Medium voltage fuses
Medium voltage fuses
MV1
12/04
Medium voltage fuses
Medium voltage fuses
IBD
7.2 UP TO 36 KV
HIGH-VOLTAGE FUSES DESIGNED FOR POWER TRANSFORMER
PROTECTION
INTERIOR/EXTERIOR USE
CERAMIC HOUSING
“MEDIUM” CLASS TRIP-INDICATOR
COMBINED WITH A LOWERED MINIMUM BREAKING CURRENT
COMPLIES WITH IEC 282-1, DIN 43625 AND VDE 0670/4
RECOMMENDATIONS
COMPLIES WITH APPLICATION RULES OF IEC PUBLICATION 787
IBD fuses are designed for the protection of HV/LV distribution transformers. The fuse technology is known
as “enclosed” melting. It ensures against any visible evidence of the fuse during its operation.
The main features include:
• enameled ceramic housing
• nickle-plated brass end caps
• solid silver fuse elements
• waterproof system for outdoor use.
IBD fuses satisfy existing operational constraints for electric networks.
Their characteristics are based on operation at ambient temperatures ranging from -25°c to +40°c, and a
maximum altitude of 1000 meters.
Dimensions (mm) Trip indicator features
European Fuses
DIN Fuses
7.2kV - 36kV
Presentation
Strength (N)
Trip (mm)
33
D45
33 35
L
MV2
12/04
Medium voltage fuses
Medium voltage fuses
European Fuses
DIN Fuses
7.2kV - 36kV
Rated Rated Minimum Breaking Maximum Power Total I2t
voltage current Ref. Number breaking capacity breaking losses @ Un Weight Catalog
Un In (A) current voltage @ In (kg) number
(Kv) (A) (KA) (Kv) (W) (103A2S)
Dimensions
LD
(mm) (mm)
Main characteristics
3/7.2
6.3 S209293 31 25 23 3.5 0.9 1.1
10 T209294 20 50 23 8.9 1.82 1.1
16 V209295 35 50 23 15 8.3 1.1
20 W209296 52 50 23 15 11 1.1
25 X209297 76 50 23 16 14 1.1
31.5 Y209298 102 50 23 20 19 1.1
40 192 Z209299 128 50 23 28 25 1.1
50 A209300 159 50 23 29 48 1.8
63 B209301 210 50 23 35 60 1.8
80 C209302 280 25 23 53 160 1.8
100 D209303 350 25 23 67 205 1.8
6.3 F209305 31 25 37 12 0.9 1.6
10 G209306 20 50 37 19 1.82 1.6
16 H209307 34 50 37 27 8.3 1.6
20 J209308 51 50 37 28 11 1.6
25 K209309 76 50 37 29 14 1.6
31.5 292 L209310 101 50 37 36 19 1.6
40 M209311 125 50 37 50 25 1.6
50 N209312 159 50 37 52 48 2.6
63 P209313 210 50 37 64 60 2.6
80 Q209314 290 25 37 115 160 2.6
100 R209315 350 25 37 120 205 2.6
6.3 T209317 31 25 55 14 4.5 1.6
10 V209318 20 50 55 30 22 1.6
16 W209319 35 50 55 40 28 1.6
20 X209320 52 50 55 42 31 1.6
25 Y209321 78 50 55 45 34 1.6
31.5 Z209322 104 50 55 55 39 1.6
40 292 A209323 125 50 55 82 42 1.6
50 N220099*
63 J220164*
80 V202671*
80 D220458*
100 442 H220186*
125 K082027* 680 50 40 69 290 5,3
6.3 S209339 31 25 70 20 4.5 2.3
10 T209340 20 50 70 42 22 2.3
16 V209341 35 50 70 57 28 2.3
20 W209342 52 50 70 60 31 2.3
25 X209343 78 50 70 64 34 2.3
31.5 Y209344 104 50 70 77 39 2.3
40 442 Z209345 128 50 70 115 42 2.3
50 A209346 150 50 70 118 50 2.3
63 B209347 200 50 70 140 107 3.9
80 H082186* 350 40 56 76 98 5,3
100 T220541*
50 M209357 150 50 70 108 50 4.6
63 N209358 200 50 70 130 107 4.6
80 537 M082190* 350 40 56 73 98 6,4
100 N082191* 460 40 56 78 165 6,4
125 P082192* 480 40 56 93 210 6,4
6.3 S209362 31 25 106 32 0.9 2.7
10 T209363 22 40 106 55 1.82 2.7
16 V209364 38 40 106 82 8.3 2.7
20 W209365 57 40 106 85 11 2.7
25 537 X209366 85 40 106 87 14 2.7
31.5 Y209367 102 40 106 125 19 4.6
40 Z209368 135 40 106 164 25 4.6
D1
=
53
D2
=
73
D1
=
53
D2
=
73
D1
=
53
D3
=
87
D3
=
87
D1
=
53
D1
=
53
D2=73
D3=87
D2=73
D3=87
D2=73
6/12
10/17.5
10/24
20/36
* For indoor use only
45DIN72V6,3P
45DIN72V10P
45DIN72V16P
45DIN72V20P
45DIN72V25P
45DIN72V31,5P
45DIN72V40P
45DIN72V50P
45DIN72V63P
45DIN72V80P
45DIN72V100P
45DIN120V6,3P
45DIN120V10P
45DIN120V16P
45DIN120V20P
45DIN120V25P
45DIN120V31,5P
45DIN120V40P
45DIN120V50P
45DIN120V63P
45DIN120V80P
45DIN120V100P
45DIN175V6,3P
45DIN175V10P
45DIN175V16P
45DIN175V20P
45DIN175V25P
45DIN175V31,5P
45DIN175V40P
45AL175V50P-2
45AL175V63P-2
45AL175V80P-2
45AL175V80P-3
45AL175V100P-3
45AL175V125P-3
45DIN240V6,3P
45DIN240V10P
45DIN240V16P
45DIN240V20P
45DIN240V25P
45DIN240V31,5P
45DIN240V40P
45DIN240V50P
45DIN240V63P
45AL240V80P-3
45AL240V100P-3
45DIN240V50P-4
45DIN240V63P-4
45AL240V80P-4
45AL240V100P-4
45AL240V125P-4
45DIN360V6,3P
45DIN360V10P
45DIN360V16P
45DIN360V20P
45DIN360V25P
45DIN360V31,5P
45DIN360V40P
Medium voltage fuses
Medium voltage fuses
MV3
12/04
European Fuses
DIN Fuses
7.2kV - 36kV
T(S)
Time vs. current characteristics
PREARCING TIME IN SECONDS
PREARCING TIME IN SECONDS
CURRENT IN AMPS. (MEAN VALUES)
CURRENT IN AMPS. (MEAN VALUES)
IP (A)
7.2 Kv
12 Kv
17.5 Kv
24 Kv
t(s)
Time vs. current characteristics
Ip (A)
36 Kv
Main characteristics
MEAN TOLERANCE : ± 20 % FOR CURRENT
MEAN TOLERANCE : ± 20 % FOR CURRENT
Medium voltage fuses
Medium voltage fuses
MV4
12/04
European Fuses
DIN Fuses
7.2kV - 36kV
The selection of fuses for the protection of HV/LV
transformers must take into account:
a) transient currents occuring in the installation
when the transformer power is switched on
b) overload currents related to normal operation
of the transformer and liable to cause prematu-
re agin.
As a rule of thumb:
Fuse rating 1.7 x transformer rated current
This relationship is given for an ambient tempe-
rature not exceeding 40°c. Beyond this, a dera-
ting factor A1 must be used
with q = ambient temperature in °c.
E.g., a 40A rated fuse installed under 60°c
ambient must be treated as a 34A rated fuse.
The table, opposite, may also be used. It has been
computed using peak transient currents from 8 to
15 times the transformer current rating and a 130
% overload rate.
Using this table also means applying the tempe-
rature derating factor A1 to the selected rating
when ambient exceeds 40°c in the fuse
environment.
A1 = V120-θ
80
A1 = = 0.86
V120-60
80
CUT-OFF CURRENT KAPEAK
AVAILABLE SHORT-CIRCUIT CURRENT KARMS
Ic (kA)
Cut-off current characteristics
Selection guide
Ip (kA)
7.2 à
36 Kv
Transformer Operating voltage
power (kV)
(kVA) 3.3 5/5.5 6/6.6 10/11 13.8 15 20/22 30/33
16 10 10 6.3 6.3 6.3 6.3 6.3
25 16 16 10 10 10 6.3 6.3
25 20 20 16 10 10 6.3 6.3
31.5 25 25 16 16 10 10 6.3
40 31.5 25 20 16 16 10 6.3
50 31.5 31.5 25 16 16 16 10
50 40 31.5 25 20 16 16 10
63 50 40 31.5 20 20 16 16
80 63 50 40 25 25 20 16
100 100 63 50 31.5 25 25 16
100 80 63 40 31.5 25 20
100 63 50 40 31.5 25
80 50 50 40 31.5
100 63 63 50 31.5
80 80 50 40
100 100 63
–– 80
100
25
50
63
80
100
125
160
200
250
315
400
500
630
800
1000
1250
1600
2000
Medium voltage fuses
Medium voltage fuses
MV5
12/04
European Fuses
DIN Fuses for Motor
3.6kV to 12kV - Type aSJB/D
According to standard IEC 2.82.1, DIN 43625 and IEC
application requirements Publication 644
32 369 P CP aSJB 45/50,8x192 32 S076468 50,8 1,0
50 369 P CP aSJB 45/50,8x192 50 T076469 50,8 1,0
63 369 P CP aSJB 45/50,8x192 63 V076470 50,8 1,0
80 369 P CP aSJB 45/50,8x192 80 W076471 50,8 1,0
100 369 P CP aSJB 45/50,8x192 100 X076472 50,8 1,0
125 369 P CP aSJB 45/50,8x192 125 Y076473 50,8 1,0
160 369 P CP aSJB 45/67x192 160 Z076474 67 1,7
200 369 P CP aSJB 45/67x192 200 A076475 67 1,7
250 369 P CP aSJB 45/76x192 250 B076476 76 2,2
315 369 P CP aSJB 45/90x192 315 C076477 88 3,0
100 369 P CP aSJB 45/50,8x292 100 N075521 50,8 1,6
125 369 P CP aSJB 45/50,8x292 125 P075522 50,8 1,6
160 369 P CP aSJB 45/50,8x292 160 Q075523 50,8 1,6
200 369 P CP aSJB 45/67x292 200 R075524 67 2,5
250 369 P CP aSJB 45/67x292 250 S075525 67 2,5
315 369 P CP aSJB 45/76x292 315 E075582 76 3,2
350 369 P CP aSJB 45/76x292 350 F075583 76 3,2
430 369 P CP aSJB 45/90x292 430 G075584 88 4,3
32 729 P CP aSJB 45/50,8x292 32 J078162 50,8 1,6
50 729 P CP aSJB 45/50,8x292 50 K078163 50,8 1,6
63 729 P CP aSJB 45/50,8x292 63 L078164 50,8 1,6
80 729 P CP aSJB 45/50,8x292 80 M078165 50,8 1,6
100 729 P CP aSJB 45/50,8x292 100 N078166 50,8 1,6
125 729 P CP aSJB 45/67x292 125 P078167 67 2,5
160 729 P CP aSJB 45/67x292 160 Q078168 67 2,5
200 729 P CP aSJB 45/90x292 200 H093709 88 4,3
250 729 P CP aSJB 45/90x292 250 R078169 88 4,3
100 729 P CP aSJB 45/50,8x442 100 Y085581 50,8 2,8
125 729 P CP aSJB 45/50,8x442 125 Z085582 50,8 2,8
160 729 P CP aSJB 45/50,8x442 160 A085583 50,8 2,8
200 729 P CP aSJB 45/76x442 200 Q085620 76 4,8
250 729 P CP aSJB 45/76x442 250 R085621 76 4,8
315 729 P CP aSJB 45/90x442 315 S085622 88 6,8
400 729 P CP aSJB 45/90x442 400 V085624 88 6,8
32 1209 P CP aSJB 45/50,8x442 32 D076478 50,8 2,8
50 1209 P CP aSJB 45/50,8x442 50 E076479 50,8 2,8
63 1209 P CP aSJB 45/50,8x442 63 F076480 50,8 2,8
80 1209 P CP aSJB 45/50,8x442 80 G076481 50,8 2,8
100 1209 P CP aSJB 45/50,8x442 100 H076482 50,8 2,8
125 1209 P CP aSJB 45/67x442 125 J076483 67 3,7
160 1209 P CP aSJB 45/67x442 160 K076484 67 3,7
200 1209 P CP aSJB 45/76x442 200 L076485 76 5,5
250 1209 P CP aSJB 45/90x442 250 M076486 88 6,2
Rated Voltage L Rating Designation Reference Diameter Weight Catalog
(kV) (mm) In(A) Number (mm) (Kg) Number
3,6
192
292
292
442
442
7,2
12
Note: These fuses are systematically equipped with a trip-indicator
Power (N)
Stroke (mm)
Characteristics of trip-indicators
45ASB36V32P-1
45ASB36V50P-1
45ASB36V63P-1
45ASB36V80P-1
45ASB36V100P-1
45ASB36V125P-1
45ASB36V160P-1
45ASB36V200P-1
45ASB36V250P-1
45ASB36V315P-1
45ASB36V100P-2
45ASB36V125P-2
45ASB36V160P-2
45ASB36V200P-2
45ASB36V250P-2
45ASB36V315P-2
45ASB36V350P-2
45ASB36V430P-2
45ASB72V32P-2
45ASB72V50P-2
45ASB72V63P-2
45ASB72V80P-2
45ASB72V100P-2
45ASB72V125P-2
45ASB72V160P-2
45ASB72V200P-2
45ASB72V250P-2
45ASD72V100P-3
45ASD72V125P-3
45ASD72V160P-3
45ASD72V200P-3
45ASD72V250P-3
45ASD72V315P-3
45ASD72V400P-3
45ASB120V32P-3
45ASB120V50P-3
45ASB120V63P-3
45ASB120V80P-3
45ASB120V100P-3
45ASB120V125P-3
45ASB120V160P-3
45ASB120V200P-3
45ASB120V250P-3
Medium voltage fuses
Medium voltage fuses
MV6
12/04
European Fuses
DIN Fuses for Motor
3.6kV to 12kV - Type aSJB/D
Times vs. current characteristics
Pre-arcing time Pre-arcing time
Cut-off current
RMS value of prospective current RMS value of prospective current
RMS value of prospective current RMS value of prospective current
Cut-off current
MN
MN
Rated Voltage Rating Breaking Peak arc Minimum Power Total operating I2t
LI
nCapacity Voltage Breaking Current dissipation for 0,7 Inat the rated voltage
(kV) (mm) (kA) (kV) (A) (W) (103A2S)
32 60 6,8 180 6 4
50 60 6,8 260 9 9
63 60 6,8 310 11 15
80 60 6,8 400 13 35
100 60 6,8 490 15 60
125 60 6,8 600 20 95
160 60 6,8 800 27 160
200 60 6,8 1000 32 340
250 60 6,8 1200 35 540
315 60 6,8 1600 41 1000
100 60 6,8 700 16 88
125 60 6,8 830 20 160
160 60 6,8 1000 27 280
200 60 6,8 1250 33 370
250 60 6,8 1750 37 720
315 60 6,8 2100 45 1200
350 60 6,8 2400 47 1700
430 60 6,8 3300 51 3200
3,6
192
M
292
N
Cut-off characteristics
Medium voltage fuses
Medium voltage fuses
MV7
12/04
European Fuses
DIN Fuses for Motor
3.6kV to 12kV - Type aSJB/D
Times vs. current characteristics
Pre-arcing time Pre-arcing time
Cut-off current
RMS value of prospective current RMS value of prospective current
RMS value of short-circuit prospective current RMS value of short-circuit prospective current
Cut-off current
PQ
PQ
Rated Voltage Rating Breaking Peak arc Minimum Power Total operating I2t
LI
nCapacity Voltage Breaking Current dissipation for 0,7 Inat the rated voltage
(kV) (mm) (kA) (kV) (A) (W) (103A2S)
32 50 13 180 10 7
50 50 13 220 14 16
63 50 13 300 18 26
80 50 13 380 20 60
100 50 13 510 25 105
125 50 13 700 29 195
160 50 13 840 37 340
200 50 13 1200 41 650
250 50 13 1600 49 1100
100 50 15 500 30 78
125 50 15 630 37 150
160 50 15 880 41 290
200 50 15 1100 47 560
250 50 15 1400 52 1000
315 50 15 1900 60 2000
400 50 15 2700 69 4100
7,2
292
P
442
Q
Cut-off characteristics
Medium voltage fuses
Medium voltage fuses
MV8
12/04
European Fuses
DIN Fuses for Motor
3.6kV to 12kV - Type aSJB/D
Times vs. current characteristics
Pre-arcing time
RMS value of prospective current
R
Rated Voltage Rating Breaking Peak arc Minimum Power Total operating I2t
LI
nCapacity Voltage Breaking Current dissipation for 0,7 Inat the rated voltage
(kV) (mm) (kA) (kV) (A) (W) (103A2S)
32 50 20 160 21 5
50 50 20 240 31 12
63 50 20 310 35 24
80 50 20 410 41 48
100 50 20 560 45 85
125 50 20 650 53 150
160 50 20 930 55 320
200 50 20 1300 62 720
250 50 20 1800 74 1280
12 442
R
RMS value of prospective current
Cut-off current
R
Medium voltage fuses
Medium voltage fuses
MV9
12/04
European Fuses
DIN Fuses for Motor
3.6kV to 12kV - Type aSJB/D
Motor
Fuses
Run up time
kW CV - HP Operating Rated 610 1530
voltage (kV)
voltage (kV)
3 3,6 45 x 192 32 45 x 192 32 45 x 192 32 45 x 192 50
3,3 3,6 45 x 192 32 45 x 192 32 45 x 192 32 45 x 192 32
3 3,6 45 x 192 50 45 x 192 50 45 x 192 50 45 x 192 63
3,3 3,6 45 x 192 50 45 x 192 50 45 x 192 50 45 x 192 50
5,5 7,2 45 x 292 32 45 x 292 32 45 x 292 32 45 x 292 32
3 3,6 45 x 192 63 45 x 192 63 45 x 192 63 45 x 192 80
3,3 3,6 45 x 192 63 45 x 192 63 45 x 192 63 45 x 192 80
5,5 7,2 45 x 292 32 45 x 292 32 45 x 292 32 45 x 292 50
