Low Voltage
Switchgear
Air Circuit
Breakers
SUPER AE
AE 1000
AE 6300
Technical Catalogue
MITSUBISHI ELECTRIC
E
J
J
F
G
H
452
220*
40
23 48
25
61
35
51
132
370
430
340
15
175*
88
144
290
340
5
40
80 288
G
72 350
410
132
C*
AB
D*
E
38 F
4 x Ø 14
268
228
C*
AB
D*
E
38 F
4 x Ø 14
268
228
K
31
Return
SUPER AE
SUPER AE
The air circuit breaker program from MITSUBISHI ELECTRIC:
Complete breaker program
Frame size from 1000 A to 6300 A
Wide performance range
Standard version “SS from 65 to 130 kA
High performance version “SH” with 130 kA
Two construction versions
Fixed and drawout
Compact design
Space savings
High interrupting capacity
Growing power demands
Optimum overload tripping system
Safer and more selectivity
Communications support
For tomorrows energy management
Air Circuit Breakers SUPER AE
About this product catalogue
Texts, figures and diagrams shown in this product catalogue are intended exclusively for explanation and assistance in planning and ordering the
electronic air circuit breakers of the SUPER AE series and the associated accessories. Only the manuals supplied with the breakers are relevant for
installation, commissioning and handling of the air circuit breakers and the accessories. The information given in this documentation must be read
before installation and commissioning of the modules.
Should questions arise with regard to the planning of modules described in this product catalogue, do not hesitate to contact MITSUBISHI ELECTRIC
EUROPE in Ratingen (Germany) or one of its distributors (see cover page).
No parts of this product catalogue may be duplicated, stored in an information system or transmitted without prior express written permission from
MITSUBISHI ELECTRIC EUROPE.
©MITSUBISHIELECTRICEUROPE12/1996
DIN ISO 9001 /
EN 29001
Zertifikat: 09 100 4371
2
Contents
BASE UNITS
Programoverview–mainunitfeatures.......................................................4
Orderinginformation.....................................................................6
ACCESSORIES
Overviewofthemainaccessories..........................................................8
Standardequipment.....................................................................9
Internaloptionalaccessoriesforallbreakers.................................................10
Optionalaccessoriesfordrawoutbreakers..................................................14
Externaloptionalaccessoriesforallbreakers ................................................16
ELECTRONIC TRIP RELAY
Programoverview–triprelayfeatures......................................................20
Specialfunctions–accessories...........................................................26
Orderinginformation....................................................................28
Operatingcharacteristics................................................................29
SPECIFICATIONS
Wiringdiagram........................................................................34
Dimensions–breaker...................................................................36
Dimensions–accessories...............................................................41
Environmentalconditions................................................................42
Specificationsformarinalapprovals........................................................45
Ordersheet...........................................................................46
Index ..................................................................................47
MITSUBISHI ELECTRIC
3
SUPER AE Series Standard series “SS”
Breaker type AE 1000 - SS AE 1250 - SS AE 1600 - SS AE 2000 - SS AE 2500 - SS AE 3200 - SS
Rated current (A) at 40 °C a INmax 1000 1250 1600 2000 2500 3200
Rated insulation voltage (V) 50/60 Hz Ui 1000 1000 1000 1000 1000 1000
Rated operating voltage (V) 50/60 Hz Ue 690 690 690 690 690 690
Number of poles 343434343434
Adjustment range
Rated current (A) Ir
General protection
(current rating adjustable)
500–600–700–
800–900–1000
625–750–875
1000–1125–1250 800–960–1120–
1280–1440–1600
1000–1200–1400–
1600–1800–2000
1250–1500–1750–
2000–2250–2500 1600–1920–2240–
2560–2880–3200
315–378–441–
504–567–630 800–960–1120–
1280–1440–1600
157–189–220–
252–284–315 625–750–875
1000–1125–1250
Generator protection
(current rating fixed) 500In1000
315In630 625In1250 800In1600 1000In2000
625In1000 1250In2500 1600In3200
Rated current for neutral pole N (A) 1000 1250 1600 2000 2500 3200
Rated service
short-circuit
breaking capacity
Ics
(kA, eff, sym.)
Breaking duty:
O-t-CO-t-CO
ICU =ICS
IEC
947-2,
EN
60947-2,
VDE
0660,
BS4752
With
instantaneous
trip
AC690V 50 50 50 50 50 50
AC600V 50 50 50 65 65 65
AC500V 65 65 65 85 85 85
Without instan-
taneous trip
(with MCR)
AC690V 42 42 42 50 50 50
AC600V 50 50 50 65 65 65
AC500V 65 65 65 65 65 65
Without inst. tripAC690V 25 25 25 45 45 45
Rated
short-circuit
making capacity
Icm
(kA, peak value)
With
instantaneous
trip
AC690V 105 105 105 105 105 105
AC600V 105 105 105 143 143 143
AC500V 143 143 143 187 187 187
Without instan-
taneous trip
(with MCR)
AC690V 88.2 88.2 88.2 105 105 105
AC600V 105 105 105 143 143 143
AC500V 143 143 143 143 143 143
Without inst. tripAC690V 52.5 52.5 52.5 94.5 94.5 94.5
Rated short time current (kA eff.) I cw
1 sec 65 65 65 65 65 65
2 sec 40 40 60 65 65 65
3 sec 30 30 50 65 65 65
Maximum total breaking time (sec) 0.04 0.04 0.04 0.04 0.04 0.04
Closing time (sec) 0.08 0.08 0.08 0.08 0.08 0.08
Number of operating cycles
(ON/OFF)
With rated current 3000 3000 2000 1500 1500 1000
Without rated current 10000 10000 10000 10000 10000 10000
Fixed
type
a 340 425 340 425 340 425 475 605 475 605 475 605
b 410 410 410 410 410 410 410 410 410 410 410 410
c 290 290 290 290 290 290 290 290 290 290 290 290
d404040404040404040404040
Drawout
type
a 300 385 300 385 300 385 435 565 435 565 435 565
b 430 430 430 430 430 430 430 430 430 430 430 430
c 368 368 368 368 368 368 368 368 368 368 368 368
d616161616161616161616161
Weight
(kg)
Fixed type Manual charging 41 51 41 51 42 52 60 72 61 73 63 75
Motor charging 44 54 44 54 45 55 63 75 64 76 66 78
Drawout type
(with cradle)
Manual charging 64 78 64 78 65 79 92 113 93 114 95 116
Motor charging 67 81 67 81 68 82 95 116 96 117 98 119
Cradleonly 263026302630354335433644
Charging type
Dimensions (mm)
SUPER AE
SUPER AE
Program Overview Specifications
BASE UNITS
For further temperatures refer to technical information on page 44.
The figures for “without instantaneous tripping” are the values when the bare main body and the external relay are combined.
The number of operating cycles with rated current also include the number of operating cycles without rated current.
All specifications without peripheral accessories (e.g. UVT control unit).
Further current ratings on request.
More details on request.
Overview on all breakers in the SUPER AE range
4
Declaration of conformity:
Standards IEC947-2, EN60947-2, VDE0660, BS4752
Certificates ASTA, LOVAG, SEV (types on request)
Marine approvals LRS, GL, BV, ABS
(other approvals on request)
Standard series “SS” High performance series “SH”
AE 4000 - SS AE 5000 - SS AE 6300 - SS AE 1000 - SH AE 1250 - SH AE 1600 - SH AE 2000 - SH AE 2500 - SH AE 3200 - SH
4000 5000 6300 1000 1250 1600 2000 2500 3200
1000 1000 1000 1000 1000 1000 1000 1000 1000
690 690 690 690 690 690 690 690 690
343434343434343434
2000–2400–2800–
3200–3600–4000 2500–3000–3500–
4000–4500–5000 3150–3780–4410–
5040–5670–6300
500–600–700
800–900–1000
625–750–875
1000–1125–1250 800–960–1120–
1280–1440–1600 1000–1200–1400–
1600–1800–2000 1250–1500–1750–
2000–2250–2500 1600–1920–2240–
2560–2880–3200
315–378–441
504–567–630
2000In4000 2500In5000 3150In6300 500In1000
315In630 625In1250 800In1600 1000In2000 1250In2500 1600In3200
3200 3200 3200 1000 1250 1600 2000 2500 3200
50 50 50 65 65 65 65 65 65
85 85 85 85 85 85 85 85 85
130 130 130 130 130 130 130 130 130
—————————
—————————
—————————
65 65 65
105 105 105 143 143 143 143 143 143
187 187 187 187 187 187 187 187 187
286 286 286 286 286 286 286 286 286
—————————
—————————
—————————
143 143 143
85 85 85
85 85 85
70 70 70
0.05 0.05 0.05 0.04 0.04 0.04 0.04 0.04 0.04
0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08
500 500 500 3000 3000 2000 1500 1500 1000
2000 2000 2000 10000 10000 10000 10000 10000 10000
——————475605475605475605475605475605475605
——————410410410410410410410410410410410410
——————290290290290290290290290290290290290
——————707070707070707070707070
875 1005 875 1005 875 1005 485 615 485 615 485 615 485 615 485 615 485 615
480 480 480 480 480 480 430 430 430 430 430 430 430 430 430 430 430 430
368 368 368 368 368 368 398 398 398 398 398 398 398 398 398 398 398 398
123 123 123 123 123 123 61 61 61 61 61 61 61 61 61 61 61 61
——————667966796679667966796881
——————698269826982698269827184
240 263 240 263 240 263 105 127 105 127 105 127 105 127 105 127 107 129
244 267 244 267 244 267 108 130 108 130 108 130 108 130 108 130 110 132
125 140 125 140 125 140 42 50 42 50 42 50 42 50 42 50 43 51
MITSUBISHI ELECTRIC
5
SUPER AE
SUPER AE
Program Overview Ordering Information
BASE UNITS
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shipping contents:
Base unit
Charging handle (for manual operation)
Electronic trip relay ST-1
4 auxiliary contacts (2 NO, 2 NC contacts)
Further elements that must be ordered:
Different trip relay if you do not want ST-1
Accessories as required
AE 1000 - SS AE1000-SS 3P FIX 25885 AE1000-SS 4P FIX 25886
AE 1250 - SS AE1250-SS 3P FIX 25887 AE1250-SS 4P FIX 25888
AE 1600 - SS AE1600-SS 3P FIX 25889 AE1600-SS 4P FIX 25890
AE 2000 - SS AE2000-SS 3P FIX 25891 AE2000-SS 4P FIX 25892
AE 2500 - SS AE2500-SS 3P FIX 25893 AE2500-SS 4P FIX 25894
AE 3200 - SS AE3200-SS 3P FIX 25895 AE3200-SS 4P FIX 25896
Standard series AE-SS Fixed type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shipping contents:
Base unit
Drawout mechanism
Cradle
Charging handle (for manual operation)
Electronic trip relay ST-1 (for AE1000–AE4000)
or ST-1A (for AE5000–AE6300)
4 auxiliary contacts (2 NO, 2 NC contacts)
AE 4000–6300 with safety shutter (SST)
Further elements that must be ordered:
Different trip relay if you do not want ST-1/ST-1A
Accessories as required
AE 1000 - SS AE1000-SS 3P D/O 25824 AE1000-SS 4P D/O 43740
AE 1250 - SS AE1250-SS 3P D/O 43743 AE1250-SS 4P D/O 43739
AE 1600 - SS AE1600-SS 3P D/O 25825 AE1600-SS 4P D/O 25826
AE 2000 - SS AE2000-SS 3P D/O 43742 AE2000-SS 4P D/O 43738
AE 2500 - SS AE2500-SS 3P D/O 43741 AE2500-SS 4P D/O 35258
AE 3200 - SS AE3200-SS 3P D/O 25827 AE3200-SS 4P D/O 25828
AE 4000 - SS AE4000-SS 3P D/O 56977 AE4000-SS 4P D/O 56978
AE 5000 - SS AE5000-SS 3P D/O 56976 AE5000-SS 4P D/O 56975
AE 6300 - SS AE6300-SS 3P D/O 56974 AE6300-SS 4P D/O 56973
Standard series AE-SS Drawout type
High performance series AE-SH Fixed type
High performance series AE-SH Drawout type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shipping contents:
Base unit
Charging handle (for manual operation)
Electronic trip relay ST-1
4 auxiliary contacts (2 NO, 2 NC contacts)
Further elements that must be ordered::
Different trip relay if you do not want ST-1
Accessories as required
AE 1000 - SH AE1000-SH 3P FIX 43713 AE1000-SH 4P FIX 43707
AE 1250 - SH AE1250-SH 3P FIX 43712 AE1250-SH 4P FIX 43706
AE 1600 - SH AE1600-SH 3P FIX 43711 AE1600-SH 4P FIX 43705
AE 2000 - SH AE2000-SH 3P FIX 43710 AE2000-SH 4P FIX 43704
AE 2500 - SH AE2500-SH 3P FIX 43709 AE2500-SH 4P FIX 43703
AE 3200 - SH AE3200-SH 3P FIX 43708 AE3200-SH 4P FIX 43702
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shipping contents:
Base unit
Drawout mechanism
Cradle
Charging handle (for manual operation)
Electronic trip relay ST-1
4 auxiliary contacts (2 NO, 2 NC contacts)
Further elements that must be ordered:
Different trip relay if you do not want ST-1
Accessories as required
AE 1000 - SH AE1000-SH 3P D/O 43701 AE1000-SH 4P D/O 43695
AE 1250 - SH AE1250-SH 3P D/O 43700 AE1250-SH 4P D/O 43694
AE 1600 - SH AE1600-SH 3P D/O 43699 AE1600-SH 4P D/O 43693
AE 2000 - SH AE2000-SH 3P D/O 43698 AE2000-SH 4P D/O 43692
AE 2500 - SH AE2500-SH 3P D/O 43697 AE2500-SH 4P D/O 43691
AE 3200 - SH AE3200-SH 3P D/O 43696 AE3200-SH 4P D/O 43690
For specification and order information about electronic trip relays refer to page 20 ff. For breaker accessories refer to page 8 ff.
Further breaker types with other rated current on request.
