 81 (x6) 59N (x2) 32S 25 Optional Arc Flash Detection Voltage Inputs: N/A Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 49, 50, 51 Map Pickup LED: 21FL 74 TCS 79 Figure 2.1-1 55 50AFD Zone-n Flash - Hand Reset, 50AFD Zone-n - Hand/self Reset The overcurrent level can be tested without an arc flash by separately energising or inverting the arc detector binary input continuously for the duration of the test for the zone being tested. If the current setting is low, gradually increase current until element operates. If the current level required is greater than the thermal limit of the relay, apply 0.9x setting, check for no operation, apply 1.1x setting, check operation. Optical sensors such as 7XG31 can be tested by application of a suitable light source. Relay instrumentation can be used to indicate binary input pickup or by the 50AFD Zone-n Flash outputs. The 7XG31 devices will typically require 10000 lx light level for 1.25ms to trigger. A high powered photographic flash is the most convenient means of initiating positive sensor operation. Note that mobile phone or small compact camera flashes may not have sufficient power to cause sensor operation but may be suitable if held directly against the sensor. Check correct indication, trip output, alarm contacts, waveform record. (c) 2013 Siemens Protection Devices Limited Page 25 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.2 Directional Earth Fault Polarity Check (67N) Derived Earth Fault, Measured Earth Fault and Sensitive Earth Fault elements can be set as directional. These are polarised from residual voltage, calculated from the 3 phase voltage inputs or the 3Vo input depending on the Phase Voltage Config setting in the CT/VT Config menu. The relay Char Angle setting is the Characteristic Phase angle of the fault impedance i.e. the phase angle of the fault current with respect to the voltage driving the current. The earth fault functions are polarised from the residual voltage which is in anti-phase with the fault voltage for a single-phase to earth fault. Care is required when testing by secondary injection with regard to current and voltage polarity. To simulate an earth fault on a relay with 3 phase-phase or 3 phase-neutral connected voltage inputs, defined by the Phase Voltage Config setting of Van,Vbn,Vcn or Va,Vb,Vc, proceed as follows. Balanced 3P voltage should first be applied, then the phase-neutral voltage magnitude on the faulted phase should be reduced in magnitude with no change in phase angle to produce Vres and simulate the fault. The fault current, on the faulted phase only, should be set at the MTA with respect to the phase-neutral voltage on the faulted phase, e.g. for a relay setting of -15, set the phase current to lag the ph-n voltage by 15. Alternatively, a single phase voltage source can be used in the above test. The polarity of this voltage, applied to the faulted phase-neutral alone, must be reversed to produce the same residual voltage (Vres) phase direction as that produced by the 3P voltage simulation described above. For the Phase Voltage Config of Vab, Vbc, Vo, the single phase voltage applied to the Vo input is used as the polarising quantity. The inversion is once again required since this input is designed to measure the residual voltage directly, as produced by an `open delta VT' arrangement. The current must be set at the MTA with respect to the inversion of this voltage. e.g. for a relay setting of -15, the phase current must lag the (Vo+180) voltage by 15, i.e. if Vo is set at 180, set Iph at -15. If the Pickup of one directional Earth Fault element is mapped to an LED, this can be used to check directional boundaries for pickup and drop-off as the current phase angle is increased and decreased. Note that the Derived Earth Fault, Measured Earth Fault and Sensitive Earth Fault have separate directional settings and must be tested individually. Figure 2.2-1 Page 26 of 82 Directional Earth Fault Boundary System Angles (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.3 Derived Earth Fault (67/50N, 67/51N) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.3-1 Derived Earth Fault Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 37, 46, 49, 60CTS, 50BF, 60CTS, 46BC, 79 Map Pickup LED: 51N-n/50N-n - Self Reset Other protection functions may overlap with these functions during testing; it may be useful to disable some functions to avoid ambiguity. Derived EF, Measured EF Sensitive EF & Restricted EF protections can be Enabled/Disabled individually or as groups in the `Function Config' menu. Derived EF elements can be separated from Measured EF and sensitive EF by arrangement of the secondary injection circuit by shorting/disconnecting I4 and I5 inputs. If any of these elements are defined as directional the correct voltage phase direction will be required to produce an operation of those elements. (c) 2013 Siemens Protection Devices Limited Page 27 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.3.1 Directional Polarity See section Directional Earth Fault Polarity Check above for testing details. Forward MTA Lag (point C) Pick-up ............. Drop-off Reverse Lead (point A) Pick-up Drop-off Lead(point B) Pick-up Drop-off Lag (point D) Pick-up MTA-85 MTA+85 MTA-85 MTA-85 ........... ............ ............ ............ Drop-off Derived EF 2.3.2 Definite Time Overcurrent..(50N) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, and check operation Apply 2x setting current if possible and record operating time Check correct indication, trip output, alarm contacts, waveform record. Note that these elements can be set to directional. Phase Dir. Is (Amps) DTL (sec) P.U. Current Amps Operate Time 2 x Is NOTES E If VTS action is set to BLOCK, this option should be tested. Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase 3P current and check that the element does not operate. If VTS action is set to Non-Directional, this option should be tested. Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element operates at its normal setting. Reverse the voltage phase direction whilst checking that the element does not reset. 2.3.3 Inverse Time Overcurrent. (51N) It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. Gradually increase current until Pickup LED operates. Apply 2x setting current and record operating time. Apply 5x setting current and record operating time. Compare to calculated values for operating times Page 28 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide P.U. D.O. & TIMING TESTS Ph. Char. Dir (NI EI VI LTI, DTL) Is (A) TM Operate Current P.U. D.O. Tol (Amps) (Amps) Operate Time 2 x Is 5 x Is Tol (sec) (sec) E Calculated Timing values in seconds for TM =1.0 Curve 2 xIs 5 xIs IEC-NI 10.03 4.28 IEC-VI 13.50 3.38 IEC-EI 26.67 3.33 IEC-LTI 120.00 30.00 ANSI-MI 3.80 1.69 ANSI-VI 7.03 1.31 ANSI-EI 9.52 1.30 Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a Follower DTL applied. 1.1.1.1 Element Blocking The Derived Earth Fault elements can be blocked by Binary Input Inhibit, VT Supervision and Inrush Detector operation. The Characteristic can be made non-directional by VT Supervision. This functionality should be checked. Element BI Inhibits VTS action Inrush Detector 51N-1 51N-2 51N-3 51N-4 50N-1 50N-2 50N-3 50N-4 (c) 2013 Siemens Protection Devices Limited Page 29 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.1.1.1 ANSI Reset If the element is configured as an ANSI characteristic, it may have a reset delay applied. If ANSI reset is selected for an IEC characteristic element, the reset will be instantaneous. ANSI reset times from operated condition to fully reset are as follows for zero applied current and TM = 1.0. The reset curve characteristic type and TM is defined by the operating characteristic. Curve Fully operated to reset with Zero current applied & TM=1 (secs) ANSI-MI 4.85 ANSI-VI 21.6 ANSI-EI 29.1 Apply current in the following sequence, a) 2x setting for a time to ensure element operation, b) Zero current for the reset time above (xTM), c) 2x setting for a time to ensure element operation. Check that the second operation (c) is similar to the first (a) and in line with the expected operate time for the element at this current level. Repeat the test with the reset time (b) reduced to 50% of the previous value. Ensure that the second operate time (c) is 50% of the first (a) operate time. Operate time (expected) Reset time (calculated) Operate time (measured) 50% Reset Time (calculated) First test (c) 50% operate time (calculated) 50% operate time (measured) Second Test (c) Check correct indication, trip output, alarm contacts, waveform record. Page 30 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.4 Measured Earth fault (67/50G,67/51G) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.4-1 Measured Earth Fault Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) for directional elements Current Inputs: I4 (IG) Disable: 50BF, 79 Map Pickup LED: . 51G-n/50G-n - Self Reset Other protection functions may overlap with these functions during testing, it may be useful to disable some functions to avoid ambiguity. Derived EF, Measured EF, Sensitive EF & Restricted EF protections can be Enabled/Disabled individually or as groups in the `Function Config' menu. Measured EF elements can be separated from Derived EF and Sensitive EF by secondary injection of current through the I4 input circuit only. If any of these elements are defined as directional the correct voltage phase direction will be required to produce an operation of those elements. (c) 2013 Siemens Protection Devices Limited Page 31 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.4.1 Directional Polarity See section Directional Earth Fault Polarity Check above for testing details. Forward MTA Lag (point C) Pick-up ............. Reverse Lead (point A) Drop-off Pick-up Drop-off Lead(point B) Pick-up Lag (point D) Drop-off Pick-up MTA-85 MTA+85 MTA-85 MTA-85 ........... ............ ............ ............ Drop-off Measured EF 2.4.2 Definite Time Overcurrent..(67/50G) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, and check operation. Apply 2x setting current if possible and record operating time. Phase Dir. Is (Amps) DTL (sec) P.U. Current Amps Operate Time 2 x Is NOTES I4 Check correct indication, trip output, alarm contacts, waveform record. Note that these elements can be set to directional. If VTS action is set to BLOCK, this option should be tested. Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element does not operate. If VTS action is set to Non-Directional, this option should be tested..Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element operates at its normal setting. Reverse the voltage phase direction whilst checking that the element does not reset. 2.4.3 Inverse Time Overcurrent. (67/51G) It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. Gradually increase current until Pickup LED operates. Apply 2x setting current and record operating time. Apply 5x setting current and record operating time. Compare to calculated values for operating times. Page 32 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide P.U. D.O. & TIMING TESTS Ph. Char. Dir (NI EI VI LTI, DTL) Is (A) TM Operate Current P.U. D.O. Tol (Amps) (Amps) Operate Time 2 x Is 5 x Is Tol (sec) (sec) I4 Calculated Timing values in seconds for TM =1.0 Curve 2 xIs 5 xIs IEC-NI 10.03 4.28 IEC-VI 13.50 3.38 IEC-EI 26.67 3.33 IEC-LTI 120.00 30.00 ANSI-MI 3.80 1.69 ANSI-VI 7.03 1.31 ANSI-EI 9.52 1.30 Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a Follower DTL applied. If VTS action is set to BLOCK, this option should be tested. Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element does not operate. If VTS action is set to Non-Directional, this option should be tested..Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element operates at its normal setting. Reverse the voltage phase direction whilst checking that the element does not reset. 1.1.1.1 Element Blocking The Measured Earth Fault elements can be blocked by Binary Input Inhibit, VT Supervision and Inrush Detector operation. The Characteristic can be made non-directional by VT Supervision. This functionality should be checked. Element BI Inhibits VTS action Inrush Detector 51G-1 51G-2 51G-3 51G-4 50G-1 50G-2 50G-3 50G-4 (c) 2013 Siemens Protection Devices Limited Page 33 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.1.1.1 ANSI Reset If the element is configured as an ANSI characteristic, it may have a reset delay applied. If ANSI reset is selected for an IEC characteristic element, the reset will be instantaneous. ANSI reset times from operated condition to fully reset are as follows for zero applied current and TM = 1.0. The reset curve characteristic type and TM is defined by the operating characteristic. Curve Fully operated to reset with Zero current applied & TM=1 (secs) ANSI-MI 4.85 ANSI-VI 21.6 ANSI-EI 29.1 Apply current in the following sequence, a) 2x setting for a time to ensure element operation, b) Zero current for the reset time above (xTM), c) 2x setting for a time to ensure element operation. Check that the second operation (c) is similar to the first (a) and in line with the expected operate time for the element at this current level. Repeat the test with the reset time (b) reduced to 50% of the previous value. Ensure that the second operate time (c) is 50% of the first (a) operate time. Operate time (expected) Reset time (calculated) Operate time (measured) 50% Reset Time (calculated) First test (c) 50% operate time (calculated) 50% operate time (measured) Second Test (c) Check correct indication, trip output, alarm contacts, waveform record. Page 34 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.5 Sensitive Earth fault (67/50S,67/51S) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.5-1 Sensitive Earth Fault Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) for directional elements Current Inputs: I5 (ISEF) Disable: 64H, 50BF, 79 Map Pickup LED: 51SEF-n/50SEF-n - Self Reset Other protection functions may overlap with these functions during testing; it may be useful to disable some functions to avoid ambiguity. Derived EF, Measured EF, Sensitive EF & Restricted EF protections can be Enabled/Disabled individually or as groups in the `Function Config' menu. Sensitive EF elements can be separated from Derived EF and Measured EF by secondary injection of current through the I5 input circuit only. If any of these elements are defined as directional the correct voltage phase direction will be required to produce an operation of those elements. (c) 2013 Siemens Protection Devices Limited Page 35 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.5.1 Directional Polarity See section Directional Earth Fault Polarity Check above for testing details. Forward MTA Lag (point C) Pick-up ............. Drop-off Reverse Lead (point A) Pick-up Drop-off Lead(point B) Pick-up Lag (point D) Drop-off Pick-up MTA-85 MTA+85 MTA-85 MTA-85 ........... ............ ............ ............ Drop-off SEF 2.5.2 Definite Time Overcurrent. (50SEF) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, and check operation. Apply 2x setting current if possible and record operating time. P.U. D.O. & TIMING TESTS Ph. Char. Dir (NI EI VI LTI, DTL) Is (A) TM Operate Current P.U. D.O. Tol (Amps) (Amps) Operate Time 2 x Is 5 x Is Tol (sec) (sec) I5(ISEF) Check correct indication, trip output, alarm contacts, waveform record. Note that these elements can be set to directional. If VTS action is set to BLOCK, this option should be tested. Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element does not operate. If VTS action is set to Non-Directional, this option should be tested. Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element operates at its normal setting. Reverse the voltage phase direction whilst checking that the element does not reset. 2.5.3 Inverse Time Overcurrent. (51SEF) It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. Gradually increase current until Pickup LED operates. Apply 2x setting current and record operating time. Apply 5x setting current and record operating time. Compare to calculated values for operating times. P.U. D.O. & TIMING TESTS Page 36 of 82 Ph. Char. Dir (NI EI VI LTI, DTL) Is (A) TM Operate Current P.U. D.O. Tol (Amps) (Amps) Operate Time 2 x Is 5 x Is Tol (sec) (sec) E (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Calculated Timing values in seconds for TM =1.0 Curve 2 xIs 5 xIs IEC-NI 10.03 4.28 IEC-VI 13.50 3.38 IEC-EI 26.67 3.33 IEC-LTI 120.00 30.00 ANSI-MI 3.80 1.69 ANSI-VI 7.03 1.31 ANSI-EI 9.52 1.30 Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a Follower DTL applied. If VTS action is set to BLOCK, this option should be tested. Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element does not operate. If VTS action is set to Non-Directional, this option should be tested..Apply balanced voltage and current. Reduce a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element operates at its normal setting. Reverse the voltage phase direction whilst checking that the element does not reset. 1.1.1.1 Element Blocking The Sensitive Earth Fault elements can be blocked by Binary Input Inhibit and VT Supervision. The Characteristic can be made non-directional by VT Supervision. This functionality should be checked. Element BI Inhibits VTS action 51SEF-1 51SEF-2 51SEF-3 51SEF-4 50SEF-1 50SEF-2 50SEF-3 50SEF-4 (c) 2013 Siemens Protection Devices Limited Page 37 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.1.1.1 ANSI Reset If the element is configured as an ANSI characteristic, it may have a reset delay applied. If ANSI reset is selected for an IEC characteristic element, the reset will be instantaneous. ANSI reset times from operated condition to fully reset are as follows for zero applied current and TM = 1.0. The reset curve characteristic type and TM is defined by the operating characteristic. Curve Fully operated to reset with Zero current applied & TM=1 (secs) ANSI-MI 4.85 ANSI-VI 21.6 ANSI-EI 29.1 Apply current in the following sequence, a) 2x setting for a time to ensure element operation, b) Zero current for the reset time above (xTM), c) 2x setting for a time to ensure element operation. Check that the second operation (c) is similar to the first (a) and in line with the expected operate time for the element at this current level. Repeat the test with the reset time (b) reduced to 5 0% of the previous value. Ensure that the second operate time (c) is 50 % of the first (a) operate time. Operate time (expected) Reset time (calculated) Operate time (measured) 50% Reset Time (calculated) First test (c) 50% operate time (calculated) 50% operate time (measured) Second Test (c) Check correct indication, trip output, alarm contacts, waveform record. Page 38 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.6 Restricted Earth fault. (64H) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.6-1 Voltage Inputs: n/a Current Inputs: I5 (IREF) Disable: 51SEF, 50SEF, 79 Map Pickup LED:. 64H - Self Reset Restricted Earth Fault The setting resistance should be measured and the value compared to that specified in the settings data. Both values should be recorded. Settings Data Resistor Value Measured The high value of setting resistance R will often interfere with secondary current injection when using a digital test set. It is normal practice in these cases to short out the resistor to allow testing; the shorting link should be removed after testing. Since the DTL setting is generally small the pick-up setting can be tested by gradually increasing current until element operates. The relay should be disconnected from the current transformers for this test. (c) 2013 Siemens Protection Devices Limited Page 39 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Apply 2x setting current if possible and record operating time Phase Is (Amps) DTL (sec) P.U. Current Amps Operate Time 2 x Is Tolerance Tolerance REF It is also desirable to check the operating voltage achieved with the setting resistor and all parallel CTs connected but de-energised. A higher capacity test set will be required for this test. Adequate current must be supplied to provide the magnetising current of all connected CTs. Precautions should be taken to ensure that no personnel are at risk of contact with any of the energised secondary wiring during the test. Settings Data Voltage Setting Measured To complete testing of the REF requires primary injection through the phase and residual (REF) CT in series to simulate an out of zone fault and ensure stability of the relay. The test can then be repeated with the REF CT secondary connections reversed to prove operation. 