Data Sheet
SS/264XR_2
ABB 2600T Series
Engineered solutions
for all applications
Base accuracy : ±0.075%
Span limits
0.2 to 60000kPa; 0.8inH2O to 8700psi
– 0.54 to 16000kPa abs; 4mmHg to 2320psia
Reliable sensing system coupled with very latest
digital technologies
Comprehensive sensor choice
optimize in-use total performance and stability
5–year stability
Flexible configuration facilities
provided locally via local keys combined with LCD
indicator or via hand held terminal or
PC configuration platform
Multiple protocol availability
provides integration with HART®, PROFIBUS PA
and FOUNDATION Fieldbus platforms offering
interchangeability and transmitter upgrade
capabilities
Broad selection of variants, options fill fluids and
wetted materials
allows total flexibility maximizing cost-effective
aspect, also providing applications with critical
process media at extended temperature range
PED compliance to sound engineering practice
(SEP)
FieldIT
2600T Series Pressure Transmitters
Model 264DR Differential
Models 264PR and 264HR Gauge
Models 264VR and 264NR Absolute
with remote seal(s)
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
2
Functional Specifications
Range and span limits
– models 264DR/264PR/264VR
General Description
Models detailed in this data sheet apply for those transmitters which
include one or two remote seal(s) connected via a capillary to the
transmitter sensor. Depending on the selected ordering code the
following models are available:
a) model 264DR which allows a differential measurement using either
two remote seals of same type and size or one remote seal (on
positive or negative side) and a standard threaded connection 1/4in
NPT on flange or 1/2in NPT through adapter, for the wet or dry leg on
the side opposite to seal.
b) models 264PR or 264VR allowing gauge or absolute measurement
respetively with the reference side at atmosphere or at vacuum. The
other side which can be the positive or negative (high or low pressure
side) features the required remote seal.
Model 264HR or 264NR have the remote seal on the positive side and the
user can select the suitable code for having the reference at armospheric
or vacuum pressure respectively for gauge or absolute measure.
The following table list the types of standard seal which can be combined
with 264xR transmitters (the mnemonic is used as reference in the
compatibility table of page 3).
Refer to seal data sheet for all data and details relevant to seal element.
All following specification data apply for identical characteristics of the two sides when the transmitter is differential with two seals.
ledoMepytlaeSeziScinomenM
W462SrefaW
04ND/ni2/11
05ND/ni2
08ND/ni3
5.1P
2P
3P
C462S eetlacimehC
degnalf ni33P
F462S
degnalF
mgarhpaidhsulf
05ND/ni2
001-08ND/ni4-3
2P
3P
degnalF
dednetxe
mgarhpaid
05ND/ni2
08ND/ni3
001ND/ni4
2E
3E
3P
U462SnoinUni2/115.1P
T462Senil-ffodedaerhTni2/125.2T
M462Senil-ffodegnalFni2/125.2T
S462S
tunnoinU
pmalcirT
lerruByrrehC
citpesA,yratinaS
05F/ni2
08F/ni3
ni4
2S
3S
3S
B462SnottuBni11B
P462S ecivresaerU
degnalf
ni2/11
ni2/12
5.1U
5.2U
rosneS
edoC
timiLegnaRreppU
)LRU(
)LRL(timiLegnaRrewoL
muminiM
naps
RD462
laitnereffid
erusaem
RP462
eguag
erusaem
RV462
etulosba
erusaem
B
aPk4
rabm04
Hni61
2
O
aPk4
rabm04
Hni61
2
O
aPk2.0
rabm2
Hni8.0
2
O
E
aPk61
rabm061
Hni46
2
O
aPk61
rabm061
Hni46
2
O
aPk61
rabm061
Hni46
2
O
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk45.0
rabm4.5
Hni61.2
2
O
F
aPk04
rabm004
Hni061
2
O
aPk04
rabm004
Hni061
2
O
aPk04
rabm004
Hni061
2
O
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk76.0
rabm7.6
Hni76.2
2
O
G
aPk56
rabm056
Hni062
2
O
aPk56
rabm056
Hni062
2
O
aPk56
rabm056
Hni062
2
O
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk1.1
rabm11
Hni53.4
2
O
H
aPk061
rabm0061
Hni246
2
O
aPk061
rabm0061
Hni246
2
O
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk76.2
rabm7.62
Hni7.01
2
O
M
aPk006
rab6
isp78
aPk006
rab6
isp78
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk01
rab1.0
isp54.1
P
aPk0042
rab42
isp843
aPk0042
rab42
isp843
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk04
rab4.0
isp8.5
Q
aPk0008
rab08
isp0611
aPk0008
rab08
isp0611
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk431
rab43.1
isp4.91
S
aPk00061
rab061
isp0232
aPk00061
rab061
isp0232
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk762
rab76.2
isp7.83
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
3
(§) Double the value with the inert filling
– models 264HR/NR Span limits
Maximum span = URL
(can be further adjusted up to ± URL (TD = 0.5) for differential
models, within the range limits)
IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR
CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS
POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS.
Zero suppression and elevation
Zero and span can be adjusted to any value within the range limits
detailed in the table as long as:
– calibrated span minimum span
Damping
Selectable time constant : 0, 0.25, 0.5, 1, 2, 4, 8 or 16s.
This is in addition to sensor response time
Turn on time
Operation within specification in less than 1s with minimum
damping.
Insulation resistance
> 100M at 1000VDC (terminals to earth)
The combinations sensor code/seal type marked (•) modify the base accuracy rating and static pressure effect; refer to performance specifications.
Although he above table defines capillary length, for some types of seal combined to the sensor, care should be taken of the maximum working
pressure of the used seal which can limit the range.
Refer to ABB for data related to application of capillary lengths greater than those specified in above table.
rosneS
edoC
egnaRreppU
)LRU(timiL
egnaRrewoL
)LRL(timiL
napSmuminiM
RH462RN462
G
aPk56
rabm056
Hni062
2
O
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk1.1
rabm11
Hni53.4
2
O
aPk1.1
rabm11
gHmm8
H
aPk061
rabm0061
Hni246
2
O
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk76.2
rabm7.62
Hni7.01
2
O
aPk76.2
rabm7.62
gHmm02
M
aPk006
rab6
isp78
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk01
rab1.0
isp54.1
aPk01
rab1.0
isp54.1
P
aPk0042
rab42
isp843
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk04
rab4.0
isp8.5
aPk04
rab4.0
isp8.5
Q
aPk0008
rab08
isp0611
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk431
rab43.1
isp4.91
aPk431
rab43.1
isp4.91
S
aPk00061
rab061
isp0232
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk762
rab76.2
isp7.83
aPk762
rab76.2
isp7.83
V
aPk00006
rab006
isp0078
)§(sbaaPk70.0
)§(sbarabm7.0
)§(gHmm5.0
aPk0002
rab02
isp092
rosneS
edoC
)stekarbni)m(htgnelyrallipacmumixamhtiwsepytlaesdewolla(ytilibitapmoC
noitarugifnoctnemerusaemsusrev
laitnereffiD
)slaesowt(
laitnereffiddnaeguag
)laeseno(
etulosba
)laeseno(
B
)5.1(3P
)5.1(3S)1(5.2T)1(3E
E
)3(3P
)3(3S,)2(5.2T,)2(3E
)1(3P
)1(3S
G-F
)3(5,2T,)4(3E,)2(2E,)6(3P,)3(2P
)6(3S,)1(2S,)3(5.2U
)2(5,2T,)3(3E,)4(3P,)2(2P
)4(3S,)3(5.2U
)2(5,2T,)3(3E,)3(3P,)2(2P
)3(3S,)3(5.2U
H
)6(3E,)6(2E,)8(3P,)8(2P,)4(5.1P
)01(3S,)3(2S,)6(5.2U,)6(5.2T
)8(3E,)4(2E,)01(3P,)6(2P,)3(5.1P
)01(3S,)2(2S,)6(5.2U,)6(5.2T
)6(3E,)3(2E,)8(3P,)5(2P,)3(5.1P
)8(3S,)2(2S,)5(5.2U,)5(5.2T
M
,)8(3E,)6(2E,)01(3P,)8(2P,)5(5.1P
)01(3S,)6(2S,)6(5.2U,)6(5.2T
,)8(3E,)6(2E,)01(3P,)8(2P,)5(5.1P
)01(3S,)6(2S,)6(5.2U,)5(5.1U,)6(5.2T
,)6(3E,)5(2E,)8(3P,)6(2P,)4(5.1P
)8(3S,)5(2S,)5(5.2U,)4(5.1U,)5(5.2T
P
,)8(3E,)6(2E,)01(3P,)8(2P,)5(5.1P
)01(3S,)6(2S,)6(5.2U,)6(5.2T
,)8(3E,)6(2E,)01(3P,)8(2P,)5(5.1P
)01(3S,)6(2S,)6(5.2U,)5(5.1U,)6(5.2T
,)6(3E,)5(2E,)8(3P,)6(2P,)4(5.1P
)8(3S,)5(2S,)5(5.2U,)4(5.1U,)5(5.2T
Q
,)8(3E,)6(2E,)01(3P,)8(2P,)5(5.1P
)01(3S,)6(2S,)6(5.2U,)6(5.2T
)3(1B,)8(3E,)6(2E,)01(3P,)8(2P,)5(5.1P
)01(3S,)6(2S,)6(5.2U,)5(5.1U,)6(5.2T
,)6(3E,)5(2E,)8(3P,)6(2P,)4(5.1P
)8(3S,)5(2S,)5(5.2U,)4(5.1U,)5(5.2T
S
,)01(3P,)8(2P,)5(5.1P
)6(5.2U,)6(5.2T
,)01(3P,)8(2P,)5(5.1P
)3(1B,)6(5.2U,)5(5.1U,)6(5.2T
,)8(3P,)6(2P,)4(5.1P
)5(5.2U,)4(5.1U,)5(5.2T
V
)6(5.2U,)5(5.1U,)3(1B
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
4
Operative limits
Temperature limits °C (°F) :
Ambient (is the operating temperature)
Lower ambient limit for LCD indicators: –20°C (–4°F)
Upper ambient limit for LCD indicators: +70°C (+158°F)
Note : For Hazardous Atmosphere applications see the temperature
range specified on the certificate/approval relevant to the aimed
type of protection
Process
Lower limit (low pressure side 264DR only)
– refer to lower ambient limits; –20°C (–4°F) for Viton gasket
Upper limit (low pressure side 264DR only)
– Silicone oil: 121°C (250°F) (1)
– Inert fluid: 100°C (212°F) (2)
(1) 100°C (212°F) for application below atmospheric pressure
(2) 65°C (150°F) for application below atmospheric pressure
The following table show characteristics of capillary/seal fill fluids when
used in transmitters with remote seal.