6
Switch-disconnector* AE-DSN Fixed type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shipping contents:
Base unit
Charging handle (for manual operation)
4 Auxiliary contacts (2 NO, 2 NC contacts)
Further elements that must be ordered:
Electronic trip relay type B if you do not want
without trip relay
Accessories as required
AE 1000 - DSN AE1000-SS 3P DSN FIX 43737 AE1000-SS 4P DSN FIX 43731
AE 1250 - DSN AE1250-SS 3P DSN FIX 43736 AE1250-SS 4P DSN FIX 43730
AE 1600 - DSN AE1600-SS 3P DSN FIX 43735 AE1600-SS 4P DSN FIX 43729
AE 2000 - DSN AE2000-SS 3P DSN FIX 43734 AE2000-SS 4P DSN FIX 43728
AE 2500 - DSN AE2500-SS 3P DSN FIX 43733 AE2500-SS 4P DSN FIX 43727
AE 3200 - DSN AE3200-SS 3P DSN FIX 43732 AE3200-SS 4P DSN FIX 38177
* Air circuit breaker without overcurrent short-circuit release
Switch-disconnector* AE-DSN Drawout type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shipping contents:
Base unit
Drawout mechanism
Cradle
Charging handle (for manual operation)
4 auxiliary contacts (2 NO, 2 NC contacts)
AE 4000–6300 with safety shutter (SST)
Further elements that must be ordered:
Electronic trip relay type B if you do not want
without trip relay
Accessories as required
AE 1000 - DSN AE1000-SS 3P DSN D/O 43725 AE1000-SS DSN 4P D/O 43719
AE 1250 - DSN AE1250-SS 3P DSN D/O 43724 AE1250-SS DSN 4P D/O 43718
AE 1600 - DSN AE1600-SS 3P DSN D/O 43723 AE1600-SS DSN 4P D/O 43717
AE 2000 - DSN AE2000-SS 3P DSN D/O 43722 AE2000-SS DSN 4P D/O 43716
AE 2500 - DSN AE2500-SS 3P DSN D/O 43721 AE2500-SS DSN 4P D/O 43715
AE 3200 - DSN AE3200-SS 3P DSN D/O 43720 AE3200-SS DSN 4P D/O 43714
AE 4000 - DSN AE4000-SS 3P DSN D/O on request AE4000-SS DSN 4P D/O on request
AE 5000 - DSN AE5000-SS 3P DSN D/O on request AE5000-SS DSN 4P D/O on request
AE 6300 - DSN AE6300-SS 3P DSN D/O on request AE6300-SS DSN 4P D/O on request
* Air circuit breaker without overcurrent short-circuit release
Connection arrangements
The following connecting methods are available for the AE type air circuit breaker.
Connection Horizontal connection Vertical connection Front connection Vertical terminal adapter Front terminal adapter
Mounting method Standard Optional Optional Accessory Optional
Fixed type
(Standard)
——— ———
(FIX-VTA) (FIX-FTA)
Drawout type
(Standard) (DR-VT) (DR-FT) (DR-VTA) (DR-FTA)
Remark Standard equipment
(shipping version) Special equipment
(on request) Special equipment
(on request) Available as accessory
(refer to page 15) Optional accessory
(on request)
MITSUBISHI ELECTRIC
7
Cylinder lock CYL Page 13
Motor charging device MD Page 10
Lifting hooks HP Page 15
Counter CNT Page 13
External power supply unit PS Page 19
Cell switch CL Page 14
Safety shutters SST Page 14
Mis insertion preventer MIP Page 14
Closing coil CC Page 11
Shunt trip device SHT Page 12
Under voltage trip device UVT Page 11
Auxiliary switch AX Page 12
UVT controller UVT Page 11
Castell lock CAL Page 13
Overview and mounting positions of the main accessories
SUPER AE
SUPER AE
Internal Accessories for all Breakers
ACCESSORIES
8
Standard Accessories
Manual charging
The spring is charged by the manual
charging handle. The breaker is closed
when the ON button is pressed, and
opened when the OFF button is pressed.
When the closing spring charging is com-
pleted, the charging indicator displays
CHARGED.
The indicator displays ON or OFF state
of the main contacts.
The breaker cannot be closed while the
OFF button is being pressed
(safety feature).
The manual charging process is one of
the standard features of the breaker and
part of the standard equipment.
OFF
OFF
ON
GESPANNT
Overview and description of the standard equipment
Drawout interlock
A safety device prevents the circuit
breaker from being pushed in or drawn
out while the breaker is on.
The drawout handle cannot be inserted
unless the OFF button is pressed.
Position lock
The device is for locking the drawout
mechanism at the TEST position. This
then indicates the TEST position.
The lock can be used during either the
drawing out or pushing-in operation.
The lock is released when the lock plate
is pushed in, and the next operation
becomes possible.
Padlocking is possible at the CON-
NECTED, TEST, and DISCONNECTED
positions. Use this lock to prevent un-
authorised changing of positions.
(The padlock should be supplied by
customer)
16
35
5
[mm]
Interphase barrier
The interphase insulation of the circuit
breaker prevent the short-circuit due to
conductive matters or dust.
The barriers are simple to add and have
been designed as fixed types and draw-
out types, to suit your requirements. The
table on the right shows you which circuit
breakers are supplied with pre-mounted
barriers.
Breaker Fixed type Drawout type
AE1000-SS
AE1600-SS 쏹쏹
AE2000-SS
AE3200-SS 쏹쏹
AE4000-SS
AE6300-SS ——
AE1000-SH –
AE3200-SH
= Standard equipment by horizontal connection
MITSUBISHI ELECTRIC
9
Motor charging device (MD)
In addition to manual operation, the
closing spring can be charged auto-
matically by an electric motor every time
the breaker is closed (ON charging
method).
If the closing spring is to be charged
automatically whenever the breaker is
opened, then this can be done through
an additional auxiliary contact (AXb)
(OFF charging method). As soon as
charging is completed, a visual display
on the front says “CHARGED”.
The “CHARGED” signal is also available
via the 413 (TS+) and 414 (TS-) terminals
(included in the standard MD configu-
ration).
There is always the option of manual
operation in an emergency. A closing
coil (CC) is required for closing the
breaker by remote control, and a shunt
trip device (SHT) is required for opening
it in this way.
This warrants the prevention of pumping,
both electronically and mechanically.
The circuit of the motor is separate from
the ON/OFF circuit (CC, SHT).
U1
(M+)
U2
(M-)
U1
(M+)
U2
(M-)
AXb
Control
supply
Control
supply
ON charging method
OFF charging method
Specifications MD-SAED24 MD-SAED48 MD-SAED60 MD-SAEAD013 MD-SAWAD013 MD-SAEAD025C MD-SAWAD025C
Application AE1000-SS/-SH –
AE3200-SS/-SH for all breakers for all breakers AE1000-SS/-SH –
AE3200-SS/-SH AE4000-SS AE6300
SS AE1000-SS/-SH
AE3200-SS/-SH AE4000-SS
AE6300 SS
Rated voltage * (V) 24 (DC) 48 (DC) 60 (DC) 100–125 (AC/DC) 100–125 (AC/DC) 200–250 (AC/DC) 200–250 (AC/DC)
Applicable voltage range (V) 20.4–26.4 40.8–52.8 51–60 85–137.5 85–137.5 170–275 170–275
Applied voltage (V) 24 48 60 100 / 125 100 / 125 200 / 250 200 / 250
Inrush current (peak value) (A) 22 14 9 10 / 12 10 / 12 5 / 6 7 / 8
Steady current (A) 6333/34/4 1/1 2 / 2
Charging time (sec) 5555555
Order information Art. no. 29453 34352 34368 32843 58320 25830 58321
* Rated frequency at AC = 50/60 Hz
Not available for AE4000-SS AE6300-SS.
Available for AE4000-SS – AE6300-SS on request.
Overview and description on the optional accessories
SUPER AE
SUPER AE
Internal Optional Accessories for all Breakers
ACCESSORIES
Charging completion switch (TS)
As soon as charging has been com-
pleted, this status is reported by the
413 (TS+) and 414 (TS-) terminals (signal
display of charged status). This function
is available during the charging process
both manually and automatically.
Specifications TS-SAE1A
Contact capacity refer to auxiliary switch
Order information Art. no. 30439
413
(TS+)
414
(TS-)
10
Undervoltage trip device (UVT)
This device is used for tripping the
breaker when the supply voltage drops
below the rated value.
The undervoltage trip device consists of a
UVT coil and a UVT controller. Both parts
must be ordered separately.
Two trip types are available:
instantaneous (for immediate tripping)
with a time delay of 0.5 or 3 seconds
All UVT controllers are fitted with addi-
tional terminals for the connection of an
emergency OFF switch. The UVT control-
ler can be mounted to the left of the the
unit.
If two rated voltages are used, the lowest
value is applied.
If an emergency OFF trip function is re-
quired, remove the shorting wire across
terminals DT1 (UO+) and DT2 (UO-) and
replace with an emergency OFF switch.
Coil
Controller D4
(UL3)
D3
(UL2)
D2
(UL1)
D1
(UL0)
DT1
(U0
+)
DT2
(U0–)
J1 (U+)
J2 J2
(U–)
J1
Circuit
voltage
Control
circuit
UVT controller
Trip button
UVT coil
Air circuit breaker
UVT circuit diagram
Notes on the circuit diagram:
The UVT, as delivered, has a shorting wire between the DT1 (UO+) and DT2 (UO-) terminals. If an emergency OFF switch is used, this contact
bridge must be removed. The emergency OFF switch is not included in the package. The maximum length of the wire between DT1 (U0+) and
DT2 (U0-) and the trip button should be 5 m. If longer distances are required please contact your nearest Mitsubishi distributor.
see note below
Specifications UCON-
SAED24-B UCON-
SAED011-B UCON-
SAEA123T-B UCON-
SAED24-05B UCON-
SAED011-05B UCON-
SAEA123T-05B UCON-
SAED24-30B UCON-
SAED011-30B UCON-
SAEA123T-30B UVT-
SAEUC
Rated voltage * (V) 24 (DC) 100–125 (DC) 100–460 (AC) 24 (DC) 100–110 (DC) 100–460 (AC) 24 (DC) 100–110 (DC) 100–460 (AC) UVT coil
Operation Instantaneous With time delay
Trip coil for
the beside
mentioned
controllers
Operating time (sec) 0.1 or less 0.1 or less 0.1 or less 0.5 or more 0.5 or more 0.5 or more 3 or more 3 or more 3 or more
Closing delay ** (sec) Approx. 1.5 Approx. 1.5 Approx. 1.5 Approx. 1.5 Approx. 1.5 Approx. 1.5 Approx. 3 Approx. 3 Approx. 3
Pick-up/drop-out voltage (V) Pick-up voltage 65–85 %, drop-out voltage 45–70 %
Trip function With open circuit (terminals DT1 (UO+), DT2 (UO–); rated 0.5 A at DC 250 V)
Power consumption (VA) 20
Order information Art. no. 30440 30441 30209 30442 30443 30206 30444 30445 30208 25912
* Rated frequency at AC= 50/60 Hz ** Delay which must be taken into account between the charging of the UVT controller and the closing of the breaker.
ACCESSORIES
Internal Optional Accessories for all Breakers
MITSUBISHI ELECTRIC
11
Closing coil (CC)
Theclosingcoilisadevicetoclosethe
breaker by remote control. Only one
closing signal (about 100 msec.) is sent
even when the closing coil supply is
maintained ON.
The closing coil is seperate from the
motor charging power supply.
Steady current is the value at maximum
rated voltage.
An interlock to prevent pumping is pro-
vided electrically. The pumping preven-
tion is not performed, when the supply
voltage is 50 % or less the minimum
rated voltage.
Closing time is from the initial energiza-
tion of the closing coil to the completion
of the closing of the main contacts.
No pumping prevention takes place if an
integrated auxiliary switch (AXb) is used
as a cut-off switch.
An auxiliary contact with high switching
capacity should be used with DC supply
voltage (HAX).
A1
(CC+)
A2
(CC-)
Control
supply
Specifications CC-SAED004A CC-SAED60 CC-SAEAD025A
Rated voltage * (V) 24–48 (DC) 60 (DC) 100–250 (AC/DC)
Applicable voltage range (V) 18–52.8 45–60 75–275
Operating voltage (V) 24 / 48 60 100 / 250
Inrush current DC (A) 3.5 / 7.0 1.1 0.6 / 1.3
AC (A) 0.5 / 1.0
Closing time (sec) 0.08 or less 0.08 or less 0.08 or less
Order information Art. no. 30399 40310 25909
* Rated frequency at AC = 50/60 Hz
SUPER AE
SUPER AE
Internal Optional Accessories for all Breakers
ACCESSORIES
Auxiliary switch (AX), HAX
These auxiliary contacts are used to
remotely indicate the ON or OFF status
of the breaker.
13
(AX+)
14
(AX-)
11
(BX+)
12
(BX-)
Specifications AX-SAE2A2BA AX-SAE5A5BA AX-SAE5A5BAD
Type Standard capacity (AX) High capacity (HAX)
Contact- Resistance
load Inductive
load Resistance
load Inductive
load Resistance
load Inductive
load
capacity 460 V 525252.5
(A) AC 250 V 10 10 10 10 10 10
125 V 10 10 10 10 10 10
250 V 0.3 0.3 0.3 0.3 3 1.5
DC 125 V 0.6 0.6 0.6 0.6 10 6
30 V 10 6 10 6 10 10
Maximum number of contacts 2 NO, 2 NC 5 NO, 5 NC 5 NO, 5 NC
Order information Art. no. 28786 25835 38468
Note: The chattering time at the time of contact ON - OFF is below 0.025 sec.
Shunt trip device (SHT)
The shunt trip device is used to open the
breaker by remote control. A cut-off switch is included.
C1
(S+)
C2
(S-)
Control
supply
Specifications SHT-SAED004A SHT-SAED60 SHT-SAED025A SHT-SAEA046A
Rated voltage * (V) 24–48 (DC) 60 (DC) 100–250 (AC/DC) 380–500 (AC)
Applicable voltage range (V) 16.8–52.8 42–66 70–275 266–550
Operating voltage (V) 24 / 48 60 100 / 250 460
Inrush current DC (A) 3.5 / 7.0 1 0.8 / 2.0
(peak value) AC (A) 0.6 / 1.7 0.6
Closing time (s) 0.04 or less (AE 4000-SS AE 6300-SS = 0.05 or less)
Order information Art. no. 27215 40309 25831 27614
* Rated frequency at AC = 50/60 Hz
12
Counter (CNT)
This is a mechanical counter which regis-
ters the total number of operating cycles
(with 1 on/off switching operation = 1 op-
erating cycle).
The number of operating cycles is dis-
played on the front of the unit.
Specifications CNT-SAE
Counter type mechanical
Display 5 digits
Order information Art. no. 25914
00000258
Interlock device (CYL, CAL)
The interlock device locks the circuit
breaker into the OFF position.
The relevant key can only be taken out in
the OFF position of the circuit breaker,
so that it can also be used for unlocking
other breakers.
There are two locking options available:
Cylinder lock (CYL)
Castell lock (CAL) *
CYL
CAL
Specifications CYL-
SAEWK CYL-
SAEWK 1 CYL-
SAEWK 2 CYL-
SAEWK 3 CYL-
SAEWK 4 CAL-
SAEWK
Interlock Cylinder Cylinder Cylinder Cylinder Cylinder Castell
Closing Basic 1 2 3 4 Basic
Order information Art. no. 25838 39485 39486 39488 39489 on request
* The closing basis for the Castell lock can be designed individually. Further details on request.