1.1.1.1 Element Blocking The Restricted Earth Fault element can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 64H Check correct indication, trip output, alarm contacts, waveform record. Check that any shorting links are removed after testing. Page 40 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.7 Negative Phase Sequence Overcurrent (46NPS) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.7-1Negative Phase Sequence Overcurrent Voltage Inputs: n/a Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 51, 51V, 51c, 37, 49, 50BF, 60CTS, 46BC Map Pickup LED: 46IT/46DT - Self Reset Where two NPS elements are being used with different settings, it is convenient to test the elements with the highest settings first. The elements with lower settings can then be tested without disabling the lower settings. The Thermal withstand limitations of the current inputs, stated in the Performance Specification should always be observed throughout testing. NPS Overcurrent can be tested using a normal 3P balanced source. Two phase current connections should be reversed so that the applied balanced 3P current is Negative Phase Sequence. (c) 2013 Siemens Protection Devices Limited Page 41 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.7.1 Definite Time NPS Overcurrent. (46DT) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, and check operation. Apply 2x setting current if possible and record operating time Phase Is (Amps) DTL (sec) P.U. Current Amps Operate Time 2 x Is Tolerance Tolerance NPS Check correct indication, trip output, alarm contacts, waveform record. 2.7.2 Inverse Time NPS Overcurrent. (46IT) It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. Gradually increase current until Pickup LED operates. Apply 2x setting current and record operating time. Apply 5x setting current and record operating time. Compare to calculated values for operating times P.U. D.O. & TIMING TESTS Ph. Char. Dir (NI EI VI LTI, DTL) Is (A) TM Operate Current P.U. D.O. Tol (Amps) (Amps) 2 x Is (sec) Operate Time 5 x Is Tol (sec) NPS Calculated Timing values in seconds for TM =1.0 Curve 2 xIs 5 xIs IEC-NI 10.03 4.28 IEC-VI 13.50 3.38 IEC-EI 26.67 3.33 IEC-LTI 120.00 30.00 ANSI-MI 3.80 1.69 ANSI-VI 7.03 1.31 ANSI-EI 9.52 1.30 Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a Follower DTL applied. Page 42 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 1.1.1.1 ANSI Reset If the element is configured as an ANSI characteristic, it may have a reset delay applied. If ANSI reset is selected for an IEC characteristic element, the reset will be instantaneous. ANSI reset times from operated condition to fully reset are as follows for zero applied current and TM = 1.0. The reset curve characteristic type and TM is defined by the operating characteristic. Curve Fully operated to reset with Zero current applied & TM=1 (secs) ANSI-MI 4.85 ANSI-VI 21.6 ANSI-EI 29.1 Apply current in the following sequence, a) 2x setting for a time to ensure element operation, b) Zero current for the reset time above (xTM), c) 2x setting for a time to ensure element operation. Check that the second operation (c) is similar to the first (a) and in line with the expected operate time for the element at this current level. Repeat the test with the reset time (b) reduced to 50 % of the previous value. Ensure that the second operate time (c) is 50 % of the first (a) operate time. Operate time (expected) Reset time (calculated) Operate time (measured) 50% Reset Time (calculated) 50% operate time (calculated) First test (c) 2.1.1.1 50% operate time (measured) Second Test (c) Element Blocking The NPS Overcurrent elements can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 46IT 46DT Check correct indication, trip output, alarm contacts, waveform record. When testing is complete reinstate any of the disabled functions. (c) 2013 Siemens Protection Devices Limited Page 43 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.8 Undercurrent. (37) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.8-1Undercurrent Voltage Inputs: n/a Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 51N, 51G, 46, 60CTS, 46BC Map Pickup LED: 37-n - Self Reset If two Undercurrent 37 elements are used with different settings, it is convenient to test the element with the lowest setting first. The higher setting element can then be tested without interference from the other element. Apply 3P balanced current at a level above the Undercurrent 37-n setting until the element resets. If DTL setting is small, gradually reduce any each phase current in turn until element operates. If DTL is large apply 1.1x setting, check for no operation, apply 0.9x setting, and check operation Testing of this element phase by phase may cause inadvertent operation of the 46 NPS Overcurrent elements. Apply 0.5x setting current and record operating time. Page 44 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Phase Is (Amps) DTL (sec) P.U. Current Amps Tolerance Operate Time 0.5 x Is Tolerance IL1(IA) IL2(IB) IL3(IC) 1.1.1.1 Element Blocking The Undercurrent elements can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 37-1 37-2 Check correct indication, trip output, alarm contacts, waveform record. (c) 2013 Siemens Protection Devices Limited Page 45 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.9 Thermal Overload (49) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.9-1Thermal Overload Voltage Inputs: n/a Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 51, 50, 37, 50BF Map Pickup LED:. 49Alarm The current can be applied from a 3P balanced supply or phase by phase from a 1P supply. Alternatively the 3 phase current inputs can be connected in series and injected simultaneously from a single 1P source. The Thermal Overload Setting and Time Constant Setting can be considered together to calculate the operating time for a particular applied current. The following table lists operate times for a range of Time Constant Settings for an applied current of 2x the Thermal Overload setting. Ensure that the thermal rating of the relay is not exceeded during this test. Page 46 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Time Constant (mins) Operate Time (sec) 1 17.3 2 34.5 3 51.8 4 69 5 86.3 10 173 15 259 20 345 25 432 30 51.8 50 863 100 1726 The Thermal State must be in the fully reset condition in order to measure the operate time correctly. This can be achieved by setting change in the Thermal protection settings menu or by pressing the Test/Reset button when the Thermal Meter is shown in the Instruments Mode. Reset the thermal State then apply 2x the Overload Setting current. Calculated Operate Time (s) Measured Operate Time (s) If the Thermal Overload Capacity Alarm is used, this can be tested by monitoring the Thermal Capacity in the instruments menu. If the Thermal time constant is longer than a few minutes, this can be assessed during the timing test above. If the Time Constant is less than a few minutes, a lower multiple of current will be required such that the rate of capacity increase is slowed to allow monitoring of the instrument to be accurate. Capacity Alarm Setting 1.1.1.1 Measured Element Blocking The Thermal element can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 49 (c) 2013 Siemens Protection Devices Limited Page 47 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.10 Over/Under Voltage 2.10.1 Phase Under/Over Voltage. (27/59) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.10-1 Phase Under/Over Voltage Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: n/a apply zero current to stabilize other functions Disable: 47, 59N, 60VTS Map Pickup LED:. 27/59-n - Self Reset Where more than one Undervoltage (27) elements are being used with different settings, it is convenient to test the elements with the lowest settings first. The elements with higher settings can then be tested without disabling the lower settings. Note that if the voltage is reduced below the 27UVG setting, the function may be blocked. VTS operation may also block the 27 Undervoltage function. Current inputs are not normally required to stabilise the relay during voltage element testing. If the `O/P Phases' is set to `All', the voltage on all phases must be reduced simultaneously. Otherwise the 3 phases should be tested individually. Page 48 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide If the DTL is short, starting from nominal voltage, slowly decrease the applied 3P or VL1 test voltage until the Pickup LED (temporarily mapped) is lit. Record the operate voltage. The LED should light at setting Volts +/- 5 %. Slowly increase the input voltage until the LED extinguishes. Record the reset voltage to check the `Hysteresis' setting. If the DTL is long, the operate level level should be checked by applying a voltage of 90 % of setting voltage. Check Hysteresis by resetting element to the operate level setting plus the hysteresis setting. Connect the relevant output contact(s) to stop the test set. Step the applied voltage to a level below the setting. The test set should be stopped at the operate time setting +/- 5 % Test inputs VL2 and VL3 by repeating the above if necessary. When testing is complete reinstate any of the disabled functions. Where more than one overvoltage (59) elements are being used with different settings, it is convenient to test the elements with the highest settings first. The elements with lower settings can then be tested without disabling the higher settings. If the `O/P Phases' is set to `All', the voltage on all phases must be increased simultaneously. Otherwise the 3 phases should be tested individually. If the DTL setting is short, starting from nominal voltage, slowly increase the applied 3P or VL1 test voltage until the Pickup LED (temporarily mapped) is lit. The LED should light at setting Volts +/- 5 % Decrease the input voltage to nominal Volts and the LED will extinguish. Record the reset voltage to check the `Hysteresis' setting. If the DTL setting is long, the operate level can be checked by applying 100 % of setting to cause operation followed by setting minus the Hysteresis setting to cause reset. Connect the relevant output contact(s) to stop the test set. Step the applied voltage to a level above the setting. The test set should be stopped at the operate time setting +/- 5 %. Test inputs VL2 and VL3 by repeating the above if necessary. Phase 27/59 setting (Volts) U/O DTL (sec) Hyst. D.O. (calculated) P.U. Volts D.O Volts Op. Time 2x Vs (OV) 0.5x Vs (UV) UV Guard Tol V1(VA) V2(VB) V3(VC) 1.1.1.1 Element Blocking The NPS Overcurrent elements can be blocked by Binary Input Inhibit and VT Supervision. This functionality should be checked. Element BI Inhibits VT Supervision 27/59-1 27/59-2 27/59-3 27/59-4 When testing is complete reinstate any of the disabled functions. (c) 2013 Siemens Protection Devices Limited Page 49 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.10.2 Undervoltage Guard (27/59UVG) If any 27 Undervoltage element is set to be inhibited by the 27 Undervoltage Guard element, this function should be tested. Connect the test voltage inputs to suit the installation wiring diagram utilising any test socket facilities available. It may be useful to temporarily map an LED as `General Pickup' to assist during testing. 27UVG operation will reset the General Pickup if no other element is operated. This LED should not be set as `Hand Reset' in the Output matrix. Starting from nominal voltage, apply a step decrease to the applied voltage to a level below the 27 Undervoltage setting but above the 27UVG setting such that an Undervoltage element operation occurs. Slowly reduce the applied voltage until the 27 Undervoltage element resets, this can be detected by the General Pickup LED reset if no other element is operated (this includes any Undervoltage element which is not UV Guarded). Phase Vs (Volts) Tol V element Used for test Blocked Volts NOTES UVG Page 50 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.10.3 VX Under/Over Voltage. (Vx 27/59) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.10-2 Vx Under/Over Voltage Voltage Inputs: V4 (VX) Current Inputs: n/a apply zero current to stabilize other functions Disable: Map Pickup LED:. Vx 27/59 - Self Reset If DTL setting is small, gradually increase single phase voltage applied to Vx input until element operates if the element is Overvoltage. Alternatively, if the element is Undervoltage, increase single phase voltage applied to Vx input until element operates. If DTL is large, for Overvoltage elements, apply 0.9x setting, check for no operation, apply 1.1x setting, check operation. For Undervoltage elements, apply 1.1x setting, check for no operation, apply 0.9x setting, check operation. Apply 2x setting voltage if possible and record operating time. Starting with the element in the operated condition, gradually increase or decrease the applied voltage until the element resets. Measure the reset voltage level to check the 27/59 Hysteresis setting. (c) 2013 Siemens Protection Devices Limited Page 51 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Phase 27/59 setting (Volts) U/O DTL (sec) Hyst. D.O. (calculated) P.U. Volts D.O Volts Op. Time 2x Vs (OV) 0.5x Vs (UV) Tolerence V4(Vx) 1.1.1.1 Element Blocking The Vx Under/Over Voltage elements can be blocked by Binary Input Inhibit and VT Supervision. This functionality should be checked. Element BI Inhibits VT Supervision 27/59x Check correct indication, trip output, alarm contacts, waveform record. Page 52 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.10.4 NPS Overvoltage (47) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.10-3 NPS Overvoltage Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: n/a apply zero current to stabilize other functions Disable: 27/59, 59N, 60VTS Map Pickup LED:. 47-n - Self Reset Where two NPS elements are being used with different settings, it is convenient to test the elements with the highest settings first. The elements with lower settings can then be tested without disabling the lower settings. NPS Overvoltage can be tested using a normal 3P balanced source. Two phase voltage connections should be reversed so that the applied balanced 3P voltage is Negative Phase Sequence. If the 47-n delay is small, gradually increased the applied balanced 3P voltage until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, and check operation. Apply 2x setting current if possible and record operating time. (c) 2013 Siemens Protection Devices Limited Page 53 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Phase 27/59 setting (Volts) U/O DTL (sec) Hyst. D.O. (calculated) P.U. Volts D.O Volts Op. Time 2x Vs Tolerence NPS 1.1.1.1 Element Blocking The NPS Overvoltage element can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 47-1 47-2 Check correct indication, trip output, alarm contacts, waveform record. Page 54 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.10.5 Neutral Overvoltage (59N) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 2.10-4 Neutral Overvoltage Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: n/a apply zero current to stabilize other functions Disable: 27/59, 47, 60VTS Map Pickup LED:. 59N-n - Self Reset The voltage source for the Neutral Overvoltage 59N function can be set as either Vn , calculated from the applied 3 phase voltage inputs or Vx, the V4 input. Apply test voltage to 1 phase input or V4 input to suit. 2.10.6 Definite Time (59NDT) If DTL setting is small, gradually increase single phase voltage until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, and check operation. Apply 2x setting voltage if possible and record operating time. (c) 2013 Siemens Protection Devices Limited Page 55 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Phase Vs (Volts) DTL (sec) P.U. Current Volts Operat e Time 2x Vs Tolerence E Check correct indication, trip output, alarm contacts, waveform record. 2.10.7 Inverse Time (59NIT) It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. Gradually increase voltage until Pickup LED operates. Apply 2x setting voltage and record operating time, Apply a higher multiple of setting voltage and record operating time. Compare to calculated values for operating times from: e 1 u top (sec onds ) ) = M e Vn u e [Vs ] - 1u Where M = Time multiplier and Vn/Vs = multiple of setting. P.U. D.O. & TIMING TESTS 2.10.8 Ph. Vs (V) TM Operate Voltage P.U. D.O. Tol (Volts) (Volts) 2.x Vs (sec) Operate Time x Vs (sec) Tol E ELEMENT BLOCKING The Neutral Overvoltage elements can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 59NIT 59NDT Check correct indication, trip output, alarm contacts, waveform record. When testing is complete reinstate any of the disabled functions. Page 56 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.10.9 Under/Over Frequency (81) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 67/ 51 (x4) 81 HBL 2 51c 37 (x2) 49 50 BF 51V 67/ 50 (x4) 37 (x2) 49 50 BF 51V 67/ 50 (x4) 67/ 51 (x4) 81 HBL 2 51c 37 (x2) 49 50 BF 51V 67/ 50 (x4) 67/ 51 (x4) 81 HBL 2 51c 46 BC 46 NPS (x2) 60 CTS 60 VTS 67/ 50N (x4) 67/ 51N (x4) 81 HBL 2N 67/ 50G (x4) 67/ 51G (x4) 81 HBL 2G 37G (x2) 67/ 50S (x4) 67/ 51S (x4) 64 H 37S (x2) 60 CTSI I4 (IG) I5 (ISEF) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 47 (x2) Note: Example shows Voltage Config = Van, Vbn, Vcn 81 (x6) 59N (x2) 74 TCS 27 59 79 Optional Figure 2.10-5 Under/Over Frequency Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: n/a apply zero current to stabilize other functions. Disable: Map Pickup LED: 81-n - Self Reset. This function can be tested by application of 1P or 3P voltage. For Over-frequency, the elements with the highest setting should be tested first and for Under-frequency the elements with the lowest settings should be tested first. The elements with other settings can then be tested without need to disable the elements already tested. Note that the relay is designed to track the gradual changes in power system frequency and that sudden step changes in frequency during testing do not reflect normal system operation. Normal `instantaneous' operation of the frequency element is 140 ms to 175 ms in line with the Performance Specification. Application of sudden step changes to frequency can add additional delay which can produce misleading test results. Gradually increase/decrease applied voltage frequency until 81-n operation occurs. Elements set for more extreme frequency fluctuation should be tested first with lesser elements disabled. (c) 2013 Siemens Protection Devices Limited Page 57 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide If the 81-n Delay setting is long it will be advantageous to map the function to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. If the delay setting is short the operation of the element can be easily checked directly. The frequency should then be gradually decreased/increased until the element resets. The reset frequency can be used to check the Hysteresis setting. If the element is set as 81-n U/V Guarded, The applied voltage must be above the 81 UV Guard Setting in the U/O Frequency menu. Apply setting frequency +0.5 Hz for Over-frequency or -0.5 Hz for Under-frequency and record operating time. Starting with the element in the operated condition, gradually increase or decrease the applied voltage until the element resets. Measure the reset voltage level to check the 81 Hysteresis setting. F (Hertz) U/O DTL (sec) Hyst. D.O. (calc.) P.U. Freq Hertz D.O. Freq. Hertz Operate