Fills fluids with FDA are defined as food fills and are Generally
Recognized As Safe (GRAS) by the US Food and Drug Administration
(FDA).
Lower limit for Viton gasket –20°C (–4°F)
Storage
Lower limit: –50°C (–58°F); –40°C (–40°F) for LCD indicators
Upper limit: +85°C (+185°F)
Pressure limits
Refer to seal specification sheet for maximum working pressure related
to the used remote seal.
Overpressure limits (without damage to the transmitter)
0.067kPa abs, 0.67mbar abs, 0.01psia (double with inert filling) to
transmitter sensor limit or flange rating of seal, whichever is less:
– 16MPa, 160bar, 2320psi for models 264DR, 264PR and 264VR
(except 7MPa, 70bar, 1015psi for sensor code B)
21MPa, 210bar, 3045psi for models 264HR/NR sensors G to S
90MPa, 900bar, 13050psi for model 264HR sensor V.
Static pressure
Transmitters for differential pressure model 264DR operates within
specifications between the following limits:
1.3kPa abs,13mbar abs, 0.2psia and 16MPa, 160bar, 2320psi
(except 7MPa, 70bar, 1015psi for sensor code B).
0.067kPa abs,0.67mbar abs, 0.1psia and 16MPa, 160bar,
2320psi (except 7MPa, 70bar, 1015psi for sensor code B) or
flange rating of seal whichever is less, using two remote seals on
both transmitter side.
Proof pressure
The transmitter can be exposed without leaking to line pressure of up to
– 28MPa, 280bar, 4000psi for model 264DR, 264PR and 264VR
40MPa, 400bar, 5900 psi for models 264HR/NR sensors G to S
90MPa, 900bar, 13050 psi for model 264HR sensor V
or two times the flange rating of seal, whichever is less
Meet ANSI/ISA–S 82.03 hydrostatic test requirements and SAMA PMC 27.1.
gnilliF
sledoM
RV/RP/RD462
sledoM
RN/RH462
ledoM
RH462
srosneS
SotF
srosneS
E,B
srosneS
SotG
rosneS
V
lioenociliS 002CD 58+dna04
)581+dna04(
58+dna52
)581+dna31(
58+dna04
)581+dna04(
58+dna04
)581+dna04(
trenI nedlaG
58+dna02
)581+dna4(
58+dna01
)581+dna41+(
58+dna02
)581+dna4(
trenI nobracolaH 58+dna02 )581+dna4( 58+dna01 )581+dna41+( 58+dna02 )581+dna4(
SDIULFLLIF
)NOITACILPPA(
SNOITIDNOCGNITAREPO
xamT
fo>sbaP@
nimP
sbarabm
)aisp(
xamT
nimP@
nimT
002CD-lioenociliS
)esopruplareneG(
)093(002
rabm53@
7.0
)10.0(
061
)023(
04
)04(
041NA-lioenociliS
)erutarepmethgiH(
)617(083
rab1@
7.0
)10.0(
003
)275(
5
)32+(
TLXmrehtlySremyloPenociliS
)erutarepmetwoL(
)212(001
rabm011@
2
)30.0(
02
)86(
001
)841(
02-MeeboeN-lioelbategeV
ADF)yratinaS-dooF(
)093(002
rab1@
031
)9.1(
051
)003(
81
)0(
)%07(retaWnirecylG
ADF)yratinaS-dooF(
)002(39
rab1@
0001
)5.41(
39
)002(
7
)02+(
28LOCRAM-liolareniM
ADF)yratinaS-dooF(
)093(002
rabm002@
33
)5.0(
04
)401(
04
)04(
nedlaGtrenI
)ecivreSnegyxO(
)023(061
rab1@
7.0
)10.0(
56
)051(
81
)0(
2.4nobracolaHtrenI
)ecivreSnegyxO(
)653(081
rabm004@
4
)60.0(
07
)851(
02
)4(
llifBBA
)slaicepsdnastniaP(
)275(003
rabm004@
7.0
)10.0(
061
)023(
01
)41+(
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
5
Environmental limits
Electromagnetic compatibility (EMC)
Comply with EN 61000–6–3 for emission and EN 61000–6–2 for
immunity requirements and test;
Radiated electromagnetic immunity level: 30V/m
(according to IEC 1000–4–3, EN61000–4–3)
Conducted electromagnetic immunity level : 30V
(according to IEC 1000–4-6, EN 61000–4–6)
Surge immunity level (with surge protector): 4kV
(according to IEC 1000-4–5 EN 61000–4–5)
Fast transient (Burst) immunity level: 4kV
(according to IEC 1000–4–4 EN 61000–4–4)
Pressure equipment directive (PED)
Comply with 97/23/EEC following sound engineering practice (SEP).
Humidity
Relative humidity: up to 100% annual average
Condensing, icing: admissible
Vibration resistance
Accelerations up to 2g at frequency up to 1000Hz
(according to IEC 60068–2–26)
Shock resistance (according to IEC 60068–2–27)
Acceleration: 50g
Duration: 11ms
Wet and dust-laden atmospheres
The transmitter is dust and sand tight and protected against immersion
effects as defined by EN 60529 (1989) to IP 67 (IP 68 on request) or by
NEMA to 4X or by JIS to C0920.
Hazardous atmospheres
With or without output meter/integral display
INTRINSIC SAFETY/EUROPE:
ATEX/ZELM approval
II 1 GD T50°C, EEx ia IIC T6 (–40°C Ta +40°C)
T95°C, EEx ia IIC T4 (–40°C Ta +85°C)
TYPE "N"/EUROPE:
ATEX/ZELM type examination (for HART)
II 3 GD T50°C, EEx nL IIC T6 (–40°C Ta +40°C)
T95°C, EEx nL IIC T4 (–40°C Ta +85°C)
(FOUNDATION Fieldbus/PROFIBUS PA): pending
FLAMEPROOF/EUROPE:
ATEX/CESI approval
II 1/2 GD T85°C, EEx d IIC T6 (–40°C Ta +75°C)
CANADIAN STANDARDS ASSOCIATION
and FACTORY MUTUAL:
– Explosionproof: Class I, Div. 1, Groups A, B, C, D
– Dust ignitionproof : Class II, Div. 1, Groups E, F, G
– Suitable for : Class II, Div. 2, Groups F, G; Class III, Div. 1, 2
– Nonincendive: Class I, Div. 2, Groups A, B, C, D
– Intrinsically safe: Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G
AEx ia IIC T6/T4, Zone 0 (FM)
STANDARDS AUSTRALIA (SAA): pending
TS/WCA Approval
Ex d IIC T5 (Tamb +85°C)/T6 (Tamb +70°C) Class 1 Zone 1;
Ex ia IIC T4 (Tamb +85°C) /T5 (Tamb +55°C) T6 Class 1 Zone 0
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
6
R(k) = Supply voltage – min. operating voltage (VDC)
–––––––––––––––––––––––––––––––––––––––
22.5
Electrical Characteristics and Options
HART digital communication and 4 to 20mA output
Power Supply
The transmitter operates from 10.5 to 42VDC with no load and is
protected against reverse polarity connection (additional load allows
operations over 42VDC).