Condensor trip device (COT)
This device allows the electrically actu-
ated opening of the breaker by remote
control within a given period of time,
despite a power cut. The COT is used
in conjunction with the shunt trip device
(SHT).
For dimensions refer to page 41.
Further details on request.
Specifications KF-100 KF-200
Rated input voltage * V AC 100/110 200/220
Rated charging voltage V140/155 280/310
Power supply capacity VA 11
Capacitor capacity µF660 150
Voltage range %60–125 60–125
Charging time (capacitor) sec 0.5 or less 0.5 or less
Trip limit time sec 900 min. 300 min.
Order information Art. no. on request on request
* Rated frequency at AC = 50/60 Hz
AC2
AC1 S1
R2
R1
R3
N6
DC–
DC+
C2
(S–)
SHT
C1
(S+)
C
Circuit diagram
MITSUBISHI ELECTRIC
13
SUPER AE
SUPER AE
Optional Acessories for Drawout Type Breakers
ACCESSORIES
Cell switch (CL)
In addition to the mechanical position in-
dicator on the front panel, it is also possi-
ble to mount these cell switches onto the
cradle.
The cell switches can be set for all the
relevant positions, i.e. connected, test
and disconnected.
Each cell switch consists of 4 individual
switches.
Safety shutters (SST)
The safety shutters cover the main con-
ductors of the cradle side (supply and
load side) automatically when the circuit
breaker is drawn out.
When checking the main circuit, the
safety shutters on the supply and load
sides can be opened independently of
one another.
The safety shutters can also be locked
with a mechanical locking device (SST
LOCK). The padlocks have to be sup-
plied by customer.
Shorting b-contact (SBC)
When moving the breaker from the con-
nected to the test positions, this contact
is used to short circuit auxiliary switch
(Axb) thus maintaining the correct
sequence of operation of the external
control circuit.
When ordering, the same number of
shorting b-contacts as auxiliary switches
(AXb) will be provided.
Specifications SBC-SAE
Application Auxiliary switch (NO)
Order information Art. no. 30456
Mis-insertion preventor (MIP)
To obtain the right drawout configuration,
it is extremely important that the breaker
unit specifications (type, current rating,
optional accessories, etc.) should match
the cradle.
Mis-insertion is prevented by a combi-
nation of matching components (on the
breaker and the cradle).
Specifications MIP-SAE
Application (breaker) AE1000–AE3200-SS/SH
Material Metal
Order information Art. no. 30455
Specifications CL-SAE211 CL-SAH211
Load Resistive Inductive Resistive Inductive
Contact capacity (A)
AC 460
AC 250
AC 125
5
10
10
2,5
10
10
5
10
10
2,5
10
10
DC 250
DC 125
DC 30
3
10
10
1,5
6
10
3
10
10
1,5
6
10
Number and type of switches 4 interchange switches 4 interchange switches
Application (breaker) AE1000-SS AE6300-SS AE1000-SH – AE3200-SH
Order information Art. no. 25840 45578
Specifications SST-
02SAE3 SST-
02SAE4 SST-
05SAE3 SST-
05SAE4 SST-
SAELOCK
Application (breaker) * AE1000–1600-SS AE2000–3200-SS /
AE1000–3200-SH Safety
shutter
lock
Breaker type Drawout
Number of poles 3434
Order information Art. no. 25836 25837 25907 25908 30458
* On breaker types AE 4000 to AE 6300 the safety shutters are already part of the standard version.
discon.
Disconnected Connected
test operation
CONNECTED
CL–C
TEST
CL-T
DISCONNECTED
CL-D
Switch function
14
Lifting hooks (HP)
These hooks are used to remove the
drawout breaker from the cradle.
The option is not necessary, when a spe-
cial lifter (bucket type) for AE-SS is used.
The fixed type breaker is equipped with
the lifting hooks as standard.
The lifting hooks can not be used for
AE4000-SS to AE6300-SS.
Specifications HP-SAE
Material Metal
Order information Art. no. 30485
Vertical terminal adapter (VTA)
Vertical terminal adapters allow you to
turn power connection by 90°. Other forms of terminal adapters on re-
quest. Dimensions see page 37 and 39.
Specifications VTA-02SAE VTA-03SAE VTA-32SAE
Application (breaker) AE1000–AE1600-SS AE2000–2500-SS/
AE1000–2500-SH AE3200-SS/SH
Shipping contents pieces 11 1
Order information Art. no. 34193 34192 34191
MITSUBISHI ELECTRIC
15
Mechanical interlock (MI)
The mechanical interlock is a secure in-
terlock prohibiting the parallel closing of
two or three breakers.
Any combination between AE1000-SS/SH
up to AE3200-SS/SH is possible.
The interlock can be simply installed on
either fixed or drawout type breakers.
With the drawout type, the interlock oper-
ates at the connecting point and can be
released at other positions, providing
secure maintenance and inspection of
the breaker.
For AE4000-SS up to AE6300-SS a com-
bination is possible only between two
breakers.
Note:
When using the mechanical interlock, the
application of the door interlock (DI) is
not possible.
1000 (Max.)
134
144
0~12
1000 (Max.)
47
Vertical mounting
Horizotal mounting
[mm]
Door interlock (DI)
This mechanical interlock device makes
it impossible to open the panel door un-
less the circuit breaker is not switched off.
The device has been designed for panel
doors with the groove on the left (stand-
ard). Locks for grooves on the right are
available on request.
A wire-type mechanical interlock is used
to allow flexibility in positioning breakers
in the panel.
Note:
When using the door interlock (DI) the ap-
plication of the mechanical interlock (MI)
is not possible.
Cabinet
door
G
Change over of
2 power supplies Change over of
2 supply systems
ON ONOFF OFF
ON
Specifications DI-SAEF DI-SAED
Application (breaker) For all breakers For all breakers
Breaker type Fixed Drawout
Order information Art. no. 31538 31537
SUPER AE
SUPER AE
Optional Accessories for all Breakers
ACCESSORIES
Specifications MI-SAE
163F MI-SAE
164F MI-SAE
323F MI-SAE
324F MI-SAE
163D MI-SAE
164D MI-SAE
323D MI-SAE
324D MI-SAW
633D MI-SAW
634D MI-SAEIW
Application (breaker) AE1000–1600SS AE2000–3200SS
AE1000–3200SH AE1000–1600SS AE2000–3200SS
AE1000–3200SH AE4000–6300SS Bowden
cable set
Breaker type Fixed Drawout
Number of poles 3 4 3 4 3 4 3 4 3 4
Order information Art. no. 30450 30451 30452 30453 30446 30447 30448 30449 62327 62326 30454
Interlocking requires a separate unit for each breaker. If you have 3 breakers, you need a separate set of bowden cables MI-SAEIW.
16
Dust cover (DC)
The transparent dust cover is hinged
onto the panel door. It has a screw lock
and prevents dust and water entering
into the circuit breaker.
Specifications DC-SAE
Protection IP 54
Order information Art. no. 42618
Terminal cover (TTC)
The terminal cover is a transparent cover
for safety finger protection of control ter-
minals. The cover protects the voltage
terminals against finger contact .
Specifications TTC-SAEF TTC-SAED
Application (breaker) Fixed Drawout
Protection IP 20 IP 20
Order information Art. no. 62482 62481
Push button cover (BC-L)
This mechanical device can be locked
with a padlock or a seal (not included in
the package) to protect the push buttons
of the breaker unit against inadvertent
ON/OFF operation.
The padlock has to be supplied by the
customer.
Specifications BCL-SAE
Material Acrylic plate
Order information Art. no. 27727
Door frame (DF)
The door frame improves the appear-
ance, after cutting out the panel door to
install the breaker.
Refer to the overall dimension drawings
on page 36, 38 and 40 for the installation
method.
Specifications DF-SAE
Material Plastic
Protection IP 20
Order information Art. no. 28319
MITSUBISHI ELECTRIC
17
Neutral current transformer (NCT)
The neutral CT is used for ground fault
protection when a 3 pole breaker is used
on a 3 phase 4 wire system. It should be
used together with a electronic trip
relay that has the ground fault protection
(GFR) option.
N2
N1
Schalter
Elektr. Auslöserelais
mit Erdschlußschutz
Stromwandler
Widerstand
Stromwandler für Neutralpol (NCT)
Diagram Current transformer
Resistor
Current transformer for neutral pole
Breaker
Electronic trip relay
with ground fault prot.
ETR Specifications NCT-
06SAE NCT-
10SAE NCT-
12SAE NCT-
16SAE NCT-
20SAE NCT-
25SAE NCT-
32SAE NCT-
40SAW NCT-
50SAW NCT-
63SAW
Application (breaker) * AE1000 AE1000 AE1250 AE1600 AE2000 AE2500 AE3200 AE4000 AE5000 AE6300
Current range (A) 630 1000 1250 1600 2000 2500 3200 4000 5000 6300
Order information Art. no. 39038 39026 33853 37323 39037 39036 39035 62330 62329 62328
* A suitable resistor (0.1 / 10 W) is attached to the product. Furthertechnical details on request.
Current transformer (CT)
These current transformers (CT and sen-
sor coil) are suitable for the main conduc-
tor and the N conductor.
Current transformers of type CT-06첸첸첸
serve the reduction of INmax
.onan
AE 1000.
Specifications CT-06
SAE031 CT-06
SAE050 CT-06
SAE063 CT-10
SAE100 CT-12
SAE125 CT-16
SAE160 CT-20
SAE200 CT-25
SAE250 CT-32
SAE320 CT-40
SAW400 CT-50
SAW500 CT-63
SAW630
Application (breaker) * AE1000
-SS AE1000
-SS AE1000
-SS AE1000
-SS AE1250
-SS AE1600
-SS AE2000
-SS/-SH AE2500
-SS/-SH AE3200
-SS/-SH AE4000
-SS AE5000
-SS AE6300
-SS
Bemessungsstrom Inmax** (A) 315 500 630 1000 1250 1600 2000 2500 3200 4000 5000 6300
Order information Art. no. 30476 30477 30478 33437 30479 30480 39539 39540 39541 62331 62332 62333
* Shipping contents includs CT and sensorcoil for 1 pole. Other transformers on request.
** At 40°C and 50/60 Hz (other temperatures see Technical Information on page 44)
SUPER AE
SUPER AE
External Optional Accessories for all Breakers
ACCESSORIES
External current transformer (ZCT)
This option is used to detect several
amperes of earth leakage when used in
combination with an electronic trip relay
that has the earth leakage tripping (ER)
option.
Two methods are available:
ZCT: three-load phase conductors
(and the neutral conductor in a 4-wire
system) are passed through the ZCT
ZT: The supply transformer’s ground
wire passes through to earth.
ETR
N2
C2 C1
L2
N1
L1
SHT
713
714
Spannungsversorgung
Externer
Summenstromwandler
Auslöserelais
Load circuit method (ZCT)
Power supply Power supply
Electronic trip relay
External current
transformer
ETR
N2
L2
C2 C1
N1
L1
SHT
713
714
Spannungsversorgung
Auslöserelais
Externer
Summenstromwandler
Transformer ground wire method (ZT)
Power supply Power supply
External current
transformer
Electronic trip relay
Specifications ZCT-163 ZCT-323 ZCT-324 ZT-15A ZT-30A ZT-40A ZT-60A ZT-80A ZT-100A
Application Load circuits Transformer ground wire
Hole diameter for wire * (mm) 230x60 (oval) 370x108 (oval) 500x108 (oval) 15 30 40 60 80 100
Order information Art. no. on request
* For detailed dimensions refer to page 41. Further specifications on request..
18
External power supply unit (PS)
This unit is used when a DC 24 V control
supply is needed for the trip indicator on
the electronic trip relay.
The unit can be installed from the front to
the left side of the breaker (for dimen-
sions please refer to page 41).
Specifications PS-A200 PS-D200 PS-A400
Rated voltage * (V) 100–110 / 200–220 (AC) 200 (DC) 380–415 (AC)
Input voltage range (%) +10 / -15 % +10 / -15 % +10 / -15 %
Input capacity 30 VA or less 30 W or less 30 VA or less
Output voltage (V) 24 (DC) ±10 % 24 (DC) ±10 % 24 (DC) ±10 %
Output current (A) 0.42 or less 0.42 or less 0.3 or less
Order information Art. no. on request on request on request
* Rated frequency at AC = 50/60 Hz
Field test devices
The test devices are for testing the
functioning of the electronic trip relay.
It allows you to test the trip relay without
the breaker being connected to the main
supply. The breaker will trip when tested.
888.888
888.88.8
STOP
a?/OCR
VT
50/60
50 Hz 60 Hz
OCR
VT
TESTING
7
4
1
0
9
6
3
SET
SIGNAL SET
SIGNAL ADJUST
STOP
SIGNAL
STOP
FREQUENCY
SIGNAL
BREAKER TESTER
UP
OPERATING
TIME
DOWN
8
8
8
?
C
OUTPUT
OUTPUT
S1S2S3
S3
S2
TC
S1
STOP
TRIP
CHECK
START
RESET
TRIP
MITSUBISHI
Y-
2000
(Y2000)
Specifications Y-160 Y-2000
Test functions LTD, STD, INST, Groundfault LTD, INST, STD,
Groundfault, pre-alarm
Power supply * 100–120 V, 200–240 V (AC) or battery 100–240 V (AC)
Test current signal setting 6-point setting possible
(20, 40, 125, 200, 500 and 2000 %) Continuously variable
(10 – 2000 %)
Others Time counter Ammeter, time counter
Order information Art. no. 27497 27496
* Rated frequency at AC = 50/60 Hz
Test jumper (TJ)
The test jumper cable is for testing the
functioning of the circuit breaker when
the unit is removed from its cradle. Take
the breaker out of its cradle and use this
cable to switch the breaker on and off
electrically, so that you can check all its
functions.
Specifications TJ-SAE
Cable length (m) 3*
Order information Art. no. 30457
* Further lengths on request
MITSUBISHI ELECTRIC
19
Applicable types B type General use
S type Generator protection
M type Power
supply Remarks Reference
Functions Code ST SPT SPGT SPET MT MPT MPGT
Standard
functions
Long-time-delay L
쏹쏹쏹쏹쏹쏹 The basic L, S and I protection functions are
also available when the control power supply
fails. Page 23, 25
+ Short-time-delay S
+ Instantaneuous I
Trip indicator TRIP 쏹쏹쏹쏹쏹쏹쏹 required *) Both LED display and relay output
terminals are available. Page 22, 24
Load current indicator LCI 쏹쏹쏹쏹쏹쏹쏹 The load state is indicate by the color
of the LED. Page 22, 24
Test terminal TEST 쏹쏹쏹쏹쏹쏹쏹 For characteristics check Page 23, 25
STD lock button 쏹쏹쏹쏹쏹쏹쏹 Convenient for checking instantaneous
operation Page 23, 25
Special
functions
Pre-alarm PAL ——쏹쏹쏹쏹쏹 required *) Both LED display and relay output
terminals are available. Page 22, 24
Ground fault GFR ——————
1. With ground fault alarm switch
2. If a 3-pole breaker is used in a 4-wire
circuit, a neutral-pole CT (NCT) has to be
ordered.