Time +/- 0.5Hz UV Guard NOTES If the element is set as 81-nU/V Guarded, this setting can be tested by applying the test voltage at a level below the 81 U/V Guard Setting at a frequency in the operate range. Increase the voltage until the relay operates. UVG UVG Setting (Volts) Freq element Used for test Blocked Volts (D.O.) Unblocked Volts (P.U.) NOTES U/O Freq 1.1.1.1 ELEMENT BLOCKING The U/O Frequency elements can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 81-1 81-2 81-3 81-4 81-5 81-6 Check correct indication, trip output, alarm contacts, waveform record. When testing is complete reinstate any of the disabled functions. Page 58 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.11 Power (32) IL1 (IA) IL2 (IB) IL3 (IC) I4 (IG) I5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 46 BC 46 NPS (x2) 60 CTS 60 VTS 67/ 50/51N (x4) 51c 81 HBL 2/5N 37G (x2) 37 50 BF 67/ 50/51G (x4) 37 50 BF 67/ 50/51S (x4) (ISEF) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 47 (x2) 32 (x2) 81 (x6) 59N (x2) 32S (x2) Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 50, 51,27 Map Pickup LED: 21FL 74 TCS 79 Figure 2.11-1 55 25 Optional Power 32-n - Self Reset This function can be tested by application 3P current and voltage. For Over-power, the elements with the highest setting should be tested first and for Under-power the elements with the lowest settings should be tested first. The elements with other settings can then be tested without need to disable the elements already tested. From the nominal power setting Sn gradually increase/decrease applied voltage or current until 32-n operation occurs. If the 32-n Delay setting is long it will be advantageous to map the function to temporarily drive the relevant Pickup output in the Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function. If the delay setting is short the operation of the element can be easily checked directly. The current or voltage should then be decreased/increased until the element resets. If the element is set as 32-n U/C Guarded, The applied current must be above the 32 U/C Guard Setting. Apply setting power +10% for Over-power or -10% for Under-power and record operating time. (c) 2013 Siemens Protection Devices Limited Page 59 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Power (xSn) U/O DTL (sec) P.U. Power (xSn) D.O. Power (xSn) Operate Time +/- 0.5Hz UC Guard NOTES 32-1 32-2 If the element is set as 32-n U/C Guarded, the setting can be tested by applying the test current at a level below the 32-n U/C Guard Setting at a power in the operate range. Increase the current until the relay operates. UCG UCG Setting (xIn) Power element Used for test Blocked Current (D.O.) Unblocked Current (P.U.) NOTES U/O Power 1.1.1.1 Element Blocking The U/O Power elements can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 32-1 32-2 Check correct indication, trip output, alarm contacts, waveform record. When testing is complete reinstate any of the disabled functions. Page 60 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.12 Sensitive Power (32S) IL1 (IA) IL2 (IB) IL3 (IC) I4 (IG) I5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 46 BC 46 NPS (x2) 60 CTS 60 VTS 67/ 50/51N (x4) 51c 81 HBL 2/5N 37G (x2) 37 50 BF 67/ 50/51G (x4) 37 50 BF 67/ 50/51S (x4) (ISEF) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 47 (x2) 32 (x2) 81 (x6) 59N (x2) 32S (x2) 25 Optional Sensitive Power Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: I4 (ISEF) Disable: 27 Map Pickup LED: 21FL 74 TCS 79 Figure 2.12-1 55 32S-n - Self Reset This function can be tested by application 1P current and 3P voltage. For Over-power, the elements with the highest setting should be tested first and for Under-power the elements with the lowest settings should be tested first. The elements with other settings can then be tested without need to disable the elements already tested. From the nominal power setting Sn gradually increase/decrease applied voltage or current until 32S-n operation occurs. If the 32S-n Delay setting is long it will be advantageous to map the function to temporarily drive the relevant Pickup output in the Output Config > Pickup Config menu. This will allow the Pick-up led to operate for the function. If the delay setting is short the operation of the element can be easily checked directly. The current or voltage should then be decreased/increased until the element resets. If the element is set as 32S-n U/C Guarded, The applied current must be above the 32S U/C Guard Setting. Apply setting power +10% for Over-power or -10% for Under-power and record operating time. (c) 2013 Siemens Protection Devices Limited Page 61 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Power (xSn) U/O DTL (sec) P.U. Power (xSn) D.O. Power (xSn) Operate Time +/- 0.5Hz UC Guard NOTES 32S-1 32S-2 If the element is set as 32S-n U/C Guarded, the setting can be tested by applying the test current at a level below the 32S-n U/C Guard Setting at a power in the operate range. Increase the current until the relay operates. UCG UCG Setting (xIn) Power element Used for test Blocked Current (D.O.) Unblocked Current (P.U.) NOTES U/O Power 1.1.1.1 Element Blocking The U/O Power elements can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 32S-1 32S-2 Check correct indication, trip output, alarm contacts, waveform record. When testing is complete reinstate the disabled functions. Page 62 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 2.13 Power Factor (55) IL1 (IA) IL2 (IB) IL3 (IC) I4 (IG) I5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50/51 (x4) 50 AFD 21 LB 51c 81 HBL 2/5 46 BC 46 NPS (x2) 60 CTS 60 VTS 67/ 50/51N (x4) 51c 81 HBL 2/5N 37G (x2) 37 50 BF 67/ 50/51G (x4) 37 50 BF 67/ 50/51S (x4) (ISEF) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 47 (x2) 32 (x2) 81 (x6) 59N (x2) 32S (x2) 25 Optional Power Factor Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 49 Map Pickup LED: 21FL 74 TCS 79 Figure 2.13-1 55 55-n - Self Reset Apply balanced 3 phase rated voltage and current. Increase current phase angle until the LED assigned to '55-n' is lit. Record this angle in the table below. Decrease the angle until the LED resets. Record the angle. 55 Setting Angle Pick-Up Drop-Off 55-1 55-2 (c) 2013 Siemens Protection Devices Limited Page 63 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide If the element is set as 55-n U/C Guarded, the setting can be tested by applying the test current at a level below the 55-n U/C Guard Setting at a power in the operate range. Increase the current until the relay operates. UCG UCG Setting (xIn) Power element Used for test Blocked Current (D.O.) Unblocked Current (P.U.) NOTES Power Factor 1.1.1.1 Element Blocking The Power Factor elements can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 55-1 55-2 Check correct indication, trip output, alarm contacts, waveform record. When testing is complete reinstate any of the disabled functions. Page 64 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Section 3: Supervision Functions 3.1 CB Fail. (50BF) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 3.1-1 Voltage Inputs: n/a Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), CB Fail Disable: Map Pickup LED: 50BF-n - Self Reset The circuit breaker fail protection time delays are initiated either from: A binary output mapped as Trip Contact in the OUTPUT CONFIG>BINARY OUTPUT CONFIG menu, or A binary input mapped as 50BF Ext Trip in the INPUT CONFIG>INPUT MATRIX menu. (c) 2013 Siemens Protection Devices Limited Page 65 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Apply a trip condition by injection of current to cause operation of a suitable protection element. Allow current to continue after the trip at a level of 110 % of the 50BF Setting current level on any phase. Measure the time for operation of operation of 50BF-1 Delay and 50BF-2 Delay. Repeat the sequence with current at 90 % of the 50BF Setting.current level after the element trip and check for no CB Fail operation. 50BF Setting (xIn) Test Current 50BF-1 Delay 50BF-2 Delay (90%) No Operation.. No Operation.. 50BF CB Faulty Operation No Delay Operation No Delay Test Current 50BF-1 Delay 50BF-2 Delay (90%) No Operation.. No Operation.. 50BF CB Faulty Operation No Delay Operation No Delay (110%) 50BF-I4 Setting (xIn) (110%) 1.1.1.1 Element Blocking The CB Fail function can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 50BF Page 66 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.2 Voltage Transformer Supervision. (60VTS) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 3.2-1 Voltage Transformer Supervision Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 27, 47, 59N Map Pickup LED: 60VTS - Self Reset (c) 2013 Siemens Protection Devices Limited Page 67 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.2.1 1 or 2 Phase VT fail Apply 3P balanced nominal current and voltage. Reduce 1 phase voltage until VTS operates, record voltage reduction level. 60VTS V Setting Setting x 3 Measured Voltage Reduction Increase the voltage until VTS resets. Increase current on 1 phase by 110 % of 3x the 60VTS I setting. Reduce voltage as above and check for no operation. Return voltage to nominal. Increase current on 1 phase by 90 % of 3x the 60VTS I.setting. Reduce voltage as above and check for VTS operation. 60VTS I Setting 3.2.2 Setting x 3 110% of Setting x 3 90% of Setting x 3 No VTS. VTS operation. 3 Phase VT fail Apply 3P balanced nominal voltage and 3P balanced current at a level between the 60VTS Ipps Load setting and the 60VTS Ipps Fault setting. Reduce the balanced Voltage on all 3 phases until the VTS operates at the 60VTS Vpps setting. Return the voltage to nominal and ensure that VTS resets. Reduce the 3P balanced current to a level below the 60VTS Ipps Load setting. Reduce the 3P balanced voltage to a level below the operate level above. Gradually increase the 3P balanced current until the VTS operates. Check that the thermal rating of the relay current inputs is not exceeded during the following test. Increase the 3P balanced current to a level above the 60VTS Ipps Fault setting. Reduce the 3P balanced voltage to a level below the operate level above. Gradually reduce the 3P balanced current until the VTS operates. Setting Measured 60VTS Vpps 60VTS Ipps Load 60VTS Ipps Fault If the VTS can be started from a status input fed from an external source, this functionality should be tested. Ext_Trig 60VTS Operation 1.1.1.1 Not Applicable. Element Blocking The VT Supervision can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 60VTS Page 68 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.3 Current Transformer Supervision. (60CTS) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 21 FL 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 21 FL 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 21 FL 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 3.3-1 Current Transformer Supervision Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) for directional elements. Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 51N, 46IT, 46DT, 46BC Map Pickup LED:. 60CTS - Self Reset The presence of NPS current without NPS voltage is used to indicate a current transformer failure. Apply normal 3P balanced current with a crossover of any two phases at a level above 60CTS Inps setting. Measure the delay to operation. Apply 3P balanced voltage with a similar phase crossover to the current. Increase the applied 3P voltage until the CTS element resets. Reduce the 3P voltage to cause CTS operation again. Gradually reduce the 3P current until the element resets. (c) 2013 Siemens Protection Devices Limited Page 69 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Setting Measured 60CTS Delay 60CTS Inps 60CTS Vnps 3.3.1 ELEMENT BLOCKING The CT Supervision function can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 60CTS Page 70 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.4 Broken Conductor. (46BC) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 3.4-1 Voltage Inputs: n/a Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 51N, 46IT, 46DT Map Pickup LED:. 46BC - Self Reset Broken Conductor Broken Conductor uses the ratio of NPS current to PPS current to detect an open circuit conductor. These quantities can be produced directly from many advanced test sets but with limited equipment the following approach can be applied. Apply 3P balanced current with normal phase rotation direction. This current will consist of PPS alone, no NPS or ZPS. Increase 1 phase current magnitude in isolation to produce NPS. The single phase unbalance current will contain equal quantities of ZPS, NPS and PPS. The NPS component will be 1/3 of the unbalance current and the total PPS component will be value of the original balanced 3P current plus 1/3 of the additional unbalance current. i.e. as the single phase unbalance current increases, the ratio of NPS to PPS will also increase. The levels of each sequence component current can be monitored in the Current Meters in Instruments Mode. (c) 2013 Siemens Protection Devices Limited Page 71 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Inject 1 A of balanced current. Gradually increase imbalance current, operating level should be as follows: 46BC Setting 46BC Setting 1P unbalance current (% of 3P current) 20% 75% 25% 100% 30% 129% 35% 161% 40% 200% 3P balanced current (A) 1P unbalance current (A) Measured Unbalance current Apply 1 A 1P unbalance current without 3P balanced current. Measure 46BC operating time. 46BC Delay setting 3.4.1 Measured ELEMENT BLOCKING The Broken Conductor element can be blocked by Binary Input Inhibit. This functionality should be checked. Element BI Inhibits 46BC Page 72 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.5 Load Blinder (21) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 37 (x2) 49 50 BF 60 CTSI 51V 67/50/ 51(x4) 50 AFD 21 LB 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/50/ 51(x4) 50 AFD 21 LB 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/50/ 51(x4) 50 AFD 21 LB 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50/51N (x4) 37 50 BF 67/ 50/51G (x4) 37 50 BF 67/ 50/51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 3.5-1 Load Blinder (21) Voltage Inputs: VL1 (VA), VL2 (VB), VL3 (VC) Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: 51-n, 51V, 51c, 46, 49, 50BF, 79 Map Pickup LED: 21LB-3P, 21LB-1P - Self Reset Load Blinders are designed to block Overcurrent elements from tripping in heavy load conditions. User settings 21LB-3P Angle and 21LB-3P Impedance allow user to define the Blinder region depending on the networks or specifically a line's loading and fault limits. The calculated impedance can be: * In Blinder Region in which case the Load Blinder FWD or REV is active depending on if the impedance is in the 1st or 4th and/or 2nd or 3rd quadrant of the R-X plot respectively. * In operate region in which case there is no active Load Blinder block and the Overcurrent element operates depending on additional factors. * A 5 degree Hysteresis is allowed between operate and block zone. (c) 2013 Siemens Protection Devices Limited Page 73 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide The design of a Load Blinder 3Ph is based on the theory that protection blocking should be issued only during definable allowable system power flow conditions i.e. an overcurrent blocking signal can only be issued when: Positive Sequence Voltage Vpps is not significantly changed, when the Vpps is above the 21LB-3P VPPS Setting. AND Negative Sequence Current Inps is lower than 21LB-3P INPS Setting AND Distributed generators feed in PPS current into the system. In case of high load in system due to distributed generation hence resulting in change of Zpps. Zpps is calculated from Vpps and Ipps. The magnitude and angle of Zpps is compared with 21LB-3P Impedance and 21LB-3P Angle to determine if the impedance is in operate or block and/or FWD or REV zone. Nominal Impedance Z = 1p.u. = VL / (3 x I) +X Point 8 Point 7 Block Zone a b Load Impedance Block Zone Phase Fault b -R Load 0 360 Impedance +R c Point 10 Point 9 Operate Zone Vpps value c a a = 21LB-3P Impedance setting b = 21LB-3P Angle +ve setting c = 21LB-3P Angle -ve setting Point 1 Point 2 Trip Level I = Vs / Z Point 6 Point 5 Point 3 Point 4 -X Figure 3.5-2 Load Blinder (21) Boundary Points Page 74 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.5.1 DETERMINING LOAD BLINDER REGIONS (21LB) Test Procedure (Using Omicron Relay Test Set) 1. Set-up the relay with default or appropriate parameter settings. 2. Set-up Omicron current and voltage settings e.g. 63.5 V and 0.5 A three-phase. 3. Select all three currents and set an appropriate initial angle for rotation on the Omicron. 4. Apply Omicron current and voltage to the relay. 5. Using the PC mouse click the appropriate arrow ` (positive degree) direction. ' to rotate the angle of current in the anti-clockwise 6. View the LEDs for indication of Load Blinder operation as the angle moves out-of or into the Load Blinder region. 7. Rotating the angle in an anti-clockwise direction will see the LEDs extinguish, this indicates the drop-off point of the Load Blinder region. Record the angle as Point1 in the table of values. 8. Rotating the angle from this point in a clockwise direction will see the LEDs illuminate which indicates the pick-up point of the Load Blinder region. Record the angle as Point 2 in the table of values. 9. Continue this process to find the other boundaries. See Error! Reference source not found. below. Angle data points (b and c) Default Settings Forward (+) Boundary Load Blinder region Angle = 20 (b) Angle Angle = 340 (-20) (c) PU (Raised) DO (Reset) PU (Raised) DO (Reset) Point 2 Point 1 Point 3 Point 4 Angle limits (b and c). Typical values. Forward (+) Boundary Load Blinder region Angle = 20 (b) Angle Forward (-) Boundary PU (Raised) 20 (c) 2013 Siemens Protection Devices Limited DO (Reset) 21 Foreward (-) Boundary Angle = 340 (-20) (c) PU (Raised) 340 DO (Reset) 339 Page 75 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.5.2 DETERMINING TRIP LEVEL Test Procedure (Using Omicron Relay Test Set) 1. Set-up the relay with default or appropriate parameter settings (see table below). 2. Set-up Omicron current and voltage settings e.g. 63.5 V and 1.0 A three-phase. 3. Select all three currents and set an appropriate initial current level for increase on the Omicron. 4. Apply Omicron current and voltage to the relay. 5. Using the PC mouse click the appropriate arrow ` ' to adjust current level. 6. View the LEDs for indication of Load Blinder operation as the current increases out-of the Load Blinder region. This is the DO point 5. 