For EEx ia and other intrinsically safe approval power supply must
not exceed 30VDC.
Ripple
20mV max on a 250 load as per HART specifications
Load limitations
4 to 20mA and HART total loop resistance :
A minimum of 250 is required for HART communication.
Optional indicators
Output meter
CoMeter and Prometer LCD:
5-digit (±99999 counts) programmable with 7.6mm. high (3in),
7-segment numeric characters plus sign and digital point for digital
indication of output value in percentage, current or engineer unit;
10-segment bargraph display (10% per segment) for analog
indication of output in percentage;
7-digit with 6mm. high (2.3in), 14-segment alphanumeric
characters, for engineer units and configuration display
Analog : 36mm (1.4in) scale on 90°.
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of analog output
in percentage.
User-definable matrix display mode with HART communication:
– process variable in pressure unit or
– output signal as percentage, current or engineering units
Display also indicates in/out transfer function, static pressure,
sensor temperature and diagnostic messages and provides
configuration facilities.
Optional surge protection
Up to 4kV
voltage 1.2 µs rise time / 50 µs delay time to half value
current 8 µs rise time / 20 µs delay time to half value
Output signal
Two–wire 4 to 20mA, user-selectable for linear or square root output,
power of 3/2 or 5/2, 5th order or two 2nd order switching point selectable
programmable polynomial output.
HART® communication provides digital process variable (%, mA or
engineering units) superimposed on 4 to 20mA signal, with protocol
based on Bell 202 FSK standard.
Output current limits (to NAMUR standard)
Overload condition
- Lower limit: 3.8mA
- Upper limit: 20.5mA
Transmitter failure mode (to NAMUR standard)
The output signal can be user-selected to a value of 3.7 or 22mA on
gross transmitter failure condition, detected by self-diagnostics.
In case of CPU failure the output is driven <3.7mA or >22mA.
(volts)
MINIMUM OPERATING VOLTAGES
10.5
with integral display
with optional output analog indicator
with optional surge protection
with ProMeter output indicator
10.7 12.3 12.5
no link on output indicator plugs
15.3
with CoMeter indicator and HART communication
13.3
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
7
PROFIBUS PA output
Device type
Pressure transmitter compliant to Profiles 3.0 Class A & B; ident.
number 052B HEX.
Power supply
The transmitter operates from 10.5 to 32VDC , polarity independent.
For EEx ia approval power supply must not exceed 17.5VDC.
Intrinsic safety installation according to FISCO model.
Current consumption
operating (quiescent): 10.5mA
fault current limiting: 20mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2 with
transmission to Manchester II modulation, at 31.25kbit/sec.
Output interface
PROFIBUS PA communication according to Profibus DP50170 Part 2/
DIN 19245 part 1–3.
Output update time
25ms
Function blocks
2 analog input, 1 transducer, 1 physical
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of output in
percentage of the analog input function block assigned to the primary
variable.
User-definable matrix display mode:
– process variable in pressure units or
– primary variable in engineering units (output of transducer block) or
– output as percentage or engineering units of analog input function
blocks
Display also indicates diagnostic messages and provides
configuration facilities.
Secondary variable, static pressure and sensor temperature can be
read.
Transmitter failure mode
On gross transmitter failure condition, detected by self-diagnostics, the
output signal can be driven to defined conditions, selectable by the user
as safe, last valid or calculated value. If electronic failure or short circuit
occur the transmitter consumption is electronically limited at a defined
value (20mA approx), for safety of the network.
FOUNDATION Fieldbus output
Device type
LINK MASTER DEVICE
Link Active Scheduler (LAS) capability implemented.
Power supply
The transmitter operates from 9 to 32VDC, polarity independent.
For EEx ia approval power supply must not exceed 24VDC (entity
certification) or 17.5VDC (FISCO certification), according to FF–816.
Current consumption
operating (quiescent): 10.5mA
fault current limiting: 20mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2 with
transmission to Manchester II modulation, at 31.25kbit/sec.
Function blocks/execution period
2 standard Analog Input blocks/25ms max (each)
1 standard PID block/70ms max.
Additional blocks
1 standard Resource block,
1 custom Pressure with calibration transducer block.
Number of link objects
25
Number of VCRs
24
Output interface
FOUNDATION fieldbus digital communication protocol to standard H1,
compliant to specification V. 1.5; FF registration number IT019000.
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of output in
percentage of the analog input function block assigned to the primary
variable.
User-definable matrix display mode:
– process variable in pressure units or
– primary variable in engineering units (output of transducer block) or
– output as percentage or engineering units of analog input function
blocks
Display also indicates diagnostic messages and provides
configuration facilities.
Secondary variable, static pressure and sensor temperature can be
read.
Transmitter failure mode
The output signal is "frozen" to the last valid value on gross transmitter
failure condition, detected by self-diagnostics which also indicate a
BAD conditions. If electronic failure or short circuit occur the transmitter
consumption is electronically limited at a defined value (20mA approx),
for safety of the network.
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
8
Operating influences
Temperature effects
per 20K (36°F) ambient temperature change on transmitter sensor
between the limits of –20°C to +65°C (–4 to +150°F):
The total temperature error is the combination of the above
transmitter effect with seal errors, as appliclable due to application
temperatures.
Refer to seal data sheet for additional effects of the remote seal.
Optional CoMeter and ProMeter ambient temperature
Total reading error per 20K (36°F) change between the ambient limits
of –20 and +70°C (-4 and +158°F) :
±0.15% of max span (16mA).
Static pressure (zero errors can be calibrated out at line pressure)
for differential measurement per 2MPa, 20bar or 290psi.
Model 264DR with remote seal(s)
zero error: ±0.25% of URL
span error: ±0.25% of reading
Multiply by 1.5 the errors for sensor codes B and E and for sensor/
seal combinations marked (•)
Supply voltage
Within voltage/load specified limits the total effect is less than
0.005% of URL per volt.
Load
Within load/voltage specified limits the total effect is negligible.
Radio frequency interference
Total effect : less than 0.10% of span from 20 to 1000MHz and for
field strengths up to 30V/m when tested with shielded conduit and
grounding, with or without meter.
Common mode interference
No effect from 100Vrms @ 50Hz, or 50VDC
Vibration effect
±0.10% of URL (according to IEC 61298–3)
URL
Span
URL
Span
URL
Span
URL
Span
Performance specifications
Stated at reference condition to IEC 60770 ambient temperature of 20°C
(68°F), relative humidity of 65%, atmospheric pressure of 1013hPa
(1013mbar), mounting position with vertical diaphragm and zero based
range for transmitter with isolating diaphragms in AISI 316 L ss or Hastelloy
and silicone oil fill and HART digital trim values equal to 4–20mA span end
points, in linear mode.
Unless otherwise specified, errors are quoted as % of span.
Some performance data are affected by the actual turndown (TD) as ratio
between Upper Range Limit (URL) and calibrated span.
IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE
PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO
OPTIMIZE PERFORMANCE CHARACTERISTICS.
Accuracy rating
% of calibrated span, including combined effects of terminal based
linearity, hysteresis and repeatability.
For fieldbus versions SPAN refer to analog input function block outscale
range
Using remote seal sizes <DN 80/3in
±0.10% for TD from 1:1 to 10:1
(±0.10% for sensor codes B and E for TD from 1:1 to 5:1)
±0.01% x for TD from 10:1 to 20:1
±0.02% x for sensor codes B and E
for TD from 5:1 to 10:1)
Using remote seal sizes DN 80/3in
±0.075% for TD from 1:1 to 10:1
( ±0.10% for sensor codes B and E for TD from 1:1 to 5:1)
±0.0075% x for TD from 10:1 to 20:1
(±0.02% x for sensor codes B and E
for TD from 5:1 to 10:1)
Multiply the values by 1.5 for sensor/seal combination marked (•) and for
transmitter for absolute measurement.
ledoM rosneS
edoC
DTrof
otpu
RD462
RP462
SotE1:01)naps%560.0+LRU%40.0(±
B1:5)naps%01.0+LRU%60.0(±
RV462SotE1:01)naps%31.0+LRU%80.0(±
RN/RH462 SotG1:01)naps%560.0+LRU%40.0(±
RH462 V1:01)naps%01.0+LRU%60.0(±
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
9
Physical Specification
(Refer to ordering information sheets for variant availability related to
specific model or versions code)
Materials
Model 264DR only – Side without seal
Process isolating diaphragms (*)
AISI 316 L ss; Hastelloy C276™; Monel 400™; Tantalum;
Hastelloy C276™ on AISI 316 L ss gasket seat.
