34.243.0030.0 1
interface
interface
ASD-NIB
Analog Signal & Discrete Non-Incendive Barrier
1 channel ASD-NIB
NIB-TA25mA-1X
Analog Signal & Discrete NIB
24-12 AWG
24 VDC
35 mA
6.2 mm
MODEL
Type
Wire Size
Voltage Output
Amperage Output
Width
Approvals
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Subject to change without notice
www.wieland-electric.ca
Self-extinguishing polyamide
IP20
-40oC to +75oC
T3C (160oC)
5 - 30 VDC
36 VDC
24 VDC
5 - 37 mA
25 mA
35 mA
0.1 mA
24 - 12 AWG
47 ohms
Group A — 25 µH/Ω | 0.27 µF
Group B — 25 µH/Ω | 0.27 µF
Group C — 60 µH/Ω | 0.81 µF
Group D — 200 µH/Ω | 2.16 µF
Green - Normal Operation
Amber - Fault Condition
Amber light typically indicates a ground
fault on the output.
At 45 VDC the fault light will illuminate
(even with no output connected)
If the temperature rises above 75oC a
thermal fuse will open the output.
Mechanical
Housing Material
Degree of Protection
Temperature Range
Temperature Code
Electrical
Input Voltage Range
Maximum Input Voltage
Maximum Output Voltage
Input Current
Nominal Output Current
Maximum Output Current
4..20mA insertion loss
Wire Gage
Internal Resistance
Field Wiring
(Recommended)
Max. Cable Inductance
Max. Loop Capacitance
Indicators
Fault Condition
Class 1, Division 2 Barrier
Provides non-incendive isolation
for analog and discrete signals
Eliminates need for explosion
proof enclosures
Eliminates costly wiring
DIN rail mountable housing
Internal thermal fuse
LED indicator warns of a fault
condition
CSA
Supply
(Positive)
Return
(Negative)
Ground
Output
(To Field)
Return
(From Field)
NOT FOR NEW DESIGNS
34.243.0010.0 1
interface
interface
NIB
Non-Incendive Barriers
ANIB
WT-NIC-24VDC/4-20mA - FU
Analog NIB
24-12 AWG
35 VDC
35 mA
20 mm
MODEL
Type
Wire Size
Max Voltage Output
Max Amperage Output
Width
Approvals
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Subject to change without notice
www.wieland-electric.ca
Self-extinguishing polyamide
IP20
-40oC to +85oC
24 - 12 AWG
T3C (160°C)
24 VDC
5 - 30 VDC
35 VDC
35 VDC
4 - 20 mA
25 mA
4 - 20 mA
25 mA
252 ohms at 4 mA, (1.01 Vd)
187 ohms at 20 mA, (3.75 Vd)
Class I, Division 2,
Groups A,B,C & D
This device is designed to provide an electrical barrier
between control devices and hazardous location devices.
This is a non-fused device, a failure may cause it to fail in
a shorted state.
Must be installed in a suitable enclosure.
Return line must be referenced to 0V, the PLC input must
have a low resistance path the 0V. This is essential to the
proper operation of the barrier in over voltage situations.
If a low impedance to 0V cannot be guaranteed on
the return path, Wieland recommends the use of two
barriers (one per signal) and to connect one of the return
terminals on each barrier directly to ground
Mechanical
Housing Material
Degree of Protection
Temperature Range
Wire Gauge
Tempature Code
Electrical
Nominal Input Voltage
Input Voltage Range
Maximum Input Voltage
Maximum Output Voltage
Nominal Input Current
Maximum Input Current
Nominal Output Current
Maximum Output Current
Loop Resistance
CSA Hazardous Location
Installation
Wiring must be suitable for the
area. The input is not protected by
the barrier
PLC input must have low
resistance to ground.
Provides non-incendive isolation
for analog signals
Eliminates need for explosion
proof enclosures
Eliminates costly wiring
DIN rail mountable housing
CSA Approved
NOT FOR NEW DESIGNS
34.243.0008.0
WT-NIC-W904-35VDC-75mA
1
interface
interface
NIB
Non-Incendive Barriers
DNIB
Discrete Non-Incendive Barrier
WT-NIC-W904-35VDC-75mA
Discrete NIB
24-12 AWG
35 VDC
75 mA
12 mm
MODEL
Type
Wire Size
Max Voltage Output
Max Amperage Output
Width
Approvals
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Part Number
Model Number
Std.
Pack
Subject to change without notice
www.wieland-electric.ca
Self-extinguishing polyamide
IP20
-40oC to +85oC
T3C (160°C)
24 VDC
5 - 30 VDC
35 VDC
35 VDC
5 - 50 mA
75 mA
50 mA
75 mA
24 - 12 AWG
470 ohms
This device is designed to provide an
electrical barrier between control devices
and hazardous location devices. This is a
non-fused device, a failure may cause it to
fail in a shorted state.
Must be installed in a suitable enclosure.
Return line must be referenced to 0V,
the PLC input must have a low resistance
path the 0V. This is essential to the proper
operation of the barrier in overvoltage
situations. If a low impedance to 0V
cannot be guaranteed on the return path,
Wieland recommends the use of two
barriers (one per signal) and to connect
one of the return terminals on each barrier
directly to ground.
Mechanical
Housing Material
Degree of Protection
Temperature Range
Tempature Code
Electrical
Nominal Input Voltage
Input Voltage Range
Maximum Input Voltage
Maximum Output Voltage
Nominal Input Current
Maximum Input Current
Nominal Output Current
Maximum Output Current
Wire Gauge
Internal Resistance
Installation
Wiring must be suitable for the
area. The input is not protected by
the barrier
PLC input must have low
resistance to ground.
This module provides isolation for a
circuit on the load side of the module
to be rated as non-incendive, and
is to be used on digital inputs or
outputs. The DNIB allows the use
of non-rated wiring to end devices
in Class 1, Zone 2 / Division 2 areas,
subject to the allowances of the
Canadian Electrical Code.
Eliminates need for explosion proof
enclosures
Eliminates costly wiring
DIN rail mountable housing