7. View the LEDs for indication of Load Blinder operation as the current decreases into the Load Blinder region. This is the PU point 6. Trip Level I = Vs / Z Default Settings Parameters Setting Impedance 42 Voltage V 63.5 Trip Level I = Vs / Z. Typical values. Parameters Setting Impedance 42 Voltage V 63.5 Page 76 of 82 DO PU Point 5 Point 6 DO PU 1.591 A 1.511 A (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.6 Trip Circuit Supervision. (74TCS) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 3.6-1 Voltage Inputs: n/a Current Inputs: n/a Trip Circuit Supervision Disable: Map Pickup LED: 74TCS-n - Self Reset The TCS-n Delay can be initiated by applying an inversion to the relevant status input and measured by monitoring of the alarm output. TCS-n Delay setting (c) 2013 Siemens Protection Devices Limited Measured Page 77 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.7 Magnetising Inrush Detector. (81HBL) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 37 (x2) 49 50 BF 60 CTSI 51V 67/ 50 (x4) 67/ 51 (x4) 50 AFD 51c 81 HBL 2 46 BC 46 NPS (x2) 60 CTS 51c 60 VTS 67/ 50N (x4) 67/ 51N (x4) 37 50 BF 67/ 50G (x4) 67/ 51G (x4) 37 50 BF 67/ 50S (x4) 67/ 51S (x4) I4 (IG) I5 (ISEF) 81 HBL 2N 37G (x2) 64 H 37S (x2) NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 27 59 79 25 47 (x2) 81 (x6) 59N (x2) 74 TCS Optional Figure 3.7-1 Magnetising Inrush Detector Voltage Inputs: n/a Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: Map Pickup LED: Logical operation of the harmonic blocking can be tested by current injection at 100 Hz to cause operation of the blocking signals. Page 78 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide 3.1 Over Fluxing Detector. (81HBL5) 7SR22 IL1 (IA) IL2 (IB) IL3 (IC) 37 (x2) 49 50 BF 51V 67/ 50 (x4) 37 (x2) 49 50 BF 51V 67/ 50 (x4) 67/ 51 (x4) 81 HBL 5 51c 37 (x2) 49 50 BF 51V 67/ 50 (x4) 67/ 51 (x4) 81 HBL 5 51c 46 BC 46 NPS (x2) 60 CTS 60 VTS 67/ 50N (x4) 67/ 51N (x4) 81 HBL 2N 67/ 50G (x4) 67/ 51G (x4) 81 HBL 2G 37G (x2) 67/ 50S (x4) 67/ 51S (x4) 64 H 37S (x2) 60 CTSI I4 (IG) I5 (ISEF) 67/ 51 (x4) 81 HBL 5 51c NOTE: The use of some functions are mutually exclusive VL1 (VA) 27 59 (x4) VL2 (VB) 27 59 (x4) VL3 (VC) 27 59 (x4) V4 (VX) 47 (x2) Note: Example shows Voltage Config = Van, Vbn, Vcn 81 (x6) 59N (x2) 74 TCS 27 59 79 Optional Figure 3.1-1 Magnetising Inrush Detector Voltage Inputs: n/a Current Inputs: IL1 (IA), IL2 (IB), IL3 (IC), Disable: Map Pickup LED: th Logical operation of the harmonic blocking can be tested by injection of 5 harmonic current (at 250Hz for 50Hz relay) to cause operation of the blocking signals. Note that injection of any level of 5th harmonic alone on a current input will cause the block to be raised since the harmonic content on this input is 100%, i.e. greater than setting. Fundamental frequency current can be injected into the other winding simultaneously to operate the 87BD or 87HS protection elements if required to test the blocking operation. Care should be taken that the thermal limits of the relay are not exceeded during these tests. More advanced test equipment is required, with the facility to combine harmonic and fundamental frequencies of current, to test the level of the blocking element. Note that the 81HBL5 Setting is set as a fraction of the total current. e.g. 0.25A at 250Hz combined with 1A at 50Hz gives a 5th harmonic content of 0.2 i.e. (0.25/(0.25+1.0)). (c) 2013 Siemens Protection Devices Limited Page 79 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide Section 4: Control & Logic Functions 4.1 Autoreclose (79) Autoreclose sequences can be specified differently for Phase. Earth, Externally Initiated and SEF faults. Sequences should be simulated for each applicable different fault type with the actual relay settings required for service installed in the relay. The relay requires that the correct indications are received at the CB auxiliary contact inputs and that the injected current and voltage used to generate protection operations are timed to the autoreclose sequence to provide a realistic simulation of the actual system conditions. The Instruments Menu contains Autoreclose Meters for the Autoreclose State and the Shot No. which are useful during sequence testing. The time stamped Events listing can be downloaded from the relay to a pc to allow diagnosis of the sequence including measurements of sequence Dead Times and other timing without the use of external measuring equipment or complex connections. 4.2 Quick Logic If this functionality is used, the logic equations may interfere with testing of other protection functions in the relay. The function of the Quick Logic equations should be tested conjunctively with connected plant or by simulation to assess suitability and check for correct operation on an individual basis with tests specifically devised to suit the particular application. Page 80 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Commissioning & Maintenance Guide Section 5: Testing and Maintenance 7SR21 & 7SR22 relays are maintenance free, with no user serviceable parts. 5.1 Periodic Tests During the life of the relay, it should be checked for operation during the normal maintenance period for the site on which the product is installed. It is recommended the following tests are carried out: Visual inspection of the metering display. 1. Operation of output contacts 2. Secondary injection of each element 5.2 Maintenance Relay failure will be indicated by the `Protection Healthy' LED being off or flashing. A message may also be displayed on the LCD. In the event of failure Siemens Protection Devices Ltd. (or one of its agents) should be contacted - see defect report sheet in section 5.3. The relay should be returned as a complete unit. No attempt should be made to disassemble the unit to isolate and return only the damaged sub-assembly. It may however be convenient to fit the withdrawable relay to the outer case from a spare relay, to avoid the disturbance of relay panel wiring, for return to Siemens Protection Devices Ltd. The withdrawable relay should never be transported without the protection of the outer case. (c) 2013 Siemens Protection Devices Limited Page 81 of 82 7SR210 & 7SR220 Commissioning & Maintenance Guide 5.3 Troubleshooting Table 5-1 Troubleshooting Guide Observation Action Relay does not power up. Check that the correct auxiliary DC voltage is applied and that the polarity is correct. Relay won't accept the password. The Password being entered is wrong. Enter correct password. If correct password has been forgotten, note down the Numeric Code which is displayed at the Change Password screen e.g. Change password = 1234567 To retrieve the password, communicate this code to a Siemens Protection Devices Ltd. representative. Protection Healthy LED flashes General failure. Contact a Siemens Protection Devices Ltd. representative. LCD screen flashes continuously. The LCD has many possible error messages which when displayed will flash continuously. These indicate various processor card faults. General failure. Contact a Siemens Protection Devices Ltd. representative. Backlight is on but no text can be seen. Adjust the contrast. Scrolling text messages are unreadable. Adjust the contrast. Relay displays one instrument after another with no user intervention. This is normal operation, default instruments are enabled. Remove all instruments from the default list and only add those that are required. Cannot communicate with the relay. Check that all of the communications settings match those used by Reydisp Evolution. Check that the Tx and Rx fibre-optic cables are connected correctly. (Tx -> Rx and Rx -> Tx). Check that all cables, modems and fibre-optic cables work correctly. Ensure that IEC 60870-5-103 is specified for the connected port (COM1, COM2, COM3 or COM4). Relays will not communicate in a ring network. Check that the Data Echo setting on all relays is set to ON. Check that all relays are powered up. Check that all relays have unique addresses. Status inputs do not work. Check that the correct DC voltage is applied and that the polarity is correct. Check that the status input settings such as the pick-up and dropoff timers and the status inversion function are correctly set. Relay instrument displays show small currents or voltages even though the system is dead. This is normal. The relay is displaying calculation noise. This will not affect any accuracy claims for the relay. If the above checklist does not help in correcting the problem please contact the local Siemens office or contact PTD 24hr Customer Support, Tel: +49 180 524 7000, Fax: +49 180 524 2471, e-mail: support.energy@siemens.com. Page 82 of 82 (c) 2013 Siemens Protection Devices Limited 7SR210 Non-Directional Relay 7SR220 Directional Relay Applications Guide The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide Document Release History This document is issue 2018/05 The list of revisions up to and including this issue is: 2011/05 First issue 2013/01 Typographical revisions and added data. Updated in line with software release. 2014/06 Typographical revisions and added data. Updated in line with software release. 2015/06 Typographical revisions and added data. Updated in line with software release. 2016/02 Typographical revisions and added data. Updated in line with software release. 2016/11 Typographical revisions and added data. 2017/08 Typographical revisions and added data. Updated in line with software release. 2017/12 Typographical revisions and added data. 2018/05 Typographical revisions and added data. Software Revision History 2011/05 2435H85008R7a-7a (7SR210) First Release 2435H85009R7a-7a (7SR220) 2013/01 2435H85008R7c-7b (7SR210) 2435H85009R7c-7b (7SR220) 2014/06 2435H85008R7f-7d (7SR210) 2435H85009R7f-7d (7SR220) 2015/06 2435H85008R8a-7f (7SR210) 2435H85009R8a-7f (7SR220) 2016/02 2435H85008R8b-7f (7SR210) Introduced journaling file system. Added 61850 logical nodes for CB Counters, metering, 50BF, 46BC, 81HBL2 and line check. Added Line Check on non-AR devices. Added 74CCS Close Circuit Supervision. Added Fault Locator feature and Check Sync feature. Fault data transmitted over 103. Additional communications data, control features, meters. Added Power Factor Meters, Load Blinding feature, Arc Flash Detector. Over current TM Setting Range extended. EN100+ Compatibility. 2435H85009R8b-7f (7SR220) 2017/08 2435H85008R8e-8a (7SR210) 2435H85009R8e-8a (7SR220) Page 2 of 48 Added 32 Directional Power, 32S Sensitive Power, 55 Power Factor, 81HLB5 Overfluxing, 67SEF Compensated Network, 67SEF Wattmetric. Increased I/O. Event Data on LCD. (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide Contents Document Release History ............................................................................................................... 2 Software Revision History ................................................................................................................ 2 Section 1: Common Functions ......................................................................................................... 5 1.1 Multiple Settings Groups ...................................................................................................... 5 1.2 Binary Inputs ........................................................................................................................ 6 1.3 Binary Outputs ..................................................................................................................... 9 1.4 LEDs .................................................................................................................................... 9 Section 2: Protection Functions..................................................................................................... 11 2.1 Time delayed overcurrent (51/51G/51N) ............................................................................. 11 2.1.1 Selection of Overcurrent Characteristics................................................................. 12 2.1.2 Reset Delay ........................................................................................................... 13 2.2 Voltage dependent overcurrent (51V) ................................................................................. 14 2.3 Cold Load Settings (51c) .................................................................................................... 14 2.4 Arc Flash Detection (50AFD) .............................................................................................. 15 2.5 Instantaneous Overcurrent (50/50G/50N) ........................................................................... 16 2.5.1 Blocked Overcurrent Protection Schemes .............................................................. 16 2.6 Sensitive Earth-fault Protection (50SEF)............................................................................. 18 2.7 Directional Protection (67) .................................................................................................. 19 2.8 Directional Earth-Fault (50/51G, 50/51N, 51/51SEF)........................................................... 22 2.9 High Impedance Restricted Earth Fault Protection (64H) .................................................... 23 2.10 Negative Phase Sequence Overcurrent (46NPS)................................................................ 25 2.11 Undercurrent (37) ............................................................................................................... 25 2.12 Thermal Overload (49) ....................................................................................................... 25 2.13 Under/Over Voltage Protection (27/59) ............................................................................... 26 2.14 Neutral Overvoltage (59N).................................................................................................. 27 2.14.1 Application with Capacitor Cone Units .................................................................... 28 2.14.2 Derived NVD Voltage ............................................................................................. 28 2.15 Negative Phase Sequence Overvoltage (47) ...................................................................... 28 2.16 Under/Over Frequency (81) ................................................................................................ 29 2.17 Power Protection ................................................................................................................ 30 2.17.1 Power (32) ............................................................................................................. 30 Section 3: CT Requirements........................................................................................................... 31 3.1 CT Requirements for Overcurrent and Earth Fault Protection ............................................. 31 3.1.1 Overcurrent Protection CTs.................................................................................... 31 3.1.2 Earth Fault Protection CTs ..................................................................................... 31 3.2 CT Requirements for High Impedance Restricted Earth Fault Protection............................. 31 Section 4: Control Functions.......................................................................................................... 32 4.1 Auto-reclose Applications ................................................................................................... 32 4.1.1 Auto-Reclose Example 1........................................................................................ 33 4.1.2 Auto-Reclose Example 2 (Use of Quicklogic with AR) ............................................ 34 4.2 Quick Logic Applications .................................................................................................... 35 4.2.1 Auto-Changeover Scheme Example ...................................................................... 35 Section 5: Supervision Functions .................................................................................................. 36 5.1 Circuit-Breaker Fail (50BF) ................................................................................................. 36 5.1.1 Settings Guidelines ................................................................................................ 36 5.2 Current Transformer Supervision (60CTS).......................................................................... 38 5.3 Voltage Transformer Supervision (60VTS).......................................................................... 39 5.4 Trip-Circuit Supervision (74TCS) ........................................................................................ 40 5.4.1 Trip Circuit Supervision Connections...................................................................... 40 (c) 2013 Siemens Protection Devices Limited Page 3 of 48 7SR210 & 7SR220 Applications Guide 5.5 Inrush Detector (81HBL2)................................................................................................... 42 5.6 Broken Conductor / Load Imbalance (46BC)....................................................................... 42 5.7 Circuit-Breaker Maintenance .............................................................................................. 42 5.8 Overfluxing Detector (81HBL5) ........................................................................................... 42 5.9 Load Blinder (21)................................................................................................................ 43 5.10 Load Blinder Design ........................................................................................................... 44 5.10.1 Application view ..................................................................................................... 44 5.10.2 Design View........................................................................................................... 45 5.10.3 Setting Example - 3 Pole Load Blinder .................................................................. 47 5.10.4 Calculating the Impedance ..................................................................................... 48 List of Figures Figure 1.1-1 Example Use of Alternative Settings Groups.................................................................... 5 Figure 1.2-1 Example of Transformer Alarm and Trip Wiring................................................................ 6 Figure 1.2-2 Binary Input Configurations Providing Compliance with EATS 48-4 Classes ESI 1 and ESI 2............................................................................................................... 8 Figure 1.4-1 LED configuration via the LED Matrix tab........................................................................ 9 Figure 1.4-2 LED configuration via the Settings \ OUTPUT CONFIG \ LED CONFIG menu................ 10 Figure 2.1-1 IEC NI Curve with Time Multiplier and Follower DTL Applied ......................................... 11 Figure 2.1-2 IEC NI Curve with Minimum Operate Time Setting Applied ............................................ 12 Figure 2.1-3 Reset Delay .................................................................................................................. 13 Figure 2.4-1 Arc Flash Detection ....................................................................................................... 15 Figure 2.5-1 General Form of DTL Operate Characteristic ................................................................. 16 Figure 2.5-2 Blocking Scheme Using Instantaneous Overcurrent Elements ....................................... 17 Figure 2.6-1 Sensitive Earth Fault Protection Application................................................................... 18 Figure 2.7-1 Directional Characteristics ............................................................................................. 19 Figure 2.7-2 Phase Fault Angles ....................................................................................................... 19 Figure 2.7-3 Application of Directional Overcurrent Protection ........................................................... 20 Figure 2.7-4 Feeder Fault on Interconnected Network ....................................................................... 21 Figure 2.8-1 Earth Fault Angles......................................................................................................... 22 Figure 2.9-1 Balanced and Restricted Earth-fault protection of Transformers ..................................... 23 Figure 2.9-2 Composite Overcurrent and Restricted Earth-fault Protection ........................................ 24 Figure 2.12-1 Thermal Overload Heating and Cooling Characteristic........................................... 25 Figure 2.14-1 NVD Application.................................................................................................... 27 Figure 2.14-2 NVD Protection Connections................................................................................. 27 Figure 2.16-1 Load Shedding Scheme Using Under-Frequency Elements................................... 29 Figure 4.1-1 Sequence Co-ordination ................................................................................................ 32 Figure 4.1-2 Example of Logic Application......................................................................................... 