A remote seal can be selected with required diaphragm (refer below)
Process flanges, adapters, plugs and drain/vent valves (*)
AISI 316 L ss; Hastelloy C276™; Monel 400™.
Bolts and nuts
AISI 316 ss bolts and nuts Class A4–50 per UNI 7323 (ISO 3506), in
compliance with NACE MR0175 Class II.
Gaskets (*)
Viton™; PTFE.
Models 264DR/PR/VR/HR/NR
Blind flange (reference and/or remote seal(s) side)
AISI 316 L ss
Seal side process diaphragm (remote seal) (*)
AISI 316 L ss; Hastelloy C276™, Tantalum;
AISI 316 L ss or Hastelloy C276™ with anti-stick coating;
AISI 316 L ss with anti-corrosion coating, AISI 316 L ss Urea Grade.
Extension material
AISI 316 L ss; Hastelloy C276™; AISI 316 L ss or Hastelloy C276™
with coating same as diaphragm.
Seal side fill fluid (remote seal)
Silicone oil-DC200™, Silicone oil-AN140™, Inert-Halocarbon™4.2,
Inert-Galden™, Silicone Polymer-Syltherm XTL™, Vegetable oil-
Neobee M-20™, Glycerin Water, Mineral oil-MARCOL 82™,
ABB fill.
Sensor fill fluid
Silicone oil (DC200); inert fill (Halocarbon™4.2 or Galden™).
Sensor housing
AISI 316 L ss.
Electronic housing and covers
Barrel version
– Copper-free content aluminium alloy with baked epoxy finish;
– Low-copper content aluminium alloy with baked epoxy finish;
– AISI 316 L ss.
DIN version
Low-copper content aluminium alloy with baked epoxy finish.
Covers O-ring
Buna N.
Local zero and span adjustments:
Glass filled polycarbonate plastic (removable).
Tagging
AISI 316ss data plate attached to the electronics housing.
Calibration
Standard: at maximum span, zero based range, ambient temperature
and pressure;
Optional: at specified range and ambient conditions;.
Optional extras
Output indicator
plug-in rotatable type, LCD or analog.
Supplemental customer tag
AISI 316 ss tag screwed/fastened to the transmitter for customer's tag
data up to a maximum of 20 characters and spaces on one line for tag
number and tag name, and up to a maximum of 3 spaced strings of 10
characters each for calibration details (lower and upper values plus
unit). Special typing evaluated on request for charges.
Surge protection (only as external unit for PROFIBUS PA and FF)
Cleaning procedure for oxygen service
Hydrogen or special service preparation
Test Certificates (test, design, calibration, material traceability)
Tag and manual language
Communication connectors
Process connections
on conventional flanges : 1/4in NPT on process axis
on adapters : 1/2in NPT on process axis
fixing threads: 7/16in–20 UNF at 41.3mm centre distance
Refer to seal data sheet for process connection variants through
remote seal.
Electrical connections
Two 1/2 NPT or M20x1.5 or PG 13.5 or 1/2 GK threaded conduit
entries, direct on housing.
Special communication connector (on request)
– HART : straight or angle Harting Han connector and one plug.
– FOUNDATION Fieldbus, PROFIBUS PA: M12x1 or 7/8.
Terminal block
HART version: three terminals for signal/external meter wiring up to
2.5mm2 (14AWG) and three connection points for test and
communication purposes.
Fieldbus versions: two terminals for signal wiring (bus connection)
up to 2.5mm2 (14AWG)
Grounding
Internal and external 6mm2 (10AWG) ground termination points are
provided.
Mounting position
Transmitter can be mounted in any position.
Electronics housing may be rotated to any position. A positive stop
prevents over travel.
Mass (without options and seals)
– models 264DR/PR/VR : 3kg approx (7lb)
models 264HR/NR: 1.7kg approx (4lb)
Add 1.5kg (3.4lb) for AISI housing.
Add 650g (1.5lb) for packing.
Packing
Carton
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
10
Configuration
Transmitter with HART communication and 4 to 20 mA
Standard configuration
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the tag plate. If a
calibration range and tag data are not specified, the transmitter will be
supplied with the plate left blank and configured as follows:
Engineering Unit Specify from table
4 mA Zero
20 mA Upper Range Limit (URL)
Output Linear
Damping 1 sec.
Transmitter failure mode Upscale
Software tag characters Blank
Optional LCD indicator/display 0 to 100.0% linear
Any or all the above configurable parameters, including Lower range–value
and Upper range-value which must be the same unit of measure, can be
easily changed using the HART hand–held communicator or by a PC
running the configuration software SMART VISION with DTM for 2600T.
The transmitter database is customized with specified flange type and
material, O–ring and drain/vent materials and meter code option.
Custom configuration (option)
The following data may be specified in addition to the standard
configuration parameters:
Descriptor 16 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
Transmitter with PROFIBUS PA communication
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the tag plate. If a
calibration range and tag data are not specified, the transmitter will be
supplied with the plate left blank and configured as follows:
Measure Profile Pressure
Engineering Unit kPa
Output scale 0% Lower Range Limit (LRL)
Output scale 100% Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)
Low-Low Limit Lower Range Limit (LRL)
Limits hysteresis 0.5% of output scale
PV filter 0 sec.
Address (settable by local key) 126
Tag 32 alphanumeric characters
Any or all the above configurable parameters, including Lower range-value
and Upper range–value which must be the same unit of measure, can be
easily changed by a PC running the configuration software SMART VISION
with DTM for 2600T.
The transmitter database is customized with specified flange type and
material, O–ring and drain/vent materials and meter code option.
Custom configuration (option)
The following data may be specified in addition to the standard
configuration parameters:
Descriptor 32 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
Transmitter with FOUNDATION Fieldbus
communication
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the tag plate. If a
calibration range and tag data are not specified, the transmitter will be
supplied with the plate left blank and the analog input function block FB1
is configured as follows:
Measure Profile Pressure
Engineering Unit kPa
Output scale 0% Lower Range Limit (LRL)
Output scale 100% Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit : Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)
Low-Low Limit Lower Range Limit (LRL)
Limits hysteresis 0.5% of output scale
PV filter time 0 sec.
Tag 32 alphanumeric characters
The analog input function block FB2 is configured for the sensor tempe-
rature measured in °C. Any or all the above configurable parameters,
including the range values, can be changed using any host compliant to
FOUNDATION fieldbus. The transmitter database is customized with
specified flange type and material, O–ring and drain/vent materials and
meter code option.
For any protocol available engineering units of pressure measure are :
Pa, kPa, MPa
inH2O@4°C, mmH2O@4°C, psi
inH2O@20°C, ftH2O@20°C, mmH2O@20°C
inHg, mmHg, Torr
g/cm2, kg/cm2, atm
mbar, bar
™ Hastelloy is a Cabot Corporation trademark
™ Monel is an International Nickel Co. trademark
™ Viton is a Dupont de Nemour trademark
™ DC200 is a Dow Corning Corporation trademark
™ Galden is a Montefluos trademark
™ Halocarbon is a Halocarbon Products Co. trademark
™ AN140 is a Wacker-Chemie trademarl
™ Neobee M20 is a Stepan Company trademark
™ Marcol is a Esso Italiana trademarl
™ Syltherm is a Dow Chemical Company trademark
(*) Wetted parts of the transmitter.
(**) U-bolt material: AISI 400 ss; screws material: high-strength alloy steel or
AISI 316 ss.
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
11
MOUNTING DIMENSIONS (not for construction unless certified) - dimensions in mm (in)
264DR/PR/VR transmitter on bracket for vertical or horizontal 60mm (2in) pipe mounting (barrel housing)
Consider one capillary only to remote seal for 264PR/VR
Certification
label
Identification tag
Adjustments
Terminal
side
Electronic
side
Integral
display
housing
Min. clearance
to remove
the cover
Output meter
housing
Barrel type
housing
Electrical
connections
Cover locking
screw
166 (6.54)
38 (1.50) 51 (2.01)
41.3 (1.63)
63 (2.48)
55 (2.17)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
86 (3.39)
Note : For 264DR side with 1/4in – 18NPT thread director with 1/2in – 14NPT through adapter, threaded process connection, gasket
groove and gaskets are in accordance with DIN 19213.
Bolting threads for fixing adapter or other devices (i.e. manifod etc.) on process flange is 7/16in–20 UNF.
