7SR210 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 51 of 61
Description Range Default
Manual Close CB
Close pulse due to Manual close being issued
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 AR Close CB
Close pulse due to auto-reclose sequence
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 Trip & Reclose
Indicates the Trip & Reclose sequence being performed
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 Trip & Lockout
Indicates the Trip & Lockout sequence being performed
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 Lockout
Indicates the auto-recloser is in the Lockout state
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 Out Of Service
Indicates the auto-recloser is out of service
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 In Service
Indicates the auto-recloser is in service
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 In Progress
Indicates an auto-reclose sequence is in progress
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 Block Extern
Indicates that Extern for the current shot has been selected to
be delayed. (This may be used to block external tripping
elements in the same way as the internal protection elements
are blocked to achieve Instantaneous / Delayed operation.)
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 CB Fail To Close
Indicates the CB was not closed at the end of the Close Pulse
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 Close Onto Fault
Indicates an element starter or trip operated during the Close
Pulse
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
79 Successful AR
Indicates that after a reclose and at the end of the Reclaim
time the CB was closed and there were no auto-reclose trip
elements operated. (This is issued for 2 secs)
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------
Successful Man Close
Indicates that after a manual close and at the end of the
Reclaim time the CB was closed and there were no auto-
reclose trip elements operated. (This is issued for 2 secs)
Combination of ( BO1, BO2, BO3,
BO4, BO5, BO6, BO7, BO8, L1,
L2, L3, L4, L5, L6, L7, L8, V1, V2,
V3, V4, V5, V6, V7, V8, V9, V10,
V11, V12, V13, V14, V15, V16 )
----------------------
----------