6 7,2 45 x 292 32 45 x 292 32 45 x 292 32 45 x 292 32
3 3,6 45 x 192 80 45 x 292 80 45 x 192 100 45 x 192 100
3,3 3,6 45 x 192 80 45 x 292 80 45 x 192 80 45 x 192 100
5,5 7,2 45 x 292 50 45 x 292 50 45 x 292 50 45 x 292 63
6 7,2 45 x 292 50 45 x 292 50 45 x 292 50 45 x 292 63
6,6 7,2 45 x 292 32 45 x 292 50 45 x 292 50 45 x 292 50
3 3,6 45 x 192 100 45 x 192 100 45 x 192 125 45 x 192 125
3,3 3,6 45 x 192 100 45 x 192 100 45 x 192 100 45 x 192 125
5,5 7,2 45 x 292 63 45 x 292 63 45 x 292 63 45 x 292 80
6 7,2 45 x 292 50 45 x 292 63 45 x 292 63 45 x 292 80
6,6 7,2 45 x 292 50 45 x 292 50 45 x 292 63 45 x 292 63
3 3,6 45 x 192 100 45 x 192 125 45 x 192 125 45 x 192 160
3,3 3,6 45 x 192 100 45 x 192 100 45 x 192 125 45 x 192 125
5,5 7,2 45 x 292 63 45 x 292 80 45 x 292 80 45 x 292 80
6 7,2 45 x 292 63 45 x 292 63 45 x 292 80 45 x 292 80
6,6 7,2 45 x 292 63 45 x 292 63 45 x 292 63 45 x 292 80
10 12 45 x 442 32 45 x 442 50 45 x 442 50 45 x 442 50
11 12 45 x 442 32 45 x 442 32 45 x 442 50 45 x 442 50
3 3,6 45 x 192 160 45 x 192 160 45 x 192 160 45 x 192 200
3,3 3,6 45 x 192 125 45 x 192 125 45 x 192 160 45 x 192 160
5,5 7,2 45 x 292 80 45 x 292 80 45 x 292 80 45 x 292 100
6 7,2 45 x 292 80 45 x 292 80 45 x 292 80 45 x 292 80
6,6 7,2 45 x 292 80 45 x 292 80 45 x 292 80 45 x 292 80
10 12 45 x 442 50 45 x 442 50 45 x 442 50 45 x 442 63
11 12 45 x 442 50 45 x 442 50 45 x 442 50 45 x 442 50
3 3,6 45 x 192 160 45 x 192 200 45 x 192 200 45 x 192 250
3,3 3,6 45 x 192 160 45 x 192 200 45 x 192 200 45 x 192 250
5,5 7,2 45 x 292 100 45 x 292 100 45 x 292 125 45 x 292 125
6 7,2 45 x 292 80 45 x 292 100 45 x 292 100 45 x 292 125
6,6 7,2 45 x 292 80 45 x 292 80 45 x 292 100 45 x 292 125
10 12 45 x 442 63 45 x 442 63 45 x 442 63 45 x 442 80
11 12 45 x 442 63 45 x 442 63 45 x 442 63 45 x 442 63
3 3,6 45 x 192 250 45 x 192 250 45 x 192 250 45 x 192 315
3,3 3,6 45 x 192 200 45 x 192 250 45 x 192 250 45 x 192 315
5,5 7,2 45 x 292 125 45 x 292 125 45 x 292 160 45 x 292 160
6 7,2 45 x 292 125 45 x 292 125 45 x 292 125 45 x 292 160
6,6 7,2 45 x 292 100 45 x 292 100 45 x 292 125 45 x 292 160
10 12 45 x 442 80 45 x 442 80 45 x 442 80 45 x 442 100
11 12 45 x 442 80 45 x 442 80 45 x 442 80 45 x 442 80
3 3,6 45 x 192 250 45 x 192 315 45 x 192 315 45 x 292 315
3,3 3,6 45 x 192 250 45 x 192 250 45 x 192 315 45 x 292 315
5,5 7,2 45 x 292 160 45 x 292 160 45 x 292 160 45 x 292 200
6 7,2 45 x 292 125 45 x 292 160 45 x 292 160 45 x 292 200
6,6 7,2 45 x 292 125 45 x 292 125 45 x 292 160 45 x 292 160
10 12 45 x 442 100 45 x 442 100 45 x 442 100 45 x 442 125
11 12 45 x 442 80 45 x 442 100 45 x 442 100 45 x 442 100
3 3,6 45 x 192 350 45 x 292 350 45 x 292 430 45 x 292 430
3,3 3,6 45 x 192 315 45 x 292 350 45 x 292 350 45 x 292 430
5,5 7,2 45 x 292 200 45 x 292 200 45 x 292 250 45 x 292 250
6 7,2 45 x 292 200 45 x 292 200 45 x 292 250 45 x 292 250
6,6 7,2 45 x 292 200 45 x 292 200 45 x 292 200 45 x 292 250
10 12 45 x 442 125 45 x 442 125 45 x 442 160 45 x 442 160
11 12 45 x 442 125 45 x 442 125 45 x 442 125 45 x 442 160
3 3,6 45 x 292 430 45 x 292 430 *2 x 45 x 292 500 *2 x 45 x 292 630
3,3 3,6 45 x 292 430 45 x 292 430 45 x 292 430 *2 x 45 x 292 630
5,5 7,2 45 x 292 250 45 x 292 250 45 x 442 315 45 x 442 315
6 7,2 45 x 292 250 45 x 292 250 45 x 292 250 45 x 442 315
6,6 7,2 45 x 292 200 45 x 292 250 45 x 292 250 45 x 442 315
10 12 45 x 442 160 45 x 442 160 45 x 442 160 45 x 442 200
11 12 45 x 442 160 45 x 442 160 45 x 442 160 45 x 442 200
5,5 7,2 45 x 442 315 45 x 442 315 45 x 442 400 45 x 442 400
6 7,2 45 x 292 250 45 x 442 315 45 x 442 315 45 x 442 400
6,6 7,2 45 x 292 250 45 x 292 250 45 x 442 315 45 x 442 400
10 12 45 x 442 160 45 x 442 200 45 x 442 315 45 x 442 200
11 12 45 x 442 160 45 x 442 160 45 x 442 200 45 x 442 200
6 7,2 45 x 442 315 45 x 442 400 45 x 442 400 45 x 442 400
6,6 7,2 45 x 442 315 45 x 442 315 45 x 442 400 45 x 442 400
10 12 45 x 442 200 45 x 442 200 45 x 442 250 45 x 442 250
11 12 45 x 442 200 45 x 442 200 45 x 442 200 45 x 442 250
6 7,2 45 x 442 400 45 x 442 400 *2 x 45 x 442 500 *2 x 45 x 442 630
6,6 7,2 45 x 442 315 45 x 442 400 45 x 442 400 *2 x 45 x 442 630
10 12 45 x 442 250 45 x 442 250 45 x 442 250 45 x 442 400
11 12 45 x 442 200 45 x 442 200 45 x 442 250 *2 x 45 x 442 320
95
70
136
100
177
130
245
180
340
250
300
220
430
315
760
560
1360
1000
3400
2500
570
420
950
700
1770
1300
2720
2000
2175
1600
The notation 2 x 45 x 292 or 2 cx 45 x 442 indicates that ratings 320 A, 500 A or 600 A consist of two fuses in parallel.
The rating of each fuse body is then 160 A, 250 A or 315 A.
Use of motor fuses
Medium voltage fuses
Medium voltage fuses
MV10
12/04
Indoor type equipment.
According to standard DIN 43624
Rated Fuse Reference Withstand voltage Catalog
Voltage length Designation Number to earth Weight Number
(kV) L(mm) (kg)
192 SI 130 45x192 R091187 27 60 2,6
292 SI 130 45x292 P092818 27 60 2,8
442 SI 130 45x442 Q092819 27 60 3
442 SI 175 45x442 Q075569 45 95 3,8
50 Hz - 1 mn
(kV RMS)
1,2/50µS
(kV peak)
3,6 / 7,2
12
The clip MR 45 reference L 096 472 be supplied separately.
Reference A C D F H L M N
Number (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
R091187 287 252 157 363 11 403 55 35
P092818 387 256 161 463 15 503 180 0
Q092819 538 256 161 613 15 653 300 0
Q075569 538 311 216 613 15 653 300 0
Fuse-base
Indicating device
Rated Voltage of Reference Number of Length of L Weight Catalog
corresponding fuse-base Designation Number microswitches flexible part Number
(kV) (mm) (mm) (kg)
7,2 MC 1-5 Flex Q E092694 1 395 560 0,205
7,2 MC 1-9 Flex Q F092695 2 395 560 0,215
12 to 36 MC 1-5 Flex Q 640 T092615 1 545 710 0,220
12 to 36 MC 1-9 Flex Q 640 K078945 2 545 710 0,230
The indicating device enables electrical actuating of the opening mechanism for a circuit or triggering of
an indicator during the melting of a fuse equipped with a trip-indicator. This very robust and original
device means freedom for any mechanical system and offers the advantage of being able to incorporate
a microswitch unit or units according to the equipment configuration.
SI130-45-192
SI130-45-292
SI130-45-442
SI175-45-442
MC1-5NFLEXQ
MC1-9NFLEXQ
MC1-5NFLEXQ640
MC1-9NFLEXQ640
European Fuses
DIN Fuses for Motor
3.6kV to 12kV - Type aSJB/D
Flexible part
Minimum R = 65 mm
2 holes Ø 5,2
Medium voltage fuses
Medium voltage fuses
MV11
12/04
FR TYPE
RATED VOLTAGES 7.2, 12, 24 AND 36 kV
CURRENT RATINGS 6.3 TO 63 A
HIGH VOLTAGE FUSES FOR TRANSFORMER PROTECTION
SUPERIOR MECHANICAL STRENGTH
OUTSTANDING WITHSTAND TO OPERATING STRESSES
FOR INDOOR USE
100% SYNTHETIC STRUCTURE
UTE C 62110, UTE C 64200, UTE C 64203 AND IEC 282-1 COMPLIANT
MODEL WITH STRIKER IEC 420 COMPLIANT
European Fuses
NF/UTE Fuses
7,2kV - 36kV Type FR
Presentation
FR-type fuses are designed to protect HV/LV power distribution transformers. Designed to be coordinated
with other equipment, these current-limiting fuses interrupt fault currents before they reach their peak. The
fault current is interrupted inside the fuse body and although this is very fast there is no sign of it outside.
The main elements in these fuses are:
• a barrel of class F insulating synthetic material
• nickel plated aluminum end contacts
• very pure silver fuse elements
• composite material fuse element holder to withstand high temperatures
Thanks to their structure, based on a synthetic material, FR fuses are the perfect answer to the stresses
involved in use inside HV bays and fuse chambers.
Technical characteristics
Rated voltage Un 7.7 to 36 kV
Current rating In 6.3 – 10 – 16 – 20 – 25 – 32 – 43 – 63 A
depending on voltage
Minimum interrupting current I3 as per chart page over
Breaking capacity I1 12,500 A
Temperature of use -25°C to +40°C
Striker: minimum force 0.5 Joules for minimum stroke 20 mm.
Strendth (N)
Trip (mm)
CHARACTERISTICS OF TRIP INDICATOR
40
20
20 40
Medium voltage fuses
Medium voltage fuses
MV12
12/04
European Fuses
NF/UTE Fuses
7,2kV - 36kV Type FR
7,2 6,3 520 55 31,5 12,5 20 12 0,3 2,1
7,2 16 520 55 80 12,5 20 26 1,6 2,1
7,2 32 520 55 160 12,5 20 44 6 2,1
7,2 43 520 55 215 12,5 20 61 12 2,1
7,2 63 520 55 315 12,5 20 71 24 2,1
12 6,3 520 55 31,5 12,5 34 25 0,3 2,1
12 16 520 55 80 12,5 34 53 1,6 2,1
12 32 520 55 160 12,5 34 89 6 2,1
12 43 520 55 215 12,5 34 123 12 2,1
12 63 520 55 315 12,5 34 142 24 2,1
24 6,3 520 55 31,5 12,5 58 25 0,63 2,1
24 16 520 55 80 12,5 58 53 3,3 2,1
24 32 520 55 160 12,5 58 89 13 2,1
24 43 520 55 215 12,5 58 123 25 2,1
24 63 520 55 315 12,5 58 142 50 2,1
36 6,3 520 55 31,5 12,5 - - - 2,1
36 10 520 55 50 12,5 - - - 2,1
36 16 520 55 80 12,5 - - - 2,1
36 20 520 55 100 12,5 - - - 2,1
36 25 520 55 125 12,5 - - - 2,1
36 32 520 55 160 12,5 - - - 2,1
Rated
voltage Un
(kV)
Current
rating In
(A)
Minimum
interrupting
current
(A)
Breaking
capacity
(kA)
Peak inter-
rupting
voltage
(kV)
Power dissipa-
tion at In
(W)
Total operating
I2t at Un (103A2s)
Dimensions
L
(mm)
D
(mm)
Dimension drawings with striker Dimension drawings w/o striker
Amplitude of current interrupted 15 262 A
lm = 2,5Ip
10000
1000
6,3A
16A
20A
25A
10A
32A
43A
63A
100
100 1000 10000 100000
Ip (A)
Ic (A)
Weight
(kg)
Medium voltage fuses
Medium voltage fuses
MV13
12/04
* Use of a 63 A fuse instead of a 43 A fuse is accepted when installed in an oil-tight compartment.
European Fuses
NF/UTE Fuses
7kV - 36kV Type FR
10 6,3 16 32 32 63 63
15 6,3 16 16 16 43 43 63
20 6,3 6,3 16 16 43 43 43*
50 100 160 250 400 630 1000
EDF recommendations Rated transformer power
Rated network
voltage (kV)
6,3A
16A
32A
43A
63A
104
103
102
101
100
10-1
10--2
10-3
10-4
101102103104
104
103
102
101
100
10-1
10--2
10-3
10-4
101102
t (s)
t (s)
103104
I (A) I (A)
FR 7.2/36 type w/o striker FR 7.2/36 type with striker
Time/current data
Guidelines for use
6,3A
16A
32A
43A
63A
Medium voltage fuses
Medium voltage fuses
MV14
12/04
7,2 6,3 FR 7,2/6,3 Z227584 FR 7,2/6,3 P E227589
7,2 16 FR 7,2/16 A227585 FR 7,2/16 P F227590
7,2 32 FR 7,2/32 B227586 FR 7,2/32 P G227591
7,2 43 FR 7,2/43 C227587 FR 7,2/43 P H227592
7,2 63 FR 7,2/63 D227588 FR 7,2/63 P J227593
12 6,3 FR 12/6,3 X210240 FR 12/6,3 P D210246
12 16 FR 12/16 73.02.136 Y210241 FR 12/16 P E210247
12 32 FR 12/32 73.02137 Z210242 FR 12/32 P F210248
12 43 FR 12/43 A210243 FR 12/43 P G210249
12 63 FR 12/63 73.02.138 B210244 FR 12/63 P H210250
24 6,3 FR 24/6,3 73.02.132 A210795 FR 24/6,3 P G227430
24 16 FR 24/16 73.02.133 B210796 FR 24/16 P H227431
24 32 FR 24/32 G226234 FR 24/32 P J227432
24 43 FR 24/43 73.02.134 C210797 FR 24/43 P K227433
24 63 FR 24/63 73.02.135 D210798 FR 24/63 P L227434
36 6,3 FR 36/6,3 K227594 FR 36/6,3 P J227616
36 10 FR 36/10 L227595 FR 36/10 P K227617
36 16 FR 36/16 M227596 FR 36/16 P L227618
36 20 FR 36/20 N227597 FR 36/20 P M227619
36 25 FR 36/25 P227598 FR 36/25 P N227620
36 32 FR 36/32 Q227599 FR 36/32 P P227621
Rated
voltage
Un
(kV)
Current
Rating
In
(A)
With trip-indicator
Without trip-indicator
Designation
EDF parts
list number
(3 fuses)
Reference
Number
Catalog
Number Designation Catalog
Number
Reference
Number
5,5 6,3 16 16 16 32 32 32 63 63 63 63 63
10 6,3 6,3 6,3 6,3 16 16 16 32 32 32 63 63 63 63
15 6,3 6,3 6,3 6,3 6,3 16 16 16 16 16 43 43 43 43 43 63
20 6,3 6,3 6,3 6,3 6,3 6,3 6,3 16 16 16 16 43 43 43 43 43 63
30 Pending
Reference and catalog number
C 13100 recommendations Rated transformer power
Rated network
voltage
European Fuses
NF/UTE Fuses
7kV - 36kV Type FR
(kV) 25 40 50 63 80 100 125 160 200 250 315 400 500 630 800 1000 1250
FR72V6,3
FR72V16
FR72V32
FR72V43
FR72V63
FR120V6,3
FR120V16
FR120V32
FR120V43
FR120V63
LOT-FR240V6,3
LOT-FR240V16
LOT-FR240V32
LOT-FR240V43
LOT-FR240V63
FR360V6,3
FR360V10
FR360V16
FR360V20
FR360V25
FR360V32
FR72V6,3P
FR72V16P
FR72V32P
FR72V43P
FR72V63P
FR120V6,3P
FR120V16P
FR120V32P
FR120V43P
FR120V63P
LOT-FR240V6,3P
LOT-FR240V16P
LOT-FR240V32P
LOT-FR240V43P
LOT-FR240V63P
FR360V6,3P
FR360V10P
FR360V16P
FR360V20P
FR360V25P
FR360V32P
Medium voltage fuses
Medium voltage fuses
MV15
12/04
Rated Size Rating Reference Catalog
Voltage (V) (A) Number Number
0,125 S093327
0,16 T093328
0,25 V093329
0,315 W093330
0,4 X093331
0,5 Z093333
0,63 A093334
1500 10x85 0,8 B093335
1 A093426
1,6 B093427
2 C093428
3,15 D093429
4 E093430
5 Y093654
6,3 Z093655
8 A093656
10 B093657
12 C093658
16 F093431 10GC15V16
Packaging 10
European Fuses
MV Intermediate Fuses (Lighting)
1.5kV - 10 x 85
10GC15V0,125
10GC15V0,16
10GC15V0,25
10GC15V0,315
10GC15V0,4
10GC15V0,5
10GC15V0,63
10GC15V0,8
10GC15V1
10GC15V1,6
10GC15V2
10GC15V3,15
10GC15V4
10GC15V5
10GC15V6,3
10GC15V8
10GC15V10
10GC15V12
Medium voltage fuses
Medium voltage fuses
MV17
12/04
European Fuses
MV Intermediate Fuses (lighting)
3.2kV and 5.5kV
Rated
Dimensions Rating
Fuse without trip-indicator Fuse with trip-indicator
Weight Catalog NumberVoltage
Designation Ref.