3. The ground fault protection (GFR) is not
available when the maximum rated current
is less than 315 / 500 A or 630 A for
AE1000-SH.
Page 27
Earth leakage ER ———— required An external ZCT and a shunt trip device
(SHT) are required (not available for
AE 4000–6300) Page 26
Accessory
OCR alarm AL 쎻쎻쎻쎻쎻쎻쎻쎻 Since the output signal is a short pulse, an
external self-holding circuit is
required. Page 25
Load current
measurement LM 쎻쎻쎻쎻쎻쎻쎻 required *) The maximum phase current flowing through
the braker can be measured. Page 27
Unusual temperature
indicator TAL 쎻쎻쎻쎻쎻쎻쎻 required *) The sensor is integrated in the breaker. Page 27
Instantaneous / MCR ———————
1. The long-time and short-time delay
function (L) is not available.
2. A changeover between instantaneous and
MCR characteristics is possible.
3. Suitable for AE 1000–3200-SS only.
3-
and
4-
pole
Short-time delay
+instantaneous
/MCR (I)
MCR
(I) 햲햲햲햲———
1. The long-time delay function (L) is not
available.
2. A change-over between instantaneous
and MCR characteristics is not possible
(not available for AE 4000–6300).
Long-time delay
+short-time delay
+instantaneous / MCR (C)
MCR
(C) 햲햲햲햲
—— A change-over between instantaneous and
MCR characteristics is possible
(not available for AE 4000–6300). Page 22, 23
4-
pole Neutral pole
overcurrent protection NP 햲햲햲햲——— Neutral pole protection with 50 % or 100 %.
Please consider when ordering
(for AE 4000–6300 on request). Page 26
Relay
power
supply
Applicable voltage range **
AC 100–120/200–240 V
DC 100–110 V
DC 125 V
DC 24 V
1
2
3
4
An external power supply for trip indication (TRIP) and relay
control is required for all type of relays.
The relay types are available in the 4 shown voltage ranges
(standard = AC100–120/200–240 V).
Please remark when ordering.
When the control power supply fails the
function of the LED displays and output
terminals are disabled.
All standard protection functions are still
available.
Equipped with function as standard. Function available as an option.
Function not available. Only one of the special versions (MCR-I, MCR-C or NP) is available as an option.
*No additional power supply is required as long as control power is available.
** Other voltages on request. Rated frequency at AC = 50/60 Hz.
Special versions
SUPER AE
SUPER AE
Program Overview Features
ELECTRONIC TRIP RELAY
Introduction and selection
Special notes:
The circuit breakers are equipped with the S type relay in ST-1 version (applicable voltage range AC 100–120/200–240 V)
as standard (refer to page 6).
All other model types and accessories can be configured and ordered individually.
In the table on page 28 the most common configurations are listed with order informations.
The trip relay type B is suitable for switch disconnectors with instantaneous MCR characteristics only.
20
Function Appli
cable
type Application
Standard protection
type S Generator protection
type M
ST SPT SPGT SPET MT MPT MPGT
Max. rated current
(INmax)All
types Maximum rated current
(INmax.) Conforms to CT ratings
(see table below)
Rated current
(IN)All
types Maximum rated current
(INmax.) ×setting 0.5–0.6–0.7–0.8–0.9–1.0
(adjustable in steps)
Uninterrupted
current (IU)Type S Rated current (IN)
×setting 0.8 to 1.0
(continuously adjustable) ——
Long-
time
delay (L)
Current (IL)
Type S Uninterrupted current (IU)
×setting 1.15 ± 10 %
(fixed) 1–1.05–1.1–1.15–1.2 ±5%
(adjustable in steps)
Type M Rated current (IN)
×setting
Time (TL)
Type S At uninterrupted current (IU)
×2Faktor 50–100–150 sec. ±20 %
(adjustable in steps) 15–20–25–30–40–60 sec. ±20 %
(adjustable in steps)
Type M At current (IL)
×1,2
Time
fine ad-
justment Type M Long-time delay
time (TL)×setting —— 0.8–0.9–1.0-1.1–1.2
(continuously adjustable)
Short-
time
delay (S)
Current
(IS)All
types
Rated current (IN)
×setting 2–3–4–6–8–10 ±15 %
(adjustable in steps) 2–2.5–3–3.5–4–4.5 ±15%
(adjustable in steps)
Time
(TS)
At short-time delay
current (IS)
×1,5
0–0.1–0.2–0.3–0.40.5 sec. ±20 %
(adjustable in steps)
Remark: the operating time for “0" is 0.05 sec.
Instanta-
neous (I) Current
(II)All
types Rated current (IN)
×setting 4–6–8–10–12–16 ±15 %
AE5000-SS: 4–6–8–10–12 ±15 %, AE6300-SS: 4–6–8–10 ±15 % (particulary adjustable in steps)
Pre-alarm
(PAL)
Current
(IP)
Type S Uninterrupted current (IU)
×setting 0.7–0.8–0.9–1.0–OVER ±10 %
(adjustable in steps) 0.84–0.88–0.92–0.96–1.0
±5%
(adjustable in steps)
Type M Long-time delay current (IL)
×setting
Time (TP)All
types
At long-time delay time (TL)
×setting 0.5 times ± 20 % 0.5 times ±20 %
Reset
system Self holding Automatic reset
Ground
fault
(GFR)
Current
(IG)All
types
Maximum rated current
(INmax.)×setting ——
0.1–0.2–0.3–0.5 ±20 %
AE4000 AE6300-SS:
0.2–0.3–0.5 ±20%
(adjustable in steps)
——
0.1–0.2–0.3–0.5 ±20 %
AE4000 AE6300-SS:
0.2–0.3–0.5 ±20%
(adjustable in steps)
Time (TG)At ground fault current (IG)
×1,5 ——0.3–0.8–1.5–3sec. ±20 %
(adjustable in steps) ——
0.3–0.8–1.5–3sec. ±20 %
(adjustable in steps)
Earth
leakage
(ER)
Current (IE)
Type S
Earth leakage current (IE)
=setting —— 1–2–3–5A±20 %
(adjustable in steps) ——
Time (TE)At earth leakage current (IE)
×1,5 ——0.3–0.8–1.5–3sec. ±20 %
(adjustable in steps) ——
Not available at IN max. 315 A, 500 A and AE 1000-SH, 630 A.
At 105 % non trip, at 125 % pick up.
Note: The electronic trip relay will be delivered set to the values shown in bold type.
“SS” type AE1000-SS AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SS AE5000-SS AE6300-SS
Rated current
(INmax
)
315, 500
630
1000 1250 1600 1250
1600
2000 2500 3200 4000 5000 6300
“SH” type AE1000-SH AE1250-SH AE16000-SH AE2000-SH AE2500-SH AE3200-SH
Rated current
(INmax
)
630
1000 1250 1600 2000 2500 3200
Characteristics setting table
Overview of rated currents (INmax
) CT ratings
MITSUBISHI ELECTRIC
21
SUPER AE
SUPER AE
S Types General Protection
ELECTRONIC TRIP RELAY
TRIP Trip Indicator
Display of tripping condition:
L for Long-time delay
S/I for short-time delay (S) /
instantaneous (I)
G for ground fault (GFR)
E for earth leakage (ER)
Both an LED display (red) and a relay
output are provided.
Remarks: ,,
PAL Pre-Alarm Display
Pre-alarm display when a pre-deter-
mined load current is reached.
Display method: Both an LED display
(yellow) and a relay output are available.
The “PAL” LED lights up when the pre-
set value is exceeded (the relay is not
activated when this happens).
The relay output is activated when the
“PAL OUT” LED lights up.
Remarks: ,,
TAL Temperature Alarm
An alarm signal is generated when the
temperature of the main contacts rises
above the threshold level (approx. 170 °C
or more).
Display methods: Both an LED indicator
(red) and a relay output are provided.
Remarks: ,,
LCI Load Current Indicator
Indicates the percentage of uninter-
rupted current (IU) in the following steps
60-70-80-90-100-OVER.
LED indication in different colours:
60–80%=green
90 100 % = yellow
OVER = red
The LEDs goes out when the breaker
trips.
AL OCR Alarm Contact
An alarm signal is output to the contact
when the breaker is tripped by one of the
following causes:
L Long-time delay
S Short-time delay
I Instananeous trip (I) or MCR
G Ground fault or
E Earth leakage
Remarks: ,
RESET Indicator Reset Button
Pressing this button resets the displays
and the relay output.
Trip indicator (TRIP)
Unusual temperature indicator (TAL)
Pre-alarm (PAL)
LM Max. Phase Current,
Load Current Measurement
Max. phase current (L-C-R display)
Phase current display (L=L1, C=L2 and
R=L3) via LED (green).
LED indicators are provided for the left,
central and right poles. One LED is al-
ways on when current is flowing through
the breaker. This function is included in
the Load current measurement option.
Load current measurement (LM)
The load current can be measured at
terminal LM. At twice the max. current
(INmax.) a signal of DC 24 V is output
(refer to wiring diagram on page 34, 35).
Remark: ,
TRIP INDICATOR
LOAD CURRENT
LARGEST PHASE
RATED CURRENT MAX
RATED CURRENT
%lu
SPGT - CIACT
ELECTRONIC TRIP RELAY
MITSUBISHI
MODEL
IN
S
U
MCR
I
S
TEST
S
TRIP
PAL
LCI
LM
RESET
TAL
L
GFR
GFR
GFR
PAL
Remarks:
All functions marked in gray are included as
standard equipment (standard relay ST-1).
This overview lists the maximum possible
functionality of the units.
Trip relays with special functions (functions
wich are not marked in gray) have to be
ordered seperately (please refer to order
informationonpage28).
Page 26 and following contain a detailled
description of all special functions.
An external power supply for trip indication
and relay control is required for all type of
relays. The voltage range for the power supply
must be within one of the following ranges:
- 1: AC 100–120 / 200–240 V (standard)
- 2: DC 100–110 V
- 3: DC 125 V
-4: DC24V
(other voltages on request)
The LED will go out when the control power
supply is interrupted or when the RESET
button is pushed.
An external self-hold circuit is required,
as the alarm signal pulse has a duration
of only 0.03 sec.
The contact rating (A) for the signal relays
are listed in the table below.
Voltage (V) Resistive load Inductive load*
AC 120
22
250
DC 30
125 0,2 0,1
*cos ϕ=0,4,L/R=7msec
22
Basic Setting
INRated Current
Setting dial
The maximum rated current can be
selected as follows:
Max. rated current (INmax
)xsetting(A)
0.5-0.6-0.7-0.8-0.9-1.0
Changing this setting changes the
following values proportionally:
Uninterrupted current (IU)
Short-time delay current (IS)
Instantaneous current (II)
Pre-alarm (IP)
Overload Protection
UUninterrupted Current (IU)
Setting dial
Rated current (IN) x setting (A)
0.8 1.0
Used for setting the continuous uninter-
rupted current value. The actual tripping
rangeisI
Ux1.05–1.25.
The load current is displayed as a per-
centage of the uninterrupted current and
thus changes proportionally when the un-
interrupted current setting is changed.
LLong-Time Delay Time (TL)
LTD TIME setting dial
Time setting (in seconds)
50-100-150
This value specifies the operating time
when the current flowing is the uninter-
rupted current set value x 2.
The pre-alarm operating time is half of
the long-time-delay time setting.
MCR INST/MCR Switch
Switch
This switch makes it possible to select
between instantaneous operation charac-
teristic (INST) and MCR characteristic.
The MCR characteristics the abbreviation
for Making Current Release. With this
characteristic, instantaneous tripping is
only possible if a short circuit occurs dur-
ing switch-ON. After the initial switch-ON,
the time delay tripping characteristic is
active but the instantaneous tripping is
not possible.
PAL Pre-Alarm Current (IP)
PAL P.U. setting dial
Rated current (IU) x setting
0,7-0,8-0,9-1,0-OVER
Current setting for pre-alarm activation.
Short-Circuit Protection (STD)
SShort-Time Delay P.U. Current (IS)
STD P.U. setting dial
Rated current (IN)xsetting(A)
2-3-4-6-8-10
Current threshold value setting for short-
time delay tripping.
SShort-Time Delay Time (TS)
STD TIME setting dial
Time-delay setting (in seconds)
0-0.1-0.2-0.3-0.4-0.5
The setting value is the operating time
when the current flowing is the short-time
delay current setting (IS)x1,5.
If the dial is set to 0 seconds the breaker
will trip in 0.05 seconds.
SShort-Time Delay Lock Button
STD LOCK button
When measuring the instantaneous trip-
ping current, press the short time delay
operation inhibit button (STD LOCK) in
order to disable the short-time-delay trip-
ping function.
Short-Circuit Protection (instantaneous)
IInstantaneous P.U. Current (II)
INST P.U. setting dial
Rated current (IN)xsetting(A)
4-6-8-10-12-16
AE5000: 4-6-8-10-12
AE6300: 4-6-8-10
Sets the threshold current value for
instantaneous tripping.
ER Earth Leakage Protection (IE)
ER P.U. Current (I
E
) setting dial
Current setting 1–2–3–5
Both external ZCT and SHT are required
(see page 18 and 24 for further details).
ER Earth Leakage Protection (TE)
ER TIME (T
E
) setting Dial
Time setting (in seconds)
0.3–0.8–1.53
The setting represents the operating time
when the current flowing is the earth leak-
age current value setting x 1,5.
The earth leakage protection facility is
not illustrated because it is only possible
to have either earth leakage or ground
fault protection.
Ground Fault Protection (GFR)
GFR Ground Fault P.U. Current (IG)
Setting dial
Max. rated current (INmax.) x setting (A)
0.1-0.2-0.3-0.5
AE4000–6300: 0.2-0.3-0.5
The function is not available when
INmax. is less than 630 A and for
AE1000-SH, INmax630 A.
GFR Ground Fault Time (TG)
Setting dial
GFR time setting (in seconds)
0.3-0.8-1.5-3
The setting specifies the operating time
when the current flowing is the ground
fault current value setting (IG)x1.5.
GFR Ground Fault Trip Switch
GFR TRIP / ALARM
The breaker will trip when the switch is
set to the “TRIP” position.
When the switch is set to the “ALARM”
position a red trip indicator LED will light
up and the relay output will be activated
when a ground fault occurs; the breaker
will not trip, however.
The switch must be set to the “TRIP posi-
tion when the overcurrent tripping char-
acteristic is activated (refer to page 27).
Others
TEST Test Terminal
Test functions:
Tripping characteristics
Long-time-delay (L)
Short-time-delay (S)
Instantaneous (I)
Pre-alarm (P)
Ground fault (GFR)
A special testing device is required
(see page 19).
