ELC Distributed I/O Adapters
MN05002003E For More Information visit: www.eaton.com 149
5.4 Installation and Wiring
Switch Definition : RUN/STOP
Status Explanation
RUN 1. RUN indicator on ELC-CARS485 is On.
2. AI/AO extension unit in RUN status.
RUN Æ STOP
1. AI/AO extension unit switches from RUN to STOP
status.
2. Y points on DI/DO extension unit are all Off.
STOP
1. RUN indicator on ELC-CARS485 is Off.
2. AI/AO extension unit in STOP status.
3. Communication control is not allowed in AI/AO
extension unit.
4. Communication control is not allowed in DI/DO
extension unit.
STOP
RUN
STOP Æ RUN
1. ELC-CARS485 re-detects the number of points in
DI/DO unit and the number of AI/AO units.
2. AI/AO extension unit switches from STOP to RUN
status.
Modbus Address Setup DIP Switch:
DIP Switch
Setting Explanation
H’01 ~ H’F0
Valid ELC-CARS485 addresses, the dip
switches are weighted as follows: ID0 ~ ID7
are: 20, 21, 22, … 26 , 27 .
H’00, H’F1 ~
H’FF
In the Modbus protocol, H’00 is defined as
broadcast mode. H’F1 ~ H’FF are incorrect
ELC-CARS485 addresses.
Communication Mode Setup DIP Switch:
PA3 PA2 PA1 PA0 A/R Communication mode
OFF OFF OFF OFF ON 7,E,1-ASCII
OFF OFF OFF ON ON 7,O,1-ASCII
OFF OFF ON OFF ON 7,E,2-ASCII
OFF OFF ON ON ON 7,O,2-ASCII
OFF ON OFF OFF ON 7,N,2-ASCII
OFF ON OFF ON ON 8,E,1-ASCII
OFF ON ON OFF ON 8,O,1-ASCII
OFF ON ON ON ON 8,N,1-ASCII
ON OFF OFF OFF ON 8,N,2-ASCII
OFF ON OFF ON OFF 8,E,1-RTU
OFF ON ON OFF OFF 8,O,1-RTU
OFF ON ON ON OFF 8,N,1-RTU
ON OFF OFF OFF OFF 8,N,2-RTU
Other settings of PA3, PA2, PA1, PA0 and A/R are invalid