Flange
To remote
seal
54 (2.13)
62 (2.44) 43 (1.69)
135 (5.31)
+
82 (3.23)
127 (5.00)
17 (0.67)
26 (1.02)
17 (0.67)
36 (1.42)
43 (1.69 71 (2.80)
54 (2.13)
135 (5.31)
+
82 (3.23)
127 (5.00)
17 (0.67)
26 (1.02)
17 (0.67)
36 (1.42)
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
12
264DR/PR/VR transmitter on bracket for vertical or horizontal 60mm (2in) pipe mounting (DIN housing)
Electrical
connections
17 (0.67)
41.3 (1.63)
63 (2.48)
179 (7.05)
38 (1.50)
51 (2.01)
55 (2.17)
148 (5.83)
36 (1.42)
26 (1.02)
17 (0.67)
82 (3.23)
102 (4.02)
82 (3.23)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
264DR/PR/VR transmitter on bracket for vertical or horizontal 60mm (2in) pipe mounting
Cover locking
screw
Certification
label
Identification
tag
To remote
seal
DIN type
housing
Terminal side
External
ground
Flange
Electronic
side
Certification
label
Adjustments
Output meter
housing
Consider one capillary only to remote seal for 264PR/VR
55 (2.17) max 7 (0.28)
142 (5.59)
86 (3.39)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
13
25 (0.98)
47 (1.85)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
70 (2.75)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
264DR/PR/VR transmitter on bracket for wall mounting (by four M8 screws)
264DR/PR/VR transmitter on flat type (for box) bracket for vertical or horizontal 60mm (2in) pipe mounting
70 (2.75)
70 (2.75)
25 (1)
Consider one capillary only to remote seal for 264PR/VR
204 (8.03)
70 (2.75)
84 (3.31)
70 (2.75)
98 (3.86)
+
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
14
170 (6.69)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
86 (3.39)
18 (0.71)
ø 65 (2.56)
135 (5.31)
16 (063)
13 (0.51)
40 (1.57)
100 (3.94)
127 (5.00)
17 (0.67)
26 (1.02)
17 (0.67)
36 (1.42)
Electrical
connections
Cover locking
screw
To remote
seal
Min. Bend Radius
150 (6)
264HR/NR transmitter on bracket for 60mm (2in) pipe mounting (barrel housing)
Sensors G, H, M, P, Q, S
264HR transmitter on bracket for 60mm (2in) pipe mounting (barrel housing)
Sensor V
100 (3.94)
56 (2.20)
135 (5.31)
46 (1.81)
127 (5.00)
17 (0.67)
26 (1.02)
17 (0.67)
36 (1.42)
40 (1.57)
86 (3.39)
S
N
O
S
S
T
I
U
C
R
I
C
S
E
L
N
O
I
N
E
T
S
O
S
T
U
R
R
E
V
U
O
C
E
L
R
E
D
R
A
G
T
N
E'
M
E
F
N
E
B
E
L
C
I
Q
U
A
T
E
A
L
S
T
I
U
C
R
I
C
I
V
E
H
C
O
P
E
E
K
V
E
R
T
I
G
T
E
H
W
N
!
Electrical
connections
Cover locking
screw
Min. Bend Radius
150 (6)
To remote
seal
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
15
Electrical connections
HART Version
FIELDBUS Versions
+
+
-
-
+
+
-
-
691HT
A B C
1
D E F
2
G H I
3
J K L
4
M N O
5
P Q R
6
S T U
7
V W X
8
Y Z #
9
@ %
& /
0+
-
PV
REVIEW SERIAL
LINK
TRIM
F1 F2 F3 F4
CONF
M
Kent-Taylor
0
4
3
5
6
7
8
9
10
20
40
0
60
100
%
2
80
M+
-
-
1
54 6
238
7
+
TEST COMM
Internal ground
termination point
Fieldbus line
(polarity independent)
External ground
termination point
Test points
4 to 20mA
Harting
pin (male)
identification
Internal ground
termination point
External ground
termination point
Hand-held
communicator
GND
Line load
Remote
indicator
Power
source
250 ohm min
Receiver
HART hand-held communicator may be connected at any wiring termination point in the loop, providing the minimum resistance
is 250 ohm. If this is less than 250 ohm, additional resistance should be added to allow communications
Optional
BUS CONNECTIONS
2
1
4
3
13
42
7/8” connector
M12 x 1 connector
NOITACIFITNEDI)elam(NIP
NOITADNUOF
subdleiF
SUBIFORP
AP
11
1
11
22
2
22
33
3
33
44
4
44
-FF
+FF
DLEIHS
DNUORG
+AP
DNUORG
AP
DLEIHS
Mating female plug NOT SUPPLIED
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
16
BASIC ORDERING INFORMATION model 264DR Differential Pressure Transmitter with remote
seal(s)
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
Quote separately one or two seals as required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 4 D RXSXXX deunitnoC
%570.0YCARUCCAESAB)s(laesetomerhtiwrettimsnarTerusserPlaitnereffiD
stimilnapS-ROSNES 6
ht
retcarahc
aPk4dna2.0
aPk61dna45.0
aPk04dna76.0
aPk56dna1.1
aPk061dna76.2
aPk006dna01
aPk0042dna04
aPk0008dna431
aPk00061dna762
rabm04dna2
rabm061dna4.5
rabm004dna7.6
rabm056dna11
rabm0061dna7.62
rab6dna1.0
rab42dna4.0
rab08dna43.1
rab061dna76.2
Hni61dna8.0
2
O
Hni46dna61.2
2
O
Hni061dna76.2
2
O
Hni062dna53.4
2
O
Hni246dna7.01
2
O
isp78dna54.1
isp843dna8.5
isp0611dna4.91
isp0232dna7.83
B
E
F
G
H
M
P
Q
S
edocesU 7
ht
retcarahc
)strapdettew(diulflliF/lairetammgarhpaiD 8
ht
retcarahc
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
ssL613ISIA
)taesISIAno(672CyolletsaH
672CyolletsaH
004lenoM
mulatnaT
ssL613ISIA
ssL613ISIA
ssL613ISIA
lioenociliS
lioenociliS
lioenociliS
lioenociliS
lioenociliS
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nedlaG-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
nobracolaH-diulftrenI
lioenociliS
nedlaG-diulftrenI
nobracolaH-diulftrenI
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotslaesowt(
)yletarapesdetouqebotslaesowt(
)yletarapesdetouqebotslaesowt(
)3etoN(
)3etoN(
)3etoN(
)3etoN(
)3etoN(
)3,1setoN(
)3,1setoN(
)3,1setoN(
)3,1setoN(
)3,1setoN(
)3,1setoN(
)3,1setoN(
)3,1setoN(
)3,1setoN(
)3,1setoN(
)2etoN(
)3,1setoN(
)3,1setoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
S
H
K
M
T
A
B
F
C
D
L
Q
P
4
5
R
2
W
)strapdettew(noitcennocdnalairetamsretpada/segnalfssecorP –9
ht
retcarahc
noitcurtsnocslaesowtrofssL613ISIA
)noitcennoclatnoziroH(ssL613ISIA
)noitcennoclatnoziroH(ssL613ISIA
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
)4etoN(
)5etoN(
)5etoN(
)5etoN(
)5etoN(
)5etoN(
)5etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
R
A
B
)noitcennoclatnoziroH(672CyolletsaH
)noitcennoclatnoziroH(672CyolletsaH
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
D
E
)noitcennoclatnoziroH(004lenoM
)noitcennoclatnoziroH(004lenoM
1
/
4
(tceridf-TPNni
7
/
61
)gnillird.S.UFNUni
1
/
2
(retpadahguorhtf-TPNni
7
/
61
)gnillird.S.UFNUni
G
H
)strapdettew(teksaG/stloB 01
ht
retcarahc
noitcurtsnocslaesowtrofsteksagtuohtiw)ECAN(ss613ISIA
ss613ISIA
ss613ISIA
)ECAN(ss613ISIA
)ECAN(ss613ISIA
notiV
EFTP
notiV
EFTP
)4etoN(
)5etoN(
)5,1setoN(
)5etoN(
)5,1setoN(
ECAN
ECAN
ECAN
R
1
2
3
4
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
17
RD462NOITAMROFNIGNIREDROCISAB XX
noitcennoclacirtcelednalairetamgnisuoH 11
ht
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()6etoN(
)ylnoesopruplareneg()6etoN(
)ylnoesopruplareneg()6etoN(
)ylnoesopruplareneg()6etoN(
)ylnoesopruplareneg()6etoN(
)ylnoesopruplareneg(
)ylnoesopruplareneg(
)ylnoesopruplareneg()6etoN(
)ylnoesopruplareneg()6etoN(
A
B
D
C
E
G
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
H
L
N
M
P
R
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocsubdleiF
S
T
V
U
Z
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)02MC(5.1x02M
5.31gP
rotcennocnaHgnitraH
rotcennocsubdleiF
J
Y
K
W
snoitpolanoitiddA/tuptuO 21
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
APSUBIFORP
APSUBIFORP
subdleiFNOITADNUOF
subdleiFNOITADNUOF
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)8,7setoN(
)7etoN(
)8,7setoN(
)8etoN(
)8,7setoN(
)8etoN(
H
1
P
2
F
3
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
18
ADDITIONAL ORDERING INFORMATION for model 264DR
