©June 2011 Littelfusewww.littelfuse.com
POWR-GARD® Fuse Datasheet
UL Class L
2
SHORT CIRCUIT
CURRENT*
APPARENT RMS SYMMETRICAL CURRENT FOR VARIOUS FUSE RATINGS
800 A 1200 A 1600 A 2000 A 3000 A 4000 A 5000 A 6000 A
5,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000
10,000 8,800 10,000 10,000 10,000 10,000 10,000 10,000 10,000
15,000 10,500 13,500 15,000 15,000 15,000 15,000 15,000 15,000
20,000 12,000 15,000 19,000 20,000 20,000 20,000 20,000 20,000
25,000 13,000 16,000 21,000 24,000 25,000 25,000 25,000 25,000
30,000 14,000 18,000 23,000 26,000 30,000 30,000 30,000 30,000
35,000 15,000 19,000 24,000 27,000 32,000 35,000 35,000 35,000
40,000 16,000 20,000 25,000 28,000 34,000 40,000 40,000 40,000
50,000 17,000 22,000 27,000 31,000 37,000 42,500 50,000 50,000
60,000 18,000 24,000 29,000 34,000 40,000 46,000 52,000 60,000
80,000 20,000 26,000 32,000 37,000 44,000 51,000 57,000 70,000
100,000 21,000 27,000 34,000 40,000 46,000 57,000 65,000 75,000
150,000 23,000 31,000 38,000 44,000 54,000 67,000 75,000 87,000
200,000 24,000 34,000 42,000 46,000 57,000 70,000 80,000 95,000
Current-Limiting Effects of KLPC (600 V) Fuses
CLASS L CURRENT-LIMITING EFFECTS
*Prospective RMS Sym met ri cal Amperes Short-Circuit Current
Note: Data derived from Peak Let-Thru Curves