Number Designation Ref.
Number
(kV) (mm) In(A) (kg)
0,16 3200 CP gLB 10.180/0,16 E081838 - - 0,03
0,315 3200 CP gLB 10.180/0,315 F081839 - - 0,03
0,5 3200 CP gLB 10.180/0,5 G081840 - - 0,03
0,8 3200 CP gLB 10.180/0,8 H081841 - - 0,03
1 3200 CP gLB 10.180/1 P089621 - - 0,03
1,25 3200 CP gLB 10.180/1,25 R078744 - - 0,03
1,6 3200 CP gLB 10.180/1,6 N081409 - - 0,03
2 3200 CP gLB 10.180/2 Q089622 - - 0,03
2,5 3200 CP gLB 10.180/2,5 S078745 - - 0,03
3,15 3200 CP gLB 10.180/3,15 M081845 - - 0,03
4 3200 CP gLB 10.180/4 R089623 - - 0,03
5 3200 CP aLB 10.180/5 M087733 - - 0,03
6 3200 CP aLB 10.180/6 S089624 - - 0,03
8 3200 CP aLB 10.180/8 T089625 - - 0,03
10 3200 CP aLB 10.180/10 V089626 - - 0,03
12 3200 CP aLB 10.180/12 W089627 - - 0,03
2 3200 CP gLD 36.190/2 P081801 - - 0,4
3,15 3200 CP gLD 36.190/3,15 Q081802 - - 0,4
4 3200 CP gLD 36.190/4 R081803 - - 0,4
5 3200 CP gLD 36.190/5 S081804 - - 0,4
6 3200 CP gLD 36.190/6 T081805 329 CP gLD 36.190/6 K081797 0,4
8 3200 CP gLD 36.190/8 V081806 329 CP gLD 36.190/8 J081796 0,4
10 3200 CP gLD 36.190/10 W081807 329 CP gLD 36.190/10 H081795 0,4
12 3200 CP gLD 36.190/12 X081808 329 CP gLD 36.190/12 G081794 0,4
16 3200 CP gLD 36.190/16 Y081809 329 CP gLD 36.190/16 F081793 0,4
20 3200 CP gLD 36.190/20 Z081810 329 CP gLD 36.190/20 E081792 0,4
25 3200 CP gLD 36.190/25 A081811 329 CP gLD 36.190/25 D081791 0,4
32 3200 CP gLD 36.190/32 B081812 329 CP gLD 36.190/32 C081790 0,4
40 3200 CP gLD 36.190/40 C081813 329 CP gLD 36.190/40 B081789 0,4
50 3200 CP gLD 36.190/50 D081814 329 CP gLD 36.190/50 A081788 0,4
63 3200 CP gLD 36.190/63 L081798 329 CP gLD 36.190/63 Z081787 0,4
80 3200 CP gLD 36.190/80 M081799 329 CP gLD 36.190/80 Y081786 0,4
100 3200 CP gLD 36.190/100 N081800 329 CP gLD 36.190/100 X081785 0,4
0,16 5500 CP gLB 10.180/0,16 A093035 - - 0,03
0,315 5500 CP gLB 10.180/0,315 B093036 - - 0,03
0,5 5500 CP gLB 10.180/0,5 W081140 - - 0,03
0,8 5500 CP gLB 10.180/0,8 V081139 - - 0,03
1 5500 CP gLB 10.180/1 T081138 - - 0,03
1,25 5500 CP gLB 10.180/1,25 N093162 - - 0,03
1,6 5500 CP gLB 10.180/1,6 S081137 - - 0,03
2 5500 CP gLB 10.180/2 R081136 - - 0,03
2,5 5500 CP gLB 10.180/2,5 P093163 - - 0,03
3,15 5500 CP gLB 10.180/3,15 Q081135 - - 0,03
4 5500 CP gLB 10.180/4 N081133 - - 0,03
2 5500 CP gLB 36.250/2 V081622 - - 0,5
3,15 5500 CP gLB 36.250/3,15 A081397 - - 0,5
4 5500 CP gLB 36.250/4 T081621 - - 0,5
5 5500 CP gLB 36.250/5 S081620 - - 0,5
6 5500 CP gLB 36.250/6 R081619 559 CP gLB 36.250/6 G081610 0,5
8 5500 CP gLB 36.250/8 Q081618 559 CP gLB 36.250/8 F081609 0,5
10 5500 CP gLB 36.250/10 P081617 559 CP gLB 36.250/10 E081608 0,5
12 5500 CP gLB 36.250/12 N081616 559 CP gLB 36.250/12 D081607 0,5
16 5500 CP gLB 36.250/16 M081615 559 CP gLB 36.250/16 C081606 0,5
20 5500 CP gLJB 36.250/20 L081614 559 CP gLJB 36.250/20 E078802 0,5
25 5500 CP gLJB 36.250/25 Q078789 559 CP gLJB 36.250/25 F078803 0,5
32 5500 CP gLJB 36.250/32 R078790 559 CP gLJB 36.250/32 G078804 0,5
40 5500 CP gLJB 36.250/40 S078791 559 CP gLJB 36.250/40 H078805 0,5
50 5500 CP gLJB 36.250/50 T078792 559 CP gLJB 36.250/50 J078806 0,5
63 5500 CP aLJB 36.250/63 V078793 559 CP aLJB 36.250/63 K078807 0,5
75 5500 CP aLJB 36.250/75 W078794 559 CP aLJB 36.250/75 L078808 0,5
2 5500 CP gLD 55.259/2 S081505 - - 1,4
3,15 5500 CP gLD 55.259/3,15 S081390 - - 1,4
4 5500 CP gLD 55.259/4 R081504 - - 1,4
5 5500 CP gLD 55.259/5 Q081503 - - 1,4
6 5500 CP gLD 55.259/6 P081502 559 CP gLD 55.259/6 A081489 1,4
8 5500 CP gLD 55.259/8 N081501 559 CP gLD 55.259/8 Z081488 1,4
10 5500 CP gLD 55.259/10 M081500 559 CP gLD 55.259/10 Y081487 1,4
12 5500 CP gLD 55.259/12 L081499 559 CP gLD 55.259/12 X081486 1,4
16 5500 CP gLD 55.259/16 K081498 559 CP gLD 55.259/16 W081485 1,4
20 5500 CP gLD 55.259/20 J081497 559 CP gLD 55.259/20 V081484 1,4
25 5500 CP gLD 55.259/25 H081496 559 CP gLD 55.259/25 T081483 1,4
32 5500 CP gLD 55.259/32 G081495 559 CP gLD 55.259/32 S081482 1,4
40 5500 CP gLD 55.259/40 F081494 559 CP gLD 55.259/40 R081481 1,4
50 5500 CP gLD 55.259/50 E081493 559 CP gLD 55.259/50 Q081480 1,4
63 5500 CP gLD 55.259/63 D081492 559 CP gLD 55.259/63 P081479 1,4
80 5500 CP gLD 55.259/80 C081491 559 CP gLD 55.259/80 N081478 1,4
100 5500 CP gLD 55.259/100 B081490 559 CP gLD 55.259/100 M081477 1,4
3,2
10 x 180
(figure 1)
36 x 190
(figure 2)
10 x 180
(figure 1)
36 x 250
(figure 3)
55 x 259
(figure 4)
5,5
10GB32V0,16
10GB32V0,315
10GB32V0,5
10GB32V0,8
10GB32V1
10GB32V1,25
10GB32V1,6
10GB32V2
10GB32V2,5
10GB32V3,15
10GB32V4
10GB32V5
10AB32V6
10AB32V8
10AB32V10
10AB32V12
36GD32V2
36GD32V3,15
36GD32V4
36GD32V5
36GD32V6,3
36GD32V8
36GD32V10
36GD32V12
36GD32V16
36GD32V20
36GD32V25
36GD320V32
36GD32V40
36GD32V50
36GD32V63
36GD32V80
36GD32V100
10GB55V0,16
10GB55V0,315
10GB55V0,5
10GB55V0,8
10GB55V1
10GB55V1,25
10GB55V1,6
10GB55V2
10GB55V2,5
10GB55V3,15
10GB55V4
36GB55V2
36GB55V20
36GB55V4
36GB55V5
36GB55V6
36GB55V8
36GB55V10
36GB55V12
36GB55V16
36GJB55V20
36GJB55V25
36GJB55V32
36GJB55V40
36GJB55V50
36AJB55V63
36AJB55V75
55GD55V2
55GD55V3,15
55GD55V4
55GD55V5
55GD55V6
55GD55V8
55GD55V10
55GD55V12
55GD55V16
55GD55V20
55GD55V25
55GD55V32
55GD55V40
55GD55V50
55GD55V63
55GD55V80
55GD55V100
Medium voltage fuses
Medium voltage fuses
MV18
12/04
FIGURE 1
FIGURE 2
FIGURE 3
FIGURE 4
Without trip-indicator
With trip-indicator
Without trip-indicator
With trip-indicator
Without trip-indicator
With trip-indicator
180
190
ø 10
36
195 43 20
ø 12
ø 7,5
250
36
259
259 20
7
5
ø 55
255 43 20
ø 12
ø 7,5
ø 55
European Fuses
MV Intermediate Fuses (lighting)
3.2kV and 5.5kV
Medium voltage fuses
Medium voltage fuses
MV19
12/04
A
B
C
Pre-arcing time
RMS value of short-circuit prospective current
Pre-arcing time
RMS value of short-circuit prospective current
Pre-arcing time
RMS value of short-circuit prospective current
Time/Current characteristics
European Fuses
MV Intermediate Fuses (lighting)
3.2kV and 5.5kV
Medium voltage fuses
Medium voltage fuses
MV20
12/04
European Fuses
MV Intermediate Fuses (lighting)
3.2kV and 5.5kV
Rated Breaking Peak arc Minimum Power Dissipation
Voltage Dimenssions Rating Capacity voltage Breaking Current at In
(kV) (mm) (A) (kA) (kV) (A) (W)
Cut-off characteristics
Cut-off current
RMS value of short-circuit prospective current
Cut-off current
RMS value of short-circuit prospective current
Cut-off current
RMS value of short-circuit prospective current
A
B
C
0,16 15 12
0,315 15 12
0,5 15 12
0,8 15 12
115 12
1,25 15 12
1,6 15 12
215 12
2,5 15 12
3,15 15 12
415 12
5 17,5 8 14 2
6 17,5 8 18 2,5
8 17,5 8 21 3,7
10 17,5 8 30 4
12 17,5 8 36 4,8
250 15
3,15 50 15
450 15
650 15
850 15
10 50 15 14
12 50 15 17
16 50 15 19
20 50 15 20
25 50 15 25
32 50 7,2 17
40 50 7,2 19
50 50 7,2 23
63 50 7,2 25
80 50 7,2 25
100 50 7,2 30
3,2
10x180
A B
36x190
C
Medium voltage fuses
Medium voltage fuses
MV21
12/04
European Fuses
MV Intermediate Fuses (lighting)
3.2kV and 5.5kV
DE
Pre-arcing time
RMS value of short-circuit prospective current
Pre-arcing time
RMS value of short-circuit prospective current
FG
Pre-arcing time
RMS value of short-circuit prospective current
Pre-arcing time
RMS value of short-circuit prospective current
Time/Current characteristics
Medium voltage fuses
Medium voltage fuses
MV22
12/04
European Fuses
MV Intermediate Fuses (lighting)
3.2kV and 5.5kV
Rated Breaking Peak arc Minimum Power Dissipation
Voltage Dimenssions Rating Capacity voltage Breaking Current at In
(kV) (mm) (A) (kA) (kV) (A) (W)
Cut-off characteristics
Cut-off current
RMS value of short-circuit prospective current
Cut-off current
RMS value of short-circuit prospective current
Cut-off current
RMS value of short-circuit prospective current
D
E
G F
0,16 10 12
0,315 10 12
0,5 10 12
0,8 10 12
110 12
1,25 10 12
1,6 10 12
210 12
2,5 10 12
3,15 10 12
410 12
2 15 15 1,5
3,15 15 15 2
4 15 15 2,3
5 15 15 2,8
615 15 4
815 15 5
10 15 15 8
12 15 15 9
16 15 15 14
20 40 12 16
25 40 12 20
32 40 12 24
40 40 12 30
50 40 12 35
63 40 12 38
75 40 12 40
230 18
3,15 30 18
430 18
530 18
630 18
830 18
10 30 18
12 30 18
16 30 18
20 30 18
25 30 12 25
32 30 12 30
40 30 12 34
50 30 12 40
63 30 12 40
80 30 12 50
100 30 12 55
5,5
10x180
A
36x250
D E
55x259
F G
Medium voltage fuses
Medium voltage fuses
MV23
12/04
European Fuses
MV Intermediate Fuses (lighting)
3.2kV and 5.5kV
Rated Withstand
voltage Voltage to earth Designation Figure Reference Weight Catalog
(kV) Number (kg) Number
50 Hz - 1 mn
(kV RMS)
1,2/50µS
(kV peak)
3,6 21 45 SI 50 10x180 5 S092706 0,22
7,2 27 60 SI 85 36x190 6 C092738 1,05
7,2 27 60 SI 85 10x180 7 D092693 0,27
7,2 27 60 SI 85 36x250 8 P092864 1,15
7,2 27 60 SI 120 55x259 9 X092227 3,9
Number of Type of fuse that Length of flexible Weight
Designation Reference
microswitches can be equipped part (mm)
Catalog
Number (kg) Number
MC 1-5 Flex E098674 1 Figure 2&3 395 0,110
MC 1-9 Flex F098675 2 Figure 2&3 395 0,120
MC 1-5 Flex Q E092694 1 Figure 4 395 0,205
MC 1-9 Flex Q F092695 2 Figure 4 395 0,215
Fuse holder
Indicating device
The clips MR 10, MR 36 and MR 55 can be supplied separately
The electrical data of microswitches is given
FIGURE 5 FIGURE 6 FIGURE 7
FIGURE 8 FIGURE 9
SI50-10-180
SI85-36-190TRA
SI85-10-180
SI85-36-250
SI130-55-259
MC1-5NFLEX
MC1-9NFLEX
MC1-5NFLEXQ
MC1-9NFLEXQ
Medium voltage fuses
Medium voltage fuses
MV25
12/04
European Fuses
Potential Transformer Fuses
5.5kV to 25.5kV - 20x127 to 20x340
Catalog number
20GG55V0,63
20GG55V1
20GG55V2
20GG55V3,15
20GF72V0,63
20GF72V1
20GF72V2
20GF72V3,15
20GC82,5V0,63
20GC82,5V1
20GC82,5V2
20GC82,5V3,15
20GC120V0,63
20GC120V1
20GC120V2
20GC120V3,15
20GC155V0,63
20GC155V1
20GC155V2
20GC155V3,15
20GLC240V0,63
20GC255V0,5
Complying with IEC 282-1 standard
Interior equipment
Rating
In (A)
0,63
1
2
3,15
0,63
1
2
3,15
0,63
1
2
3,15
0,63
1
2
3,15
0,63
1
2
3,15
0,63
0,5
Note: These fuses are never equipped with a trip-indicator. Connecting clips MR 20,6.