34 Figure 4.2-1 Example Use of Quick Logic.......................................................................................... 35 Figure 5.1-1 Circuit Breaker Fail ........................................................................................................ 36 Figure 5.1-2 Single Stage Circuit Breaker Fail Timing ........................................................................ 37 Figure 5.1-3 Two Stage Circuit Breaker Fail Timing ........................................................................... 37 Figure 5.4-1 Trip Circuit Supervision Scheme 1 (H5) ......................................................................... 40 Figure 5.4-2 Trip Circuit Supervision Scheme 2 (H6) ......................................................................... 41 Figure 5.4-3 Trip Circuit Supervision Scheme 3 (H7) ......................................................................... 41 Figure 5.9-1 Paralleled Transformers and Feeders ............................................................................ 43 Figure 5.10.1-1 Impedance Setting and Angle Setting .................................................................... 44 Figure 5.10.2.1-1 Logic Diagram 3 Phase....................................................................................... 45 Figure 5.10.2.2-1 Logic Diagram 1 Phase....................................................................................... 46 Figure 5.10.3-1 Scheme and Impedance Illustration ....................................................................... 47 List of Tables Table 2-1 Table 5-2 Table 5-3 Table 5-4 Table 5-5 Page 4 of 48 Application of IDMTL Characteristics Determination of CT Failure (1 or 2 Phases) Determination of VT Failure (1 or 2 Phases) Determination of VT Failure (3 Phases) Magnetic Inrush Bias 13 37 38 38 41 (c) 2013 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide Section 1: Common Functions 1.1 Multiple Settings Groups Alternate settings groups can be used to reconfigure the relay during significant changes to system conditions e.g. Primary plant switching in/out. Summer/winter or day/night settings. switchable earthing connections. Loss of Grid connection (see below) Start generators Trip non-essential loads Local Generation Industrial system draws power from grid system during normal operation Select alternate settings group Relays normally use settings group 1 On loss of mains: Local generation switched in. Non essential loads tripped Relays on essential circuits switched to settings group 2 to reflect new load and fault currents RADIAL SUBSTATION Non-essential loads Figure 1.1-1 Example Use of Alternative Settings Groups (c) 2013 Siemens Protection Devices Limited Page 5 of 48 7SR210 & 7SR220 Applications Guide 1.2 Binary Inputs Each Binary Input (BI) can be programmed to operate one or more of the relay functions, LEDs or output relays. These could be used to bring such digital signals as Inhibits for protection elements, the trip circuit supervision status, autoreclose control signals etc. into the Relay. Alarm and Tripping Inputs A common use of binary inputs is to provide indication of alarm or fault conditions e.g. transformer Buchholz Gas or Buchholz Surge conditions. The Binary Inputs are mapped to LED(s), waveform storage trigger and binary outputs. Note that transformer outputs which require high speed tripping, such as a Buchholz Surge, should be wired to a binary input to provide LED indication and also have a parallel connection wired to directly trip the circuit via a blocking diode, see fig. 1.2-1: Figure 1.2-1 Example of Transformer Alarm and Trip Wiring Page 6 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide The Effects of Capacitance Current The binary inputs have a low minimum operate current and may be set for instantaneous operation. Consideration should be given to the likelihood of mal-operation due to capacitance current. Capacitance current can flow through the BI for example if an earth fault occurs on the dc circuits associated with the relay. The binary inputs will be less likely to mal-operate if they: 1 Have both the positive and negative switched (double-pole switched). 2 Do not have extensive external wiring associated with them e.g. if the wiring is confined to the relay room. Where a binary input is both used to influence a control function (e.g. provide a tripping function) and it is considered to be susceptible to mal-operation the external circuitry can be modified to provide immunity to such disturbances, see fig 1.2-2. AC Rejection The default pick-up time delay of 20 ms provides immunity to ac current e.g. induced from cross site wiring. (c) 2013 Siemens Protection Devices Limited Page 7 of 48 7SR210 & 7SR220 Applications Guide ESI-1 + 470 30 V DC Nominal (24 V to 37.5 V Operative) IOP > 10 mA ESI-2 + 220 30 V DC Nominal (24 V to 37.5 V Operative) IOP > 20 mA BI (19 V) 1K5 BI (19 V) 820 - + 1K6 - 48 V DC Nominal (37.5 V to 60 V Operative) IOP > 10 mA + 820 48 V DC Nominal (37.5 V to 60 V Operative) IOP > 20 mA BI (19 V) BI (19 V) 820 1K5 - - BI DTL = 10 ms (10 F, 60 V Capacitance discharge) + 2K0 + 110 V DC Nominal (87.5 V to 137.5 V Operative) IOP > 25 mA 1K2 110 V DC Nominal (87.5 V to 137.5 V Operative) IOP > 50 mA BI (19 V) 560 BI (19 V) 330 - - BI DTL = 10 ms (10 F, 150 V Capacitance discharge) + 110 V DC Nominal (87.5 V to 137.5 V Operative) IOP > 25 mA + 110 V DC Nominal (87.5 V to 137.5 V Operative) IOP > 50 mA BI (88 V) BI (88 V) 1K3 2K7 - - BI DTL = 10 ms (10 F, 150 V Capacitance discharge) Resistor power ratings: 30 V DC Nominal >3 W 48 V DC Nominal >3 W 110 V DC Nominal >10 W (ESI-1) 110 V DC Nominal >20 W (ESI-2) Resistors must be wired with crimped connections as they may run hot Figure 1.2-2 Binary Input Configurations Providing Compliance with EATS 48-4 Classes ESI 1 and ESI 2 Page 8 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 1.3 Binary Outputs Binary Outputs are mapped to output functions by means of settings. These could be used to bring out such digital signals as trips, a general pick-up, plant control signals etc. All Binary Outputs are Trip rated Each can be defined as Self or Hand Reset. Self-reset contacts are applicable to most protection applications. Hand-reset contacts are used where the output must remain active until the user expressly clears it e.g. in a control scheme where the output must remain active until some external feature has correctly processed it. Case contacts 26 and 27 will automatically short-circuit when the relay is withdrawn from the case. This can be used to provide an alarm that the Relay is out of service. Notes on Self Reset Outputs With a failed breaker condition the relay may remain operated until current flow in the primary system is interrupted by an upstream device. The relay will then reset and attempt to interrupt trip coil current flowing through an output contact. Where this level is above the break rating of the output contact an auxiliary relay with heavy-duty contacts should be utilised. 1.4 LEDs Output-function LEDs are mapped to output functions by means of settings. These could be used to display such digital signals as trips, a general pick-up, plant control signals etc. User Defined Function Key LEDs are used to indicate the status of Function Key operation. These do not relate directly to the operation of the Function Key but rather to its consequences. If a Function Key is depressed to close a Circuit-Breaker, the associated LED would show the status of the Circuit-Breaker closed Binary Input. Each LED can be defined as Self or Hand Reset. Hand reset LEDs are used where the user is required to expressly acknowledge the change in status e.g. critical operations such as trips or system failures. Self-reset LEDs are used to display features which routinely change state, such as Circuit-Breaker open or close. The status of hand reset LEDs is retained in capacitor-backed memory in the event of supply loss. Each LED can be assigned as red, yellow or green in colour. There are two methods for doing this: 1) In the LED Matrix tab, to assign the LED as a red colour select a box on the red row. To assign the LED as a green colour select a box on the green row. To assign the LED as a yellow colour, select boxes on both the red and green rows. NB: If there are no boxes selected the LED will not illuminate. Figure 1.4-1 LED configuration via the LED Matrix tab (c) 2013 Siemens Protection Devices Limited Page 9 of 48 7SR210 & 7SR220 Applications Guide In the OUTPUT CONFIG\LED CONFIG menu in the Settings tab, to assign the required LED as a particular colour, either red or green, type the LED number in the appropriate row. To assign the required LED as a yellow colour, type the LED number in both red and green rows. NB: If a LED number is not assigned that particular LED will not illuminate. Figure 1.4-2 LED configuration via the Settings \ OUTPUT CONFIG \ LED CONFIG menu Page 10 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide Section 2: Protection Functions 2.1 Time delayed overcurrent (51/51G/51N) The 51-n characteristic element provides a number of time/current operate characteristics. The element can be defined as either an Inverse Definite Minimum Time Lag (IDMTL) or Definite Time Lag (DTL) characteristic. If an IDMTL characteristic is required, then IEC, ANSI/IEEE and a number of manufacturer specific curves are supported. IDMTL characteristics are defined as "Inverse" because their tripping times are inversely proportional to the Fault Current being measured. This makes them particularly suitable to grading studies where it is important that only the Relay(s) closest to the fault operate. Discrimination can be achieved with minimised operating times. To optimise the grading capability of the relay additional time multiplier, `Follower DTL' (Fig. 2.1-1) or `Minimum Operate Time' (Fig. 2.1-2) settings can be applied. 1000.00 1000.00 100.00 100.00 10.00 Operating Time (Seconds) Operating Time (Seconds ) 10.00 1.00 1.00 0.10 0.10 0.01 0.01 1 10 100 Current (x Is) 1000 1 10 100 1000 Current (x Is) Figure 2.1-1 IEC NI Curve with Time Multiplier and Follower DTL Applied (c) 2013 Siemens Protection Devices Limited Page 11 of 48 7SR210 & 7SR220 Applications Guide 1000.00 OPERATE ZONE 100.00 Operating Time (Seconds) 10.00 Min Operate Time = 4sec IEC NI Curve: TM = 1 1.00 0.10 0.01 1 10 100 1000 Current (x Is) Figure 2.1-2 IEC NI Curve with Minimum Operate Time Setting Applied To increase sensitivity, dedicated Earth fault elements are used. There should be little or no current flowing to earth in a healthy system so such relays can be given far lower pick-up levels than relays which detect excess current ( > load current) in each phase conductor. Such dedicated earth fault relays are important where the fault path to earth is a high-resistance one (such as in highly arid areas) or where the system uses high values of earthing resistor / reactance and the fault current detected in the phase conductors will be limited. 2.1.1 Selection of Overcurrent Characteristics Each pole has two independent over-current characteristics. Where required the two curves can be used: To produce a composite curve To provide a two stage tripping scheme Where one curve is to be directionalised in the forward direction the other in the reverse direction. The characteristic curve shape is selected to be the same type as the other relays on the same circuit or to grade with items of plant e.g. fuses or earthing resistors. The application of IDMTL characteristic is summarised in the following table: Page 12 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide OC/EF Curve Characteristic IEC Normal Inverse (NI) Application Generally applied ANSI Moderately Inverse (MI) IEC Very Inverse (VI) Used with high impedance paths where there is a significant difference between fault levels at protection points ANSI Very Inverse (VI) IEC Extreme Inversely (EI) Grading with Fuses ANSI Extremely Inverse (EI) IEC Long Time Inverse (LTI) Used to protect transformer earthing resistors having long withstand times Recloser Specific Use when grading with specific recloser Table 2-1 2.1.2 Application of IDMTL Characteristics Reset Delay The increasing use of plastic insulated cables, both conventionally buried and aerial bundled conductors, have given rise to the number of flashing intermittent faults on distribution systems. At the fault position, the plastic melts and temporarily reseals the faulty cable for a short time after which the insulation fails again. The same phenomenon has occurred in compound-filled joint boxes or on `clashing' overhead line conductors. The repeating process of the fault can cause electromechanical disc relays to "ratchet" up and eventually trip the faulty circuit if the reset time of the relay is longer than the time between successive faults. To mimic an electromechanical relay the relay can be user programmed for an ANSI DECAYING characteristic when an ANSI operate characteristic is applied. Alternatively a DTL reset (0 to 60 seconds) can be used with other operate characteristics. For protection of cable feeders, it is recommended that a 60 second DTL reset be used. On overhead line networks, particularly where reclosers are incorporated in the protected system, instantaneous resetting is desirable to ensure that, on multiple shot reclosing schemes, correct grading between the source relays and the relays associated with the reclosers is maintained. R3 R2 R1 FAULT Clashing conductors or re-sealing cable Electro-mechanical Relay Argus (Inst. Reset) TRIP Argus (DTL Reset) TRIP Time Time Figure 2.1-3 Reset Delay (c) 2013 Siemens Protection Devices Limited Page 13 of 48 7SR210 & 7SR220 Applications Guide 2.2 Voltage dependent overcurrent (51V) Reduced voltage can indicate a fault on the system, it can be used to make the 51 elements more sensitive. Typically Voltage Dependent Over-current (51V) is applied to: Transformer Incomers: Where the impedance of the transformer limits fault current the measured voltage level can be used to discriminate between load and fault current. Long lines: Where the impedance of the line limits fault current the measured voltage level can be used to discriminate between load and fault current. Generator circuits: When a Generator is subjected to a short circuit close to its terminals the shortcircuit current follows a complex profile. After the initial "sub-transient" value, generally in the order of 7 to 10 times full load current, it falls rapidly (around 10 ms to 20 ms) to the "transient" value. This is still about 5 to 7 times full load and would be sufficient to operate the protection's over-current elements. However the effect on armature reactance of the highly inductive short-circuit current is to increase significantly the internal impedance to the synchronous reactance value. If the Automatic Voltage Regulation (AVR) system does not respond to increase the excitation, the fault current will decay over the next few seconds to a value below the full load current. This is termed the steady state fault current, determined by the Generator's synchronous reactance (and pre-fault excitation). It will be insufficient to operate the protection's over-current elements and the fault will not be detected. Even if AVR is active, problems may still be encountered. The AVR will have a declared minimum sustained fault current and this must be above the protection over-current settings. Close-in short circuit faults may also cause the AVR to reach its safety limits for supplying maximum excitation boost, in the order of several seconds, and this will result in AVR internal protection devices such as diode fuses to start operating. The generator excitation will then collapse, and the situation will be the same as when no AVR was present. The fault may again not be detected. Current grading remains important since a significant voltage reduction may be seen for faults on other parts of the system. An inverse time operating characteristic must therefore be used. The VDO Level - the voltage setting below which the more sensitive operating curve applies - must be set low enough to discriminate between short-circuits and temporary voltage dips due to overloads. However, it must also be high enough to cover a range of voltage drops for different circuit configurations, from around 0.6Vn to almost zero. Typically it will be set in the range 0.6 to 0.8Vn. 2.3 Cold Load Settings (51c) Once a Circuit-Breaker has been open for a period of time ed, higher than normal levels of load current may flow following CB re-closure e.g. heating or refrigeration plant. The size and duration of this current is dependent upon the type of load and the time that the CB is open. The feature allows the relay to use alternative Shaped Overcurrent (51c) settings when a Cold Load condition is identified. The cold load current and time multiplier settings will normally be set higher than those of the normal overcurrent settings. The relay will revert to its usual settings (51-n) after elapse of the cold load period. This is determined either by a user set delay, or by the current in all 3-phases falling below a set level (usually related to normal load levels) for a user set period. Page 14 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 2.4 Arc Flash Detection (50AFD) The overcurrent setting should be set above maximum load current and below the minimum expected arc fault current. Optical sensor location should be arranged to provide full coverage of the protected chambers. See 7XG31 technical documentation. Sensor inputs are configured in Zones to provide the required tripping. i.e. the line circuit breaker alone should be tripped for arc faults in the cable termination and CT compartment. The whole busbar must be cleared for arc faults which cannot be identified as being on the line side of the circuit breaker. Overcurrent supervision can only be applied if the arrangement ensures that current will be measured for all arc faults. In Figure , Zone 2 can only be supervised by current if the feeders are radial and cannot supply fault current with CB A open. Arc sensor pickup can be transferred between relays using IEC 61850 GOOSE allowing Zone2 50AFD to be duplicated in all relays. A Zone1 Zone2 Figure 2.4-1 Arc Flash Detection (c) 2013 Siemens Protection Devices Limited Page 15 of 48 7SR210 & 7SR220 Applications Guide 2.5 Instantaneous Overcurrent (50/50G/50N) Operating time Each instantaneous element has an independent setting for pick-up current and a follower definite time lag (DTL) which can be used to provide time grading margins, sequence co-ordination grading or scheme logic. The "instantaneous" description relates to the pick-up of the element rather than its operation. Figure 2.5-1 General Form of DTL Operate Characteristic Instantaneous elements can be used in current graded schemes where there is a significant difference between the fault current levels at different relay point. The Instantaneous element is set to pick up at a current level above the maximum Fault Current level at the next downstream relay location, and below its own fault current level. The protection is set to operate instantaneously and is often termed `Highset Overcurrent'. A typical application is the protection of transformer HV connections - the impedance of the transformer ensuring that the LV side has a much lower level of fault current. The 50-n elements have a very low transient overreach i.e. their accuracy is not appreciably affected by the initial dc offset transient associated with fault inception. 2.5.1 Blocked Overcurrent Protection Schemes A combination of instantaneous and DTL elements can be used in blocked overcurrent protection schemes. These protection schemes are applied to protect substation busbars or interconnectors etc. Blocked overcurrent protection provides improved fault clearance times when compared against normally graded overcurrent relays. The blocked overcurrent scheme of busbar protection shown in Figure 2.4-2 illustrates that circuit overcurrent and earth fault protection relays can additionally be configured with busbar protection logic. The diagram shows a substation. The relay on the incomer is to trip for busbar faults (F1) but remain inoperative for circuit faults (F2). In this example the overcurrent and earth fault settings for the incomer 50-1 element are set to below the relevant busbar fault levels. 