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XXXX XXXX XXXX XXXX XXXX XXXX XXXX
)strapdettew()noitisopdnalairetam(evlavtnev/niarD
ssL613ISIA
ssL613ISIA
ssL613ISIA
672CyolletsaH
672CyolletsaH
672CyolletsaH
004lenoM
004lenoM
004lenoM
sixassecorpno
potedisegnalfno
mottobedisegnalfno
sixassecorpno
potedisegnalfno
mottobedisegnalfno
sixassecorpno
potedisegnalfno
mottobedisegnalfno
)9etoN(
)9etoN(
)9etoN(
)01etoN(
)01etoN(
)01etoN(
)11etoN(
)11etoN(
)11etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
1V
2V
3V
4V
5V
6V
7V
8V
9V
noitacifitreclacirtcelE aixEEytefaScisnirtnIDG1yrogetaCIIpuorGXETA
dxEEfoorpemalFDG2/1yrogetaCIIpuorGXETA
)21etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC
1
/
2
)gnisuoh5.31gPdna02M,TPNni
)21etoN(5T/6TCIIdxE+4T/5T/6TCIIaixEAASailartsuAsdradnatSotfoorpemalFytefaScisnirtnI
htiwylno(lavorppa)MF(lautuMyrotcaF
1
/
2
)noitcennoclacirtcele5.31gPdna02M,TPNni
1E
2E
3E
4E
5E
6E
retemtuptuO
noitarbilacdradnatS,reteMorP
noitarbilaclaicepS,reteMorP
elacs%0010raenilrotacidnituptuogolanA
elacs010toorerauqsrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)elacstoorerauqsrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)noitarugifnocremotsucreteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
)21etoN(
1D
2D
3D
4D
5D
6D
7D
8D
DCLlargetnI
yalpsidlargetniDCLlatigiD 1L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomepiproF
gnitnuomllawroF
gnitnuomllawroF
xobrofepyttalF
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
leetsnobraC
ssL613ISIA
leetsnobraC
ssL613ISIA
ssL613ISIA
1B
2B
3B
4B
5B
egruS
rotcetorPtneisnarT/egruS )21etoN( 1S
launamgnitarepO
namreG
nailatI
hcnerF
1M
2M
4M
egaugnalgat&slebaL
namreG
nailatI
hcnerF
1T
2T
4T
etalpgatlanoitiddA
etalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoC
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°4taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°4taisp/O
motsuC
2N
3N
4N
5N
6N
erudecorpnoitaraperP
P)teksagEFTPdnalliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
=xam
T;nobracolaHrofaPM9ronedlaGrofaPM21
=xam
F°041/C°06
noitaraperpecivresnegordyH
noitaraperpsecivreslaicepS
1P
2P
4P
setacifitreC
)tniop-9(noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
1C
6C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
1H
3H
rotcennoC
8/7subdleiF
1x21MsubdleiF
yrtnethgiartsnaHgnitraH
yrtneelgnanaHgnitraH
)subdleiFNOITADNUOFrofDEDNEMMOCER(
)APSUBIFORProfDEDNEMMOCER(
)31,8setoN(
)31,8setoN(
)31,7setoN(
)31,7setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
19
Note 1: Suitable for oxygen service
Note 2: Not wetted – Hastelloy C276™ on AISI seat for sensor code B
Note 3: Not wetted – Not available with sensor code B
Note 4: Not available with diaphragm/fill code S, H, K, M, T, A, B, F, C, D, L, Q, P, 4, 5
Note 5: Not available with diaphragm/fill code R, 2, W.
Note 6: Select type in additional ordering code
Note 7: Not available with Electronic Housing code Z, R, G and W
Note 8: Not available with Electronic Housing code P, E and K
Note 9: Not available with Process flanges/adapters code D, E, G, H, R
Note 10: Not available with Process flanges/adapters code A, B, G, H, R
Note 11: Not available with Process flanges/adapters code A, B, D, E, R
Note 12: Not available with PROFIBUS PA and FF output code 2 or 3
Note 13: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B, J, Y
Hastelloy is a Cabot Corporation trademark
Monel is an International Nickel Co. trademark
Viton is a Dupont de Nemour trademark
Galden is a Montefluos trademark
Halocarbon is a Halocarbon Products Co. trademark
Standard delivery items (can be differently specified by additional ordering code)
Adapters supplied loose
Plug on axis (no drain/vent valves)
General purpose (no electrical certification)
No meter/display, no mounting bracket, no surge protection
English manual and labels
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
20
BASIC ORDERING INFORMATION model 264PR Gauge Pressure Transmitter with remote seal
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 4 P RXSXXXXX
%570.0YCARUCCAESABlaesetomerhtiwrettimsnarTerusserPeguaG
stimilnapS-ROSNES 6
ht
retcarahc
aPk61dna45.0
aPk04dna76.0
aPk56dna1.1
aPk061dna76.2
aPk006dna01
aPk0042dna04
aPk0008dna431
aPk00061dna762
rabm061dna4.5
rabm004dna7.6
rabm056dna11
rabm0061dna7.62
rab6dna1.0
rab42dna4.0
rab08dna43.1
rab061dna76.2
Hni46dna61.2
2
O
Hni061dna76.2
2
O
Hni062dna53.4
2
O
Hni246dna7.01
2
O
isp78dna54.1
isp843dna8.5
isp0611dna4.91
isp0232dna7.83
E
F
G
H
M
P
Q
S
edocesU 7
ht
retcarahc
diulflliF/lairetammgarhpaiD 8
ht
retcarahc
ssL613ISIA
ssL613ISIA
ssL613ISIA
lioenociliS
nedlaG-diulftrenI
nobracolaH-diulftrenI
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaeseno(
)1etoN(
)1etoN(
R
2
W
lairetamsretpada/segnalfssecorP –9
ht
retcarahc
noitcurtsnoclaesrofssL613ISIA R
stloB 01
ht
retcarahc
noitcurtsnoclaesrofsteksagtuohtiw)ECAN(ss613ISIA ECANR
noitcennoclacirtcelednalairetamgnisuoH 11
ht
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocsubdleiF
)02MC(5.1x02M
5.31gP
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg(
)ylnoesopruplareneg(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
A
B
D
C
E
G
H
L
N
M
P
R
S
T
V
U
Z
J
Y
K
W
snoitpolanoitiddA/tuptuO 21
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
APSUBIFORP
APSUBIFORP
subdleiFNOITADNUOF
subdleiFNOITADNUOF
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)4,3setoN(
)3etoN(
)4,3setoN(
)4etoN(
)4,3setoN(
)4etoN(
H
1
P
2
F
3
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
21
ADDITIONAL ORDERING INFORMATION for model 264PR
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XX XXXX XXXX XXXX XXXX XXXX XXXX
noitacifitreclacirtcelE aixEEytefaScisnirtnIDG1yrogetaCIIpuorGXETA
dxEEfoorpemalFDG2/1yrogetaCIIpuorGXETA
)5etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC
1
/
2
)gnisuoh5.31gPdna02M,TPNni
)5etoN(5T/6TCIIdxE+4T/5T/6TCIIaixEAASailartsuAsdradnatSotfoorpemalFytefaScisnirtnI
htiwylno(lavorppa)MF(lautuMyrotcaF
1
/
2
)noitcennoclacirtcele5.31gPdna02M,TPNni
1E
2E
3E
4E
5E
6E
retemtuptuO
noitarbilacdradnatS,reteMorP
noitarbilaclaicepS,reteMorP
elacs%0010raenilrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)noitarugifnocremotsucreteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)5etoN(
)5etoN(
)5etoN(
)5etoN(
)5etoN(
)5etoN(
1D
2D
3D
5D
7D
8D
DCLlargetnI
yalpsidlargetniDCLlatigiD 1L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomepiproF
gnitnuomllawroF
gnitnuomllawroF
xobrofepyttalF
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
leetsnobraC
ssL613ISIA
leetsnobraC
ssL613ISIA
ssL613ISIA
1B
2B
3B
4B
5B
egruS
rotcetorPtneisnarT/egruS )5etoN( 1S
launamgnitarepO
namreG
nailatI
hcnerF
1M
2M
4M
egaugnalgat&slebaL
namreG
nailatI
hcnerF
1T
2T
4T
etalpgatlanoitiddA
etalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoC
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°4taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°4taisp/O
motsuC
2N
3N
4N
5N
6N
erudecorpnoitaraperP
P)lliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
=xam
T;nobracolaHrofaPM9ronedlaGrofaPM21
=xam
F°041/C°06
noitaraperpecivresnegordyH
noitaraperpsecivreslaicepS
1P
2P
4P
setacifitreC