Weight
(kg)
0,08
0,08
0,08
0,08
0,12
0,12
0,12
0,12
0,12
0,12
0,12
0,12
0,16
0,16
0,16
0,16
0,16
0,16
0,16
0,16
0,215
0,215
Reference
Number
F076802
G076803
J076805
K076806
V077850
W077851
Y077853
Z077854
D095775
E095776
G095778
H095779
L076807
M076808
P076810
Q076811
K095827
V097814
W097815
H220025
N078235
D099915
Designation
5 500 CP gL 20x127/0,63
5 500 CP gL 20x127 /1
5 500 CP gL 20x127 /2
5 500 CP gL 20x127/3,15
7 200 CP gL 20x190/0,63
7 200 CP gL 20x190 /1
7 200 CP gL 20x190 /2
7 200 CP gL 20x190/3,15
8 250 CP gL 20x190/0,63
8 250 CP gL 20x190 /1
8 250 CP gL 20x190 /2
8 250 CP gL 20x190/3,15
12 000 CP gL 20x254/0,63
12 000 CP gL 20x254 /1
12 000 CP gL 20x254 /2
12 000 CP gL 20x254/3,15
15 500 CP gL 20x254/0,63
15 500 CP gL 20x254 /1
15 500 CP gL 20x254 /2
15 500 CP gL 20x254/3,15
24 000 CP gL 20x340/0,63
25 500 CP gL 20x340/0,5
Rated voltage
(kV)
Fuses for the protection of low power receptors
5,5
7,2
8,25
12
15,5
24
25,5
L
(mm)
127
190
190
254
254
340
340
Medium voltage fuses
Medium voltage fuses
MV26
12/04
European Fuses
Potential Transformer Fuses
5.5kV to 25.5kV - 20x127 to 20x340
Rated voltage
(kV)
5,5
7,2 / 8,25
12 / 15,5
24
25,5
Electrical data on fuses for the protection of low power receptors
L
(mm)
Rating
In(A)
0,63
1
2
3,15
0,63
1
2
3,15
0,63
1
2
3,15
0,63
0,5
Ip = RMS value of short-circuit prospective current
t(s)= Pre-arcing time
Ic = Cut-off current
Breaking
capacity (kA)
20
20
20
20
20
20
20
20
20 /16
20 / 16
20 / 16
20 / 16
16
16
Peak arc voltage
(kV)
22
22
22
22
25 /33
25 /33
25 /33
25 /33
42 / 62
42 /62
42 / 62
42 / 62
84
102
Power dissipation at In
(W)
1,6
1,8
2,5
4,1
1,9 / 2,5
2,2 / 2,9
3,1 / 4,1
6,0 / 6,7
3,2 / 4,8
3,6 / 5,6
5,2 / 7,8
8,6 / 13
6,7
11,8
104
103
102
101
1
10-1
10-2
10-3
10-4
1 10 100 Ip (A)
0,01 0,1 1 10
Ic(kA)
1
Time-current characteristics Cut-off characteristics
127
190
254
340
340
t (s)
Ip (A)
Medium voltage fuses
Medium voltage fuses
MV27
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
5kV, 8 kV and 15kV Ferrule mounted fuses
Amp-trap CS-3 E-rated 5kV, 8kV and 15kV fuses have either 2”
or 3” diameter barrels with ferrules and are mounted in spring
reinforced clips. They are UL listed as “general purpose current-
limiting fuses” and are for use indoors (or outdoors in a weath-
erproof enclosure). The unique time-current characteristic of
Ferraz Shawmut E-rated fuses allows them to be closely sized
to transformer full-load rated current, as recommended by IEEE
guidelines, without being affected by normal magnetizing
inrush current. CS-3 fuses are typically sized at transformer
rated current of 133%, thereby providing superior overall pro-
tection.
Features /Benefits
• UL Listed for compatibility with UL listed equipment
• Ferrule mounting for standard clips and
interchangeability with other brands of fuses
• Current Limiting for superior equipment protection
• Blown-fuse indicator gives positive identification
of open fuse
• Non-venting for silent operation
Ratings
A055F
AC: 5E to 450E
5.5kV, 63kA I.R. Sym.
A825X
AC: 10E to 200E
8.25kV, 50kA I.R. Sym.
A155F
AC: 5E TO 200E
15.5kV, 50kA I.R. Sym.
Highlights
• E-Rated
• UL Listed
• Complies with ANSI C37.46
Applications
Protection for 5.5, 8.25 or 15.5kV transformers
or distribution systems
Definitions
E-rating
E-rated fuses operate as follows:
100E or less - must melt in 300 seconds (5 mins.)
on 200 to 240% of E (ampere) rating.
Over 100E - must melt in 600 seconds (10 mins.)
on 220 to 264% of E (ampere) rating.
Example - A 100E fuse must melt in 300 seconds
with an applied current of 200 to 240 amperes.
General Purpose Current-Limiting Fuse
A general purpose current-limiting power fuse is
one that is capable of interrupting all currents
from its rated interrupting rating down to the
current that causes melting of the fusible ele-
ment in one hour.
Spring-Reinforced Clips for CS-3 Fuses:
228-700-530 (One pair of clips)
For 3” diameter, 2 barrels max.
Approvals
UL Listed to JEEG, “Fuses Over 600 Volts”
File # E 143362
Medium voltage fuses
Medium voltage fuses
MV28
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
5.5kV Ferrule Mounted
Reference Numbers, Ratings, Dimensions, CS-3 Series, 5.5kV
FIGURE A FIGURE B FIGURE C
Catalog Reference Ampere Number Fig.
Dimensions Inches (mm) Interrupting
Number Number Rating of Barrels Rating
RMS SYM.*Amp.
ABC
A055F1CORO-5E S213364 5E
A055F1CORO-7E T214377 7E
A055F1CORO-10E A222709 10E
A055F1CORO-15E P223228 15E
A055F1CORO-20E E201047 20E 1 A 14.11 2.2 .19 63,000
A055F1CORO-25E N201561 25E (358) (56) (4.8)
A055F1CORO-30E H203557 30E Tripped
A055F1CORO-40E V212331 40E Force
A055F1CORO-50E J212850 50E 1 lb.
A055F1CORO-65E J213862 65E
A055F1DORO-10E T214883 10E
A055F1DORO-15E M218465 15E
A055F1DORO-20E T221967 20E
A055F1DORO-25E C222711 25E
A055F1DORO-30E Q223229 30E
A055F1DORO-40E G201049 40E
A055F1DORO-50E Q201563 50E 1 B
A055F1DORO-65E V203591 65E
A055F1DORO-80E A211301 80E 15.88 3.0 0.5
A055F1DORO-100E V214378 100E (403) (76) (13) 63,000
A055F1DORO-125E Y217440 125E Tripped
A055F1DORO-150E G217954 150E Force
A055F1DORO-175E F218988 175E 2 lbs.
A055F1DORO-200E Y219510 200E
A055F2DORO-250E G218989 250E
A055F2DORO-300E Z219511 300E
A055F2DORO-350E V221968 350E 2 C
A055F2DORO-400E D222712 400E
A055F2DORO-450E R223230 450E
5.5kV Max. – Ferrule Mounted Style – 12” (305mm) Clip Centers – 3” (76.2mm) Barrel Diameter
5.5kV Max. – Ferrule Mounted Style – 12” (305mm) Clip Centers – 2” (50.8mm) Barrel Diameter
A 0 5 5 F 1 D 0 R 0 - 1 0 0 E
Ampere Rating
Revision/No.
Special Features
Diameter (C=2”, D=3”)
No. of Barrels
Style (F=Ferrule Mount)
Max. Voltage Rating (055=5.5kV)
Amp-trap Fuse
CATALOG NUMBERING SYSTEM
Medium voltage fuses
Medium voltage fuses
MV29
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
TIME IN SECONDS
CURRENT IN AMPERES
TOTAL CLEARING TIME – CURRENT DATA, 5.5KV FUSES
A055F1CORO – 5E to 65E
MINIMUM MELTING TIME – CURRENT DATA, 5.5KV FUSES
CURRENT IN AMPERES
A055F1CORO – 5E to 65E
TIME IN SECONDS
Medium voltage fuses
Medium voltage fuses
MV30
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
MINIMUM MELTING TIME – CURRENT DATA, 5.5KV FUSES
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A055F1DORO – 10E to 200E and A055F2DORO – 250E to 450E
TOTAL CLEARING TIME – CURRENT DATA, 5.5KV FUSES
A055F1DORO – 10E to 200E and A055F2DORO – 250E to 450E
TIME IN SECONDS
Medium voltage fuses
Medium voltage fuses
MV31
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A055F1CORO – 5E to 65E
Peak Let-Thru Current Data, 5.5kV CS-3 Fuses
A055F1DORO – 10E to 200E and A055F2DORO – 250E to 450E
Peak Let-Thru Current Data, 5.5kV CS-3 Fuses
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
Medium voltage fuses
Medium voltage fuses
MV32
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
8.25kV Ferrule Mounted
FIGURE A
FIGURE B
3 (76)
3
(76)
3 (76)
3
(76)
15.88 REF
(403)
15.88 REF
(403)
.50 (13)
.38
(9.6)
2 LB TRIP FORCE
.50 (13)
.38 (9.6)
2 LB TRIP FORCE
Catalog Reference Ampere Number Figure Interrupting
Number Number Rating of Barrels Rating RMS
SYM. Amperes*
A825X10E-1 - 10E 1 A
A825X15E-1 - 15E 1 A
A825X20E-1 C215903 20E 1 A
A825X25E-1 G216413 25E 1 A
A825X30E-1 P216926 30E 1 A 50,000
A825X40E-1 L217958 40E 1 A
A825X50E-1 R218469 50E 1 A
A825X65E-1 K218992 65E 1 A
A825X80E-1 C219514 80E 1 A
A825X100E-1 M211818 100E 1 A
A825X125E-1 A212336 125E 2 B
A825X150E-1 N213866 150E 2 B 50,000
A825X200E-1 X214886 200E 2 B
8.25kV Max. – Ferrule Mounted Style – 12” (305mm) Clip Center – 3” (76.2mm) Barrel Diameter
* RMS ASYM. AMPS = RMS SYM. AMPERES x 1.6
Medium voltage fuses
Medium voltage fuses
MV33
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
A825X (10E to 200E) -1
A825X (10E to 200E) -1
TIME IN SECONDS
CURRENT IN AMPS X 10
CURRENT IN AMPS X 10
TIME IN SECONDS
TOTAL CLEARING TIME – CURRENT DATAMINIMUM MELTING TIME – CURRENT DATA
Medium voltage fuses
Medium voltage fuses
MV34
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
A825X (10E to 200E) -1
Peak Let-Thru Current Data, E-Rated Fuses
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM PEAK CURRENT CIRCUIT CAN PRODUCE - 2.6 XRMS SYM. AMPS
Medium voltage fuses
Medium voltage fuses
MV35
12/04
15.5kV Ferrule Mounted
FIGURE A
FIGURE B
FIGURE C
Indicator Flush with Surface
in Untripped Position Blown Fuse Indicator
Catalog Numbering System, Ratings, Dimensions, CS-3 Series, 15.5kV
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
Catalog Reference Ampere Number Fig. Dimensions Inches (mm) Interrupting
Number Number Rating of Barrels Rating
RMS SYM.*Amp.
ABC
A155F1CORO - 5E 5E
7E 7E
10E 10E 1 A 17.03 2.2 .19 50,000
15E 15E (433) (56) (4.8)
20E 20E Tripped
25E 25E Force
30E 30E 1 lb.
A155F1DORO - 10E 10E
15E 15E
20E 20E
25E 25E 1 B 18.87 3.0 0.5 50,000
30E 30E (479) (76) (13)
40E 40E Tripped
50E 50E Force
2 lbs.
A155F2DORO - 65E 65E
80E 80E 2 C
100E 100E
A155F1DORO - 65E 65E
80E 80E 1 B 21.75 3.0 0.5 50,000
100E 100E (552) (76) (13)
Tripped
A155F2DORO - 125E 125E Force
150E 150E 2 C 2 lbs.
175E 175E
200E 200E
15.5kV Max. – Ferrule Mounted Style – 15” (381mm) Clip Centers – 3” (76.2mm) Barrel Diameter
15.5kV Max. – Ferrule Mounted Style – 18” (457mm) Clip Centers – 3” (76.2mm) Barrel Diameter
15.5kV Max. – Ferrule Mounted Style – 15” (381 mm) Clip Centers – 2” (50.8mm) Barrel Diameter
* RMS ASYM. AMPERES = RMS SYM. AMPERES x 1.6
A 1 5 5 F 1 D 0 R 0 - 1 0 0 E
Ampere Rating
Revision/No.
Special Features
Diameter (C=2”, D=3”)
No. of Barrels
Style (F=Ferrule Mount)
Max. Voltage Rating (155=15.5kV)
Amp-trap Fuse
CATALOG NUMBERING SYSTEM
E218E987
X219509
S214882
X215392
L216923
F217953
L218464
E216411
A217442
J217956
P218467
H218990
A219512
W221969
Q218468
J218991
B215902
S223231
J201051
A215901
F216412
N216925
B217443
K217957
Medium voltage fuses
Medium voltage fuses
MV36
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A155F1CORO – 5E to 30E
Minimum Melting Time – Current Data, 15.5kV Fuses
A155F1CORO – 5E to 30E
Total Clearing Time – Current
Data, 15.5kV Fuses
TIME IN SECONDS
Medium voltage fuses
Medium voltage fuses
MV37
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
MINIMUM MELTING TIME – CURRENT DATA, 15.5KV FUSES
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A155F1DORO – 10E to 50E and A155F2DORO – 65E to 100E
TOTAL CLEARING TIME – CURRENT DATA, 15.5KV FUSES
A155F1DORO – 10E to 50E and A155F2DORO – 65E to 100E
Medium voltage fuses
Medium voltage fuses
MV38
12/04
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A155F1DORO – 65E to 100E and
A155F2DORO – 125E to 200E
Minimum Melting Time – Current
Data, 15.5kV Fuses
A155F1DORO – 65E to 100E and
A155F2DORO – 125E to 200E
Total Clearing Time – Current
Data, 15.5kV Fuses
Medium voltage fuses
Medium voltage fuses
MV39
12/04
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A155F1DORO – 10E to 50E
A155F2DORO – 65E to 100E
Peak Let-Thru Current Data,
15.5kV CS-3 Fuses
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A155F1CORO – 5E to 30E
Peak Let-Thru Current Data,
15.5kV CS-3 Fuses
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A155F1DORO – 65E to 100E
A155F2DORO – 125E to 200E
Peak Let-Thru Current Data, 15.5kV CS-3 Fuses
American Fuses
E-Rated
5.5kV, 8.25kV and 15.5kV - CS 3 Series
Medium voltage fuses
Medium voltage fuses
MV41
12/04
American Fuses
E-Rated
5.5kV - Bolt-in Series
5kV Bolt-in fuses
Amp-trap Bolt-in Series E-rated fuses are single, double or triple
barrel (3” diam.) with end mounts designed for bolting directly
to equipment bus or terminal pads. They are UL listed and are
for use indoors (or outdoors in a weatherproof enclosure). The
unique time-current characteristic of Ferraz Shawmut E-rated
fuses allows them to be closely sized to transformer full load
rated current, as recommended by IEEE guidelines, without
being affected by normal magnetizing inrush current.
Bolt-in fuses are typically sized at transformer rated current of
133%, thereby providing superior overall protection.
Features /Benefits
UL Listed for compatibility with UL listed
equipment
Bolt-in mounting for direct connection to bus
or terminals
Current Limiting for superior equipment
protection
Blown-fuse indicator gives positive identification
of open fuse
Non-venting for silent operation
Metal Embossed Catalog Number and
manufacturing date for lasting identification
Ratings
A055B
AC: 10E to 900E
5500V max, 63kA I.R. Sym.
Approvals
• UL Listed to JEEG, “Fuses Over 600 Volts”
• UL File # E143362
Highlights
• E-Rated
• UL Listed
• Complies with ANSI C37.46
Applications
• Protection for 5.5kV transformers or
distribution systems
Definitions
E-rating
E-rated fuses operate as follows:
Over 100E - must melt in 600 seconds (10 mins.)
on 220 to 264% of E (ampere) rating.
Example - A 750E fuse must melt in 600 seconds
with an applied current of 1650 to 1980 amperes.
General Purpose Current-Limiting Fuse
A general purpose current-limiting power fuse is
one that is capable of interrupting all currents from
its rated interrupting rating down to the current
that causes melting of the fusible
element in one hour.
Medium voltage fuses
Medium voltage fuses
MV42
12/04
American Fuses
E-Rated
5.5kV - Bolt-in Series
FIGURE B
FIGURE C
FIGURE A
CATALOG NUMBERING SYSTEM
A 0 5 5 B 1 D A R 0 - 5 0 E
Ampere Rating
Revision/No.