50-1 time delay is set longer than it would take to acknowledge receipt of a blocking signal from an outgoing circuit. Close up faults on the outgoing circuits will have a similar fault level to busbar faults. As the incomer 50-1 elements would operate for these faults it is necessary to provide a blocking output from the circuit protections. The 50-1 elements of the output relays are given lower current settings than the incomer 50-1 settings, the time delay is set to 0ms. The output is mapped to a contact. The outgoing relay blocking contacts of all circuits are wired in parallel and this wiring is also connected to a BI on the incomer relay. The BI on the incomer relay is mapped to block its 50-1 element. Page 16 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide Figure 2.5-2 Blocking Scheme Using Instantaneous Overcurrent Elements Typically a time delay as low as 50 ms on the incomer 50-1 element will ensure that the incomer is not tripped for outgoing circuit faults. However, to include for both equipment tolerances and a safety margin a minimum time delay of 100 ms is recommended. This type of scheme is very cost effective and provides a compromise between back-up overcurrent busbar protection and dedicated schemes of busbar protection. Instantaneous elements are also commonly applied to autoreclose schemes to grade with downstream circuit reclosers and maximise the probability of a successful auto-reclose sequence - see section 4. (c) 2013 Siemens Protection Devices Limited Page 17 of 48 7SR210 & 7SR220 Applications Guide 2.6 Sensitive Earth-fault Protection (50SEF) Earth fault protection is based on the assumption that fault current levels will be limited only by the earth fault impedance of the line and associated plant. However, it may be difficult to make an effective short circuit to earth due to the nature of the terrain e.g. dry earth, desert or mountains. The resulting earth fault current may therefore be limited to very low levels. Sensitive earth fault (SEF) protection is used to detect such faults. The RM range of relays have a low burden, so avoiding unacceptable loading of the CTs at low current settings. SEF provides a backup to the main protection. A DTL characteristic with a time delay of several seconds is typically applied ensuring no interference with other discriminative protections. A relatively long time delay can be tolerated since fault current is low and it is impractical to grade SEF protection with other earth fault protections. Although not suitable for grading with other forms of protection SEF relays may be graded with each other. Where very sensitive current settings are required then it is preferable to use a core balance CT rather than wire into the residual connection of the line CTs. The turns ratio of a core balance CT can be much smaller than that of phase conductors as they are not related to the rated current of the protected circuit. Since only one core is used, the CT magnetising current losses are also reduced by a factor of 3. Figure 2.6-1 Sensitive Earth Fault Protection Application There are limits to how sensitive an SEF relay may be set since the setting must be above any line charging current levels that can be detected by the relay. On occurrence of an out of zone earth fault e.g. on circuit 3 the elevation of sound phase voltage to earth in a non-effectively earthed system can result in a zero sequence current of up 3 times phase charging current flowing through the relay location. The step change from balanced 3-phase charging currents to this level of zero sequence current includes transients. It is recommended to allow for a transient factor of 2 to 3 when determining the limit of charging current. Based on the above considerations the minimum setting of a relay in a resistance earthed power system is 6 to 9 times the charging current per phase. Page 18 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 2.7 Directional Protection (67) Each overcurrent stage can operate for faults in either forward or reverse direction. Convention dictates that forward direction refers to power flow away from the busbar, while reverse direction refers to power flowing towards the busbar. The directional phase fault elements, 67/50 and 67/51, work with a Quadrature Connection to prevent loss of polarising quantity for close-in phase faults. That is, each of the current elements is directionalised by a voltage derived from the other two phases. This connection introduces a 90 Phase Shift (Current leading Voltage) between reference and operate quantities which must be allowed for in the Characteristic Angle setting. This is the expected fault angle, sometimes termed the Maximum Torque Angle (MTA) as an analogy to older Electro-mechanical type relays Example: Expected fault angle is -30 (Current lagging Voltage) so set Directional Angle to: +90 -30 = +60. A fault is determined to be in the selected direction if its phase relationship lies within a quadrant +/- 85 either side of the Characteristic Angle setting. Figure 2.7-1 Directional Characteristics A number of studies have been made to determine the optimum MTA settings e.g. W.K Sonnemann's paper "A Study of Directional Element Connections for Phase Relays". Figure 2.6-2 shows the most likely fault angle for phase faults on Overhead Line and Cable circuits. Figure 2.7-2 Phase Fault Angles (c) 2013 Siemens Protection Devices Limited Page 19 of 48 7SR210 & 7SR220 Applications Guide Directional overcurrent elements allow greater fault selectivity than non-directional elements for interconnected systems where fault current can flow in both directions through the relaying point. Consider the network shown in fig. 2.6-3. The Circuit breakers at A, B, E and G have directional overcurrent relays fitted since fault current can flow in both directions at these points. The forward direction is defined as being away from the busbar and against the direction of normal load current flow. These forward looking IDMTL elements can have sensitive settings applied i.e. low current and time multiplier settings. Note that 7SR22 relays may be programmed with forward, reverse and non-directional elements simultaneously when required by the protection scheme. Figure 2.7-3 Application of Directional Overcurrent Protection Page 20 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide Figure 2.7-4 Feeder Fault on Interconnected Network Considering the D-G feeder fault shown in fig. 2.6-4: the current magnitude through breakers C and D will be similar and their associated relays will similar prospective operate times. To ensure that only the faulted feeder is isolated G FWD must be set to be faster than C. Relay G will thus Trip first on FWD settings, leaving D to operate to clear the fault. The un-faulted Feeder C-E maintains power to the load. Relays on circuits C and D at the main substation need not be directional to provide the above protection scheme. However additional directional elements could be mapped to facilitate a blocked overcurrent scheme of busbar protection. At A and B, forward looking directional elements enable sensitive settings to be applied to detect transformer faults whilst reverse elements can be used to provide back-up protection for the relays at C and D. By using different settings for forward and reverse directions, closed ring circuits can be set to grade correctly whether fault current flows in a clockwise or counter clockwise direction i.e. it may be practical to use only one relay to provide dual directional protection. 2 Out of 3 Logic Sensitive settings can be used with directional overcurrent relays since they are directionalised in a way which opposes the flow of normal load current i.e. on the substation incomers as shown on fig. 2.6-4. However on occurrence of transformer HV or feeder incomer phase-phase faults an unbalanced load current may still flow as an un balanced driving voltage is present. This unbalanced load current during a fault may be significant where sensitive overcurrent settings are applied - the load current in one phase may be in the operate direction and above the relay setting. Where this current distribution may occur then the relay is set to CURRENT PROTECTION>PHASE OVERCURRENT> 67 2-out-of-3 Logic = ENABLED Enabling 2-out-of-3 logic will prevent operation of the directional phase fault protection for a single phase to earth fault. Dedicated earth-fault protection should therefore be used if required. (c) 2013 Siemens Protection Devices Limited Page 21 of 48 7SR210 & 7SR220 Applications Guide 2.8 Directional Earth-Fault (50/51G, 50/51N, 51/51SEF) The directional earth-fault elements, either measure directly or derive from the three line currents the zero sequence current (operate quantity) and compare this against the derived zero phase sequence voltage (polarising quantity). The Technical Manual `Description of Operation' details the method of measurement. The required setting is entered directly as dictated by the system impedances. Example: Expected fault angle is -45 (i.e. residual current lagging residual voltage) therefore 67G Char Angle = -45 However directional earth elements can be selectable to use either ZPS or NPS Polarising. This is to allow for the situation where ZPS voltage is not available; perhaps because a 3-limb VT is being used. Care must be taken as the Characteristic Angle will change if NPS Polarising is used. Once again the fault angle is completely predictable, though this is a little more complicated as the method of earthing must be considered. Figure 2.8-1 Earth Fault Angles Page 22 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 2.9 High Impedance Restricted Earth Fault Protection (64H) Restricted Earth Fault (REF) protection is applied to Transformers to detect low level earth faults in the transformer windings. Current transformers are located on all connections to the transformer. During normal operation or external fault conditions no current will flow in the relay element. When an internal earth fault occurs, the currents in the CTs will not balance and the resulting unbalance flows through the relay. The current transformers may saturate when carrying high levels of fault current. The high impedance name is derived from the fact that a resistor is added to the relay leg to prevent relay operation due to CT saturation under through fault conditions. The REF Trip output is configured to provide an instantaneous trip output from the relay to minimise damage from developing winding faults. The application of the element to a Argus RM-Star transformer is shown in Figure 2.8-1. Although the connection on the Argus RM winding is more correctly termed a Balanced Earth-Fault element, it is still usually referred to as Restricted Earth Fault because of the presence of the transformer. Balanced Earth Fault Restricted Earth Fault Figure 2.9-1 Balanced and Restricted Earth-fault protection of Transformers The calculation of the value of the Stability Resistor is based on the worst case where one CT fully saturates and the other balancing CT does not saturate at all. A separate Siemens Protection Devices Limited Publication is available covering the calculation procedure for REF protection. To summarise this: The relay Stability (operating) Vs voltage is calculated using worst case lead burden to avoid relay operation for through-fault conditions where one of the CTs may be fully saturated. The required fault setting (primary operate current) of the protection is chosen; typically, this is between 10 % and 25 % of the protected winding rated current. The relay setting current is calculated based on the secondary value of the operate current, note, however, that the summated CT magnetising current @ Vs must be subtracted to obtain the required relay operate current setting. Since the relay operate current setting and stability/operating voltage are now known, a value for the series resistance can now be calculated. A check is made as to whether a Non-Linear Resistor is required to limit scheme voltage during internal fault conditions - typically where the calculated voltage is in excess of 2 kV. The required thermal ratings for external circuit components are calculated. (c) 2013 Siemens Protection Devices Limited Page 23 of 48 7SR210 & 7SR220 Applications Guide Composite overcurrent and REF protection can be provided using a multi-element relay as. overcurrent elements series stabilising resistor 25 REF element non-linear resistor Figure 2.9-2 Composite Overcurrent and Restricted Earth-fault Protection Although core-balance CTs are traditionally used with elements requiring sensitive pickup settings, cost and size usually precludes this on REF schemes. Instead single-Phase CTs are used and their secondary's connected in parallel. Where sensitive settings are required, the setting must be above any line charging current levels that can be detected by the relay. On occurrence of an out of zone earth fault the elevation of sound phase voltage to earth in a non-effectively earthed system can result in a zero sequence current of up 3 times phase charging current flowing through the relay location. The step change from balanced 3-phase charging currents to this level of zero sequence current includes transients. It is recommended to allow for a transient factor of 2 to 3 when determining the limit of charging current. Based on the above considerations the minimum setting of a relay in a resistance earthed power system is 6 to 9 times the charging current per phase. High impedance differential protection is suitable for application to auto transformers as line currents are in phase and the secondary current through the relay is balanced to zero by the use of CTs ratios at all three terminals. High impedance protection of this type is very sensitive and fast operating for internal faults. Page 24 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 2.10 Negative Phase Sequence Overcurrent (46NPS) The presence of Negative Phase Sequence (NPS) current indicates an unbalance in the phase currents, either due to a fault or unbalanced load. NPS current presents a major problem for 3-phase rotating plant. It produces a reaction magnetic field which rotates in the opposite direction, and at twice the frequency, to the main field created by the DC excitation system. This induces double-frequency currents into the rotor which cause very large eddy currents in the rotor body. The resulting heating of the rotor can be severe and is proportional to (I2)2 t. Generators and Motors are designed, manufactured and tested to be capable of withstanding unbalanced current for specified limits. Their withstand is specified in two parts; continuous capability based on a figure of I2, and short time capability based on a constant, K, where K = (I2)2 t. NPS overcurrent protection is therefore configured to match these two plant characteristics. 2.11 Undercurrent (37) Undercurrent elements are used in control logic schemes such as Auto-Changeover Schemes, Auto-Switching Interlock and Loss of Load. They are used to indicate that current has ceased to flow or that a low load situation exists. For this reason simple Definite Time Lag (DTL) elements may be used. For example, once it has been determined that fault current has been broken - the CB is open and no current flows - an auto-isolation sequence may safely be initiated. 2.12 Thermal Overload (49) The element uses measured 3-phase current to estimate the real-time Thermal State, , of cables or transformers. The Thermal State is based on both past and present current levels. = 0% for unheated equipment, and = 100% for maximum thermal withstand of equipment or the Trip threshold. Figure 2.12-1 Thermal Overload Heating and Cooling Characteristic For given current level, the Thermal State will ramp up over time until Thermal Equilibrium is reached when Heating Effects of Current = Thermal Losses. The heating / cooling curve is primarily dependent upon the Thermal Time Constant. This must be matched against that quoted for the item of plant being protected. Similarly the current tripping threshold, Iq is related to the thermal withstand of the plant. Thermal Overload is a slow acting protection, detecting faults or system conditions too small to pick-up fast acting protections such as Phase Overcurrent. An Alarm is provided for at or above a set % of capacity to indicate that a potential trip condition exists and that the system should be scrutinised for abnormalities. (c) 2013 Siemens Protection Devices Limited Page 25 of 48 7SR210 & 7SR220 Applications Guide 2.13 Under/Over Voltage Protection (27/59) Power system under-voltages on may occur due to: System faults. An increase in system loading, Non-energized power system e.g. loss of an incoming transformer During normal system operating conditions regulating equipment such as transformer On Load Tap Changers (OLTC) and generator Automatic Voltage Regulators (AVR) ensure that the system runs within acceptable voltage limits. 7SR24 undervoltage/DTL elements can be used to detect abnormal undervoltage conditions due to system overloads. Binary outputs can be used to trip non-essential loads - returning the system back to its normal operating levels. This `load shedding' should be initiated via time delay elements so avoiding operation during transient disturbances. An under voltage scheme (or a combined under frequency/under voltage scheme) can provide faster tripping of non-essential loads than under-frequency load shedding so minimising the possibility of system instability. Where a transformer is supplying 3-phase motors a significant voltage drop e.g. to below 80% may cause the motors to stall. An undervoltage element can be set to trip motor circuits when the voltage falls below a preset value so that on restoration of supply an overload is not caused by the simultaneous starting of all the motors. A time delay is required to ensure voltage dips due to remote system faults do not result in an unnecessary disconnection of motors. To confirm presence/loss of supply, the voltage elements should be set to values safely above/below that where a normal system voltage excursion can be expected. The switchgear/plant design should be considered. The `Dead' level may be very near to the `live' level or may be significantly below it. The variable hysteresis setting allows the relay to be used with all types of switchgear. System over-voltages can damage component insulation. Excessive voltage may occur for: Sudden loss of load A tap changer run-away condition occurs in the high voltage direction, Generator AVR equipment malfunctions or Reactive compensation control malfunctions. System regulating equipment such as transformer tap changers and generator AVRs may correct the overvoltage - unless this equipment mal-functions. The overvoltage/DTL elements can be used to protect against damage caused by system overvoltages. If the overvoltage condition is small a relatively long DTL time delay can be used. If the overvoltage is more severe then another element, set at a higher pickup level and with a shorter DTL can be used to isolate the circuit more quickly. Alternatively, elements can be set to provide alarm and tripping stages, with the alarm levels set lower than the tripping stages. The use of DTL settings allows a grading system to be applied to co-ordinate the network design, the regulating plant design, system plant insulation withstand and with other overvoltage relays elsewhere on the system. The DTL also prevents operation during transient disturbances. The use of IDMTL protection is not recommended because of the difficulty of choosing settings to ensure correct co-ordination and security of supply. Page 26 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 2.14 Neutral Overvoltage (59N) Neutral Overvoltage Displacement (Residual Overvoltage) protection is used to detect an earth fault where little or no earth current flows. This can occur where a feeder has been tripped at its HV side for an earth fault, but the circuit is still energised from the LV side via an unearthed transformer winding. Insufficient earth current would be present to cause a trip, but residual voltage would increase significantly; reaching up to 3-times the normal phase-earth voltage level. If Neutral Overvoltage protection is used, it must be suitably time graded with other protections in order to prevent unwanted tripping for external system earth faults. Figure 2.14-1 NVD Application Typically NVD protection measures the residual voltage (3V0) directly from an open delta VT or from capacitor cones - see fig. 2.13-2 below. Figure 2.14-2 (c) 2013 Siemens Protection Devices Limited NVD Protection Connections Page 27 of 48 7SR210 & 7SR220 Applications Guide 2.14.1 Application with Capacitor Cone Units Capacitor cones provide a cost effective method of deriving residual voltage. The wide range of capacitor cone component values used by different manufacturer's means that the relay cannot be connected directly to the cones. The external adaptor unit contains parallel switched capacitors that enable a wide range of values to be selected using a DIL switch and hence the Capacitor Cone output can be scaled to the standard relay input range. 