)tniop-9(noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
1C
6C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
1H
3H
rotcennoC
8/7subdleiF
1x21MsubdleiF
yrtnethgiartsnaHgnitraH
yrtneelgnanaHgnitraH
)subdleiFNOITADNUOFrofDEDNEMMOCER(
)APSUBIFORProfDEDNEMMOCER(
)6,4setoN(
)6,4setoN(
)6,3setoN(
)6,3setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
22
Note 1: Suitable for oxygen service
Note 2: Select type in additional ordering code
Note 3: Not available with Electronic Housing code Z, R, G and W
Note 4: Not available with Electronic Housing code P, E and K
Note 5: Not available with PROFIBUS PA and FF output code 2 or 3
Note 6: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B, J, Y
Galden is a Montefluos trademark
Halocarbon is a Halocarbon Products Co. trademark
Standard delivery items (can be differently specified by additional ordering code)
General purpose (no electrical certification)
No meter/display, no mounting bracket, no surge protection
English manual and labels
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
23
BASIC ORDERING INFORMATION model 264HR Gauge Pressure Transmitter with remote seal
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 4 H RXXXXX
%570.0YCARUCCAESABlaesetomerhtiwrettimsnarTerusserPeguaG
stimilnapS-ROSNES 6
ht
retcarahc
aPk56dna1.1
aPk061dna76.2
aPk006dna01
aPk0042dna04
aPk0008dna431
aPk00061dna762
aPk00006dna0002
rabm056dna11
rabm0061dna7.62
rab6dna1.0
rab42dna4.0
rab08dna43.1
rab061dna76.2
rab006dna02
Hni062dna53.4
2
O
Hni246dna7.01
2
O
isp78dna54.1
isp843dna8.5
isp0611dna4.91
isp0232dna7.83
isp0078dna092
G
H
M
P
Q
S
V
diulflliF/lairetammgarhpaiD 7
ht
retcarahc
)Vrosnesrof672CyolletsaH(ssL613ISIA
ssL613ISIA
ssL613ISIA
lioenociliS
nedlaG-diulftrenI
nobracolaH-diulftrenI
)1etoN(
)1etoN(
R
2
W
noitcennocssecorP –8
ht
retcarahc
)epytnottubtpecxe(laesetomeR
laesetomerepytnottuB
)yletarapesdetouqebotlaeseno(
)yletarapesdetouqebotlaesnottubeno()2etoN(
R
G
noitcennoclacirtcelednalairetamgnisuoH 9
ht
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
A
B
D
C
E
G
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
H
L
N
M
P
R
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocsubdleiF
S
T
V
U
Z
snoitpolanoitiddA/tuptuO 01
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
APSUBIFORP
APSUBIFORP
subdleiFNOITADNUOF
subdleiFNOITADNUOF
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)5,4setoN(
)4etoN(
)5,4setoN(
)5etoN(
)5,4setoN(
)5etoN(
H
1
P
2
F
3
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
24
ADDITIONAL ORDERING INFORMATION for model 264HR
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XX XXXX XXXX XXXX XXXX XXXX XXXX
noitacifitreclacirtcelE
aixEEytefaScisnirtnIDG1yrogetaCIIpuorGXETA
dxEEfoorpemalFDG2/1yrogetaCIIpuorGXETA
)6etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC
1
/
2
)gnisuoh5,31gPdna02M,TPNni
)6etoN(5T/6TCIIdxE+4T/5T/6TCIIaixEAASailartsuAsdradnatSotfoorpemalFytefaScisnirtnI
htiwylno(lavorppa)MF(lautuMyrotcaF
1
/
2
)noitcennoclacirtcele5,31gPdna02M,TPNni
1E
2E
3E
4E
5E
6E
retemtuptuO
noitarbilacdradnatS,reteMorP
noitarbilaclaicepS,reteMorP
elacs%0010raenilrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)noitarugifnocremotsucreteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)6etoN(
)6etoN(
)6etoN(
)6etoN(
)6etoN(
)6etoN(
1D
2D
3D
5D
7D
8D
DCLlargetnI
yalpsidlargetniDCLlatigiD 1L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomepiproF
)gnisuohISIArofelbatiustoN( leetsnobraC
ssL613ISIA
1B
2B
egruS
rotcetorPtneisnarT/egruS )6etoN( 1S
launamgnitarepO
namreG
nailatI
hcnerF
1M
2M
4M
egaugnalgat&slebaL
namreG
nailatI
hcnerF
1T
2T
4T
etalpgatlanoitiddA
etalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoC
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°4taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°4taisp/O
motsuC
2N
3N
4N
5N
6N
erudecorpnoitaraperP
P)lliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
=xam
T;nobracolaHrofaPM9ronedlaGrofaPM21
=xam
F°041/C°06 1P
setacifitreC
)tniop-9(noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
1C
6C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
1H
3H
rotcennoC
8/7subdleiF
1x21MsubdleiF
yrtnethgiartsnaHgnitraH
yrtneelgnanaHgnitraH
)subdleiFNOITADNUOFrofDEDNEMMOCER(
)APSUBIFORProfDEDNEMMOCER(
)7,5setoN(
)7,5setoN(
)7,4setoN(
)7,4setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
25
Note 1: Suitable for oxygen service - NOT AVAILABLE FOR SENSOR V
Note 2: Not available with sensor code G, H, M, P
Note 3: Select type in additional ordering code
Note 4: Not available with Electronic Housing code Z, R, G
Note 5: Not available with Electronic Housing code P, E
Note 6: Not available with PROFIBUS PA and FF output code 2 or 3
Note 7: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B
Galden is a Montefluos trademark
Halocarbon is a Halocarbon Products Co. trademark
Standard delivery items (can be differently specified by additional ordering code)
General purpose (no electrical certification)
No meter/display, no mounting bracket, no surge protection
English manual and labels
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
26
BASIC ORDERING INFORMATION model 264VR Absolute Pressure Transmitter with remote seal
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 4 V RXSXXXXX
%570.0YCARUCCAESABlaesetomerhtiwrettimsnarTerusserPetulosbA
stimilnapS-ROSNES 6
ht
retcarahc
aPk61dna45.0
aPk04dna76.0
aPk56dna1.1
aPk061dna76.2
aPk006dna01
aPk0042dna04
aPk0008dna431
aPk00061dna762
rabm061dna4.5
rabm004dna7.6
rabm056dna11
rabm0061dna7.62
rab6dna1.0
rab42dna4.0
rab08dna43.1
rab061dna76.2
gHmm021dna4
gHmm003dna5
gHmm084dna8
gHmm0021dna02
isp78dna54.1
isp843dna8.5
isp0611dna4.91
isp0232dna7.83
E
F
G
H
M
P
Q
S
edocesU 7
ht
retcarahc
diulflliF/lairetammgarhpaiD 8
ht
retcarahc
ssL613ISIA
ssL613ISIA
ssL613ISIA
lioenociliS
nedlaG-diulftrenI
nobracolaH-diulftrenI
)yletarapesdetouqebotepytnoinutpecxelaeseno(
)yletarapesdetouqebotepytnoinutpecxelaeseno(
)yletarapesdetouqebotepytnoinutpecxelaeseno(
)1etoN(
)1etoN(
R
2
W
lairetamsretpada/segnalfssecorP –9
ht
retcarahc
noitcurtsnoclaesrofssL613ISIA R
stloB 01
ht
retcarahc
noitcurtsnoclaesrofsteksagtuohtiw)ECAN(ss613ISIA ECANR
noitcennoclacirtcelednalairetamgnisuoH 11
ht
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocsubdleiF
)02MC(5.1x02M
5.31gP
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg(
)ylnoesopruplareneg(
)ylnoesopruplareneg()2etoN(
)ylnoesopruplareneg()2etoN(
A
B
D
C
E
G
H
L
N
M
P
R
S
T
V
U
Z
J
Y
K
W
snoitpolanoitiddA/tuptuO 21
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
APSUBIFORP
APSUBIFORP
subdleiFNOITADNUOF
subdleiFNOITADNUOF
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)4,3setoN(
)3etoN(
)4,3setoN(
)4etoN(
)4,3setoN(
)4etoN(
H
1
P
2
F
3
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
27
ADDITIONAL ORDERING INFORMATION for model 264VR
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XX XXXX XXXX XXXX XXXX XXXX XXXX
noitacifitreclacirtcelE aixEEytefaScisnirtnIDG1yrogetaCIIpuorGXETA
dxEEfoorpemalFDG2/1yrogetaCIIpuorGXETA
)5etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC
1
/
2
)gnisuoh5.31gPdna02M,TPNni
)5etoN(5T/6TCIIdxE+4T/5T/6TCIIaixEAASailartsuAsdradnatSotfoorpemalFytefaScisnirtnI