The bold marked values show the setting at
time of shipment.
MITSUBISHI ELECTRIC
23
SUPER AE
SUPER AE
M Types Generator Protection
ELECTRONIC TRIP RELAY
TRIP Trip Indicator
Display of tripping condition:
L for Long-time delay
S/I for short-time delay (S) /
instantaneous (I)
G for ground fault (GFR)
Both an LED display (red) and a relay
output are provided.
Remarks: ,,
PAL Pre-Alarm Display
Pre-alarm display when a pre-deter-
mined load current is reached.
Display method: Both an LED display
(yellow) and a relay output are available.
The PAL” LED lights up when the pre-
set value is exceeded (the relay is not
activated when this happens).
The relay output is activated when the
“PAL OUT” LED lights up.
Remarks: ,,
TAL Temperature Alarm
An alarm signal is generated when the
temperature of the main contacts rises
above the threshold level (approx. 170 °C
or more).
Display methods: Both an LED indicator
(red) and a relay output are provided.
Remarks: ,,
LCI Load Current Indicator
Indicates the percentage of uninterrup-
ted current (IU) in the following steps
50-60-70-80-90-100-OVER.
LED indication in different colours:
50–70%=green
80 90 % = yellow
100%=red
The LEDs goes out when the breaker
trips.
AL OCR Alarm Contact
An alarm signal is output to the contact
when the breaker is tripped by one of the
following causes:
L Long-time delay
S Short-time delay
I Instananeous trip (I)
G Ground fault
Remarks: ,
RESET Indicator Reset Button
Pressing this button resets the displays
and the relay output.
Trip indicator (TRIP)
Unusual temperature indicator (TAL)
Pre-alarm (PAL)
LM Max. Phase Current,
Load Current Measurement
Max. phase current (L-C-R display)
Phase current display (L=L1, C=L2 and
R=L3) via LED (green).
LED indicators are provided for the left,
central and right poles. One LED is al-
ways on when current is flowing through
the breaker. This function is included in
the Load current measurement option.
Load current measurement (LM)
The load current can be measured at
terminal LM. At twice the max. current
(INmax.) a signal of DC 24 V is output
(refer to wiring diagram on page 34, 35).
Remark: ,
TRIP INDICATOR
LOAD CURRENT
LARGEST PHASE
RATED CURRENT MAX
RATED CURRENT
%l
L
MPGT - 4ACT
ELECTRONIC TRIP RELAY
MITSUBISHI
MODEL
IN MAX
PAL
PAL
GFR
LCI
L
L
TRIP
TAL
LM
RESET
S
I
S
TEST
S
L
GFR
GFR
Remarks:
All functions marked in gray are included as
standard equipment (standard relay ST-1).
This overview lists the maximum possible
functionality of the units.
Trip relays with special functions (functions
which are not marked in gray) have to be
ordered seperately (please refer to order
informationonpage28).
Page 26 and following contain a detailled
description of all special functions.
An external power supply for trip indication
and relay control is required for all type of
relays. The voltage range for the power supply
must be within one of the following ranges:
- 1: AC 100–120 / 200–240 V (standard)
- 2: DC 100–110 V
- 3: DC 125 V
-4: DC24V
(other voltages on request)
The LED will go out when the control power
supply is interrupted or when the RESET
button is pushed.
An external self-hold circuit is required,
as the alarm signal pulse has a duration
of only 0.03 sec.
The contact rating (A) for the signal relays
are listed in the table below.
Voltage (V) Resistive load Inductive load*
AC 120
22
250
DC 30
125 0,2 0,1
*cos ϕ=0,4,L/R=7msec
24
Basic Setting
INMAX Rated Current
RATED CURRENT
The rated current will be preset to a fixed
value at time of shipment (select a value
between 0.5 and 1 of the maximum rated
current).
Thevalueisstampedontherelay.
Overload Protection
LLong-Time Delay Current (IL)
LTD P.U. setting dial
Rated current (IN) x setting (A)
1-1.05-1.1-1.15-1.2
The breaker trips within a range from
(IL) x 0.95 to 1.05.
The load current is displayed as a percent-
age of the long-time delay current (IL).
The pre-alarm set value varies proportion-
ally to the long-time delay current setting.
LLong-Time Delay Time (TL)
LTD TIME setting dial
Time setting (seconds)
15-20-25-30-40-60
This value specifies the operating time
when the current flowing is the long-time
delay current set value (IL) x1.2.
The pre-alarm operating time is half of
the long-time delay setting.
LLong-Time Delay TimeFINE (TL)
FINE adjustment dial
Fine adjustment of long-time delay time.
Allows continuous adjustment from 0.8 to
1.2 of the long-time-delay setting value (TL).
This setting has no influence on the
pre-alarm time.
PAL Pre-Alarm (IP)
PAL P.U. setting dial
Long-time-delay current value (IL)
xsetting
0.84-0.88-0.92-0.96-1.0
Threshold value for pre-alarm operation.
Short-Circuit Protection (STD)
SShort-Time Delay P.U. Current (IS)
STD P.U. setting dial
Rated current (IN)xsetting(A)
2-2.5-3-3.5-4-4.5
Current threshold value setting for short-
time delay tripping.
SShort-Time Delay Time (TS)
STD TIME setting dial
Time delay setting (in seconds)
0-0.1-0.2-0.3-0.4-0.5
The setting value is the operating time
when the current flowing is the short-time
delay current setting (IS)x1.5.
If the dial is set to 0 seconds the breaker
will trip in 0.05 seconds.
SShort-Time Delay Lock Button
STD LOCK button
When measuring the instantaneous trip-
ping current, press the short time delay
operation inhibit button (STD LOCK) in
order to disable the short-time-delay trip-
ping function.
Short-Circuit Protection (instantaneous)
IInstantaneous P.U. Current (II)
Rated current (IN)xsetting(A)
4-6-8-10-12-16
AE5000: 4-6-8-10-12
AE6300: 4-6-8-10
Sets the threshold current value for
instantaneous tripping.
Ground Fault Protection
GFR Ground Fault P.U. Current (IG)
GFR P.U.
Max. rated current (INmax.) x setting (A)
0.1-0.2-0.3-0.5
AE4000–6300: 0.2-0.3-0.5
This function is not available if max. rated
current values INmax. is less than 630 A
and for AE1000-SH, INmax630 A.
GFR Ground Fault Time (TG)
GFR TIME
Time setting (in seconds)
0.3-0.8-1.5-3
The setting specifies the operating time
when the current flowing is the ground
fault current value setting (IG)x1.5.
GFR Ground Fault Trip Switch
GFR TRIP / ALARM
The breaker will trip when the switch is
set to the “TRIP” position.
When the switch is set to the “ALARM”
position a red trip indicator LED will light
up and the relay output will be activated
when a ground fault occurs; the breaker
will not trip, however.
The switch must be set to the “TRIP posi-
tion when the overcurrent tripping char-
acteristic is activated (refer to page 27).
Others
TEST Test Terminal
Test functions:
Tripping characteristics
Long-time-delay (L)
Short-time-delay (S)
Instantaneous (I)
Pre-alarm (P)
Ground fault (GFR)
A special testing device is required
(see page 19).
The bold marked values show the setting
at time of shipment.
MITSUBISHI ELECTRIC
25
Earth leakage protection (ER)
The earth leakage alarm facility is real-
ised with an electronic trip relay with
earth leakage protection (ER charac-
teristics) and an external ZCT (refer to
page 18 and 21). When earth leakage
current flows an alarm is activated but
the breaker does not trip (see the earth
leakage alarm system wiring diagram).
If you require the breaker to trip upon
earth leakage you must also install an
SHT device (see the earth leakage trip-
ping system wiring diagram). Observe
the voltage range specifications for the
voltage tripping device SHT, The voltage
tripping device (SHT) is suitable for
250 V AC/DC or less.
The earth leakage protection is not
available for AE4000 to AE6300-SS.
ETR
N2
L2
N1
L1
SHT
713
C1C2 714
Earth leakage tripping system
External ZCT
for Ground wire
Control power supply
Electronic trip relay
(with earth leakage protection)
ETR
BZ
N2 N1
L1
513
544
L2
Earth leakage alarm system
External ZCT
for ground wire
Earth leakage
alarm buzzer
Control power supply
Electronic trip relay
(with earth leakage protection)
Neutral pole overcurrent protection (NP)
This function protects the neutral pole
(4th pole) of the circuit breaker against
overcurrent.
Neutral pole overcurrent protection can
be set to operate at 50% or 100% of the
rated current. The function prevents pos-
sible destruction of the neutral pole by in-
creased load current in this pole caused
by load equipment that generates third
harmonic wave forms. This function is
only possible with type S relays with
neutral pole overcurrent function and a
4-pole breaker.
Neutral pole protection for AE4000 to
AE6300-SS on request.
I
>
Current sensor coil
Same phase
Load equipment that generates
third harmonic wave form
current
Pre-alarm (PAL)
If the load current flowing through the
breaker exceeds the preset value the
“PAL LED lights up and a relay output is
activated. This is a useful option for en-
suring a continuous power supply to an
important circuit.
The operating characteristic shown in the
graph is proportional to half of the long-
time-delay tripping characteristic. It has
been designed to prevent unnecessary
alarms from inrush currents to the load.
TLrepresents the long-time delay time.
The general use relay output is of a self-
hold type; the relay type for generator
protection features auto reset. (The con-
trol power supply and reset button re-
quired for the LED display is also used
internally for the pre-alarm).
1h
10 min.
2 min.
1 min.
30 sec
10 sec
4sec
1sec
0.4 sec
0.1 sec
0.04 sec
2010 40 60
100 200 400
600
100020004000
6000
70%
Pre-alarm
current setting range
Overcurrent
characteristics
T =50 sec
L
Pre-alarm
characteristics
Pre-alarm
operating time
for T =150 sec
L
Pre-alarm
operating time
for T =50 sec
L
OVER
T =150 sec
L
Characteristics (type S)
Current (%)
Time (t)
SUPER AE
SUPER AE
Special Functions Accessories
ELECTRONIC TRIP RELAY
26
Ground fault protection (GFR)
When ground fault currents of several
hundred amperes flow, it is possible that
the long-time-delay or short-time-delay
functionsmaynotbeabletoprotectthe
circuit. The ground fault function (GFR)
can provide the necessary protection in
these situations. Response sensitivity
can be set in the range 0.1–0.2–0.3–0.5,
multiplied by the maximum rated current
(INmax.); operating time can be set in
the range 0.3–0.8–1.5–3 seconds.
No control power supply is required
for this function.
Similary with a 3 pole breaker, ground
fault protection is also possible for a
3-phase, 3-wire circuit.
In a 3-phase, 4-wire circuit ground
fault protection is also possible if the
3-pole breaker is combined with a
neutral pole CT (NCT). See page 18
for details.
The ground fault protection is not
available if the max. rated current
(INmax.) is less than 315 A or 500 A
and less than 630 A for AE1000SH.
GFR
4 pole breaker Current sensor coil
Electronic trip relay
(with ground fault protection GFR)
OCR alarm (AL)
The OCR alarm is a short-time operating
contact (NO contact) that indicates when
the breaker has tripped as a result of an
overcurrent situation. The AL unit is inte-
grated in the electronic trip relay.
It operates when the breaker trips due to
long-time-delay, short-time-delay, instan-
taneous/MCR and ground fault (GFR).
It is not activated when the breaker is
tripped by the earth leakage (ER) protec-
tion facility
Note:
Though control power supply is not
required for the operation of the overcur-
rent alarm (AL), an external self-hold
circuit is required since the relay output
is only activated for 0.03 seconds.
When a continuous output signal from
the OCR alarm (AL) is required, please
use the output signal from the trip indica-
tors L, S/I and G, which is operated by
thesamecausesastheOCRalarm.
Load current measurement (LM)
A direct current voltage signal which is
converted from the effective value cur-
rent in the electronic trip relay is taken
out externally by using an isolation ampli-
fier. Use the receiving indicator that can
be operated by an input of 0–5 V DC
since the voltage signal proportional to
the largest phase current is transmitted.
Moreover the voltage signal which is pro-
portional to the largest phase current is
then used to light the appropiate phase
LED (the control supply is that used for
the trip indicator).
Note:
Please consider that the wiring is within
3 m of the breaker control circuit terminal
by using a twisted pair wire (with over
40 turns/meter).
The required control power supply for the
LED indicator is common to the trip indi-
cator
10
200100
0025
5
Output characteristics
Current (% of INmax
)
Voltage (V DC)
Accuracy (±5%)
Temperature alarm (TAL)
When the temperature of the main con-
tacts exceeds a pre-determind (approx.
170° C), a LED lights up and a relay con-
tact (NO contact) is activated.
This helps to prevent malfunctions and
increase the service life of the contacts
as it makes it possible to detect even
temporary temperature increases. Since
the relay output is self holding a temporary
rise in temperature more than 6 hours
can also be detected (the control supply
and the reset button are used in common
with the trip indicator).
Note:
The power supply which is required for
the LED indicators, is additionally used
for the internal temperature measure-
ment.
MITSUBISHI ELECTRIC
27
SUPER AE
SUPER AE
Ordering Information
ELECTRONIC TRIP RELAY
Unless otherwise indicated, all circuit
breakers in the standard package are
deliver with the electronic trip relay ST-1
or ST-1A (see overview on pages 6 and 7).
If you require a different relay for a given
circuit breaker, simply specify the rele-
vant electronic trip relay separately when
ordering the breaker.
The table on the right gives you an over-
view of different trip relays. For detailed
information please refer to page 20.
The table below gives you a selection of
the most common electronic trip relays
with the relevant ordering details. To order
a certain relay, make sure you state the
relevant order code.
Ordering procedure
Type (code) Voltage code Accessory
SPT 1 A
A = AL (OCR alarm)
C = LM (Load current meas.)
T = TAL (Temperature alarm)
= no accessory wanted
Trip relay Operating functions Voltage code Accessory
Type Version PAL GFR ER MCR/C MCR/I NP MCR/
INST 1234ALLMTAL
S
ST ——————— 쎻쎻쎻
ST-C ——— 쎻쎻쎻
ST-I —— 쎻쎻쎻
ST-N 쎻쎻쎻
SPT —————— 쎻쎻쎻
SPT-C ————— 쎻쎻쎻
SPT-I ————— 쎻쎻쎻
SPGT 쏹쏹————— 쎻쎻쎻
SPGT-C 쏹쏹——— 쎻쎻쎻
SPGT-I 쏹쏹———— 쎻쎻쎻
SPET ———— 쎻쎻쎻
SPET-C 쏹쏹——— 쎻쎻쎻
SPET-I —— 쎻쎻쎻
M
MT ——————— 쎻쎻쎻
MPT —————— 쎻쎻쎻
MPGT 쏹쏹————— 쎻쎻쎻
BB-C —————————— ——
Function included in the relevant trip relay.
Function available as an option.
Function either not included or not available.
