571-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
HFE2500 Series
Features
u 1U rackmount containing up to 4 units
u Internal ORing MOSFET & Current Share
u High Effi ciency
u Up to 9,500W in 1U rack
2500W 1U Front End Power Supplies
Key Market Segments & Applications
(1) See installation manual for detailed specifi cations & test methods
(2) Derate linearly 1.3%/V from 100VAC to 85VAC input
Model
Input Voltage Range (2) VAC 85 - 265VAC, 47 - 63Hz. See model selector for power derating
Input Current (Max) 100/230VAC A 15 / 12A
Inrush Current A <50A
Power Factor Correction - Meets EN61000-3-2, PF > 0.98 at full load
Temperature Coeffi cient %/°C <0.02%/°C
Overcurrent Protection % 105 - 115%
Overvoltage Protection (1) % 110% (Tracking). Cycle AC to reset or utilize Remote On/Off
Overtemperature Protection (1) - Shutdown with automatic reset. Warning signal provided
Hold-up time ms >10ms, 115/230VAC Input, 80% loading
Leakage Current mA < 0.75 / 1.5mA, 100 / 230VAC, 60Hz
Remote Sense Compensation - HFE2500-12: 0.25V / Wire, HFE2500-24: 0.5V / Wire, HFE2500-48: 1V / Wire
Indicators - AC OK: Green LED, DC OK / Fail: Green / Red LED
Remote On/Off - Unit ON: 0 - 0.6V or short, OFF: 2 - 15V or open circuit
Parallel Operation (1) - Yes, single wire current share, 95% accuracy, up to 8 units
AC Fail Signal - Open Collector, ON when AC is within 85 - 270VAC
DC Good Signal - Open Collector, ON when output is above 85 to 95% of setpoint (tracking)
Remote Adjust (1) - By either external 0 - 5V signal or 1k potentiometer
I2C Interface (1) - Isolated from output, Add suffi x /S, PMBus compatible
Auxiliary Output - 11.2 - 12.5V, 0.5A, 240mV ripple and noise
Operating Temperature °C -10 to +70°C, derate 2%/°C from 50 to 60°C, 2.5%/°C from 60 to 70°C
Storage Temperature °C -30 to +85°C
Humidity (Non condensing) %RH Operating: 10 - 90%RH, Storage: 10 - 95%RH
Cooling - Two variable speed internal fans, airfl ow exits across input/output connector
Withstand Voltage - I/P to O/P 3kVAC, I/P to GND 2kVAC, O/P to GND: HFE2500-12, -24V 500VAC, HFE2500-48 1.5kVAC
Isolation Resistance >100MΩ at 25°C & 70%RH, Output to Ground 500VDC
Vibration (Basic transportation) - Meets IEC60068-2-64
Shock (Basic transportation) - Meets IEC60068-2-27
Safety Agency Certi cations - UL60950-1 (Listed), EN60950-1, CE Mark
Conducted and Radiated EMI - EN55022 & FCC part 15; Conducted class B, Radiated class A
Immunity - IEC61000-4-2 (lv 2,3), -3 (lv 2), -4 (lv 2), -5 (lv 3,4), -6 (lv 2), -8 (lv 4), -11
Size (W x H x D) in Power Supply: 4.21 x 1.61 x 12.8”, Rack: 17.5 x 1.72 x 15.8”
Weight g Power Supply: 2100g, Rack: 5000g
Warranty yrs Three Years
Specifi cations
(HFE2500-48 model)