htiwylno(lavorppa)MF(lautuMyrotcaF
1
/
2
)noitcennoclacirtcele5.31gPdna02M,TPNni
1E
2E
3E
4E
5E
6E
retemtuptuO
noitarbilacdradnatS,reteMorP
noitarbilaclaicepS,reteMorP
elacs%0010raenilrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)noitarugifnocremotsucreteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)5etoN(
)5etoN(
)5etoN(
)5etoN(
)5etoN(
)5etoN(
1D
2D
3D
5D
7D
8D
DCLlargetnI
yalpsidlargetniDCLlatigiD 1L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomepiproF
gnitnuomllawroF
gnitnuomllawroF
xobrofepyttalF
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
)gnisuohISIArofelbatiustoN(
leetsnobraC
ssL613ISIA
leetsnobraC
ssL613ISIA
ssL613ISIA
1B
2B
3B
4B
5B
egruS
rotcetorPtneisnarT/egruS )5etoN( 1S
launamgnitarepO
namreG
nailatI
hcnerF
1M
2M
4M
egaugnalgat&slebaL
namreG
nailatI
hcnerF
1T
2T
4T
etalpgatlanoitiddA
etalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoC
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°4taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°4taisp/O
motsuC
2N
3N
4N
5N
6N
erudecorpnoitaraperP
P)lliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
=xam
T;nobracolaHrofaPM9ronedlaGrofaPM21
=xam
F°041/C°06
noitaraperpecivresnegordyH
noitaraperpsecivreslaicepS
1P
2P
4P
setacifitreC
)tniop-9(noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
1C
6C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
1H
3H
rotcennoC
8/7subdleiF
1x21MsubdleiF
yrtnethgiartsnaHgnitraH
yrtneelgnanaHgnitraH
)subdleiFNOITADNUOFrofDEDNEMMOCER(
)APSUBIFORProfDEDNEMMOCER(
)6,4setoN(
)6,4setoN(
)6,3setoN(
)6,3setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
28
Note 1: Suitable for oxygen service
Note 2: Select type in additional ordering code
Note 3: Not available with Electronic Housing code Z, R, G and W
Note 4: Not available with Electronic Housing code P, E and K
Note 5: Not available with PROFIBUS PA and FF output code 2 or 3
Note 6: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B, J,
Galden is a Montefluos trademark
Halocarbon is a Halocarbon Products Co. trademark
Standard delivery items (can be differently specified by additional ordering code)
General purpose (no electrical certification)
No meter/display, no mounting bracket, no surge protection
English manual and labels
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
29
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
BASIC ORDERING INFORMATION model 264NR Absolute Pressure Transmitter with remote seal
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 4 N RXXXXX
%570.0YCARUCCAESABlaesetomerhtiwrettimsnarTerusserPetulosbA
stimilnapS-ROSNES 6
ht
retcarahc
aPk56dna1.1
aPk061dna76.2
aPk006dna01
aPk0042dna04
aPk0008dna431
aPk00061dna762
rabm056dna11
rabm0061dna7.62
rab6dna1.0
rab42dna4.0
rab08dna43.1
rab061dna76.2
gHmm084dna8
gHmm0021dna02
isp78dna54.1
isp843dna8.5
isp0611dna4.91
isp0232dna7.83
G
H
M
P
Q
S
diulflliF/lairetammgarhpaiD 7
ht
retcarahc
ssL613ISIA
ssL613ISIA
ssL613ISIA
lioenociliS
nedlaG-diulftrenI
nobracolaH-diulftrenI
)1etoN(
)1etoN(
R
2
W
noitcennocssecorP –8
ht
retcarahc
laesetomeR
laesetomerepytnottuB
)yletarapesdetouqebotsepytnoinudnanottubtpecxelaeseno(
)2etoN()yletarapesdetouqebotlaesnottubeno(
R
G
noitcennoclacirtcelednalairetamgnisuoH 9
ht
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
)ylnoesopruplareneg()3etoN(
A
B
D
C
E
G
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocnaHgnitraH
rotcennocsubdleiF
H
L
N
M
P
R
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
1
/
2
TPNni
)02MC(5.1x02M
5.31gP
1
/
2
KGni
rotcennocsubdleiF
S
T
V
U
Z
snoitpolanoitiddA/tuptuO 01
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
APSUBIFORP
APSUBIFORP
subdleiFNOITADNUOF
subdleiFNOITADNUOF
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)5,4setoN(
)4etoN(
)5,4setoN(
)5etoN(
)5,4setoN(
)5etoN(
H
1
P
2
F
3
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
30
ADDITIONAL ORDERING INFORMATION for model 264NR
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XX XXXX XXXX XXXX XXXX XXXX XXXX
noitacifitreclacirtcelE
aixEEytefaScisnirtnIDG1yrogetaCIIpuorGXETA
dxEEfoorpemalFDG2/1yrogetaCIIpuorGXETA
)6etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC
1
/
2
)gnisuoh5,31gPdna02M,TPNni
)6etoN(5T/6TCIIdxE+4T/5T/6TCIIaixEAASailartsuAsdradnatSotfoorpemalFytefaScisnirtnI
htiwylno(lavorppa)MF(lautuMyrotcaF
1
/
2
)noitcennoclacirtcele5,31gPdna02M,TPNni
1E
2E
3E
4E
5E
6E
retemtuptuO
noitarbilacdradnatS,reteMorP
noitarbilaclaicepS,reteMorP
elacs%0010raenilrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)noitarugifnocremotsucreteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)6etoN(
)6etoN(
)6etoN(
)6etoN(
)6etoN(
)6etoN(
1D
2D
3D
5D
7D
8D
DCLlargetnI
yalpsidlargetniDCLlatigiD 1L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomepiproF
)gnisuohISIArofelbatiustoN( leetsnobraC
ssL613ISIA
1B
2B
egruS
rotcetorPtneisnarT/egruS )6etoN( 1S
launamgnitarepO
namreG
nailatI
hcnerF
1M
2M
4M
egaugnalgat&slebaL
namreG
nailatI
hcnerF
1T
2T
4T
etalpgatlanoitiddA
etalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoC
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
F.ged=erutarepmeT;C°4taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°02taisp/O
Hni=erusserPdradnatS
2
C.ged=erutarepmeT;C°4taisp/O
motsuC
2N
3N
4N
5N
6N
erudecorpnoitaraperP
P)lliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
=xam
T;nobracolaHrofaPM9ronedlaGrofaPM21
=xam
F°041/C°06 1P
setacifitreC
)tniop-9(noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
1C
6C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
1H
3H
rotcennoC
8/7subdleiF
1x21MsubdleiF
yrtnethgiartsnaHgnitraH
yrtneelgnanaHgnitraH
)subdleiFNOITADNUOFrofDEDNEMMOCER(
)APSUBIFORProfDEDNEMMOCER(
)7,5setoN(
)7,5setoN(
)7,4setoN(
)7,4setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
31
Note 1: Suitable for oxygen service
Note 2: Not available with sensor code G, H, M, P
Note 3: Select type in additional ordering code
Note 4: Not available with Electronic Housing code Z, R, G
Note 5: Not available with Electronic Housing code P, E
Note 6: Not available with PROFIBUS PA and FF output code 2 or 3
Note 7: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B
Galden is a Montefluos trademark
Halocarbon is a Halocarbon Products Co. trademark
Standard delivery items (can be differently specified by additional ordering code)
General purpose (no electrical certification)
No meter/display, no mounting bracket, no surge protection
English manual and labels
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
2600T Pressure Transmitters
Model 264DR, 264PR, 264HR, 264VR, 264NR SS/264XR_2
ABB Ltd
Howard Road, St. Neots
Cambridgeshire, PE19 3EU
UK
Tel: +44(0)1480 475321
Fax: +44(0)1480 217948
ABB Inc.
125 E. County Line Road
Warminster, PA 18974
USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183
ABB SACE spa
Business Unit Instrumentation
Via Statale 113
22016 Lenno (CO) Italy
Tel: +39 0344 58111
Fax: +39 0344 56278
SS/264XR_2
ABB has Sales & Customer Support
expertise in over 100 countries worldwide
www.abb.com/instrumentation
The Company’s policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
Printed in Italy (01.04)
© ABB 2004