Special Features
Diameter (D=3”)
No. of Barrels
Style (B= Bolt-in Mount)
Max. Voltage Rating (055=5.5kV)
Amp-trap Fuse
Designation Reference Ampere Number Figure Interrupting Rating
Number Rating Of Barrels RMS SYM. Amperes*
A055B1DARO-10E 10E 1 A
A055B1DARO-15E 15E 1 A
A055B1DARO-20E 20E 1 A
A055B1DARO-25E 25E 1 A
A055B1DARO-30E 30E 1 A
A055B1DARO-40E 40E 1 A
A055B1DARO-50E 50E 1 A
A055B1DARO-65E 65E 1 A 63,000
A055B1DARO-80E 80E 1 A
A055B1DARO-100E 100E 1 A
A055B1DARO-125E 125E 1 A
A055B1DARO-150E 150E 1 A
A055B1DARO-175E 175E 1 A
A055B1DARO-200E 200E 1 A
A055B2DARO-250E 250E 2 B
A055B2DARO-300E 300E 2 B
A055B2DARO-350E 350E 2 B 63,000
A055B2DARO-400E 400E 2 B
A055B2DARO-450E 450E 2 B
A055B2DORO-450E 450E 2 C
A055B2DORO-500E 500E 2 C 63,000
A055B2DORO-600E 600E 2 C
5.5kV Max. – Bolt-in Style – 23.73 (602,7mm) Hole Centers – 3" (76.2mm) Barrel Diameter
5.5kV Max. – Bolt-in Style – 17.88" (454mm) Hole Centers – 3" (76.2mm) Barrel Diameter
5.5kV Max. – Bolt-in Style – 17.88" (454mm) Hole Centers – 3" (76.2mm) Barrel Diameter
* RMS ASYM. AMPS = RMS SYM. AMPERES x 1.6
S221966
B222710
F201048
P201562
W212332
Medium voltage fuses
Medium voltage fuses
MV43
12/04
A055B1DARO - 10E to 200E - A055B2DARO - 250E to 450E
A055B1DARO - 10E to 200E - A055B2DARO - 250E to 450E
CURRENT IN AMPS
CURRENT IN AMPS
TOTAL CLEARING TIME – CURRENT DATAMINIMUM MELTING TIME – CURRENT DATA
TIME IN SECONDS
TIME IN SECONDS
American Fuses
E-Rated
5.5kV - Bolt-in Series
Medium voltage fuses
Medium voltage fuses
MV44
12/04
American Fuses
E-Rated
5.5kV - Bolt-in Series
A055B2D0RO - 450E to 600E
A055B2D0RO - 450E to 600E
TIME IN SECONDS
CURRENT IN AMPS
CURRENT IN AMPS
TIME IN SECONDS
TOTAL CLEARING TIME – CURRENT DATAMINIMUM MELTING TIME – CURRENT DATA
Medium voltage fuses
Medium voltage fuses
MV45
12/04
American Fuses
E-Rated
5.5kV - Bolt-in Series
A055B1DARO - 10E to 200E - A055B2DARO - 250E to 450E
Peak Let-Thru Current Data, E-Rated Fuses
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
A055B2D0RO - 450E to 600E
Peak Let-Thru Current Data, E-Rated Fuses
MAXIMUM PEAK CURRENT CIRCUIT CAN PRODUCE
2.6 X RMS SYM. AMPS
MAXIMUM PEAK CURRENT CIRCUIT CAN PRODUCE
2.6 X RMS SYM. AMPS
Medium voltage fuses
Medium voltage fuses
MV46
12/04
American Fuses
E-Rated
5.5kV - Bolt-in Series
Catalog Numbers, Ratings, Dimensions, Bolt-in Series, 5.5kV
Interrupting
Designation Reference Old Catalog Ampere Number of Rating
Number Number Rating Barrels RMS SYM.* Amperes
A055B3DORO-750E K212851 A550X750E-4 750E 3 63,000
900E T213365 900E-4 900E
5.5kV Bolt-in
* RMS ASYM. AMPERES = RMS SYM. AMPERES x 1.6
Indicator Flush with Surface
in Untripped Position
Blown Fuse Indicator
23.73
(603)
1.50
(38)
.44
(12) x.81
(24)
.44
(12)
25.11
(638)
22.37
(568)
1.26
(32)
3.00
(76)
.38
(10)
11.62
(296)
CATALOG NUMBERING SYSTEM
A 0 5 5 B 3 D 0 R 0 - 9 0 0 E
Ampere Rating
Revision/No.
Special Features
Diameter (D=3”)
No. of Barrels
Style (C= Bolt-in Mount)
Max. Voltage Rating (055=5.5kV)
Amp-trap Fuse
5.5kV Max. – Bolt-in Style – 23.73” (603mm) Hole Centers – 3” (76.2mm) Barrel Diameter
Medium voltage fuses
Medium voltage fuses
MV47
12/04
American Fuses
E-Rated
Bolt-in Series
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A055B3DORO – 750E to 900E
Minimum Melting Time – Current
Data, 5.5kV Fuses
A055B3DORO – 750E to 900E
Total Clearing Time – Current
Data, 5.5kV Fuses
PEAK LET-THRU CURRENT
DATA – 5.5KV BOLT-IN FUSES
MAX. INSTANTANEOUS PEAK LET-THRU AMPERES
A055B3DORO – 750E to 900E
Medium voltage fuses
Medium voltage fuses
MV49
12/04
American Fuses
E-Rated
5.5kV - 15.5kV CL-14 series
5kv and 15kV Clip-Lock Mounted Fuses
Amp-trap CL-14 E-rated 5kV and 15kV fuses have 3" diameter barrels and
mount in unique cam-locking clips, for superior connections as well as
easy installation and replacement. They are UL listed as “general purpose
current-limiting fuses” and are for use indoors (or outdoors in a
weatherproof enclosure). The unique time-current characteristic of Ferraz
Shawmut E-rated fuses allows them to be closely sized to transformer full
load rated current, as recommended by IEEE guidelines, without being
affected by normal magnetizing inrush current. CL-14 fuses are typically
sized at transformer rated current of 133%, thereby providing superior
overall protection.
Features /Benefits
UL Listed for compatibility with UL listed
equipment
Clip-Lock mounting for reliable high integrity
connection into circuit
Current limiting for superior equipment
protection
Blown-fuse indicator gives positive
identification
of open fuse
Non-venting for silent operation
Metal Embossed Catalog Number and
manufacturing date for lasting identification
Ratings
A055C
AC: 10E to 600E
5.5kV, 63kA I.R. Sym.
A155C
AC: 10E TO 300E
15.5kV, 50kA I.R. Sym
Highlights
• E-Rated
• UL Listed 5.5kV
• Complies with ANSI C37.46
Applications
Protection for 5.5kV or 15.5kV
transformers or distribution systems
Approvals
• UL Listed to JEEG, “Fuses Over 600 Volts”
• UL File # E143362
Definitions
E-rating
E-rated fuses operate as follows:
100E or less - must melt in 300 seconds (5 mins.)
at 200 to 240% of E (ampere) rating.
Over 100E - must melt in 600 seconds (10 mins.)
at 220 to 264% of E (ampere) rating.
Example - A 100E fuse must melt in 300 seconds
with an applied current of 200 to 240 amperes.
General Purpose Current-
Limiting Fuse
A general purpose current-limiting power fuse is
one that is capable of interrupting all currents
from its rated interrupting rating down to the cur-
rent that causes melting of the fusible element in
one hour.
Clip-Lock Clips for CL-14 Fuses:
228-700-520 (One pair of clips)
Medium voltage fuses
Medium voltage fuses
MV50
12/04
American Fuses
E-Rated
5.5kV - 15.5kV CL-14 series
5.5kV Clip-Lock Mounted CATALOG NUMBERING SYSTEM
FIGURE A FIGURE B FIGURE C
Indicator Flush with Surface
in Untripped Position
Blown Fuse Indicator
A 0 5 5 C 2 D 0 R 0 - 4 5 0 E
Ampere Rating
Revision/No.
Special Features
Diameter (D=3”)
No. of Barrels
Style (C= Clip Lock Mount)
Max. Voltage Rating (055=5.5kV)
Amp-trap Fuse
Catalog Numbers, Ratings, Dimensions, CL-14 Series, 5.5kV
* RMS ASYM. Amperes = RMS SYM. Amperes x 1.6
Dimensions Inches Interrupting
New Catalog Reference Old catalog Ampere Number Fig. (mm) Rating
Number Number Number Rating of Barrels ABC RMS SYM
Amperes
A055C1DORO-10E 225-007-937 10E
15E 938 15E
20E 939 20E
25E 940 25E
30E 941 30E 1 A 16.81 16.12 0.5 63,000
40E 942 40E (427) (410) (13)
50E 943 50E Tripped
65E 944 65E Force
80E 945 80E 2 lbs.
100E 946 100E
125E 947 125E
150E 948 150E
A055C1DORO-200E 225-007-949 200E
250E 950 250E
300E 951 300E 1 A 22.81 22.12 0.5 63,000
400E 952 400E (580) (562) (13)
A055C2DORO-450E 953 450E Tripped
500E 954 500E 2 B Force
600E 955 600E 2 lbs.
5.5kV Max. – Clip Lock Style – 21.25” (540mm) Clip Centers – 3” (76.2mm) Barrel Diameter
5.5kV Max. – Clip-Lock Style – 15.25” (387mm) Clip Centers – 3” (76.2mm) Barrel Diameter
R213363
Q214880
X215898
J216921
D217951
C218985
V219507
Q221964
Z222708
G212848
G213860
R214375
V215390
B216408
W217438
J218462
N223227
D201046
M201560
Medium voltage fuses
Medium voltage fuses
MV51
12/04
MINIMUM MELTING TIME – CURRENT DATA, 5.5KV FUSES
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A055C1DORO – 10E to 400E and A055C2DORO – 450E to 600E
TOTAL CLEARING TIME – CURRENT DATA, 5.5KV FUSES
A055C1DORO – 10E to 400E and A055C2DORO – 450E to 600E
American Fuses
E-Rated
5.5kV - 15.5kV CL-14 series
Medium voltage fuses
Medium voltage fuses
MV52
12/04
American Fuses
E-Rated
Bolt-in Series
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A055C1DORO – 10E to 400E and A055C2DORO – 450E to 600E
Peak Let-Thru Current Data, 5.5kV CL-14 Fuses
Medium voltage fuses
Medium voltage fuses
MV53
12/04
Reference and Catalog Numbers, Ratings,
Dimensions, CL-14 Series, 15.5kV
FIGURE A FIGURE B FIGURE C
15.5kV Clip-Lock Mounted
Indicator Flush with Surface
in Untripped Position
Blown Fuse Indicator
American Fuses
E-Rated
5.5kV - 15.5kV CL-14 series
CATALOG NUMBERING SYSTEM
A 1 5 5 C 1 D 0 R 0 - 8 0 E
Ampere Rating
Revision/No.
Special Features
Diameter (D=3”)
No. of Barrels
Style (C= Clip Lock Mount)
Max. Voltage Rating (155=15.5kV)
Amp-trap Fuse
* RMS ASYM. Amperes = RMS SYM. Amperes x 1.6
Dimensions Inches Interrupting
New Catalog Reference Old catalog Ampere Number Fig. (mm) Rating
Number Number Number Rating of Barrels ABC RMS SYM
Amperes
A155C1DORO-10E 225-007-967 10E
15E 968 15E 19.81 19.12 0.5
20E 969 20E (504) (486) (13)
25E 970 25E 1 A Tripped 50,000
30E 971 30E Force
40E 972 40E 2 lbs.
50E 973 50E
A155C1DORO-65E 225-007-974 65E
80E 975 80E 1 A 22.81 22.12 0.5 50,000
100E 976 100E (580) (562) (13)
A155C2DORO-125E 977 125E 2 B
A155C3DORO-150E 978 150E Tripped
200E 979 200E Force .
250E 980 250E 3 C 2 lbs
300E 981 300E
15.5kV Max. – Clip-Lock Style – 21.25” (540mm) Clip Centers – 3” (76.2mm) Barrel Diameter
15.5kV Max. – Clip-Lock Style – 18.25" (464mm) Clip Centers – 3" (76.2mm) Barrel Diameter
Z211300
T212330
H212849
H213861
S214376
R214881
W215391
Y215899
C216409
F203463
K216922
K218463
D218986
W219508
R221965
Medium voltage fuses
Medium voltage fuses
MV54
12/04
American Fuses
E-Rated
5.5kV - 15.5kV CL-14 series
MINIMUM MELTING TIME – CURRENT DATA, 15.5KV FUSES
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A155C1DORO – 10E to 100E / A155C2DORO - 125E
A155C3DORO – 150E to 300E
TOTAL CLEARING TIME – CURRENT DATA, 15.5KV FUSES
A155C1DORO – 10E to 100E / A155C2DORO - 125E
A155C3DORO – 150E to 300E
Medium voltage fuses
Medium voltage fuses
MV55
12/04
American Fuses
E-Rated
5.5kV - 15.5kV CL-14 series
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A155C1DORO – 10E to 100E - A155C2DORO – 125E
A155C3DORO – 150E to 300E
Peak Let-Thru Current Data, 15.5kV CL-14 Fuses
Medium voltage fuses
Medium voltage fuses
MV57
12/04
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
R-RATED MOTOR STARTER FUSES
Amp-trap®R-rated fuses are current-limiting, high inter-
rupting rating fuses intended for the short-circuit protec-
tion of medium voltage motors and motor controllers. R-
rated fuses have a minimum interrupting rating and must
be coordinated with overload relays in combination
motor starters. The motor starter manufacturer generally
specifies the R-rated fuse size. Amp-trap R-rated fuses
are-rated 2R to 36R, at 2.4, 4.8, and 7.2kV. 4.8 and 7.2kV
fuses are UL Recognized. The 4.8kV (A480R) is available
with hookeye tab. The 7.2kV (A072F) series has the same
dimensions as the 4.8kV (A480R), allowing smaller 7.2kV
equipment or 4.8kV upgrades. The A072B is a bolt-in
7.2kV fuse.
Features /Benefits
Ferrule mounting for standard clips and
interchangeability with other brands of fuses.
7.2kV series has the same dimensions as
4.8kV fuses, allowing compact, higher
voltage-rated equipment designs.
7,2kV bolt-in design for improved
design flexibility.
• Optional hookeye on 4.8 kV for non
load-break isolation by hookstick.
Ratings
A240R
AC: 2R to 36R
2750V, 45kA I.R. Sym.
A480R
AC: 2R to 36R
5500V, 63kA I.R. Sym.
A072F - A072B
AC: 2R to 24R
7200V, 50kA I.R. Sym.
Back-up type Current-Limiting Fuse:
A current limiting fuse which can interrupt any current
between it’s rated minimum interrupting current and it’s
maximum interrupting current. Backup fuses are not
designed or intended to open under overload conditions.
Highlights
• R-Rated
• UL Recognized in 4.8 and 7,2 kV ratings
Applications
Short circuit protection of medium voltage motors and
motor controllers
Approvals
• Ferraz Shawmut certified
- A240R @ 2750V, 45kA Sym.
• UL Recognized Component
- A480R @ 5080V, 50kA, Sym.
- A072F @ 7200V, 50kA, Sym.
- A072B @ 7200V, 50kA, Sym.
• UL file # E93367
Spring-reinforced clips
• 228-700-530 (one pair of clips)For 3” diameter,
2 barrels max.
Medium voltage fuses
Medium voltage fuses
MV58
12/04
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
A240R 2.4kV Ferrule Style
Catalog and Reference Numbers, Ratings, Dimensions, 2.4kV
* This rating defines the fuse’s long-term thermal capability per ANSI C37 46-1981 and should not be
the sole factor for selecting a specific R-rating.
** Not recommended for use in fuse clips which grasp only one barrel.
FIGURE A FIGURE B FIGURE C
3
(76)
(76) (76) (76)
(12,7) (84,1) (84,1) (84,1)
(12,7) (12,7)
(76) (76) (76) (76) (76)
33 333
Indicator flush with surface
2 lb. Force (Tripped)
Catalog Reference Continous Minimum
Number Number Ampere Dim. Interrupting Maximum
Fig. Size Rating L Rating Tested
Standard at 40˚ Rms Amperes RMS RMS
Asym Sym
A240R2R J201557 2R 70 170
A240R3R F211812 3R 100 250
A A240R4R E212846 4R 130 340
A240R6R E213858 6R 170 10-7/8 500 70kA 45kA
A240R9R P214373 9R 200 (276mm) 760 @ @
A24OR12R R219504 12R 230 1000 2750V 2750V
BA24OR18R N221962 18R 390 1500
A240R24R L223225 24R 450 1950
C A240R36R W211297 36R** 650 2900
A240R
Medium voltage fuses
Medium voltage fuses
MV59
12/04
MINIMUM MELTING TIME – CURRENT DATA, 2.4KV FUSES
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A240R2R to 36R, 2400 Volts
A240R2R to 36R, 2400 Volts
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
TOTAL CLEARING TIME – CURRENT DATA, 2.4KV FUSES
Medium voltage fuses
Medium voltage fuses
MV60
12/04
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A240R2R to 36R, 2400 Volts
Peak Let-Thru Current Data, R-Rated Fuses
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
Medium voltage fuses
Medium voltage fuses
MV61
12/04
A480R 4.8kV Ferrule Style
* This rating defines the fuse’s long-term thermal capability per ANSI C37 46-1981 and should not be the sole factor for selecting a
specific R-rating.