Important: neutral pole overcurrent protection is only available for 4-pole breakers.
The MCR function is not available for high performance breakers (i.e. the AE-SH series) and
breaker types AE4000-SS up to AE6300-SS.
AC 100–120, 200–240 V
DC 100–110 V
DC 125 V
DC 24 V
Type Code Description Application Ordering information Art. no.
S
ST-1 Standard trip relay without optional functions, AC 100-120 V and AC 200–240 V all breakers Standard
ST-1A AC 100–120 V and AC 200–240 V, with OCR alarm (AL)
AE1000–AE4000-SS/SH ST-01SAEA024B-A 27494
AE5000-SS ST-50SAWA024B-A 62334
AE6300-SS ST-63SAWA024B-A 62335
ST-2A Standard trip relay without optional functions,
DC 100–110 V, with OCR alarm (AL)
AE1000–AE4000-SS/SH ST-01SAED011-A 30461
AE5000-SS ST-50SAWD011-A 62338
AE6300-SS ST-63SAWD011-A 62339
ST-4A Standard trip relay without optional functions,
DC 24 V, with OCR alarm (AL)
AE1000–AE4000-SS/SH ST-01SAED24-A 30460
AE5000-SS ST-50SAWD24-A 62336
AE6300-SS ST-63SAWD24-A 62337
SPT-1A Trip relay with pre-alarm function (PAL), AC 100–120 V und AC 200–240 V, with OCR alarm (AL)
AE1000–AE4000-SS/SH
SPT-01SAEA024B-A 30462
SPT-2A Trip relay with pre-alarm function (PAL), DC 100–110 V, with OCR alarm (AL) SPT-01SAED011-A 30130
SPT-4A Trip relay with pre-alarm function (PAL), DC 24 V, with OCR alarm (AL) SPT-01SAED24-A 30463
SPGT-1A Trip relay with pre-alarm function (PAL) and ground fault protection (GFR),
AC 100-120 V and AC 200–240 V, with OCR alarm (AL)
AE1000–AE3200-SS/SH SPGT-01SAE024B-A 30468
AE4000-SS SPGT-40SAWA24B-A 62340
AE5000-SS SPGT-50SAWA24B-A 62341
AE6300-SS SPGT-63SAWA24B-A 62342
SPGT-2A Trip relay with pre-alarm function (PAL), ground fault protection (GFR), DC 100-110 V, with OCR alarm (AL) AE1000–AE3200-SS/SH SPGT-01SAED011-A 30470
SPGT-4A Trip relay with pre-alarm function (PAL) ground fault protection (GFR),
DC 24 V, with OCR alarm (AL)
AE1000–AE3200-SS/SH SPGT-01SAED24-A 30469
AE4000-SS SPGT-40SAWD24-A 62343
AE5000-SS SPGT-50SAWD24-A 62344
AE6300-SS SPGT-63SAWD24-A 62345
M
MT-1 Trip relay for generator protection with pre-alarm function (PAL), AC 100-120 V and AC 200–240 V AE1000–AE3200-SS/SH MT-01SAE024B 27495
MPT-1, A Trip relay for generator protection with pre-alarm function (PAL), AC 100-120 V and AC 200–240 V, with OCR
alarm (AL)
AE1000–AE4000-SS/SH MPT-01SAE024B-A 27990
AE5000-SS MPT-50SAWA024B-A 62360
AE6300-SS MPT-63SAWA024B-A 62361
MPT-4, A Trip relay for generator protection with pre-alarm function (PAL), DC 24 V, with OCR alarm (AL)
AE1000–AE4000-SS/SH MPT-01SAED24-A 30473
AE5000-SS MPT-50SAWD24-A 62362
AE6300-SS MPT-63SAWD24-A 62363
BB-C Closing short-circuit current actuator AE1000–AE3200-SS BC-01SAE 34157
B-C-A Closing short-circuit current actuator with OCR alarm (AL) AE1000–AE3200-SS BC-01SAE-A 34159
28
10 1000 2000 500020010012020 50 5005
1000
10
1
0,1
200
100
20
2
300
40
400
50
4
500
60
5
0,5
0,05
0,4
0,04
0,3
0,03
0,2
0,02
30
x10
x12 x16
x4 x6 x8
Current (% of rated current IN max)
Time (sec.)
Max. time of
let-through current
Maximum
breaking time
65 kA max.
65 kA max.
Adjustable range for
INST/MCR
pick-up current II
Max. setting of
external OCR
Setting at shipment
Maximum times of let-through current (65 kA)
B type characteristics for AE1000-SS to AE3200-SS/DSN
MITSUBISHI ELECTRIC
29
SUPER AE
SUPER AE
Operating Characteristics Type S
ELECTRONIC TRIP RELAY
Breaker types AE1000-SS/SH to AE3200-SS/SH
x0,1
x0,9
x0,8
x0,7
10 1000 2000 5000200100 12020 50 5005
1000
10
1
0,1
200
100
20
2
300
40
400
50
4
500
60
5
0,5
0,05
0,4
0,04
0,3
0,03
0,2
0,02
30
T = 150
L
0,3 0,3
0,4
x2 x3 x4 x6 x8
x10
x10
x12
x16
x4 x6 x8
0,2
0,1
3
0
1,5
0,8
0,5
x0,1
x0,2
x0,3
x0,5
T = 100
L
T=50
L
50
100
150
Ooperating time [sec]
SShort-time delay operation time (Ts) setting range
(Short-time delay current x 1.5) 0-0.1-0.2-0.3-0.4-0.5
IInstantaneous current (II) setting range
Rated current x setting 4-6-8-10-12-16
Pre-alarm operation time (TP)
Long-time delay operation time x 0.5
PAL Pre-alarm current (IP) setting range
Uninterrupted current x setting 0.7-0.8-0.9-1.0-OVER
GFR Ground fault current (IG) setting range
Max. rated current x setting 0.1-0.2-0.3-0.5
GFR Ground fault operation time (TG) setting range
(Ground fault current x 1.5) 0.3-0.8-1.5-3
LLong-time delay operation time (TL) setting range
(Uninterrupted current x 2) 50-100-150
SShort-time delay current (IS) setting range
Rated current x setting 2-3-4-6-8-10
Current
Long time delay, pre-alarm % of uninterrupted current (IU)
Short-time delay / instantaneous % of rated current (IN)
Ground fault % of max. rated current (IN MAX.)
Setting at shipment
Trip relay with
MCR function
(for AE-SS only)
30
Operating Characteristics Type S
x0,1
x0,9
x0,8
x0,7
10 1000 2000 5000200100 12020 50 5005
1000
10
1
0,1
200
100
20
2
300
40
400
50
4
500
60
5
0,5
0,05
0,4
0,04
0,3
0,03
0,2
0,02
30
T = 150
L
0,3 0,3
0,4
x2 x3 x4 x6 x10
x8
x10
x16
x4 x6 x8
0,2
0,1
3
0
1,5
0,8
0,5
x0,5
x0,2
x0,3
x12
T = 100
L
T=50
L
50
100
150
50
Operating time [sec]
Current
Long-time delay, pre-alarm % of uninterrupted current (IU)
Short-time delay / instantaneous % of rated current (IN)
Ground fault % of max. Rated current (IN MAX.)
Pre-alarm operation time (TP)
Long-time delay operation time x 0.5
GFR Ground fault current (IG) setting range
Max. rated current x setting 0.2-0.3-0.5
PAL Pre-alarm current (IP) setting range
Uninterrupted current x setting 0.7-0.8-0.9-1.0-OVER
LLong-time delay operation time (TL) setting range
(Uninterrupted current x 2) 50-100-150
SShort-time delay current (IS) setting range
Rated current x setting 2-3-4-6-8-10
GFR Ground fault operation time (TG) setting range
(Ground fault current x 1.5) 0.3-0.8-1.5-3
SShort-time delay operation time (Ts) setting range
(Short-time delay current x 1.5) 0-0.1-0.2-0.3-0.4-0.5
IInstantaneous current (II) setting range
Rated current x setting AE4000-SS: 4-6-8-10-12-16
AE5000-SS: 4-6-8-10-12
AE6300-SS: 4-6-8-10
Setting at shipment
Breaker types AE4000-SS to AE6300-SS
MITSUBISHI ELECTRIC
31
SUPER AE
SUPER AE
Operating Characteristics Type M
ELECTRONIC TRIP RELAY
Breaker types AE1000-SS/SH to AE3200-SS/SH
10 1000 2000 500020010012020 50 5005
1000
10
1
0,1
200
100
20
2
300
40
400
50
4
500
60
5
0,5
0,05
0,4
0,04
0,3
0,03
0,2
0,02
3030
0,3 0,3
0,4
x2
x3
x3,5
x2,5
x4
x10
x12
x16
x4 x6 x8
0,2
0,1
3
0
1,5
0,8
0,5
x0,1
x0,2
x0,3
x0,5
T=60
L
T=40
L
T=30
L
T=25
L
T=20
L
T=15
L
60
40
25 20 30
15
Operating time [sec]
LLong-time delay current (IP) setting range
Rated current x setting 1.0-1.05-1.1-1.15-1.2
Pre-alarm operation time (TP)
Long-time delay operation time x 0.5
GFR Ground fault current (IG) setting range
Max. rated current x setting 0.1-0.2-0.3-0.5
PAL Pre-alarm current (IP) setting range
Long-time delay current x setting 0.84-0.88-0.92-0.96-1.0
SShort-time delay current (IS) setting range
Rated current x setting 2-2.5-3-3.5-4-4.5
GFR Ground fault operation time (TG) setting range
(Ground fault current x 1.5) 0.3-0.8-1.5-3
SShort-time delay operation time (Ts) setting range
(Short-time delay current x 1.5) 0-0.1-0.2-0.3-0.4-0.5
Current
Pre-alarm % Long time delay current (IU)
Long-/short-time delay/instantaneous % of rated current (IN)
Ground fault % of max. rated current (IN MAX.)
IInstantaneous current (II) setting range
Rated current x setting 4-6-8-10-12-16
Setting at shipment
LLong-time delay operation time (TL) setting range
(Long-time delay current x 1.2) 15-20-25-30-40-60
32
10 1000 2000 5000200100 12020 50 5005
1000
10
1
0,1
200
100
20
2
300
40
30
400
50
4
500
60
5
0,5
0,05
0,4
0,04
0,3
0,03
0,2
0,02
x2
x3
x3,5
x4,5
x2,5
x4
0
T=60
L
T=40
L
T=30
L
T=25
L
T=20
L
T=15
L
60
40
20
30
25
15
0,3
3
1,5
0,8
x0,5
x0,2
x0,3
0,3
0,4
x10
x16
x4 x6 x8
0,2
0,1
0
0,5
x12
Operating time [sec]
IInstantaneous current (II) setting range
Rated current x setting AE4000-SS: 4-6-8-10-12-16
AE5000-SS: 4-6-8-10-12
AE6300-SS: 4-6-8-10
Current
Pre-alarm Long time delay current (IU)
Long-/short-time delay/instantaneous % of rated current (IN)
Ground fault % of max. rated current (IN MAX.)
GFR Ground fault operation time (TG) setting range
(Ground fault current x 1.5) 0.3-0.8-1.5-3
SShort-time delay operation time (Ts) setting range
(Short-time delay current x 1.5) 0-0.1-0.2-0.3-0.4-0.5
GFR Ground fault current (IG) setting range
Max. rated current x setting 0.2-0.3-0.5
Pre-alarm operation time (TP)
Long-time delay operation time x 0.5
LLong-time delay current (IP) setting range
Rated current x setting 1.0-1.05-1.1-1.15-1.2
SShort-time delay current (IS) setting range
Rated current x setting 2-2.5-3-3.5-4-4.5
PAL Pre-alarm current (IP) setting range
Long-time delay current x setting 0.84-0.88-0.92-0.96-1.0
LLong-time delay operation time (TL) setting range
(Long-time delay current x 1.2) 15-20-25-30-40-60
Setting at shipment
Breaker types AE4000-SS to AE6300-SS
Operating Characteristics Type M
MITSUBISHI ELECTRIC
33
SUPER AE
SUPER AE
Wiring Diagram
SPECIFICATIONS
Super AE air circuit breakers with electronic trip relay type S or M
The following circuit diagram shows the breaker with fully equipped accessories.
Terminal Code Function Remark Terminal Code Function Remark
13/14, 23/24, 33/34,
43/44, 53/54 AXa Auxiliary switch contact a NO contact N1 / N2 NP Neutral pole CT or ext. ZCT
11/12, 21/22, 31/32,
41/42, 51/52 AXb Auxiliary switch contact b NC contact M1 / M2 LM Load current measurement
413 / 414 TS Charged signal NO contact 97 / 98 AL OCR alarm contact
U1 / U2 MD Motor charging 513 / 524/534/544 TRIP Trip indication contact L, S/I, G or E Signal
A1 / A2 CC Closing coil 513 / 554 PAL Pre-alarm indication contact Signal
C1 / C2 SHT Shunt trip 513 / 564 TAL Temperature alarm indication contact Signal
J1 / J2 UVT Under-voltage trip L1 / L2 / L3 Electronic trip relay unit controlpower supply See table on p. 35
713 / 714 ER Earth leakage trip e.g. for SHT trip 311 – 344 Cell switches (drawout type breakers only)
Description of terminal layout
TAL
Xa
G/E
AL+R+
{
CL
AL
CL CL CL
CLc AL–T1–R2– R1– T4– T2–
S/IPL
342 344 332 334 322 324 312 314
311 98524L3 L2 554 534
97L1
EN 50005
EN 50005
CLc CLc
341
CLc
331 321
CLb CLa CLb CLa CLb CLa CLb CLa
564 544 513
T5 T3 T0+
Main
circuit Cell switches
Electronic
trip relay
see
left table
on page 35
Reset
2000 V
Dielectric voltage
1500 V
Dielectric voltage
Electronic
trip relay
34
AXAXAXAXAXAXAXAXAXAX
SHT
UVT SHT CC
SBC
SBC
SBC
SBC
SBC
M
LM+ CT+ S+ CC+ M+ TS+ B10+ B9+ B8+ B7+ B6+ A5+ A4+ A3+ A2+ A1+
M1 N1 C1 A1 U1 413 51 41 31 21 11 53 43 33 23 13
U+
J1
ST+
713
A4–
A5– A3– A2– A1–
B6–B7–B8–B9–B10–TS–
LM– CT– ST– U– S– CC– M–
44
54 34 24 14
1222324252414
M2 N2 714 J2 C2 A2 U2
UVT
refer to
page 11
Auxiliary switches
Indication
“CHARGED”
Under-voltage
trip
Electrical
operation
circuit Charged signal
refer to
page
26
OFF
ON OFF ON
2000 V
Dielectric voltage
When using coil loads such as DC mag-
netic switches, etc. as operating voltage
in the peripheral circuits, install diodes,
surge absorbers, etc. as a countermea-
sure against surge (counter electromo-
tive force) at the time of switching. On
the drawout type, the control circuit termi-
nal block should be moved to the left or
right by 5 mm after the cables are con-
nected.