581-800-526-2324 • www.us.tdk-lambda.com/lp/ Revision A5: May 2012
HFE2500 Series
Output Adjust Max Current Max Power Max Current Max Power
Model Voltage Range(1) (Vin>170VAC) (Vin>170VAC) (100<Vin<170VAC)(2) (100<Vin<170VAC)(2)
HFE2500-12 12V 9.6 - 13.2V 200A 2400W 125A 1500W
HFE2500-12/S 12V 9.6 - 13.2V 200A 2400W 125A 1500W
HFE2500-24 24V 19.2 - 29V 104A 2496W 62A 1488W
HFE2500-24/S 24V 19.2 - 29V 104A 2496W 62A 1488W
HFE2500-48 48V 38.4 - 58V 52A 2496W 31A 1488W
HFE2500-48/S 48V 38.4 - 58V 52A 2496W 31A 1488W
Load Line Ripple & Effi ciency
Model Reg Reg Noise(1) (%)(3) I2C
HFE2500-12 60mV 30mV 240mV 90 / 92% -
HFE2500-12/S 60mV 30mV 240mV 90 / 92% Yes
HFE2500-24 120mV 60mV 240mV 90 / 92% -
HFE2500-24/S 120mV 60mV 240mV 90 / 92% Yes
HFE2500-48 240mV 120mV 480mV 91 / 93% -
HFE2500-48/S 240mV 120mV 480mV 91 / 93% Yes
Model Selector
Model Description Maximum Rack Current
HFE2500-S1U Four slot 19” rack, IEC320-C20 input connector 320A each side (640A total)
HFE2500-S1U-TB Four slot 19” rack, Terminal Block input connector 320A each side (640A total)
HFE2500/BP One slot blanking panel, two provided with each rack -
Accessories
For Additional Information, please visit
us.tdk-lambda.com/lp/products/hfe-series.htm
Outline HFE2500S1U
(3) At 75% load, 100 / 230VAC input
426.5 ±1.0
1.2
409.0 1.0
10.0
2.0
445.0 ±1.0
11.0
A A A A
HOLES FOR BLANK
PANEL MOUNTING.
USE FLAT HEAD SCREW
M3x6 8 PLACES
MARKED "A"
SEE NOTE 2.
MODEL KEY
FOR DIFFERENT
OUTPUT VOLTAGE
MODELS.
333.0 TYP x2
15.0 TYP x2
13.0 TYPx2
13.0 TYP x2
M5 HOLES FOR
MOUNTING BRACKETS.
4 PLACES
SEE NOTE 3.
483.0 ±1.0
24.5
43.6
+
0.4
0.0
6.0
31.7
466.2 ±1.0
SEE NOTE 1.
14.0 TYPx2
16.0 TYPx2
17.0 TYPx2
22.0 TYP x2
125.8
82.5 61.0
214.5
10.7
88.5 273.6
14.0
24.6 TYP
MODULE "A"
MODULE "C"
MODULE "D"
OUTPUT
BUS BAR "-V"
OUTPUT
BUS BAR "+V"
OUTPUT
BUS BAR "-V"
OUTPUT
BUS BAR "+V"
PMBUS ADRESS
SEE NOTE 4.
MODULE "B"
AIR FLOW
DIRECTION
SEE NOTE 5.
MODULE "A"
MODULE "B"
MODULE "C"
MODULE "D"
CONNECTOR DESCRIPTION: IPLT1-120-01-L-D-RA(SAMTEC)
SIGNALS & CONTROL CONNECTOR PINS ASSIGNMENT
MATING CONNECTOR: IPD1-20-D (SAMTEC)
1
40 2
39
4. REFER TO INSTRUCTION MANUAL FOR SETTING DETAILS.
5. MODEL NAME, VOLTAGE AND CURRENT RATING AND
SAFETY APPROVALS SYMBOLS WILL BE SHOWN HERE
ACCORDING TO THE SPECIFICATION.
6. THE HFE-S1U RACK IS SHOWN WITH 4 HFE2500
UNITS INSTALLED.
NOTES
1. MOUNTING HOLES FOR RACK 19". USE M6x12 SCREWS TO FIX THE
UNIT TO A RACK.
2. USE NUT,FLAT WASHER AND SPRING WASHER FOR LOAD WIRES
FIXING. USE LUG STUD M6 FOR LOAD WIRES.RECOMMENDED
TORQUE: 42-56 Kgf.cm
3. TO FIX THE MOUNTING BRACKET TO THE CHASSIS USE M5x10 SEMS
SCREWS .RECOMMENDED TIGHTENING TORQUE 27~31Kgf.cm.
SCREWS MUST NOT PENETRATE THE CHASSIS MORE THAN 6.0 mm.