** Not recommended for use in fuse clips which grasp only one barrel.
Catalog and Reference Numbers, Ratings, Dimensions, 4.8kV
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
Catalog Reference Continous Minimum 1 Phase Interrupting Rating
Number Number Ampere Dim. Interrupting UL Component Maximum
Fig. Size Rating L Rating Recognition Tested
Standard at 40˚ Rms Amperes RMS RMS RMS RMS
Asym Sym Asym Sym
A480R2R-1 P221963 a2R 70 190
A480R3R-1 K201558 3R 100 225
A480R4R-1 G211813 4R 130 330
A A480R5R-1 Q213362 5R 150 400 80kA 50kA 100kA 63kA
A480R6R-1 Q214374 6R 170 15-7/8 500 @ @ @ @
A480R9R-1 W215897 9R 200 (403mm) 740 5080V 5080V 5500V 5500V
A480R12R-1 N214878 12R 230 955
B A480R18R-1 Z216406 18R 390 1440
A480R24R-1 H218461 24R 450 1910
C A480R36R-1 C201045 36R** 650 2810
A480R2R-1HE X222706 2R 70 190
A480R3R-1HE S203428 3R 100 225
A480R4R-1HE R212328 4R 130 330
A A480R5R-1HE F213859 5R 150 16-1/8 400 80kA 50kA 100kA 63kA
A480R6R-1HE P214879 6R 170 (410mm) 500 @ @ @ @
A480R9R-1HE A216407 9R 200 740 5080V 5080V 5500V 5500V
A480R12R-1HE S215388 12R 230 955
B A480R18R-1HE G216919 18R 390 1440
A480R24R-1HE A218983 24R 450 1910
FIGURE A FIGURE B FIGURE C
Indicator flush with surface
2 lb. Force (Tripped)
Indicator flush
(Tripped position)
Hookeye illustration
33 333
(76)
(76) (76) (76)
(8)
(25.4)
(12,7) (84,1) (84,1) (84,1)
(12,7)
(76) (76) (76) (76) (76)
3
A480R-1HE with hookeye
A480R-1
Medium voltage fuses
Medium voltage fuses
MV62
12/04
MINIMUM MELTING TIME – CURRENT DATA, 4.8KV FUSES
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
TOTAL CLEARING TIME – CURRENT DATA, 4.8KV FUSES
A480R-1, and A480R-1HE, 4800 Volts
A480R-1, and A480R-1HE, 4800 Volts
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
Medium voltage fuses
Medium voltage fuses
MV63
12/04
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A480R-1 and A480R-1HE, 4800 Volts
Peak Let-Thru Current Data, R-Rated Fuses
Medium voltage fuses
Medium voltage fuses
MV64
12/04
7.2kV Ferrule & Bolt-in Types
Blown Fuse Indicator
Extends 0.5 in. (12.7mm) when
fuse opens,
with 2 lbs. of force at end of travel
(413.1)
(6.3)
16.26
(413.1)
7.62
(194)
19.25
(488)
17.88
(454.2) 1.53
(38.8)
.44 x .91
(11 x 23)
.25
(6.3)
16.26
(92.2)
3.63
.25
(76.2)
3.00
(76)
3 3
15.88
(403)
15.88
(403)
33
3
3.312
(84.1)
0.5
(12.7) 0.5
(12.7)
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
A 0 7 2 F 1 D 0 R 0 - 12R
R Rating
Revision/No.
Special Features
Diameter (D=3")
No. of Barrels
Style (F=Ferrule , B=Bolt-in Mount)
Nominal Voltage Rating (072=7.2kV)
Amp-trap Fuse
CATALOG NUMBERING SYSTEM
Reference and Catalog Numbers, Ratings, Dimensions, 7.2kV
Allowable Minimum 1 Phase Interrupting Rating
Figure Catalog Reference Rating Continuous Interrupting UL Component Recognition
Number Number Ampere Rating Rating
at 40˚C RMS Amperes RMS Asym. RMS Sym.
A072F1DORO-2R 2R 70 190
A072F1DORO-3R 3R 100 225
A072F1DORO-4R 4R 130 330
A A072F1DORO-5R 5R 150 400 80kA 50kA
A072F1DORO-6R 6R 170 500 @@
A072F1DORO-9R 9R 200 740 7200V 7200V
A072F1DORO-12R 12R 230 955
BA072F2DORO-18R 18R 390 1440
A072F2DORO-24R 24R 450 1910
A072B1DARO-2R 2R 70 190
A072B1DARO-3R 3R 100 225
A072B1DARO-4R 4R 130 330 80kA 50kA
C A072B1DARO-5R 5R 150 400 @ @
A072B1DARO-6R 6R 170 500 7200V 7200V
A072B1DARO-9R 9R 200 740
A072B1DARO-12R 12R 230 955
DA072B2DARO-18R 18R 390 1440
A072B2DARO-24R 24R 450 1910
Ferrule Type
Bolt-in Type
(76) (76)(76)
FIGURE A FIGURE B
FIGURE D
FIGURE C
M214877
R215387
T215895
Y216405
F216918
T217436
N214372
G218460
Z218982
H201556
R203427
V211296
E211811
P212326
D212845
B201044
N213360
D213857
Medium voltage fuses
Medium voltage fuses
MV65
12/04
MINIMUM MELTING TIME – CURRENT DATA, 7.2KV FUSES
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A072F2 and A072B, 7200 Volts
TOTAL CLEARING TIME – CURRENT DATA, 7.2KV FUSES
A072F and A072B, 7200 Volts
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
Medium voltage fuses
Medium voltage fuses
MV66
12/04
American Fuses
R-Rated
2.4kV - 4.8kV/7.2kV - A 240R/A 480R/A 072F/A 072B
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
AO72F and A072B2, 7200 Volts
Peak Let-Thru Current Data, R-Rated Fuses
Medium voltage fuses
Medium voltage fuses
MV67
12/04
1.37 (35)
2.75 (70)
.78 (20)
American Fuses
R-Rated
3.3kV/5.3kV/7.2kV - A 033D1/A055D1/A072D1
R-RATED IEC DIN Style MV FUSES
Amp-trap R-rated DIN style fuses are current limiting, high interrupting rat-
ing fuses, intended for the short circuit protection of medium voltage
motors and motor controllers. This product range offers North
American R-rated performance in the IEC 282-1 DIN
mounting configuration of 442mm. R-rated fuses are applied as back up
fuses that have a minimum interrupting rating, and must be coordinated
with overload relays in combination motor starters.
Amp-trap R-rated, DIN type fuses are offered in voltage ratings of 3.3kV,
5.3kV and 7.2kV in ratings from 2R to 19R. All fuses within this product
group are ULcomponent recognized.
Features /Benefits
Clip Mount DIN 45: R-rated fuses with North
American ANSI characteristics in a standard DIN
442mm size.
Ratings
A033D1
AC: 2R to 19R*
3300V max, 65kA I.R. Sym.
A055D1
AC: 2R to 19R*
5300V max, 65kA I.R. Sym.
A072D1
AC: 2R to 19R*
7200V max, 65kA I.R. Sym.
Back-up type Current-Limiting
Fuse:
A current limiting fuse which can interrupt any
current between it’s rated minimum interrupting
current and it’s maximum interrupting current.
Backup fuses are not designed or intended to
open under overload conditions.
Highlights
• R-Rated
• UL Recognized
Applications
Short circuit protection of medium voltage
motors and motor controllers
Approvals
• UL Recognized Component
• UL file # E93367
Spring-reinforced clips
• MR45 & Spring ref.# L096472
Fuse-Holder
• SI 24/442 Ref # K209425
In compliance with IEC 282-1, DIN standard
43625.
Definitions
R-Rating:
An “R” rated fuse will melt in the range of 15 to
35 seconds at a value of current equal to 100
times the “R” rating.
* Note: Ratings above 19R may
be achieved by paralleling fuses.
Please consult factory for details.
Medium voltage fuses
Medium voltage fuses
MV68
12/04
American Fuses
R-Rated
3.3kV/5.3kV/7.2kV - A 033D1/A055D1/A072D1
FIGURE A
Continuous Continuous Minimum 1 Phase InterRupting Rating
Fig. Designation Reference Size Amp Rating Amp Rating Inter. Rating Maximum Tested
Number at 55°C** at 40°C** RMS Amperes
A033D1DSRO-2R 2R 63 70 180
A033D1DSRO-3R 3R 90 100 270
A033D1DSRO-4R 4R 115 130 355
A033D1DSRO-5R 5R 135 150 450
A A033D1DSRO-6R 6R 150 170 550 100kA 65kA
A033D1DSRO-9R 9R 180 200 710 @ @
A033D1DSRO-12R 12R 210 230 1100 3300V 3300V
A033D1DSRO-13R 13R* 230 260 1200
A033D1DSRO-16R 16R* 270 300 1500
A033D1DSRO-19R 19R* 280 310 1700
A055D1DSRO-2R 2R 63 70 180
A055D1DSRO-3R 3R 90 100 270
A055D1DSRO-4R 4R 115 130 355
A055D1DSRO-5R 5R 135 150 450
A A055D1DSRO-6R 6R 150 170 550 100kA 65kA
A055D1DSRO-9R 9R 180 200 710 @ @
A055D1DSRO-12R 12R 210 230 1100 5500V 5500V
A055D1DSRO-13R 13R* 230 260 1200
A055D1DSRO-16R 16R* 270 300 1500
A055D1DSRO-19R 19R* 280 310 1700
A072D1DSRO-2R 2R 63 70 180
A072D1DSRO-3R 3R 90 100 270
A072D1DSRO-4R 4R 115 130 355
A072D1DSRO-5R 5R 135 150 450
A A072D1DSRO-6R 6R 150 170 550 100kA 65kA
A072D1DSRO-9R 9R 180 200 710 @ @
A072D1DSRO-12R 12R 210 230 1100 7200V 7200V
A072D1DSRO-13R 13R* 230 260 1200
A072D1DSRO-16R 16R* 270 300 1500
A072D1DSRO-19R 19R* 280 310 1700
RMS Asym RMS sym
7.2kV Max. DIN IEC Style 442 mm
5.5kV Max. DIN IEC Style 442 mm
3.3kV Max. DIN IEC Style 442 mm
* 13R, 16R and 19R are not standard ratings defined in ANSI C37.46.
** This rating defines the thermal capability of the fuse per ANSI 37.46 and should not be the sole factor in fuse selection.
Indicator flush with surface before fuse opens.
Indicator extends 1.0”(25.4mm) after fuse opens.
Indicator exerts 4.5 LB force at end of travel.
Medium voltage fuses
Medium voltage fuses
MV69
12/04
American Fuses
R-Rated
3.3kV/5.3kV/7.2kV - A 033D1/A055D1/A072D1
MINIMUM MELTING TIME – CURRENT DATA
TIME IN SECONDS
CURRENT IN AMPS
TIME IN SECONDS
CURRENT IN AMPS
A033D1, 3300 Volts - A055D1, 5300 Volts - A072D1, 7200 Volts
TOTAL CLEARING TIME – CURRENT DATA
A033D1, 3300 Volts - A055D1, 5300 Volts - A072D1, 7200 Volts
Medium voltage fuses
Medium voltage fuses
MV70
12/04
American Fuses
R-Rated
3.3kV/5.3kV/7.2kV - A 033D1/A055D1/A072D1
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
A033D1, 3300 Volts - A055D1, 5300 Volts - A072D1, 7200 Volts
Peak Let-Thru Current Data, R-Rated Fuses
MAXIMUM PEAK CURRENT CIRCUIT CAN PRODUCE
2.6 X RMS SYM.AMPS
Medium voltage fuses
Medium voltage fuses
MV71
12/04
Catalog Number Dimensions - inches Fuse Clips*
Prefix A B C Centers Cat. NO.
A240T 4-5/8 13/16 5/8 4.0” CO8917P
A480T 5-5/8 13/16 5/8 5.0” CO8917P
A500T 5-5/8 1 9/16 5.0” -
A720T 9-1/2 13/16 5/8 8.88” CO8917P
Dimensions
E-Rating Catalog Number Reference Number
2400V 4800V 5000V 7200V 2400V 4800V 5000V 7200V
1/2E A240T1/2E A480T1/2E A500T1/2E-1 A720T1/2E-1
1E A240T1E A480T1E A500T1E-1 A720T1E-1
2E A240T2E A480T2E A500T2E-1 A720T2E-1
3E - A480T3E A500T3E-1 A720T3E-1
4E - A480T4E A500T4E-1 -
5E A240T5E A480T5E A500T5E-1 -
Standard Fuse Ampere Ratings, Catalog and Reference Numbers
POTENTIAL TRANSFORMER FUSES
Ferraz Shawmut E-rated PT fuses are current limiting fuses
with high interrupting rating, used for primary winding-
protection of potential transformers. They are small
dimension, ferrule-type fuses and mounted in standard
clips. Ratings are 1/2E to 5E at 2.4, 4.8, and 5.0 kV at
7,2kV rating are 1/2E to 3E
Features /Benefits
• Current limiting protection for transformers
• Ferrule mounting for ease of installation in
standard clips
• Compact size saves valuable mounting space
• Fiberglass body provides dimensional stability in
harsh industrial environments
• Metal embossed catalog number for lasting
identification
Ratings
A240T
AC: 1/2E to 5E
2400VAC, 50kA I.R. Sym.
A48OT
AC: 1/2E to 5E
4800VAC, 50kA I.R. Sym.
Highlights
• E-Rated
• Current-Limiting
Applications
Primary protection for 2.4, 4.8, 5.0 or 7.2kV
potential transformer
A500T
AC: 1/2E to 5E
5000VAC, 50kA I.R. Sym.
A720T
AC: 1E to 3E
7200VAC, 50kA I.R. Sym.
American Fuses
Potential Transformer Fuses (E-Rated)
2.4kV to 7.2 kV - A240T / A480T / A500 / A072T
P212855 C215397 S218470 Z203710
P213867 D215904 D219515 E211305
A214383 H216414 X221970 P211820
- Q216927 G222715 C212338
- C217444 W223234 -
Y214887 M217959 W201568 -
Medium voltage fuses
Medium voltage fuses
MV72
12/04
American Fuses
Potential Transformer Fuses (E-Rated)
2.4kV to 7.2 kV - A240T / A480T / A500 / A072T
MELTING TIME – CURRENT DATA - PT FUSES - 2400V
MELTING TIME – CURRENT DATA - PT FUSES - 4800V
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A240T1/2E to 5E
A480T1/2E to 5E
Medium voltage fuses
Medium voltage fuses
MV73
12/04
TIME IN SECONDS
CURRENT IN AMPERES
TIME IN SECONDS
CURRENT IN AMPERES
A500T1/2E-1 to 5E-1 Melting Time
Current Data - PT Fuses - 5000V
A720T1E-1 and A720T2E-1
Melting Time – Current Data
PT Fuses - 7200V
American Fuses
Potential Transformer Fuses (E-Rated)
2.4kV to 7.2 kV - A240T / A480T / A500 / A072T
Medium voltage fuses
Medium voltage fuses
MV75
12/04
American Fuses
Capacitor
Ampere
Rating
6 to 25 Amps
30 to 50 Amps
60 to 95 Amps
100 to 150 Amps
160 to 300 Amps
600V 2400V 3000V 4300V 5500V
1500V
Ratings Table
Mounting Configurations
Please consult factory for mounting configurations availability
Voltage Rating Range
TYPE 10 - INNER THREAD
TO SCREW
TYPE 15 - EXTERNAL FEMALE
TO BOLT
TYPE 50 - SCREW TO BOLT
(L BRACKET)
TYPE 60 - BOLT (L BRACKET) TO BOLT
(L BRACKET)
TYPE 70
TUBE TO TUBE
As a complement to the wide variety of fuse lines
developed by Ferraz Shawmut for every market and
application type, we also offer a line of capacitor fuses
ranging from 600 VAC to 5500 VAC. The Ferraz
Shawmut capacitor fuse range offers many models
with the same electrical
ratings but with various blade, studs, or end-contact
designs in order to satisfy specific
customer needs.
Features /Benefits
• Cartridge type
• Full range operation
• Indicator for most types
• Direct mounting on capacitor
• Prevent rupture of failed capacitor
• Special mounting
brackets available
Ratings
600VAC to 5500VAC
6A to 300A
TYPE 20 - SCREW TO BOLT
(FLAT BRACKET)
TYPE 30 - EXTERNAL FEMALE TO BOLT
(L BRACKET)
TYPE 40 - EXTERNAL FEMALE TO
EXTERNAL FEMALE
TYPE 121 - EXTERNAL FEMALE
TO EXTERNAL FEMALE
Medium voltage fuses
Medium voltage fuses
MV77
12/04
Type IDT 10
FOR HIGH VOLTAGE
OVERHEAD NETWORKS
INDICATES INSULATION FAULTS BY DETECTION OF
CURRENTS IN GROUND CIRCUITS
USABLE ON ALL HIGH VOLTAGE DISTRIBUTION
NETWORKS REGARDLESS OF NEUTRAL RATES
CONNECTS DIRECTLY TO THE GROUNDCABLE OF THE POLES
MAY BE RESET AFTER OPERATION
OPERATES AUTONOMOUSLY, WITHOUT BATTERIES
RESISTANT TO TOUGH WEATHER CONDITIONS
INSENSITIVE TO LIGHTNING AND OPERATING CURRENTS
DETECTS DAMAGE TO LIGHTNING ARRESTERS,
TRANSFORMERS AND INSULATORS
Presentation
The insulation fault indicator is presented in the form of a compact case made of a highly sturdy synthetic
material. A window on the front enables the viewing of a red warning light in case of operation. This
signal may be seen from 10 meters away, across a 120 ° sector.
The IDT20 Comp counts current pulses due to lightning - A6- digits electromechanical meter indicate the
number of lightning strikes.
Two conductive contacts on the front allow the indicator to be reset.
The case contains a 16 mm diameter hole for the passage of a ground cable. The indicator is delivered
with an 80 cm cable section and two crimping sleeves to prevent the ground circuit from being cut during
installation. Two openings on the back enable the device to be attached to the pole by metal strip.