Electrical connection Terminals
Voltage L1 L2 L3
AC 100–120 V 쏹쏹
200–240 V 쏹쏹
DC 100–110 V +
DC 125 V +
DC 24 V +
Power supply for
electronic trip relay Description of symbols for the accessory
Description
Symbol Function Symbol Function
MMotor G or E Ground fault trip or earth leakage indication lamp
CC Closing coil PPre-alarm indication lamp
SHT Shunt trip device TAL Unusual temperatur indication lamp
UVT Undervoltage trip device Self-holding relay
AL OCR alarm Wiring by factory
LLong-time delay trip indication lamp Wiring by customer
S/I Short-time delay trip indication lamp
MITSUBISHI ELECTRIC
35
SUPER AE
SUPER AE
Dimensions Fixed Type Breaker
SPECIFICATIONS
175*
88
144
290
340
5
40
80 288
G
72 350
410
132
C*
AB HHH
J
23
D*
E
38 F
4 x Ø 14
268
228
4-Ø13
K
17
38
25
95
25
25
2-Ø13
50
25
17
38
31
Anschlußbereich
AE1000–1600-SS
*Befestigungsmaße
AE2000–3200-SS
AE1000–3200-SH
Operating panel center
Control terminals
External accessory
(e.g. UVT controller)
Neutral pole
Front view Side view Rear view
Main circuit terminals
Operating panel center
Panel center
AE2000–3200-SS
AE1000–3200-SH
Earth
terminal
screw M8
Interphase barrier
Inside of panel
(thickness 1.6 to 3.2)
[mm]
* Mounting pitch
Connecting area
Door frame and panel-cut
235
345
175
8-Ø7
247
271
381
324
357
175
Operating panel center Operating panel center
Breaker
mounting
frame
Panel-cut Door frame panel-cut
[mm]
Breaker
mounting
frame
Breaker types AE1000 to AE3200-SS/SH with standard connection (horizontal terminals)
Breaker type Poles A B C D E F G H J K
AE1000 1600-SS 3 142 142 156 156 170 170 15 85 50 40
4 142 227 156 241 170 255 15 85 50 40
AE2000 3200-SS 3 232 187 246 201 260 215 20 130 95 40
4 232 317 246 331 260 345 20 130 95 40
AE1000 3200-SH 3 232 187 246 201 260 215 20 130 95 70
4 232 317 246 331 260 345 20 130 95 70
36
Breaker types AE1000 to AE3200-SS/SH with vertical terminal adapter (VTA)
50
T
85 85 85
130 130 130
23
100
147
97
X
50
50
39,5
64,5
182
47
57
15,5 125
109,5
T
X
Version B
Operating panel center
Version A
Neutral pole
Neutral pole
AE1000–1600-SS
AE2000–3200-SS
AE1000–3200-SH
[mm]
Vertical terminal adapter (VTA)
2-
Ø
13
50
25
15 38
25
2-
Ø
13
50
15
38
5-
Ø
13
125
15
38
25 25
25
25
T
T
T
T
Version A Version B [mm]
Breaker Vers. T
AE1000–1600-SS A15
AE2000–2500-SS B20
AE3200-SS B25
AE1000–2500-SH B20
AE3200-SH B25
Breaker X T
AE1000–1600-SS 108 15
AE2000–2500-SS 123 20
AE3200-SS 123 25
AE1000–2500-SH 153 20
AE3200-SH 153 25
MITSUBISHI ELECTRIC
37
SUPER AE
SUPER AE
Dimensions Drawout Type Breaker
SPECIFICATIONS
Breaker types AE1000 to AE3200-SS/SH with standard connection (horizontal terminals)
AB
C
59
42,5
40
D
K
L
KK
4-
Ø
13
15
38
25
103
25
25
2-
Ø
13
50
25
15
38
228
200*
23
E
J
J
F
G
H
452
220*
40
23 48
25
61
35
51
132
370
430
340
15
Erdunganschluß-
schraube M8 AE1000–1600-SS
*Befestigungsmaß
4x 14
Anschlußbereich
AE2000–3200-SS
AE1000-3200-SH
Erdungsanschluß-
schraube M8
(gegenüber-
liegende Seite)
Handkurbel-
öffnung
92
Operating panel center
Control terminals Test position
External accessory
(e.g. UVT controller)
Neutral pole
Front view
Side view
Rear view
Main circuit terminal
Operating panel center
Disconnected position
Inside of the panel
(thickness 1.6 to 3.2)
Panel center for
AE2000–3200-SS
AE1000–3200-SH
[mm]
Drawout position
Interphase barrier
* Mounting pitch
Drawout handle
insertion port
Ground terminal
screw M8
Connecting area
Earth terminal
screw M8
(on opposite side)
Breaker type Pole A B C D E F G H J K L
AE1000–1600-SS 3 150 150 149 149 311 368 366 172 15 85 50
4 150 235 149 234 311 368 366 172 15 85 50
AE2000–3200-SS 3 240 195 239 194 311 368 366 172 25 130 103
4 240 325 239 324 311 368 366 172 25 130 103
AE1000–3200-SH 3 240 195 265 220 341 398 396 202 25 130 103
4 240 325 265 350 341 398 396 202 25 130 103
Drawout handle, door frame and panel-cut
235
367
195
8-Ø7
247
271
381
324
357
195
Ø22
Ø
12
200
200
169
max.173
345
Operating panel center
Breaker
mounting
frame
Breaker
Drawout handle Panel-cut Door frame panel-cut
Breaker
mounting
frame
[mm]
38
Breaker types AE1000 to AE3200-SS/SH with vertical terminal adapter
2-
Ø
13
50
25
15 38
25
2-
Ø
13
50
15
38
5-
Ø
13
125
15
38
25 25
25
25
T
T
T
T
Version A Version B [mm]
Breaker Vers. T
AE1000–1600-SS A15
AE2000–2500-SS B20
AE3200-SS B25
AE1000–2500-SH B20
AE3200-SH B25
50
T
85 85 85
130 130 130
23
100
147
97
131
50
50
59,5
84,5
182
67
57
4,5
146
125
125
T
Neutral pole
Neutral pole
Version B
AE2000–3200-SS
AE1000–3200-SH
Version A
AE1000–1600-SS
Operating panel center
[mm]
Breaker T
AE1000–1600-SS 15
AE2000–2500-SS 20
AE3200-SS 25
AE1000–2500-SH 20
AE3200-SH 25
Vertical terminal adapter (VTA)
MITSUBISHI ELECTRIC
39
SUPER AE
SUPER AE
Dimensions Breaker
SPECIFICATIONS
5-Ø13
125
25
53
25
25
25
25
431,5
42,5
196 262 262 235
4P: 561,5
3P: 431,5
382
14
25 Y
103 X
373,5 3P: 458,5
4P: 588,5
3P: 480
4P: 610
44
28 28
42,5
90
345,5
4x M12
Anschlußbereich
Erdungsanschluß-
schraube M8 Erdungsanschluß-
schraube M8
(gegenüberlie-
gende Seite)
Befestigungs-
schrauben
2x M12
395
184
530*
228 311
366
172 220*
368
40
23 48
123
35
51
182
117
420
125 125
480
340
75
400
15
15
Operating panel center
Control terminal
External accessories
(e.g. UVT controller)
Front view
Side view
Rear view Main circuit terminals
Disconnect position
Test position
Drawout position
Drawout
handle
radius 100
Lifting hook hole
Neutral Pole
Operating panel center
Mounting
screws M12
Inside of the panel
(thickness 1.6 to 3.2)
* Mounting pitch
[mm]
Connecting area
Fixing bolts
2xM12
Earth terminal
screw M8
(on opposite side)
Earth terminal
screw M8
Breaker types AE4000 to AE6300-SS with standard connection (vertical)
235
367
245
8-
Ø
7
247
271
381
324
357
245
Ø
22
Ø
12
200
200
169
max.173
345
Operating panel center
Breaker
mounting
frame
Breaker
Drawout handle Panel-cut Door frame panel-cut
Breaker
mounting
frame
[mm]
Drawout handle, door frame and panel-cut
Type Dimensions*
XY
AE4000-SS
AE5000-SS 100 20
AE6300-SS 105 25
* please check before mounting!
40
Dimensions Accessory
G
H
J
CD
F
A
E
B
Fixing hole
(screw M8) Secondary output terminals
(screws M3.5 x 0.6)
[mm]
External ZCT for load circuits
External ZCT for transformer ground wire
E
70
90
CD
3
B
A
100
30
7
9
12
C
2
D
G
E
B
A
H
F
28
40
52
6
7,7
ZT15A 40 A ZT60A 100 A
Self-lifting terminals
screws M3,5 Fixing hole for
screws M6
For M5
[mm]
4- 7
Ø
90
90
4-R6
90
87
13,3
15,4
110,6
106
16
75
100
45 45
45 45
Ø
104
Front view Side view
Screw M4
[mm]
Condenser trip device (COT) UVT controller, external power supply (PS)
182.2
118
14.5
2156.5
8.2
6.75 9.3 7.8
72
19
11
45
87.9
14.6
19.8
Mounting
screw
Terminal screw M3.5
[mm]
.Type ZCT
163 ZCT
323 ZCT
324
Size
A230 370 500
B60 108 108
C104 104 104
D200 200 200
E323 460 600
F250 400 550
G47 47 48
H72 72 72
J92 92 92
.. Type ZT
15A ZT
30A ZT
40A ZT
60A ZT
80A ZT
100A
Size
A48 68 85 140 160 185
B15 30 40 60 80 100
C29 37 43 73 82 93
D62 82 92 150 169 190
E46 66 81 46 48 50
F15 30 40
G70 90 100
H25 50 50
MITSUBISHI ELECTRIC
41
SUPER AE
SUPER AE
Operating Conditions, Technical Information
SPECIFICATIONS
When a short-circuit current is interrupted by the breaker, ionised
gases flow out of the exhaust openings of the arc extinguishing
chamber. This makes it necessary to observe the insulation
clearance shown in the table on the right.
The clearances required for maintenance work have also been
taken into consideration in the table.
A clearance of 300 mm or more is necessary for inspection
of the arc extinguishing chambers and main contacts.
The dimension D represents the wiring space required for
the control terminal block.
Dimension B becomes larger when the breaker is fitted with
the UVT controller, mechanical interlock, door interlock, etc.
Further details available on request.
B
B
A
C
D
A
Electrical equipment, appliances and screen
Side
plate
Mounting
surface
Breaker type AE1000–3200-SS AE1000–3200-SH
AE4000–6300-SS
Applicable voltage AC 600 V AC 660, 690 V AC 690 V
Fixed type
A0 100 200
B50 50 50
C 162 162
D50 50 200
Drawout type
A0 100 200
B50 50 50
C 240 240
D50 50 200
all dimensions in mm
Insulation clearances at the supply side
42
Service conditions
Normal service conditions
If all the following normal working conditions are satisfied (and
not specified otherwise) the AE series air circuit breakers may
be used:
Ambient air temperature
Range max. +40 °C to min. –5 °C (the average value how-
ever should not exceed +35 °C in any 24-hour period).
Altitude
2000 m (6600 feet) or less
Environmental conditions
The air must be free of dust and corrosive gases. Do not use
and store in atmospheres with sulfide gas, ammonia gas etc.
(H2S0,01 ppm, SO20,1 ppm, NH3not measurable).
The relative humidity should be of 85% or less at
a max. of +40 °C.
Installation conditions
When installing AE series circuit breakers always follow the
instructions provided in the catalogue and in the instruction
manual.
Storage temperature
A range of max. +60 °C to min. -20 °C is recommended to
store. However, the average over 24 hours must not exceed
+35 °C.
Replacement
Lifetime is approx. 15 years. For detailed information please
refer to the instruction manual.
Special service conditions
In case of special service conditions, modified circuit breakers
are available (please specifiy when ordering). Service life may
be shorter dependend on service conditions.
Special environmental conditions
Using breakers in a high temperature and/or humidity envi-
ronment can result in deterioration of insulation durability and
other electrical or mechanical features. Breakers used in
such environments should be specially treated to a higher
corrosion proof specification and against moistural fungus.
Where corrosive gases are present in the environment it is
recommended that breakers to a higher corrosion proof
specification are ordered (further details on request).
Special ambient temperature
If the ambient temperature exceeds +40 °C, the continuous
current rating must be reduced. The reduction value
depends on the applicable standard (please refer to the
following page).
Special altitude
When breakers are used at altitudes above 2,000 m the heat
radiation rate is reduced, decreasing the operation voltage,
uninterrupted current and breaking capacity. Reduced at-
mospheric pressure can also reduce insulation durability.
Further details available on request.
Installation in a separate cabinet
If the breaker is installed in a special cabinet, the following
clearances have to be taken into consideration.
Example:
The smallest possible cabinet dimensions for 3-pole Super AE breakers
with up to 1600 A are: Hight=680 mm, Width=540 mm, Depth=368 mm.
120120
130
120
Rear plate Upper plate
Cabinet walls metal or plastic
Lower plate
Side
plate
Side
plate Door
MITSUBISHI ELECTRIC
43
Standard series “SS” High performance series “SH”
Breaker type Resistance
(m)Reactance
(m)Power
consumption (W) Breaker type Resistance
(m)Reactance
(m)Power
consumption (W)
AE1000-SS Fixed 0.026 0.060 26 AE1000-SH Fixed 0.018 0.047 18
Drawout 0.040 0.091 40 Drawout 0.028 0.071 28
AE1250-SS Fixed 0.024 0.060 38 AE1250-SH Fixed 0.016 0.047 25
Drawout 0.038 0.091 60 Drawout 0.026 0.071 41
AE1600-SS Fixed 0.016 0.063 41 AE1600-SH Fixed 0.014 0.047 36
Drawout 0.030 0.095 77 Drawout 0.024 0.071 61
AE2000-SS Fixed 0.010 0.047 40 AE2000-SH Fixed 0.012 0.047 48
Drawout 0.020 0.071 80 Drawout 0.022 0.071 88
AE2500-SS Fixed 0.008 0.047 50 AE2500-SH Fixed 0.010 0.047 63
Drawout 0.018 0.071 113 Drawout 0.020 0.071 125
AE3200-SS Fixed 0.007 0.048 72 AE3200-SH Fixed 0.009 0.048 92
Drawout 0.014 0.072 143 Drawout 0.016 0.072 164
AE4000-SS Drawout 0.013 0.062 210
AE5000-SS Drawout 0.011 0.062 275
AE6300-SS Drawout 0.0085 0.062 340
Internal resistance, reactance and power consumption (per pole)
Deratings (A) by ambient temperature
Standard Ambient
temperature AE1000-SS
AE1000-SH AE1250-SS
AE1250-SH AE1600-SS
AE1600-SH AE2000-SS
AE2000-SH AE2500-SS
AE2500-SH AE3200-SS
AE3200-SH AE4000-SS AE5000-SS AE6300-SS
IEC 947-2,
EN 60947-2,
VDE 0660,
BS 4752
(Reference tempera-
ture = 40 °C)
40 °C 1000 1250 1600 2000 2500 3200 4000 5000 6300
45 °C 1000 1250 1600 2000 2500 3200 4000 5000 6000
50 °C 1000 1250 1600 2000 2500 3200 4000 5000 5750
55 °C 1000 1250 1550 (1600) 2000 2450 3000 3900 5000 5500
60 °C 1000 1200 (1250) 1500 (1600) 2000 2350 2900 3750 4750 5200
LR, AB, GL
(Reference tempera-
ture = 45 °C)
45 °C 1000 1250 1600 2000 2500 3200 4000 5000 6000
50 °C 1000 1250 1600 2000 2500 3200 4000 5000 5750
55 °C 1000 1250 1550 2000 2450 3050 3900 5000 5500
60 °C 1000 1200 1500 2000 2350 2900 3750 4750 5200
All data in the above table are based on test conditions, connecting methods and size of the mounting rails conforming to
IEC947-2, EN60947-2, VDE0660 etc.