2.14.2 Derived NVD Voltage Alternatively NVD voltage can be derived from the three phase to neutral voltages, this setting is available within the relay. Note with this method the NVD protection may mal-operate during a VT Fail condition. 2.15 Negative Phase Sequence Overvoltage (47) Negative Phase Sequence (NPS) protection detects phase unbalances and is widely used in protecting rotating plant such as motors and generators. However such protection is almost universally based on detecting NPS Current rather than Voltage. This is because the NPS impedance of motors etc. is much less than the Positive Phase Sequence (PPS) impedance and therefore the ratio of NPS to PPS Current is much higher than the equivalent ratio of NPS to PPS Voltage. NPS Voltage is instead used for monitoring busbar supply quality rather than detecting system faults. The presence of NPS Voltage is due to unbalanced load on a system. Any system voltage abnormality is important since it will affect every motor connected to the source of supply and can result in mass failures in an industrial plant. The two NPS Voltage DTL elements should therefore be used as Alarms to indicate that the level of NPS has reached abnormal levels. Remedial action can then be taken, such as introducing a Balancer network of capacitors and inductors. Very high levels of NPS Voltage indicate incorrect phase sequence due to an incorrect connection. Page 28 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 2.16 Under/Over Frequency (81) During normal system operation the frequency will continuously vary over a relatively small range due to the changing generation/load balance. Excessive frequency variation may occur for: Loss of generating capacity, or loss of mains supply (underfrequency): If the governors and other regulating equipment cannot respond to correct the balance, a sustained underfrequency condition may lead to a system collapse. Loss of load - excess generation (overfrequency): The generator speeds will increase causing a proportional frequency rise. This may be unacceptable to industrial loads, for example, where the running speeds of synchronous motors will be affected. In the situation where the system frequency is falling rapidly it is common practise to disconnect non-essential loads until the generation-load balance can be restored. Usually, automatic load shedding, based on underfrequency is implemented. Underfrequency relays are usually installed on the transformer incomers of distribution or industrial substations as this provides a convenient position from which to monitor the busbar frequency. Loads are disconnected from the busbar (shed) in stages until the frequency stabilises and returns to an acceptable level. The relay has six under/over frequency elements. An example scheme may have the first load shedding stage set just below the nominal frequency, e.g. between 49.0 Hz and 49.5 Hz. A time delay element would be associated with this to allow for transient dips in frequency and to provide a time for the system regulating equipment to respond. If the first load shedding stage disconnects sufficient plant the frequency will stabilise and perhaps return to nominal. If, however, this is not sufficient then a second load shedding stage, set at a lower frequency, will shed further loads until the overload is relieved. This process will continue until all stages have operated. In the event of the load shedding being unsuccessful, a final stage of underfrequency protection should be provided to totally isolate all loads before plant is damaged, e.g. due to overfluxing. An alternative type of load shedding scheme would be to set all underfrequency stages to about the same frequency setting but to have different length time delays set on each stage. If after the first stage is shed the frequency doesn't recover then subsequent stages will shed after longer time delays have elapsed. Network Incomer STAGE 1: Least important STAGE 2 STAGE 3 STAGE 4 Generator G59 300/5 STAGE 5 STAGE 6 5 1 2 6 5 3 4 2 4 Essential Load Figure 2.16-1 Load Shedding Scheme Using Under-Frequency Elements (c) 2013 Siemens Protection Devices Limited Page 29 of 48 7SR210 & 7SR220 Applications Guide 2.17 Power Protection 2.17.1 Power (32) Parallel Busbar Feeder If power is fed to a busbar through two parallel infeeds, then in the event of any fault on one of these infeeds it should be selectively interrupted. This ensures a continued supply to the busbar through the remaining the remaining infeed. For this purpose directional devises are needed which detect a shortcircuit current or a power flow from the busbar in the direction of the infeed. Reverse-power protection can be set far below the rated power. Motor Protection An under power element protects against a loss of load condition by measuring the real power flow. This feature provides an alternative to under current measurement as load loss may result in only a small change in current. The under power output is initiated by a voltage element operating after a definite time delay. The applied power setting will typically be 10-20% below minimum load, the power and time delay settings must take into account: Where rated power cannot be reached during starting (for example where the motor is started with no connected load) it may be necessary to inhibit this function for a set time. This feature requires a 52a circuit breaker auxiliary contact mapped to an opto input to get the information CB Closed/CB Open. Directional power measurement may operate on occurrence of a system power supply fail or system fault. Power flow into the motor will reverse since the motor will act as a generator due to the inertia of the connected load. General Calculation Real, apparent or reactive power is set in the relay as a multiple of the relay (or secondary) nominal power where: Nominal relay power (secondary) = relay nominal current x relay nominal voltage. CT ratio = 400:1 VT ratio = 33000:110 = = = = 3 x VL x IL 3 x 110 x 1 190.53 VA 1 xSn Example: Nominal secondary apparent power (S): Nominal 3-phase VA (secondary) When calculating the required operate value in primary quantities the CT and VT ratios must be considered i.e. where the above corresponds to a nominal primary 3-phase apparent power (S) of: Nominal 3-phase VA (primary) = = = = 3 x VL x IL 3 x 330000 x 400 22.863 MVA 1 xSn The primary nominal VA calculated above may not match that of the protected primary plant and so settings should be adjusted accordingly. Page 30 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide Section 3: CT Requirements 3.1 CT Requirements for Overcurrent and Earth Fault Protection 3.1.1 Overcurrent Protection CTs a) For industrial systems with relatively low fault current and no onerous grading requirements - a class 10P10 with VA rating to match the load. b) For utility distribution networks with relatively high fault current and several grading stages - a class 5P20, with VA rating to match the load. Note: If an accuracy limit factor is chosen which is much lower than the maximum fault current it will be necessary to consider any effect on the protection system performance and accuracy e.g. grading margins. For i.d.m.t.l. applications, because the operating time at high fault current is a definite minimum value, partial saturation of the CT at values beyond the overcurrent factor has only a minimal effect. However, this must be taken into account in establishing the appropriate setting to ensure proper grading. c) For dtl applications utilities as for (b) above - a class 5P10 (or 20), with rated burden to suit the load. Note: Overcurrent factors do not need to be high for definite time protection because once the setting is exceeded magnitude accuracy is not important. Often, however, there is also the need to consider instantaneous HighSet overcurrent protection as part of the same protection system and the settings would normally be of the order of 10x the CT rating or higher. Where higher settings are to be used then the overcurrent factor must be raised accordingly, e.g. to P20. 3.1.2 Earth Fault Protection CTs Considerations and requirements for earth fault protection are the same as for Phase fault. Usually the relay employs the same CT's e.g. three phase CTs star connected to derive the residual earth fault current. The accuracy class and overcurrent accuracy limit factors are therefore already determined and for both these factors the earth fault protection requirements are normally less onerous than for overcurrent. 3.2 CT Requirements for High Impedance Restricted Earth Fault Protection For high impedance REF it is recommended that: Low reactance CTs to IEC 60044 Class PX are used, this allows a sensitive current setting to be applied. All CT's should, if possible have identical turns ratios. The knee point voltage of the CTs must be greater than 2 x 64H setting voltage Vs. Where the REF function is used then this dictates that the other protection functions are also used with class PX CTs. A full explanation of how to specify CTs for use with REF protection, and set REF relays is available on our website: www.siemens.com/energy (c) 2013 Siemens Protection Devices Limited Page 31 of 48 7SR210 & 7SR220 Applications Guide Section 4: Control Functions 4.1 Auto-reclose Applications Automatic circuit reclosing is extensively applied to overhead line circuits where a high percentage of faults that occur are of a transient nature. By automatically reclosing the circuit-breaker the function attempts to minimise the loss of supply to the customer and reduce the need for manual intervention. The function supports up to 4 ARC sequences. That is, 4 x Trip / Recloses followed by a Trip & Lockout. A lockout condition prevents any further attempts, automatic or manual, to close the circuit-breaker. The number of sequences selected depends upon the type of faults expected. If there are a sufficient percentage of semipermanent faults which could be burnt away, e.g. fallen branches, a multi shot scheme would be appropriate. Alternatively, if there is a high likelihood of permanent faults, a single shot scheme would minimise the chances of causing damage by reclosing onto a fault. In general, 80% of faults will be cleared by a single Trip and Reclose sequence. A further 10% will be cleared by a second Trip and Reclose. Different sequences can be selected for different fault types (Phase/Earth/Sensitive Earth faults). The Deadtime is the interval between the trip and the CB close pulse being issued. This is to allow for the line to go `dead' after the fault is cleared. The delay chosen is a compromise between the need to return the line to service as soon as possible and prevented unnecessary trips through re-closing too soon. The Reclaim Time is the delay following a re-closure before the line can be considered back in service. This should be set long enough to allow for protection operation for the same fault, but not so long that two separate faults could occur in the same Autoreclose (ARC) sequence and cause unnecessary lockouts. Since large fault currents could potentially damage the system during a prolonged ARC sequence, there are also settings to identify which protection elements are High-sets and these can cause an early termination of the sequence. Where a relay is to operate as part of an ARC scheme involving a number of other relays, the feature attempts to clear any faults quickly without regard to normal fault current grading. It does this by setting each Trip element to be either Delayed or Instantaneous. Instantaneous Trips are set to operate at just above maximum load current with small delays while Delayed Trips are set to suit actual fault levels and with delays suitable for current grading. A typical sequence would be 2 Instantaneous Trips followed by a Delayed Trip & Lockout: * When any fault occurs, the relay will trip instantaneously and then reclose. * If this does not clear the fault, the relay will do the same again. * If this still does not clear the fault, the fault is presumed to be permanent and the next Trip will be Delayed and so suitable for grading with the rest of the network. Thus allowing downstream protection time to operate. * This Trip will Lockout the ARC sequence and prevent further recloses. It is important that all the relays in an ARC scheme shadow this process - advancing through their own ARC sequences when a fault is detected by an element pickup even though they are not actually causing a trip or reclose. This is termed Sequence Co-ordination and prevents an excessive number of recloses as each successive relay attempts to clear the fault in isolation. For this reason each relay in an ARC scheme must be set with identical Instantaneous and Delayed sequence of trips. Figure 4.1-1 Sequence Co-ordination Page 32 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide The relay closest to the fault (D) would step through its Instantaneous Trips in an attempt to clear the fault. If unsuccessful, the relay would move to a Delayed Trip sequence. The other relays in the network (A, B and C) would recognise the sequence of Pick-up followed by current switchoff as ARC sequences. They would therefore also step to their Delayed Trip to retain co-ordination with the respective downstream devices. The next Trip would be subject to current grading and Lockout the ARC sequence such that the fault is cleared by the correct CB. 4.1.1 Auto-Reclose Example 1 Requirement: Settings shall provide four phase fault recloses - two instantaneous and two delayed - and only two recloses for faults detected by the SEF protection. Proposed settings include: CONTROL & LOGIC > AUTORECLOSE PROT'N: 79 P/F Inst Trips: 50-1 79 P/F Delayed Trips: 51-1 79 SEF Delayed Trips: 51SEF-1 CONTROL & LOGIC > AUTORECLOSE CONFIG 79 Num Shots: 4 CONTROL & LOGIC > AUTORECLOSE CONFIG > P/F SHOTS 79 P/F Prot'n Trip 1 : Inst 79 P/F Prot'n Trip 2 : Inst 79 P/F Prot'n Trip 3 : Delayed 79 P/F Prot'n Trip 4 : Delayed 79 P/F Delayed Trips to Lockout : 3 CONTROL & LOGIC > AUTORECLOSE CONFIG > SEF SHOTS 79 SEF Prot'n Trip 1 : Delayed 79 SEF Prot'n Trip 2 : Delayed 79 SEF Delayed Trips to Lockout : 3 Note that Instantaneous' shots are inhibited if the shot is defined as `Delayed' (c) 2013 Siemens Protection Devices Limited Page 33 of 48 7SR210 & 7SR220 Applications Guide Auto-Reclose Example 2 (Use of Quicklogic with AR) TIME 4.1.2 Figure 4.1-2 Example of Logic Application Requirement: The relay at location `A' it is required to provide a reclose sequence of 2 Instantaneous followed by 2 delayed recloses. Where the fault current level is between the values `I1' and `I2' and the first trip is initiated from the 51-1 (IDMT) element, the IDMT characteristic should trip the CB and lockout the auto-reclose. Typical settings are: CONTROL & LOGIC > AUTORECLOSE PROT'N: 79 P/F Inst Trips: 50-1 79 P/F Delayed Trips: 51-1 CONTROL & LOGIC > AUTORECLOSE CONFIG > P/F SHOTS 79 P/F Prot'n Trip 1 : Inst 79 P/F Prot'n Trip 2 : Inst 79 P/F Prot'n Trip 3 : Delayed 79 P/F Prot'n Trip 4 : Delayed The above settings are suitable at values of fault current above `I2' however were a fault to occur with a current value between `I1' and `I2' this would be detected by the 51-1 element only. As Prot'n Trip 1 = Inst then the relay would trip and reclose whereas it is required to lockout for this occurrence. To provide a lockout for the above faults an additional element 50-2 with identical settings to 50-1 is assigned as a Delayed Trip and is used in conjunction with the Quick Logic feature i.e. OUTPUT CONFIG>OUTPUT MATRIX: 51-1 = V1 OUTPUT CONFIG>OUTPUT MATRIX: 50-2 = V2 OUTPUT CONFIG>OUTPUT MATRIX: E1 = V3 CONTROL & LOGIC>QUICK LOGIC: E1 = V1.!V2 INPUT CONFIG>INPUT MATRIX: 79 Lockout = V3 Page 34 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 4.2 Quick Logic Applications 4.2.1 Auto-Changeover Scheme Example Figure 4.2-1 Example Use of Quick Logic The MV installation illustrated above is fed from two incomers. To limit the substation fault level the busbar is run with CB3 open. When a fault occurs on one of the incomers it is isolated by the circuit protection. To re-supply the disconnected loads from the remaining incomer CB3 is closed. If the line fault occurs on incomer 1 it must be confirmed that CB 1 has opened before CB3 can be closed. The relay on incomer 1 confirms that a trip has been issued to CB1 (e.g. Binary Output 2), that CB 1 has opened (e.g. Binary Input 1) and that no current flows in the circuit (e.g. 37-1 = Virtual 1): Incomer 1 Relay is Configured: CB1 Open auxiliary switch wired to B.I. 1 Trip output to CB1 = B.O. 2 OUTPUT CONFIG>OUTPUT MATRIX: 37-1 = V1 OUTPUT CONFIG>OUTPUT MATRIX: E1 = BO3 CONTROL & LOGIC>QUICK LOGIC: E1 = O2.I1.V1 The output from Incomer 1 (BO3) relay is input to the relay on CB 3 (Binary Input 1). A panel switch may be used to enable the On-Load Change-over scheme (Binary Input 2). Before Closing CB3 a check may be made that there is no voltage on busbar 1 (27/59-1 = Virtual 1). CB 3 is closed from Binary Output 3. CB3 Relay is Configured: Panel switch (ON-Load Change-over Enabled) wired to B.I. 1 OUTPUT CONFIG>OUTPUT MATRIX: 27/59-1 = V1 OUTPUT CONFIG>OUTPUT MATRIX: E1 = BO3 CONTROL & LOGIC>QUICK LOGIC: E1 = I1.I2.V1 If required a time delay can be added to the output using the CONTROL & LOGIC > QUICK LOGIC: E1 Pickup Delay setting. (c) 2013 Siemens Protection Devices Limited Page 35 of 48 7SR210 & 7SR220 Applications Guide Section 5: Supervision Functions 5.1 Circuit-Breaker Fail (50BF) Where a circuit breaker fails to operate to clear fault current the power system will remain in a hazardous state until the fault is cleared by remote or back-up protections. To minimise any delay, CB Failure protection provides a signal to either re-trip the local CB or back-trip `adjacent' CBs. The function is initiated by the operation of user selectable protection functions or from a binary input. Current flow is monitored after a tripping signal has been issued if any of the 50BF current check elements have not reset before the timers have expired an output is given. For CB trips where the fault is not current related an additional input is provided (50BF Mech Trip) which monitors the CB closed input and provides an output if the circuit breaker has not opened before the timers expire. The relay incorporates a two-stage circuit breaker fail feature. For some systems, only the first will be used and the CB Failure output will be used to back-trip the adjacent CB(s). On other systems, however, this output will be used to re-trip the local CB to minimise potential disruption to the system; if possible via a secondary trip coil and wiring. The second CB Failure stage will then be used to back-trip the adjacent CB(s). If the CB is faulty and unable to open, a faulty contact can be wired to the CB faulty input of the relay and if a trip occurs while this input is raised the CB fail delay timers may be by-passed to allow back tripping to occur without delay. Figure 5.1-1 Circuit Breaker Fail 5.1.1 Settings Guidelines 50BF Setting The phase current setting must be set below the minimum protection setting current. 