Operation
Ground currents caused by insulation faults are measured by an integrated current transformer. An electro-
nic panel processes the transformer output signal and controls the operation of the warning light in the
event it exceeds a preset threshold. The signal is maintained even after power on the line has been dis-
connected, enabling the operator to quickly detect the fault location.
Resetting and testing of the indicator are ensured by an IDT 101 type reset device.
Before fault After fault
MV Fault Indicator
IDT10 and IDT20
Medium voltage fuses
Medium voltage fuses
MV78
12/04
MV Fault Indicator
IDT 10 and IDT 20
A/ Fixing indicator to electric pole
The indicator is installed in a horizontal position, facing in either direction.
The indicator may be attached to a wooden or concrete pole.
On concrete poles, the indicator may be placed either on flat side or in a corner.
The different configurations are described below.
Two openings located at the back of the case are designed to accommodate a stainless steel strip, 20
mm wide and 0.4 mm thick, in order to fix the indicator to the post by hooping.
The hole in the indicator case must be positioned as closely as possible to the ground cable.
WARNING: During attachment, the strip must pass between the ground cable and the post in order to
prevent the cable from being tightened against the post during hooping.
wooden pole
ground cable
indication
ground cable
ground cable
strip
strip
strip
indication
indication
concrete poles
concrete poles
Technical characteristics
IDT 10 IDT 20 IDT 20 Com
Reference numbers
- Detection currents: 50 Hz
50 Hz
- Minimum detection currents:
- Sensitivity to 3 waves 5ms (EDF specification)
- Non detection current: 2ms rectangular wave
- Non detection current: wave 4/10µs
- Resetting unit
- Weight
- Counting lightning current pulses
- Minimum operating current for the counter. Ipeak:
- Maximum operating current for the counter. Ipeak:
- Insensitivity of the counter: - 1/2 sinusoid wave Ipeak:
- 50Hz, Ipeak:
- Power supply
- Isolated from pole @
- Climatic conditions
- Protection rating / impact withstand
D210223
15A / 500ms
10A / 143ms
9A
50A
150A
100kA
E210753
0.950kg
W229099
15A / 100ms
10A / 110ms
4A
no
250A
100kA
F229867
1kg
V225970
15A / 100ms
10A / 110ms
4A
no
250A
100kA
F229867
1.2kg
400A wave 8/20µs
100kA wave 4/10µs
300A / for 3.1ms
300A / for 700 ms
No counter
Completely independent power supply
(no batteries) 2kV 50Hz and 5kV wave 1.2/50µs
-25 to +70°C / Relative humidity 100%
IP 56 / IK 07
Medium voltage fuses
Medium voltage fuses
MV79
12/04
B/ Connecting the ground cable
Once the indicator is attached to the pole:
- Introduce the cable section into the case via the 16 mm hole
- Approximately center the cable section within the case
- Place and crimp a C25 E connector to attach the upper end of the cable section to the ground cable
- Place and crimp the second C25 E connector to attach
- Ensure that both connections are properly completed
- Cut the ground cable just below the upper connector and just above the lower connector
- Remove the piece of ground cable shunted by the cable section
ground cable
ground cable
ground cable
C25E
connector
C25E
connector
C25E
connector
C25E
connector
strip
strip
cable section cable section
ground cable
MV Fault Indicator
IDT10 and IDT20
Medium voltage fuses
Medium voltage fuses
MV81
12/04
MV Fault Indicator
Cabletroll 2500
EARTH FAULT CURRENT
SENSING SYSTEM
FAULT SENSING IN FAULTY SECTIONS OF
underground NETWORKS
FOR INDOOR OR OUTDOOR CABLES
UP TO 36KV
PROGRAMMABLE trip level
increased visibility through high intensity led
or optional xenon flash unit
easy-to-install
uv-stabilized POLYCARBONATE housing
Ground Light
Designation Reference fault sensitivity Indication Catalog
Number signalling reset Number
Cabletroll J208641 Fixed levels 1/ Timer reset A pair of LED and (or CT2500-2510
2500/2510 of temporisation relay contacts optional Xénon
40, 80, 120 A (off, 2, 4, 8, 16 (N. O.) flash unit
or or 32 hours) 120 V DC/ 1A
continuously 2/ 15 seconds gives a 1-second
adjustable after a successful impulse
from 5-120 A repowering
Cabletroll 2500 fault detectors have been designed for use outdoors or in sheltered areas.
Normal operating conditions:
• Ambient temperature from – 40°C to + 70°C
• Lithium battery lifetime: 10 years for LED application at 20°C ambient or 2,500 hour operation.
• Weight: 750 g
Medium voltage fuses
Medium voltage fuses
MV82
12/04
Functional description
Ground faults in general
In networks with directly earthed zero-point, a
ground fault is equivalent to a phase-to-ground
short circuit. In that case the current magnitude will
be somewhat less than in the case of a phase-to-
phase short circuit. For networks that do not have
directly earthed zero-point, the magnitude of the
singular ground fault current is ruled by the size of
the galvanically interconnected network, voltage
level, type of cable and the zero-point equipment.
Ground Fault Element
The Ground Fault Element is a summing current
transformer (CT) which generates a current when
the vectorial sum of the 3 phase currents becomes
different from zero, i.e. during ground fault. With
no ground fault, the vectorial sum is approximately zero.
Mounting
Ground faults in Element
The element connects to the indicator
via its ready-mounted cable (2.0 m).
Multi-core cable: The element is
mounted on the screened part of the
cable, below the stripback point,
according to the mounting instruc-
tions. The screen is turned back under-
neath the flexible CT-core and termina-
ted at the ground point. The principle
is shown in figure opposite.
Ground faults Indicator
The Indicator should be mounted in a readily visible
location. It can be mounted on a pole or a wall with
the two enclosed self-threading screws. The Indicator
is also suited for mounting with stainless steel or PVC
cable ties. Both options are illustrated in figure above.
Remove the front cover of the indicator to access
holes for screws/ties. See figure for further details.
Mounting of
Ground Fault Indicator
Overview
Cabletroll 2500 is a ground fault sensing system. It
consists of a Ground Fault Element and Ground
Fault Indicator. It can be mounted in high voltage
underground cable distribution networks with sys-
tem voltage from 6 to 36 kV.
The sealed Ground Fault Element mounts on most
widely used cable types, while the weatherproof
indicator is well suited for outdoor mounting (See
fig. 1).
The indicator is fitted with a high intensity LED for
local indication and an optional Xenon flash unit. It
is also equipped with a pair of relay contacts for
connection to remote indicators, which communi-
cate via cable and/or radio.
The trip level for ground fault can be set on-site to
fixed values of 40A, 80A or 120A. It is factory set to
40A. In addition, the trip level can be continuously
adjusted in the ranges 5-40A, 8-80A or 12-120A.
CABLETROLL 2500
Ground Fault
Element:
Screen turnback
Ground fault sensor principle
ground fault
indicator
ground fault
element
ground
cable box
remote indicator
current
sensor
earth
1 Cable sheath
2 Summing current
transformer
3 Cable coupling box
4 Ground wire
5 Ground fault indicator
OPTIONAL
XENON FLASH
UNIT
POTENTIOMETER
FOR TRIP LEVEL
ADJUSTING
TERMINAL
STRIPS
TENSION
RESTRAINERS
BATTERY
CONNECTOR
COVER SCREW
BASE
STAINLESS STEEL OR PVC
CABLES TIES
SILICON
GASKET
MAGNET
PARKING
SCREW
TO OPEN THE COVER:
CAREFULLY OUTBEND
THE LOCK ON THE
BOTH SIDES
MV Fault Indicator
Cabletroll 2500
Medium voltage fuses
Medium voltage fuses
MV83
12/04
Save time and money!
Let CABLETROLL 2700 track down
your faulty sections
and save you the guess
work and time involved in traditional
methods of switching during faults
Microcontroller based indicator
Programmable function in software
Separate indication of ground fault and shorT circuit faults
Indication of phase and fault type remote signaling outputs
Multiple power supply alternatives
Multi-reset function: Manually, programmable, timer, remote and by voltage return
Response time adaptable to relay protection
System description
Cabletroll 2700 is a complete system for indication of earth-fault and short circuit faults in an underground
6-36V cable network.
The system consist of three different modules:
• Ground fault element with a split core for sensing the imbalance during ground faults
• 2 (or3) sensors for detecting short-circuits
• Processing unit including power supply and indication unit with flashing LED's for local indication
and relay contacts for remote signalling, controlled by a microcontroller.
Trip level for ground fault is continuously adjustable within the range of 5-240A. Short circuit trip level is
adjustable within the range of 300-1000A.
The system has separate indicators for ground fault and short-circuit faults.
Three LED's show which phases are involved in the short circuit.
For remote signaling, two pairs of relay contacts are available; ground fault and short circuit.
Operating mode
Functions are controlled by a microprocessor and all time delays and operation of the indication unit are
programmed in software, making it very easy to adapt to different requirements.
Different operating modes are available:
• Immediate indication of both permanent and transient faults
• Immediate local and remote indication of both permanent and transient faults causing circuit
breaker tripping
• Postponed operation of relay contacts, allowing closing-cycles to finish before
remote-indication is activated Indication of permanent faults only
• Both timer and voltage reset can be enabled or disabled independently
MV Fault Indicator
Cabletroll 2700
Medium voltage fuses
Medium voltage fuses
MV84
12/04
Technical specifications
Trip levels
Ground fault: 40, 80,105, 120, 1601 210 and
240A (fixed levels) or continuously adjustable
from 5-240A.
Short Circuit: Adjustable in the range 300 - 1000 A
Response time
• Independant adjustable time delays for ground
fault and short circuit faults.
Indication
• Visual by 4 internal LED’s
• External LED / Xenon flash (optional)
• 0utputs for remote indication
Inputs
• Ground Fault Element
• 3 x Short-Circuit Element (AMP fiber optic
connector)
• External power 230V AC
• External 5-30 (72V) DC/AC -power
• External reset
Outputs
• LED-3 / FlashTroll 1500 (for indication outside
the kiosk by LED or Xenon-flash)
• Relay 1: Volt free NO / NC for ground fault
indication
• Relay 2: Volt free NO / NC for short-circuit
indication
• Signal output to communication module
• Optical output (AMP) ground fault indication
(Optional)
Optical output (AMP) for short-circuit
indication(Optional)
MV Fault Indicator
Cabletroll 2700
Medium voltage fuses
Medium voltage fuses
MV85
12/04
Test/reset
• Magnet contacts for activating test/reset
without opening housing.
• Internal push-button for test/reset.
• Remote reset (closed contact)
• External reset 230V AC
• Reset from internal timer: 2, 4, 8, 12, 16, 24
and 32 hours.
Power supply alternatives
• Internal lithium battery
• Internal sealed lead rechargable battery
(giving 50 hrs back-up)
• External 230 VAC
• External 5 - 30 V DC / AC
• By using a Power Box-DC/DC-converter,
external power can be in the range of 5-72 V
DC/ AC, and the CT 2700 will be galvanic
insulated from power source.
Power consumption
Surveillance mode: < 50 mA (minimum 7 years
operation with Lithium-battery providing 2hrs
activation 10 times year).
Alarm mode:< 50 mA depending on external
indication.
Temperature range: -40 / +70 deg.
Function:-
Function can easily be adpated to different
conditions by setting parameters in software,
such as response time, reset timing, operation
of relays etc.
Basic modes
Mode 0: Immediate local and remote indica-
tion. Voltage reset enabled. Timer
reset disabled. Indication of both
permanent and transient fault.
Mode 1: Immediate local and remote indica-
tion. Voltage reset disabled. Timer
reset enabled. Indication of both
permanent and transient fault.
Mode 2: Immediate local and remote indica-
tion
Voltage reset enabled. Timer reset
enabled.
Indication of both permanent and
transient fault causing circuit brea-
ker tripping.
Mode 3: Postponed operation of relay
contacts, allowing reclosing-cycles
to finish before
remote-indication is activated. Reset
functions as for Mode 2.
Indication of permanent faults only.
Battery : Every 2500 hours of indication,
change normally every 7 years.
EMC: The indicator is designed according
to current EMC-standards for immu-
nity and emission.
MV Fault Indicator
Cabletroll 2700
Medium voltage fuses
Medium voltage fuses
MV87
12/04
MV Fault Indicator
Cabletroll 3600
Directional fault current indicator
for underground systems
Presentation
CABLETROLL 3600 directional Fault Current Indicators (FCI) are designed to help the operator locate faults
on underground lines. They detect both single phase-to-ground (PTG) and phase-to-phase (PTP) faults in
systems with 300A impedance or compensated neutral grounding. And they use a brand-new detection
technique that offers significant advantages over the conventional technique of existing detectors working
on current thresholds. That new technology means that unlike conventional detectors, they can operate
on systems with high capacitive current (combined overhead/underground networks with a high propor-
tion of cable, very long underground networks).
The CABLETROLL 3600 FCI is capable of discriminating between PTP and PTG faults, and indicating the
direction of the latter type.
It can be used on networks from 6 to 36 kV for the following applications:
CABLETROLL 3600 LDAC:
installed on strategic points in the network (switching points, branching points), it assists the
operator by visually signaling the passage of a PTG or PTP fault current.
CABLETROLL 3600 LDAC LV:
when used in combination with remote-controlled switchgear, it assists the operator in remote
control by providing contacts that alert the remote control system to the passage of a PTG or PTP
fault current.
CABLETROLL 3600 LDAU:
installed temporarily on a disturbed network, it identifies what sections are responsible for faults
and gives a time and date system the data required to analyze faults, whether persistent or
transient.
Medium voltage fuses
Medium voltage fuses
MV88
12/04
MV Fault Indicator
Cabletroll 3600
The CABLETROLL 3600 works on the principle of directional fault indication described in EDF
patent 9209549.
The following block diagram shows the CABLETROLL 3600 indicator's main circuits.
In the initial milliseconds after a PTG fault, voltage and current transients are generated on the system.
Using a microprocessor to interpret the phase displacement between residual voltage and residual current,
the circuit can indicate in which direction the PTG fault is located (up-line or down-line of the indicator's
pick-up coils).
For PTP faults the working principle is that of an ammeter (current threshold).
There are 6 standard models:
Description and working principle
Function Power supply Outside Designations References Catalog
connections number number
S 210765
W 210998
T 210766
X 210999
Y 211000
V 210767
CT3600LDAC
CT3600LDAC-CP
CT3600LDACBT
CT3600LDACBT-CP
CT3600LDAU
CT3600LDAUBT
Assistance in
autonomous
operation
Batteries (power for 4
years in operation) None
None
CABLETROLL 3600 LDAC
CABLETROLL 3600 LDAC
counter
Assistance in
autonomous operation
with counter
Requires remote
control unit
COMTROLL 3600
W210768
Batteries
(power for 4 years
in operation)
Assistance in operation
with LV power supply 230 VAC
Outside contacts
provided to transmit
indicator light data
CABLETROLL 3600 LDAC BT
Counter
CABLETROLL 3600 LDAC BT
CABLETROLL 3600 LDAU BT
CABLETROLL 3600 LDAU
Outside contacts
provided to transmit
indicator light data
230 VAC
Assistance in
autonomous operation
with counter
Requires remote
control unit
COMTROLL 3600
W210768
Autonomous
diagnosis
Requires remote
control unit
COMTROLL 3600
W210768
Diagnosis with LV
power supplyRequires
remote
control unit
COMTROLL 3600
W210768
Connection to a time
and date system provided
Batteries
(power for 4 years
in operation)
230 VAC Connection to a time
and date system provided
Medium voltage fuses
Medium voltage fuses
MV89
12/04
MV Fault Indicator
Cabletroll 3600
General
When a CABLETROLL 3600 detects a fault current, it alerts the operator either visually with a signal light
or through contacts (CABLETROLL 3600 AC LV or AU).
As soon as the existence of a fault is confirmed, the signal light on the CABLETROLL 3600 lights up and
stays lit until one of the following events occurs:
Forward voltage returns to the HV line (voltage reset).
The internal 2 hour time delay ends (timer reset).
The indicator is reset by the operator using either the reset button on the front of the main box or the
COMTROLL infrared remote control unit (manual reset).
PTG fault indication
The principle of directional PTG fault indication is to
locate what part of the line is the origin of a PTG
fault. To do this each pick-up coil has a GREEN sig-
nal and a RED signal. The coils must be mounted
in such a way that the GREEN signal is on the BUS-
BAR side and the RED signal is on the NETWORK
side.
If the GREEN signal light is lit up, the fault is on the
GREEN side, i.e. the BUSBAR side.
If the RED signal light is lit up, the fault is on the RED
side, i.e. the NETWORK side.
PTP fault indication
In this case the CABLETROLL 3600 FCI works like a conven-
tional fault indicator and no direction is indicated. All the fault
indicators between the feeding substation and the fault flash
the green signal light and the red signal light alternately
(once every second).
Application of a CABLETROLL 3600 FCI
GREEN
BUSBAR SIDE
RED
NETWORK SIDE
Green signal light Red signal light
PTG fault location
PTG fault location
Medium voltage fuses
Medium voltage fuses
MV90
12/04
MV Fault Indicator
Cabletroll 3600
PTG faults
Any PTG fault characterized by a residual current
over 60A peak + 10A and a residual voltage of 9kV
+ 2kV is detected.
Once those thresholds are exceeded, the fault indi-
cator waits 40 ms to detect a residual voltage Vr
greater than 3.5kV ± 0.5kV before indicating that
there is indeed a fault.
Double PTG faults
A fault considered as a "double PTG fault" consists
of a simultaneous PTG fault on two different phases
in a system powered by the same HV transformer
but grounded at two geographically distant points.
