SIMATIC
Process Control System PCS 7
SIMATIC Management Console -
Software update
Installation Manual
Only valid for software update of the SIMATIC
Management Console from V8.0 SP1 to V8.0 SP1
Update 1
06/2013
A5E32467461-AA
Software update
1
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in
this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
A5E32467461-AA
Ⓟ 06/2013 Technical data subject to change
Copyright © Siemens AG 2013.
All rights reserved
Table of contents
1 Software update............................................................................................................................................5
SIMATIC Management Console - Software update
Installation Manual, 06/2013, A5E32467461-AA 3
Software update 1
Note
The following computers are changed by the steps to be executed:
• Computers with installed SIMATIC Management Console
• Computers in the plant with installed SIMATIC Management Agent
Requirements
Installed software on the computer with installed SIMATIC Management Console
SIMATIC Management Console V8.0 SP1
Required software packages
SIMATIC Management Console V8.0 SP1 Update1
SIMATIC Management Agent V8.0 SP1 Update1
Basic procedure
The SIMATIC Management Console is updated in four steps:
1. Store the installation files
2. Back up the configuration and setting data of the SIMATIC Management Console
3. Update the computer with installed SIMATIC Management Console
4. Restore the configuration and setting data of the SIMATIC Management Console
5. Update the computers in the plant with installed SIMATIC Management Agent
SIMATIC Management Console - Software update
Installation Manual, 06/2013, A5E32467461-AA 5
Storing the installation files
1. Download the required software packages from the Internet (http://
support.automation.siemens.com/WW/view/en/74786126):
Note
The software packages to be installed must be available on a shared path.
Make sure that the selected path names do not exceed 85 characters when you set
the paths for the software.
Select a path with a unique name for each software package:
Example:
\\<Computer>\<Path>\<SMMC_Version_and_Date> (example path for the
SIMATIC Management Console Vxx software package)
\\<Computer>\<Path>\<SMA_Version_and_Date> (example path for the SIMATIC
Management Agent Vxx software package)
Make sure that you only unzip the Web Package. Enable the option "Extract the product
without being installed".
Backing up the configuration and setting data
1. Start the SIMATIC Management Console application.
2. Select the menu command File > Data > Back up data....
Follow the instructions in the dialogs. The following data is backed up:
Configuration and setting data
Inventory data
3. Select the menu command Edit > Disable console assignment.
4. End the SIMATIC Management Console.
Updating the computer with installed SIMATIC Management Console
1. Open the path in which you have stored the SIMATIC Management Console software
package.
Information on this step is available in paragraph "Basic procedure", step 1: in the example
"...\SMMC_Version_and_Date".
2. Start the setup.exe file.
Follow the instructions in the dialogs.
3. Perform a restart of the computer once the installation is complete.
The installation of the new version of the SIMATIC Management Console is complete.
Software update
SIMATIC Management Console - Software update
6Installation Manual, 06/2013, A5E32467461-AA
Restoring the configuration and setting data
You need to restore the configuration and setting data of the SIMATIC Management Console.
Follow the steps outlined below:
1. Start the SIMATIC Management Console application.
2. Select the menu command File > Data > Restore data... .
3. Select the path of the backed up configuration and setting data.
4. Perform a restart of the computer once the restoration is complete.
The restoration of the configuration and setting data is complete.
Updating the computers in the plant with installed SIMATIC Management Agent
You need to update the computers in the plant with installed SIMATIC Management Agent.
Follow the steps outlined below:
1. Start the SIMATIC Management Console application.
2. Select the Options > Settings menu command.
3. Open the "SIMATIC Management Agent Setup" tab.
4. Select the "setup.exe" file in the path in which you have stored the SIMATIC Management
Agent software package.
Information on this step is available in paragraph "Basic procedure", step 1: in the example
"...\SMA_Version_and_Date".
5. Select the "Network" node in the network view of the SIMATIC Management Console.
6. Select the menu command Update SMAgent... from the shortcut menu.
7. Select the computers to be installed.
Follow the instructions in the dialogs.
The computers in the plant with installed SIMATIC Management Agent are updated to the new
version with this process.
Result
The update of the SIMATIC Management Console as well as the computers in the plant with
installed SIMATIC Management Agent is complete.
Software update
SIMATIC Management Console - Software update
Installation Manual, 06/2013, A5E32467461-AA 7