www.murata-ps.com/support
RBQ-12/33-D48
Quarter-Brick 400-Watt Isolated DC-DC Converters
MDC_RBQ-12/33-D48.A01Δ Page 12 of 15
Thermal Shutdown
To prevent many over temperature problems and damage, these converters
include thermal shutdown circuitry. If environmental conditions cause the
temperature of the DC-DCs to rise above the Operating Temperature Range
up to the shutdown temperature, an on-board electronic temperature sensor
will power down the unit. When the temperature decreases below the turn-on
threshold, the converter will automatically restart. There is a small amount of
hysteresis to prevent rapid on/off cycling.
CAUTION: If you operate too close to the thermal limits, the converter may
shut down suddenly without warning. Be sure to thoroughly test your applica-
tion to avoid unplanned thermal shutdown.
Temperature Derating Curves
The graphs in this data sheet illustrate typical operation under a variety of
conditions. The Derating curves show the maximum continuous ambient air
temperature and decreasing maximum output current which is acceptable
under increasing forced airfl ow measured in Linear Feet per Minute (“LFM”).
Note that these are AVERAGE measurements. The converter will accept brief
increases in current or reduced airfl ow as long as the average is not exceeded.
Note that the temperatures are of the ambient airfl ow, not the converter
itself which is obviously running at higher temperature than the outside air.
Also note that “natural convection” is defi ned as very fl ow rates which are not
using fan-forced airfl ow. Depending on the application, “natural convection” is
usually about 30-65 LFM but is not equal to still air (0 LFM).
Murata Power Solutions makes Characterization measurements in a closed
cycle wind tunnel with calibrated airfl ow. We use both thermocouples and an
infrared camera system to observe thermal performance. As a practical matter,
it is quite diffi cult to insert an anemometer to precisely measure airfl ow in
most applications. Sometimes it is possible to estimate the effective airfl ow if
you thoroughly understand the enclosure geometry, entry/exit orifi ce areas and
the fan fl owrate specifi cations.
CAUTION: If you exceed these Derating guidelines, the converter may have
an unplanned Over Temperature shut down. Also, these graphs are all collected
near Sea Level altitude. Be sure to reduce the derating for higher altitude.
Output Fusing
The converter is extensively protected against current, voltage and tempera-
ture extremes. However your output application circuit may need additional
protection. In the extremely unlikely event of output circuit failure, excessive
voltage could be applied to your circuit. Consider using an appropriate fuse in
series with the output.
Output Current Limiting
Current limiting inception is defi ned as the point at which full power falls below
the rated tolerance. See the Performance/Functional Specifi cations. Note par-
ticularly that the output current may briefl y rise above its rated value in normal
operation as long as the average output power is not exceeded. This enhances
reliability and continued operation of your application. If the output current is
too high, the converter will enter the short circuit condition.
Output Short Circuit Condition
When a converter is in current-limit mode, the output voltage will drop as the
output current demand increases. If the output voltage drops too low (approxi-
mately 97% of nominal output voltage for most models), the PWM controller
will shut down. Following a time-out period, the PWM will restart, causing
the output voltage to begin rising to its appropriate value. If the short-circuit
condition persists, another shutdown cycle will initiate. This rapid on/off cycling
is called “hiccup mode.” The hiccup cycling reduces the average output cur-
rent, thereby preventing excessive internal temperatures and/or component
damage. A short circuit can be tolerated indefi nitely.
The “hiccup” system differs from older latching short circuit systems
because you do not have to power down the converter to make it restart. The
system will automatically restore operation as soon as the short circuit condi-
tion is removed.
Remote On/Off Control
On the input side, a remote On/Off Control can be specifi ed with either logic
type. Please refer to the Connection Diagram on page 1 for On/Off connections.
Positive-logic models are enabled when the On/Off pin is left open or is
pulled high to +15V with respect to –VIN. Positive-logic devices are disabled
when the On/Off is grounded or brought to within a low voltage (see Specifi ca-
tions) with respect to –VIN.
Negative-logic models are on (enabled) when the On/Off is grounded or
brought to within a low voltage (see Specifi cations) with respect to –VIN. The
device is off (disabled) when the On/Off is left open or is pulled high to +15VDC
Max. with respect to –VIN.
Dynamic control of the On/Off function should be able to sink specifi ed
signal current when brought low and withstand specifi ed voltage when brought
high. Be aware too that there is a fi nite time in milliseconds (see Specifi cations)
between the time of On/Off Control activation and stable output. This time will
vary slightly with output load type and current and input conditions.
Output Capacitive Load
These converters do not require external capacitance added to achieve
rated specifi cations. Users should only consider adding capacitance to reduce
switching noise and/or to handle spike current load steps. Install only enough
capacitance to achieve noise objectives. Excess external capacitance may
cause degraded transient response and possible oscillation or instability.
C1 = 1µF
C2 = 10µF
C3 = 470µF
R
LOAD
C2 C3
C1 SCOPE
+VOUT
-VOUT
Figure 6. Measuring Output Ripple and Noise (PARD)