The two faults may be located on the same feeder
or on two different feeders. In this case any fault
characterized by a residual current over 250Arms ±
50A is detected.
PTP faults
Any PTP fault characterized by a current over
450Arms + 80A is detected.
Return of forward voltage
The return of forward HV voltage (resetting the FCI)
is accepted when voltage on the system is at least
10kVrms + 2kV.
The CABLETROLL 3600 FCI consists of six parts:
Voltage measurement:
subassembly consisting of a male WAGO-type ter-
mination ref. 723-604/000-042 (see connection
diagram) connected to a 7 m (or optional 12 m)
cable. This cable is then connected to the termi-
nal block on the main unit of the FCI. The male
connector is connected to a female part (not sup-
plied with the FCI) that leads to the portable ter-
minations for disconnectable connectors (not sup-
plied with the indicator).
Current measurement:
subassembly consisting of three current sensors,
each with a detection element with its own cable
and a collar to fasten the sensor on the HV
cables. The three cables running out from the
sensors are fitted with a current transformer (CT)
connector (see connection diagram) that must be
connected to the current sensor cable
(see hereafter).
Current sensor cable:
7 m (or optional 12 m) cable connected to a con-
nector. One end of this cable must be connected
via CT connectors to the current sensors and the
other to the terminal block of the main FCI unit.
Multi-core cable:
7 m (or optional 12 m) cable to connect the dis-
play unit to the main FCI unit.
Main unit containing:
the electronic board, the power supply, the TEST
and RESET buttons and the terminal blocks for
connection to outside elements.
• Display unit consisting of a weatherproof and impact resistant casing containing the green and red signal
lights. This unit must be installed outside the substation or the cubicle.
Fault indication characteristics
FCI construction
Medium voltage fuses
Medium voltage fuses
MV91
12/04
MV Fault Indicator
Cabletroll 3600
Main unit Display unit
Cable (not supplied) Cable for connection to the
display unit
230 V
power supply
Voltage
measurement
cable
Current
sensors
GREEN
side
Current
sensor cable
WAGO-type
connector
Portable terminations for
disconnectable connectors
Grounding system
CT connector
Medium voltage fuses
Medium voltage fuses
MV93
12/04
Linetroll Z208126 ISET 4A ISC > 3 to 5 m Programmable LED LT111K
111K Adjustable 2 times Xenon Flash Diode
on 7 I load Storage up to
15 or 50 A line 1,5 - 12 H 24 h
Linetroll 111K indicators are designed for outdoor installation.
Normal operating conditions:
• Ambient temperature between – 40°C and + 70°C
• Lithium battery lifespan: 5 to 10 years depending on ambient temperature or every 500 hours
of operations
• Weight: 750 g
Catalog
Number
Catalog
Number
Reference
Number Ground
fault
Short-circuit
fault
Maximum sensitivity
Permanent
fault
Transient
fault
Indication
Recommended dis-
tance between link
and indicator
POLE-MOUNTED FAULT INDICATORS
Main characteristics
Fault sensing in faulty sections of overhead networks
OUTDOOR use for 6 to 66 kV networks
Programmable and fitted to any configuration
Easy-to-install
Increased visibility through Xenon flash indication
MV Fault Indicator
Linetroll 111K
Medium voltage fuses
Medium voltage fuses
MV94
12/04
MV Fault Indicator
Linetroll 111K
Mounting
Linetroll 111K mounts with screws (included) or wrapping bands. This enables installation on either wood
or concrete poles.
Functional description
Linetroll®111Ks fault sensing is based on detection
of the electromagnetic field below the conductors.
The unit is fully self-contained; no external transfor-
mers or connections of any kind is required.
To determine whether or not the line is faulted, the
indicator looks for a specific sequence in the line
conditions before it starts flashing. The general
sequence is as follows.
1. The line should be energized for at least
3 seconds.
2. The line current should increase rapidly above the
value set by the user (the nominal trip level).
3. The line should be de-energized.However, the
user may program the operating criteria to suit
local requirements by manipulating a bank of
microswitches inside the indicator.
Overview
Linetroll®111K indicators are used to locate short-circuit and earth faults in overhead power distribution
networks. Linetroll 111K is a 3-phase unit fully covering the different types of potential fault configurations.
Indicators are placed at strategic locations along the line, such as after branching points and sectionalisers.
The indicator may be pole-mounted, 3-5 meters below the conductors, by means of screws or wrapping-
bands. Live line mounting is done safely, easily and rapidly.
Upon detection of a line fault, the indicator gives off an intermittant Xenon gas flash. This flash can be seen
at up to 200 - 300 metres distance in full daylight and 2 - 3 km at night. The indicator lens allows for uni-
form 360 degree monitoring. Upon fault sensing, all indicators installed between the feeding substation and
the fault will operate. Indicators place behind the fault remain idle.
LINE CURRENT
ENERGIZING
OF LINE APPEARANCE
OF FAULT
INDICATOR
FLASHING INDICATOR
INDICATOR IDLE
Medium voltage fuses
Medium voltage fuses
MV95
12/04
DIRECTIONAL FAULT CURRENT
INDICATOR FOR OVERHEAD LINES
Presentation
LINETROLL®3500 is a pole-mounted intelligent Fault Current Indicator (FCI) for use in electrical power net-
works. It uses brand-new detection technology that provides major benefits over previous FCI technology.
LT3500 aims at tracking down the fault site rather than monitoring the exact fault current level.
FCIs contribute to improving the quality of supply in electrical distribution networks by providing instant
information about fault sites. Based on this information, power rerouting and repair work can commence
quickly. Outage duration and the use of manpower for fault-searching can be reduced by as much as 75%,
a substantial saving potential for any utility.
For Distribution Automation (DA) purposes, or in combination with remote-controlled switchgear, FCIs
used as in-formation sources represent a good alternative to automatic reclosers and sectionalisers.
Reconnection of faulted lines as well as disconnection of healthy lines is avoided. Wear and tear of person-
nel and equipment is reduced.
Strategic application (large numbers) of FCIs represents an important tool in the search for optimum elec-
trical energy supply quality and price. For any utility, the use of FCIs translates to increased earnings and
improved goodwill and credibility among customers.
LINETROLL® 3500 is designed for application on 1- or 3-phase overhead distribution lines at voltages from
6-132 kV. It is able to discriminate between phase-to-phase (PTP) faults and phase-to-ground (PTG) faults
and offers direc-tional capabilities on PTG faults, pointing towards the fault site.
LT 3500 represents a breakthrough in FCI performance and is applicable in networks of any neutral earth-
ing method. The basic version of the unit exhibits 1 out of 2 available factory default characteristics, exclu-
sively tailored for service in the following types of network: solid earthing versus impedance earthing or
isolated networks.
It is designed to flawlessly meet the challenges of networks that undergo extensions and/or modifications,
power re-routing and heavy load variations. All of this without the need for time-consuming network
capacitance and fault current magnitude calculations, saving a lot of expensive time. The trick is that, con-
trary to earlier fault indicator generations, LT3500's performance remains uninfluenced by capacitive dis-
charge currents when applied in isolated or impedance earthed networks.
Unmatched application flexibility and product lifetime is achieved through modular hardware design and
software upgradeability.
Several methods of fault detection can be utilised simultaneously, offering many possibilities for adapting
the function of the unit to some of the protection relay characteristics.
Maintenance requirements are very low thanks to sophisticated power management and a selection of
power supply packs of adequate capacity.
MV Fault Indicator
Linetroll 3500
Medium voltage fuses
Medium voltage fuses
MV96
12/04
MV Fault Indicator
Linetroll 3500
APPLICATION OF LINETROLL®3500
When LT3500 detects a fault current, it will indicate
this by flashing lights or by other means (optional).
The unit is able to discriminate between PTG and
PTP faults on any kind of network with regard to the
earthing method in use.
The fault indicator light will keep flashing until a pre-
determined automatic reset condition is fulfilled.
Such an automatic reset condition can be the return
of voltage to the line (voltage reset), time lapsed
since fault occurred (timer reset) or other.
Manual reset can be carried out on-site by rotating
the display unit to the RESET position, either by
hand or by use of a special TEST/RESET TOOL. The
test/reset tool must be used when the indicator can-
not be reached from the ground.
Performance in coil- (Petersen),
coil+ resistor-, resistor earthed
networks and isolated networks.
PTG faults
All LT3500s mounted in the network supplied from
the same feeder will indicate, flashing a single-color
light, red or green. The color determines the relative
direction to the fault site.
When approaching the front of the indicator, i.e.
when you see the indicator in front of the pole:
a) if the indication color is red; turn back along
the line, the fault site is in the opposite direction
b) if the indication color is green; continue for-
ward along the line, the fault site lies ahead
PTP faults
LT3500s mounted along the fault current path be-
tween the feeder and the fault site will indicate,
flashing alternating red and green lights.
Bi-colored alternating indication means that a PTP
fault has occurred downstream from the indicator.
Figure 0-1.
LT3500 delivers directional performance on PTG
faults. Different feeding directions do not affect
the indication pattern.
Figure 0-2.
How to interpret network diagrams:
Bird's eye view of pole with indicator, indication
alternatives and fault site(s).
Medium voltage fuses
Medium voltage fuses
MV97
12/04
MV Fault Indicator
Linetroll 3500
Figure 0-3.
Single PTG fault results in uncomplicated indica-
tion pattern and fault site tracking. Figure 0-4.
LT3500 performance on PTP faults. Different
feeding directions give different indication patterns.
Performance in solid earthed networks
PTG faults and PTP faults are indicated equally.
The criteria for detection and indication of PTG and PTP faults can be programmed individually, compris-
ing a combination of di/dt and overcurrent techniques.
Only LT3500s mounted along a fault current path between a feeder and the fault site will indicate by flash-
ing lights.
Inversely, a fault site should be located downstream from a flashing FCI. More precisely, the fault site should
be located between the last flashing FCI and the first idle FCI.
Medium voltage fuses
Medium voltage fuses
MV98
12/04
MV Fault Indicator
Linetroll 3500
LT3500 is the result of several years of research, development and testing aimed at setting new standards
for re-liability and functionality of FCIs.
A few hints
The unit continuously monitors the electromagnetic field on site. It looks for particular sequences of field
changes to take place. Upon recognition of such a sequence, the unit samples and stores information in
memory for immediate analysis. Based on analysis, the unit either indicates a faulted line or resumes triv-
ial surveillance. The exact sensitivity to fault current magnitude is not critical for correct operation.
Fault category display
Phase-to-Ground and Phase-to-Phase faults can be indicated individually, as can transient faults versus per-
manent faults. For on-site monitoring, faults are indicated by flashing lamps in the display unit. The flash-
ing pattern defines what kind of fault the unit has detected. The display unit can be rotated horizontally
to allow easy monitoring from any position.
Directionality
A great advantage to LT3500 is its directional capability. In impedance earthed or isolated networks the
unit is able to tell its relative position to a phase-to-ground fault site.
Maintenance
Maintenance of FCIs normally involves replacing the batteries. A range of battery packs is available for
LT3500, allowing some flexibility with respect to service intervals.
IR programming unit
RTU interface and/or
external power supply connector card
Solar power pack
VHF radio + solar power pack
UHF radio + solar power pack
Xenon display unit
Test/reset tool
Battery packs
Operation
MountingOptional extras
Medium voltage fuses
Medium voltage fuses
MV99
12/04
Directional fault current indicator for
overhead lines
Présentation
LINETROLL 3600 directional Fault Current Indicators (FCI) are designed to help the operator locate faults on
overhead lines. They detect both single phase-to-ground (PTG) and phase-to-phase (PTP) faults in systems
with 300A impedance or compensated neutral grounding. And they use a brand-new detection technique
that offers significant advantages over the conventional technique of existing detectors working on current
thresholds. That new technology means that unlike conventional detectors, they can operate on systems
with high capacitive current (combined overhead/underground networks with a high proportion of cable).
The LINETROLL 3600 FCI is capable of discriminating between PTP and PTG faults, and indicating the
direction of the latter type.
It can be used on networks from 6 to 132 kV for the following applications:
LINETROLL 3600 PDAC: installed on strategic points in the network (switching points, branching points),
it assists the operator by visually signaling the passage of a single- or multi-phase fault current.
LINETROLL 3600 PDAT: when used in combination with remote-controlled switchgear, it assists the oper-
ator in remote control by providing contacts that alert the remote control system to the passage of a PTG or
PTP fault current.
LINETROLL 3600 PDAU: installed temporarily on a disturbed network, it identifies what sections are
responsible for faults and gives a time and date system the data required to analyze faults, whether persist-
ent or transient.
MV Fault Indicator
Linetroll 3600
Medium voltage fuses
Medium voltage fuses
MV100
12/04
Description and working principle
The LINETROLL 3600 works on the principle of directional fault indication described in EDF patent 9209549.
The following block diagram shows the LINETROLL 3600 indicator's main circuits.
In the initial milliseconds after a PTG fault, voltage and current transients are generated on the system. Using
a microprocessor to interpret the phase displacement between residual voltage and residual current, the cir-
cuit can indicate in which direction the PTG fault is located (up-line or down-line of the support the pole is
strapped to).
For PTP faults the working principle is that of an ammeter (current threshold).
There are 5 standard models:
MV Fault Indicator
Linetroll 3600
Sensors Main circuit Indicator lights
Red
Green
Red
Green
Power supply
Outside contacts
Function Power supply Outside Designations References Catalog
connections number number
P 210762
V 210997
Q 210763
T 210996
R 210764
LT3600PDAC
LT3600PDAC-CP
LT3600PDAT
LT3600PDAT-CP
LT3600PDAU
Assistance in
operation
Batteries (power for 4
years in operation) None
None
LINETROLL 3600 PDAC
LINETROLL 3600 PDAC
counter
Assistance in operation
with counter
Requires remote
control unit
COMTROLL 360
W210768
Batteries
(power for 4 years
in operation)
Assistance in remote
operation 12 VDC
Outside contacts
provided to transmit
indicator light data
LINETROLL 3600 PDAT
Counter
LINETROLL 3600 PDAT
CABLETROLL 3600 PDAU
Outside contacts
provided to transmit
indicator light data
12 VDC
Assistance in operation
with counter
Requires remote
control unit
COMTROLL 360
W210768
Diagnosis
Requires remote
control unit
COMTROLL 360
W210768
Connection to a time
and date system provided
Batteries
(power for 4 years
in operation)
Medium voltage fuses
Medium voltage fuses
MV101
12/04
Application of a LINETROLL 3600 FCI
General
When a LINETROLL 3600 detects a fault current, it alerts the operator either visually with a signal light or
through contacts (LINETROLL 3600 AT or AU).
As soon as the existence of a fault is confirmed, the signal light on the LINETROLL 3600 lights up and stays
lit until one of the following events occurs:
- Forward voltage returns to the HV line (voltage reset).
- The internal 2 hour time delay ends (timer reset).
- The operator resets the fault indicator using either the "manual" system on the box or the COMTROLL
infrared remote control unit (manual reset). The device can be reset manually by turning the display unit
to the signal light reset position and then turning it back to its original position.
PTG fault indication
The principle of directional PTG fault indication is to locate what part of the line is the origin of a PTG fault.
To do this, the LINETROLL 3600 PTG fault indicator has two signal lights:
- A Red light on the front of the box
- A Green light on the back, on the side where the device is supported.
If the GREEN signal light is lit up, the fault is on
the GREEN side, i.e. the side of the support.
If the RED signal light is lit up, the fault is on the RED
side, i.e. the side opposite the support.
PTP fault indication
In this case the LINETROLL 3600 FCI works like a convention-
al fault indicator and no direction is indicated. All the fault indi-
cators between the feeding substation and the fault flash the
green signal light and the red signal light alternately
(once every second).
MV Fault Indicator
Linetroll 3600
Green signal
light
Red signal
light
PTG fault
location
PTG fault
location
Support Support
Medium voltage fuses
Medium voltage fuses
MV102
12/04
Sensitivities are defined in the reference set-up shown below.
Please inquire for any other set-up desired.
PTG faults
Any PTG fault characterized by a residual current over
60A peak + 10A and a residual voltage of 9kV + 2kV
is detected.Once those thresholds are exceeded, the
fault indicator waits 40 ms to detect a residual voltage
Vr greater than 3.5kV + 0.5kV before indicating that
there is indeed a fault.
PTP faults
Any PTP fault characterized by a current over 450Arms
+ 80A is detected.
Double PTG faults
A fault considered as a "double PTG fault" consists of
a simultaneous PTG fault on two different phases in a
system powered by the same HV transformer but
grounded at two geographically distant points. The
two faults may be located on the same feeder or on
two different feeders. In this case any fault character-
ized by a residual current over 250Arms + 50A is
detected.
Return of forward voltage
The return of forward HV voltage (resetting the FCI) is
accepted when voltage on the system is at least
10kVrms + 2kV.
The LINETROLL 3600 FCI consists of four parts:
A support to be strapped on the pole with a metal strip. That
support may have openings for wiring to connect the device
to other equipment and a connection to a time and date
system.
A main box containing the sensors, the electronic boards and
the batteries.
A display unit on the bottom of the box. That display unit may
be rotated 90° to improve visibility if required. It is also used
to reset and test the fault indicator.
A top cap screwed onto the main box. That cap may be
equipped with an optional solar panel to power the FCI.
Fault indication characteristics
FCI construction
MV Fault Indicator
Linetroll 3600
Support
See-through
top cap
Main
box
Display unit
in its case
Green
side