50BF Setting-I4 The EF or SEF current setting must be set below the minimum protection setting current. 50BF Ext Trig Any binary input can be mapped to this input to trigger the circuit breaker fail function. Note current must be above setting for the function to operate. 50BF Mech Trip Any binary input can be mapped to this input to trigger the circuit breaker fail function. Note for the function to operate the circuit breaker closed input is used to detect a failure, not the current. 50BF CB Faulty Any binary input can be mapped to this input, if it is energised when a trip initiation is received an output will be given immediately (the timers are by passed). Page 36 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 50BF DTL1/50BF DTL2 The time delays run concurrently within the relay. The time delay applied to the CB Fail protection must be in excess of the longest CB operate time + relay reset time + a safety margin. First Stage (Retrip) Trip Relay operate time 10 ms Reset Time 20 ms CB Tripping time 50 ms Safety Margin 40 ms Overall First Stage CBF Time Delay 120 ms Second Stage (Back Trip) First CBF Time Delay 120 ms Trip Relay operate time 10 ms CB Tripping time 50 ms Reset Time of measuring element 20 ms Margin 60 ms Overall Second Stage CBF Time Delay 260 ms The safety margin is extended by 1 cycle for the second CBF stage as this will usually involve a back-trip of a Busbar tripping scheme. The timing sequence for each stage of the circuit breaker fail function is as below. Relay Operation and CBF Timer Started System Fault Main Trip Relay Operation 20 Backtrip Trip Relay Reset of CBF elements does not occur Backtrip Operation Failure of CB to trip 40 60 80 CB Backtrip Sucessful 100 120 140 160 180 200 220 240 260 280 300 320 ms from fault occuring 340 CB Operate Time Stage 1 CBF Timer (Backtrip) = 120ms Figure 5.1-2 Single Stage Circuit Breaker Fail Timing Relay Operation and CBF Timer Started System Fault Backtrip Trip Relay Operation CBF Retrip Trip Relay Main Trip Relay Operation 40 CB's Fails to Trip 60 80 No Reset of CBF elements CBF Retrip Operation Reset of CBF elements CBF Back trip Operation Failed CB Retrip Operation 100 120 140 Operation of all BB CB's No Reset of CBF elements 160 180 200 220 240 260 280 300 320 340 360 ms from fault occuring CB Operate Time Stage 1 CBF Timer (Retrip) = 120ms Stage 2 CBF Timer (Backtrip) = 250ms Figure 5.1-3 Two Stage Circuit Breaker Fail Timing (c) 2013 Siemens Protection Devices Limited Page 37 of 48 7SR210 & 7SR220 Applications Guide 5.2 Current Transformer Supervision (60CTS) When a CT fails, the current levels seen by the protection become unbalanced. A large level of NPS current is therefore detected - around 0.3 x In for one or two CT failures. However this condition would also occur for a system fault. To differentiate between the two conditions, the element uses NPS voltage to restrain the CTS algorithm as show in the accompanying table. NPS Current NPS Voltage Decision > Setting > Setting System Fault > Setting < Setting CT Failure Table 5-2 Determination of CT Failure (1 or 2 Phases) Following a CT Failure, there should be little or no NPS voltage. Perhaps 0.1 x Vn as a maximum. Operation is subject to a time delay to prevent operation for transitory effects. A 3-phase CT failure is considered so unlikely (these being independent units) that this condition is not tested for. Page 38 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 5.3 Voltage Transformer Supervision (60VTS) Although VTs rarely fail themselves, VT Supervision presents a common application because of the failure of protective Fuses connected in series with the VTs. When a VT failure occurs on one or two phases, the voltage levels seen by the protection become unbalanced. A large level of NPS voltage is therefore detected - around 0.3 x Vn for one or two VT failures. However this condition would also occur for a system fault. To differentiate between the two conditions, the element uses NPS current to restrain the VTS algorithm as show in the accompanying table. NPS Voltage NPS Current Decision > Setting > Setting System Fault > Setting < Setting VT Failure Table 5-3 Determination of VT Failure (1 or 2 Phases) Following a VT Failure, the level of NPS current would be dependent solely upon load imbalance - perhaps 0.1 x In as a maximum. Operation is subject to a time delay to prevent operation for transitory effects. NPS voltage and current quantities are used rather than ZPS since the latter makes it difficult to differentiate between a VT failure and a Phase-Phase fault. Both conditions would generate little or no ZPS current. However the element provides an option to use ZPS quantities to meet some older specifications. There are possible problems with using NPS quantities due to load imbalances. These would also generate significant levels of NPS current and so possibly cause a VT failure to be missed. This problem can be overcome by careful selection of settings, however, setting the NPS current threshold above the level expected for imbalance conditions. If a failure occurs in all 3 Phases of a Voltage Transformer, then there will be no NPS or ZPS voltage to work with. However the PPS Voltage will fall below expected minimum measurement levels. This could also be due to a `close in' fault and so PPS Current must remain above minimum load level BUT below minimum fault level. PPS Voltage PPS Current Decision < Setting > Minimum Fault Level System Fault < Setting Minimum Load Level < VT Failure AND < Minimum Fault Level Table 5-4 Determination of VT Failure (3 Phases) Operation is again subject to a time delay to prevent operation for transitory effects. Alternatively a 3 Phase VT failure can be signalled to the relay via a Binary Input taken from the Trip output of an external MCB. This can also be reset by a Binary Input signal. VTS would not normally be used for tripping - it is an alarm rather than fault condition. However the loss of a VT would cause problems for protection elements that have voltage dependant functionality. For this reason, the relay allows these protection elements - under-voltage, directional over-current, etc. - to be inhibited if a VT failure occurs. (c) 2013 Siemens Protection Devices Limited Page 39 of 48 7SR210 & 7SR220 Applications Guide 5.4 Trip-Circuit Supervision (74TCS) Binary Inputs may be used to monitor the integrity of the CB trip circuit wiring. A small current flows through the B.I. and the trip circuit. This current operates the B.I. confirming the integrity of the auxiliary supply, CB trip coil, auxiliary switch, C.B. secondary isolating contacts and associated wiring. If monitoring current flow ceases the B.I. drops off and if it is user programmed to operate one of the output relays, this can provide a remote alarm. In addition, an LED on the relay can be programmed to operate. A user text label can be used to define the operated LED e.g. "Trip CCT Fail". The relevant Binary Input is mapped to 74TCS-n in the INPUT CONFIG>INPUT MATRIX menu. To avoid giving spurious alarm messages while the circuit breaker is operating the input is given a 0.4 s Drop-off Delay in the INPUT CONFIG>BINARY INPUT CONFIG menu. To provide an alarm output a normally open binary output is mapped to 74TCS-n. 5.4.1 Trip Circuit Supervision Connections The following circuits are derived from UK ENA S15 standard schemes H5, H6 and H7. For compliance with this standard: Where more than one device is used to trip the CB then connections should be looped between the tripping contacts. To ensure that all wiring is monitored the binary input must be at the end of the looped wiring. Resistors must be continuously rated and where possible should be of wire-wound construction. Scheme 1 (Basic) Figure 5.4-1 Trip Circuit Supervision Scheme 1 (H5) Scheme 1 provides full Trip supervision with the circuit breaker Open or Closed. Where a `Hand Reset' Trip contact is used measures must be taken to inhibit alarm indications after a CB trip. Page 40 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide Scheme 2 (Intermediate) Figure 5.4-2 Trip Circuit Supervision Scheme 2 (H6) Scheme 2 provides continuous Trip Circuit Supervision of trip coil with the circuit breaker Open or Closed. It does not provide pre-closing supervision of the connections and links between the tripping contacts and the circuit breaker and may not therefore be suitable for some circuits which include an isolating link. Scheme 3 (Comprehensive) Figure 5.4-3 Trip Circuit Supervision Scheme 3 (H7) Scheme 3 provides full Trip supervision with the circuit breaker Open or Closed. (c) 2013 Siemens Protection Devices Limited Page 41 of 48 7SR210 & 7SR220 Applications Guide 5.5 Inrush Detector (81HBL2) This element detects the presence of high levels of 2nd Harmonic current which is indicative of transformer Inrush current at switch-on. These currents may be above the operate level of the overcurrent elements for a short duration and it is important that the relay does not issue an incorrect trip command for this transient network condition. If a magnetic inrush condition is detected operation of the overcurrent elements can be blocked. Calculation of the magnetising inrush current level is complex. However a ratio of 20% 2nd Harmonic to Fundamental current will meet most applications without compromising the integrity of the Overcurrent protection. There are 3 methods of detection and blocking during the passage of magnetising inrush current. Phase Blocking only occurs in those phases where Inrush is detected. Large, Single Phase Transformers - Auto-transformers. Cross All 3-phases are blocked if Inrush is detected in any phase. Traditional application for most Transformers but can give delayed operation for Switchon to Earth Fault conditions. Sum Composite 2nd Harmonic content derived for all 3-phases and then compared to Fundamental current for each individual phase. Provides good compromise between Inrush stability and fast fault detection. Table 5-5 5.6 Magnetic Inrush Bias Broken Conductor / Load Imbalance (46BC) This feature is used to detect an open circuit condition when a conductor breaks or a mal-operation occurs in phase segregated switchgear. There will be little or no fault current and so overcurrent elements will not detect the condition. However the condition can be detected because there will be a high content of NPS (unbalance) current present. An NPS / PPS ratio > 50% will result from a Broken Conductor condition. Operation is subject to a time delay to prevent operation for transitory effects. 5.7 Circuit-Breaker Maintenance The Relay provides CB Total Trip Count, CB Delta Trip Count, CB Count to AR Block and CB Frequent Operation 2 Counters along with an I t CB Wear Counter to estimate the amount of wear and tear experienced by a CircuitBreaker. Alarm can be provided once set levels have been exceeded. Typically estimates obtained from previous circuit-breaker maintenance schedules or manufacturers data sheets are used for setting these alarm levels. The relay instrumentation provides the current values of these counters. 5.8 Overfluxing Detector (81HBL5) An increase in transformer or decrease in system frequency may result in the transformer becoming over-excited. The 81HBL5 element can be used to prevent protection operation e.g. prevent differential protection operation during acceptable over-excitation conditions. Page 42 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 5.9 Load Blinder (21) NB: It is important to observe the convention regarding Forward and Reverse directions of current. Load Blinders are used with directional overcurrent elements to block forward tripping during periods of high load currents that can occur in distribution networks. The blinder is operated during user defined load conditions and is used in conjunction with the relay protection elements. One of the major factors contributing to high load conditions is an increase of distributed generation capacity which can feed power back into the network contrary to the `normal' direction of power flow. This can result in current levels above the relay setting and can cause tripping of overcurrent elements. One typical example is on paralleled incoming transformer circuits, forward directional overcurrent elements are parametised such that they detect faults on the transformer LV connections for currents flowing in the direction contrary to the `normal' load flow. These forward elements have a relatively low current setting, typically <45% of transformer rating, as current normally only flows in this direction during fault conditions. When embedded generation is connected into the downstream network, these relays limit the level of current that can be fed back into the grid. Load Blinders measure the system impedance and are set to differentiate between a fault having a relatively low impedance and a fault having a relatively high impedance. Additional measurands are also considered to increase the security of operation. Figure 5.9-1 Paralleled Transformers and Feeders (c) 2013 Siemens Protection Devices Limited Page 43 of 48 7SR210 & 7SR220 Applications Guide 5.10 Load Blinder Design 5.10.1 Application view It is important to observe the convention regarding Forward and Reverse directions of current. Load Blinders are designed to block forward overcurrent elements from tripping during defined load conditions. User settings 21LB-1/3P Impedance, 21LB-1/3P Angle +ve and 21LB-1/3P Angle -ve (`a', `b' and `c' in Figure 5.10.1-1 Impedance Setting and Angle Setting) allow the user to define the Blinder region depending on the network configuration - specifically the line loading and fault levels. The measured impedance: a. b. Is used to confirm the forward or reverse flow of current i.e. load blinder operated. Is used to confirm that current flow is outside the defined limits of load flow i.e. load blinder not operated. The transition between operated and non-operated is subject to a 5 degree hysteresis adjustment. Nominal Impedance Z = 1p.u. = VL / (3 x I) +X Point 8 Point 7 Block Zone a b Load Impedance Block Zone Phase Fault b -R Load 0 360 Impedance +R c Point 10 Point 9 Operate Zone Vpps value c a a = 21LB-3P Impedance setting b = 21LB-3P Angle +ve setting c = 21LB-3P Angle -ve setting Point 1 Point 2 Trip Level I = Vs / Z Point 6 Point 5 Point 3 Point 4 -X Figure 5.10.1-1 Impedance Setting and Angle Setting Page 44 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 5.10.2 Design View 5.10.2.1 Load Blinder 3Ph Figure 5.10.2.1-1 Logic Diagram 3 Phase The 3-phase load blinder has the following setting parameters: 21LB - 3P Angle +ve 21LB - 3P Angle -ve 21LB - 3P Impedance 21LB - 3P VPPS 21LB - 3P INPS The design of Load Blinder 3Ph takes into consideration that the protection blocking should only be issued during definable allowable system power flow conditions i.e. an overcurrent blocking signal can only be issued when: a. b. c. Positive Sequence Voltage Vpps is not significantly reduced i.e. is above the 21LB-3P VPPS Setting. AND Negative Sequence Current Inps is lower than 21LB-3P INPS Setting AND The impedance measured in all phases is within the operate zone. Zpps is calculated from Vpps and Ipps. The calculated Zpps is used to determine if the impedance is in the operate zone i.e. greater than the 21LB-3P Impedance setting and less than the 21LB-3P Angle settings. Suitable settings can be chosen to provide overcurrent blocking in the forward or reverse directions. (c) 2013 Siemens Protection Devices Limited Page 45 of 48 7SR210 & 7SR220 Applications Guide 5.10.2.2 Load Blinder 1Ph The single phase Load Blinder provides phase segregated blocking outputs. The Inps level is not considered whereas operation of the load blinder is inhibited during earth fault conditions i.e. when the Izps level exceeds the I21LB-1P IZPS setting. Figure 5.10.2.2-1 Logic Diagram 1 Phase The single phase load blinder has the following setting parameters: 21LB - 1P Angle +ve 21LB - 1P Angle -ve 21LB - 1P Impedance 21LB - 1P VPPS 21LB - 1P IZPS The design of single phase load blinder takes into consideration the following effects of a high unbalanced load non-fault condition. The blinder is operated when: a. b. c. Positive Sequence Voltage Vpps is not significantly changed. A high 21LB-1P VPPS setting will allow inhibiting Load Blinders in case of larger voltage drops (representing fault situation). AND Zero Sequence Current Izps is lower than 21LB-1P IZPS Setting., AND The impedance measured per phase is within the operate zone. Zphase is calculated from Vphase (peak) and Iphase (peak). The calculated Zphase is used to determine if the impedance for that phase is in the operate zone i.e. greater than 21LB-1P Impedance setting and less than 21LB-1P Angle settings. Suitable settings can be chosen to provide outputs in the forward or reverse directions. Page 46 of 48 (c)2018 Siemens Protection Devices Limited 7SR210 & 7SR220 Applications Guide 5.10.3 Setting Example - 3 Pole Load Blinder Load blinders used to block overcurrent relay so that tripping does not occur for load current levels with a P.F. 0.94 to Unity. T1 T2 90MVA 132/33kV -10% to +20% (1%) Z = 8% 1574A Overcurrent Fwd setting: = 90% of 50% =40.5MVA = 709A @ 33kV 1600/1A 33000/110V Fwd Nominal Impedance Z = 1p.u. = VL / (3 x I) +X Point 8 Point 7 Operate Zone Vpps value Block Zone a b Load Impedance Block Zone Phase Fault b -R 0 Load 360 Impedance +R c a c a = 21LB-3P Impedance setting b = 21LB-3P Angle +ve setting c = 21LB-3P Angle -ve setting Point 10 Point 9 Point 1 Point 2 Trip Level I = Vs / Z Point 6 Point 5 Point 3 Point 4 -X Figure 5.10.3-1 Scheme and Impedance Illustration (c) 2013 Siemens Protection Devices Limited Page 47 of 48 7SR210 & 7SR220 Applications Guide 5.10.4 Calculating the Impedance 21LB-3P Impedance setting (`a') This is the minimum system impedance that allows operation of the load blinder; it is set in secondary Ohms. To enable blocking of the overcurrent element for values of current up to say 1.5 times the nominal load current value (to allow for temporary reverse overload conditions) the setting is calculated from: - ZS = VLsecy Isecy = 110 3 1.5 = 42 Note: the equivalent primary impedance to the above: - ZP = Z S CTAsecy CTprim VLprim VLsecy = 42 1 33000 = 7.88W 1600 110 21LB-3P Angle setting (`b' and `c') A setting of 20 degrees will allow blocking of the overcurrent element for system load power factors between 0.94 and Unity. 21LB-3P VPPS setting The Blinder is only operational during normal load levels of reverse load flow. Where reverse current flow is caused by a system fault the positive sequence voltage will reduce significantly. To facilitate Load Blinder operation the system should be substantially balanced i.e. positive phase sequence voltage will be high. A setting of 0.95 Vn is selected i.e. 21LB-VPPS setting = 0.95 x 63.5 = 60 V. 21LB-3P INPS setting The Blinder is only operational during normal load levels of reverse load flow. The system should be substantially balanced i.e negative phase sequence current will be low. A 21LB-3P INPS setting = 0.05 In is selected. Page 48 of 48 (c)2018 Siemens Protection Devices Limited Unrestricted Siemens Protection Devices Limited P.O. Box 8, North Farm Road Hebburn, Tyne & Wear NE31 1TZ United Kingdom Phone: +44 (0)191 401 7901 Fax: +44 (0)191 401 5575 E-mail: marketing.spdl.gb@siemens.com For enquires please contact our Customer Support Center Phone: +49 180/524 8437 (24hrs) Fax: +49 180/524 2471 E-mail: support.energy@siemens.com EMEA-T10050-00-76GB October 2018 www. siemens.com/energy Unrestricted