The figures in brackets ( ) in the above table indicate the reduced current values exclusive to AE-SH series.
SUPER AE
SUPER AE
Operating Conditions, Technical Information
SPECIFICATIONS
44
Specifications for marinal standards
SUPER AE Series Standard series „SS“
Breaker type AE1000-SS AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SS AE5000-SS AE6300-SS
Rated current (A) IN max 1000 1250 1600 2000 2500 3200 4000 5000 6300
Rated insulation voltage (V) 50/60 Hz Ui 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated operating voltageg (V) 50/60 Hz Ue 690 690 690 690 690 690 690 690 690
Number of poles 333333333
Adjustment
range (A) Ir General protection
(current rating adjustable) 500In1000
315In630 625In1250 800In1600 1000In2000
625In1000 1250In2500 1600In3200 2000In4000 2500In5000 3150In6300
Rated service
short-circuit
breaking capacity
Ics
(kA, eff, sym.)
Breaking duty:
O-t-CO-t-CO
ICU =ICS
LR with instan-
taneous trip
AC690V 50 50 50 50 50 50
AC600V 65 65 65 87 87 87
AC500V 65 65 65 85 85 85 133 133 133
AB with instan-
taneous trip
AC690V 50 50 50 50 50 50
AC600V 65 65 65
AC500V 65 65 65 85 85 85
GL with instan-
taneous trip
AC690V 50 50 50 50 50 50
AC600V 65 65 65
AC500V 65 65 65 85 85 85
BV with instan-
taneous trip
AC690V 50 50 50 50 50 50
AC600V 65 65 65
AC500V 65 65 65 85 85 85
NK with instan-
taneous trip
AC600V 50 50 50 65 65 65 87 87 87
AC500V 65 65 65 85 85 85 133 133 133
Rated service
short-circuit
making capacity
Icm
(kA, peak value)
LR with instan-
taneous trip
AC690V 106 106 106 143 143 143
AC600V 143 143 143 211 211 211
AC500V 151 151 151 196 196 196 330 330 330
AB with instan-
taneous trip
AC690V 105 105 105 105 105 105
AC600V 143 143 143
AC500V 143 143 143 187 187 187
GL with instan-
taneous trip
AC690V 106 106 106 106 106 106
AC600V 143 143 143
AC500V 151 151 151 196 196 196
BV with instan-
taneous trip
AC690V 106 106 106 106 106 106
AC600V 143 143 143
AC500V 151 151 151 196 196 196
NK with instan-
taneous trip
AC600V 112 112 112 143 143 143 211 211 211
AC500V 147 147 147 196 196 196 330 330 330
* Further current ratings on request.
SUPER AE Series High performance series „SH“
Breaker type AE1000-SH AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH
Rated current (A) IN max 1000 1250 1600 2000 2500 3200
Rated insulation voltage (V) 50/60 Hz Ui 1000 1000 1000 1000 1000 1000
Rated operating voltageg (V) 50/60 Hz Ue 690 690 690 690 690 690
Number of poles 333333
Adjustment
range (A) Ir General protection
(current rating adjustable) 500In1000
315In630 625In1250 800In1600 1000In2000 1250In2500 1600In3200
Rated service
short-circuit
breaking capacity
Ics (kA, eff, sym.)
Br. duty: O-t-CO-t-CO
ICU =ICS
LR with instan-
taneous trip
AC690V 68 68 68 68 68 68
AC600V 87 87 87 87 87 87
AC500V 133 133 133 133 133 133
NK with instan-
taneous trip
AC690V
AC600V 130 130 130 130 130 130
Rated service
short-circuit
making capacity
Icm
(kA, peak value)
LR with instan-
taneous trip
AC690V 173 173 173 173 173 173
AC600V 211 211 211 211 211 211
AC500V 330 330 330 330 330 330
NK with instan-
taneous trip
AC690V
AC600V 317 317 317 317 317 317
MITSUBISHI ELECTRIC
45
SUPER AE
SUPER AE
Specimen Sheet for Breaker Ordering
ORDER FORM
Company: .........................
Department: .........................
Name: .........................
Street: .........................
Adress: .........................
Phone: .........................
Fax: .........................
Base unit
Pos. Number Item (type) Order number
(Art. no.) Description Special version*
(e.g. varying
connection arrangement)
Trip relay*
(for order code, refer to p 28)
Accessory
for Pos. Number Item (type) Order number
(Art. no.) Description Special version*
(e.g. varying
power supply) Remarks
MITSUBISHI ELECTRIC EUROPE
Factory Automation
Gothaer-Str. 8
D-40880 Ratingen
Fax: 02102/486-407
Notes for ordering:
For your order please exclusively use the item names and order numbers (art. no.) specified in this catalogue.
* If only the standard model is desired or no special version is wanted, please mark it in the concerning field with a dash.
46
INDEX
A
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Ambient temperature. . . . . . . . . . . . . . . . . . . . . . . . . . 43, 44
Auxiliary switch (AX), (HAX). . . . . . . . . . . . . . . . . . . . . . . . 12
C
Cellswitch(CL)................................. 14
Certificates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Characteristics setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Charging completion switch (TS). . . . . . . . . . . . . . . . . . . . 10
Charging handle (manual charging) . . . . . . . . . . . . . . . . . . 9
Closing coil (CC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Counter (CNT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Condensor trip device (COT). . . . . . . . . . . . . . . . . . . . 13, 41
Connection arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CT ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Current transformer (CT) . . . . . . . . . . . . . . . . . . . . . . . . . . 18
D
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36–41
Doorframe(DF)................................. 17
Door interlock (DI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Drawout handle.............................. 38,40
Drawout interlock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dust cover (DC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
E
Earth leakage protection (ER) . . . . . . . . . . . . . . . . . . . . . . 26
Electronic trip relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
External power supply (PS) . . . . . . . . . . . . . . . . . . . . . 19, 41
External ZCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18, 41
F
Field test devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
G
Ground fault protection (GFR) . . . . . . . . . . . . . . . . . . . . . . 27
I
Insulation clearance at the supply side . . . . . . . . . . . . . . . 42
Interlock device (CYL, CAL) . . . . . . . . . . . . . . . . . . . . . . . 13
Internal resistance per pole . . . . . . . . . . . . . . . . . . . . . . . . 44
Interphase barrier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
L
Lifting hooks (HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Load current measurement (LM) . . . . . . . . . . . . . . . . . . . . 27
M
Manual charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Marine approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 45
Mechanical interlock (MI). . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mis-insertion preventer (MIP). . . . . . . . . . . . . . . . . . . . . . . 14
Motor charging (MD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
N
Neutral current transformer (NCT) . . . . . . . . . . . . . . . . . . . 18
Neutral pole overcurrent protection (NP) . . . . . . . . . . . . . . 26
O
Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Operating characteristics . . . . . . . . . . . . . . . . . . . . . . 29–33
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . 6, 7, 28
Order sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Overcurrent OCR-Alarm (AL). . . . . . . . . . . . . . . . . . . . . . . 27
P
Panelcut................................... 38,40
Performance ............................ 4,5,20,45
Position lock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Power consumption per pole. . . . . . . . . . . . . . . . . . . . . . . 44
Pre-alarm (PAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Program overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Push button cover (BC-L) . . . . . . . . . . . . . . . . . . . . . . . . . 17
R
Reactance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Resistance per pole. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
S
Safety shutters (SST) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Shorting b-contact (SBC). . . . . . . . . . . . . . . . . . . . . . . . . . 14
Shunt trip device (SHT) . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 4, 5, 20, 45
Standard accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Switch-disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
T
Temperature alarm (TAL). . . . . . . . . . . . . . . . . . . . . . . . . . 27
Terminal adapter . . . . . . . . . . . . . . . . . . . . . . . . . . 15, 37, 39
Terminal cover (TTC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Terminal layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35
Test jumper (TJ). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Trip relay type M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24, 25
Trip relay type S. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22, 23
U
Undervoltage trip device (UVT) . . . . . . . . . . . . . . . . . . . . . 11
UVT controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11, 41
V
Vertical terminal adapter (VTA) . . . . . . . . . . . . . . . 15, 37, 39
W
Wiringdiagram .............................. 34,35
MITSUBISHI ELECTRIC
47
Specifications subject to change without notice.
Art. no.: 62093-B, Printed in Germany 12.96 FACTORY AUTOMATION
MITSUBISHI ELECTRIC EUROPE B.V.
GOTHAER STR. 8, D-40880 RATINGEN, TEL. +49 (21 02) 4 86-0, FAX +49 (21 02) 4 86-1 12
www.mitsubishi-automation.com
HEADQUARTERS
MITSUBISHI ELECTRIC CORPORATION JAPAN
2-2-3 Marunouchi Chiyoda-Ku
Mitsubishi Denki Bldg.
Tokyo 100-8310
Tel.: +81 (0) 3 / 3218-3176
Fax: +81 (0) 3 / 3218-2422
MITSUBISHI ELECTRIC EUROPE B.V. EUROPE
GERMAN BRANCH
Gothaer Straße 8
D-40880 Ratingen
Germany
Tel.: +49 (0) 21 02 / 486-0
Fax: +49 (0) 21 02 / 4 86-1 12
E mail: megfamail@meg.mee.com
MITSUBISHI ELECTRIC EUROPE B.V. UK
UK BRANCH
Travellers Lane
GB-Hatfield Herts. AL10 8 XB
Great Britain
Tel.:+44(0)707/276100
Fax:+44(0)707/278695
MITSUBISHI ELECTRIC AUTOMATION, INC. USA
500 Corporate Woods Parkway
Vernon Hills, IL 60061
Tel.: +1 (847) 478 2100
Fax: +1 (847) 478 2283
EUROPEAN REPRESENTATIVES
Emac S.A. BELGIUM
Industrialaan 1
B-1702 Groot-Bijgaarden
Tel.: +32 (0) 2 / 481 02 11
Fax: +32 (0) 2 / 481 03 01
E mail: bpa@emac.be
ELPEFA A/S DENMARK
Geminivej 32
DK-2670 Greve
Tel.: +45(0) 43/959595
Fax: +45(0) 43/959590
E mail: elpefa@elpefa.dk
URHO TUOMINEN OY FINLAND
Palopellonkatu 7
FIN-04251 Kerava
Tel.: +358 (0) 9 / 274 64 11
Fax: +358 (0) 9 / 274 64 141
E mail: komponentit@urhotuominen.fi
Antonios Drepanias S.A. GREECE
193 Lenorman Str.
GR-10442 Athen
Tel.: +30(0)15/141910-940
Fax: +30(0)15/144393
E mail:
CARPANETO & C. S.p.A. ITALY
Via Ferrero 10
I-10090 Cascine Vica-Rivoli (TO)
Tel.: +39 011 / 959 01 11
Fax: +39 011 / 959 02 50
E mail: info.carpaneto@carpaneto.it
MITSUBISHI ELECTRIC EUROPE B.V. IRELAND
Westgate Business Park
IRL-Dublin 22
Tel.: +353 (0) 1 450 50 07
Fax: +353 (0) 1 456 13 37
E mail:
IMTECH Marine & Industry NETHERLANDS
Postbox 5054
NL-3008 AB-Rotterdam
Tel.: +31 (0) 10 / 487 19 11
Fax: +31 (0) 10 / 487 17 17
E mail: info@renhs.nl
SCANELEC AS NORWAY
Leirvikåsen 43B
N-5179 Godvik-Bergen
Tel.: +47(0)55/506000
Fax: +47(0)55/506001
E mail: scanelec@scanelec.no
MPL Technology SP.z.o.o POLAND
ul. Wroclawska 53
PL-30011 Kraków
Tel.: +48 (0) 12 / 632 28 85
Fax: +48 (0) 12 / 632 47 82
E mail: mpl@krakow.ipl.net
EUROPEAN REPRESENTATIVES
ISO-SIGMA PORTUGAL
Rua Faria Guimaraes, 121
P-4000 Porto
Tel.:+351(0)2/524611
Fax:+351(0)2/524895
E mail: isolx@iso-sigma.pt
TUINGDOR ROMANIA
20, Fierarilor Street
RO-72126 Bucaresti
Tel.: +40 (0) 1 / 211 98 01
Fax: +40 (0) 1 / 210 71 81
E mail: tuingdor@pcnet.ro
MITSUBISHI ELECTRIC EUROPE B.V. SPAIN
Calle Joan Buscallá, 2–4
E-08190 Sant Cugat del Vallés
Tel.: +34 (9) 3 / 565 31 60
Fax: +34 (9) 3 / 589 15 79
E mail: industrial@sp.mee.com
Euro Energy Components SWEDEN
Energigatan 15
S-43422 Kungsbacka
Tel.: +46 (0) 300 / 518 00
Fax: +46 (0) 300 / 164 75
E mai: energy@scandi.se
TRIELEC AG SWITZERLAND
Mühlentalstr. 136
CH-8201 Schaffhausen
Tel.: +41 (0) 52 / 625 84 25
Fax: +41 (0) 52 / 625 88 25
E mail: trielec1@schaffhausen.ch
HEDEF TURKEY
Barboros Bulvari Iba Bloklari
Gazi Umur Pasa Sok. 9/4
TR-Balmuncu/Istanbul
Tel.: +90 (0) 212 / 275 48 76
Fax: +90 (0) 212 / 275 88 65
E mail: hedef@hedef.net
REPRESENTATIVE MIDDLE EAST
GINO INDUSTRIES LTD. ISRAEL
3, Ophir St.
IL-Haifa 32235
Tel.: +972 (0) 4 / 862 50 23
Fax: +972 (0) 4 / 867 42 27
E mail: gino-ind@actcom.co.il