Type: DILM12−01(24VDC)
Article No.: 276880
Ordering information
Rated operational current AC−3 400 V IeA 12
Max. rating for three−phase motors, 50 – 60 Hz AC−3
230 V PkW 3.5
Max. rating for three−phase motors, 50 – 60 Hz AC−3
400 V PkW 5.5
Max. rating for three−phase motors, 50 – 60 Hz AC−3
690 V PkW 6.5
Max. rating for three−phase motors, 50 – 60 Hz AC−4
230 V PkW 2
Max. rating for three−phase motors, 50 – 60 Hz AC−4
400 V PkW 3
Max. rating for three−phase motors, 50 – 60 Hz AC−4
690 V PkW 4.4
Conventional thermal current I th = I e AC−1 Open Ith = IeA 20
For use with DILA−XHI(V)..
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations × 10610
DC operated Operations × 10610
Operating frequency, mechanical
AC operated Operations/h 9000
DC operated Operations/h 9000
Climatic proofing Damp heat, constant, to IEC 60068−2−78
Damp heat, cyclical, to IEC 60068−2−30
Ambient temperature
Open °C −25/60
1
Enclosed °C −25/40
Storage °C −40/80
Mechanical shock resistance (IEC/EN 60068−2−27)
Half−sinusoidal shock, 20 ms
Main contacts
Make contact g 10
Auxiliary contacts
Make contact g 7
Break contact g 5
Protection type IP20
Protection against direct contact when actuated from
front (IEC 536) Finger− and back−of−hand proof
Weight
AC operated kg 0,23
DC operated kg 0,28
Terminal capacity Main cable
Solid mm21 × (0.75 – 4)
2 × (0.75 – 2.5)
Flexible with ferrule mm21 × (0.75 – 2.5)
2 × (0.75 – 2,5)
Solid or stranded AWG 18 – 14
Anschlussschraube Hauptleiter M3.5
Tightening torque Nm 1.2
Terminal capacity Control circuit cables
Solid mm21 × (0.75 – 4)
2 × (0.75 – 2.5)
Flexible with ferrule mm2 1 × (0.75 – 2.5)
2 × (0.75 – 2.5)
Solid or stranded AWG 18 – 14
Anschlussschraube Hilfsleiter M3.5
Tightening torque Nm 1.2
Tool
Main cable
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 × 5.5
1 × 6
Control circuit cables
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 × 5.5
1 × 6
Terminal capacity Main cable
Solid mm20.75 – 2.5
flexible mm20.75 – 2.5
flexible with ferrules mm20.75 – 2.5
Solid or stranded AWG 18 – 14
Terminal capacity Control circuit cables
Solid mm20.75 – 2.5
2
Flexible mm20.75 – 2.5
Flexible with ferrule mm20.75 – 2.5
Solid or stranded AWG 18 – 14
Tool
Stripping length mm 10
Screwdriver blade width mm 3,5
Main conducting paths
Rated impulse withstand voltage Uimp V AC 8000
Overvoltage category/pollution degree III/3
Rated insulation voltage
AC UiV AC 690
Rated operational voltage UeV AC 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and contacts V AC 400
between the contacts V AC 400
Making capacity (cos Õ to IEC/EN 60947) up to 690
VA 144
Breaking capacity
220/230 V A 120
380/400 V A 120
500 V A 100
660/690 V A 70
Component lifespan
AC−3/AC−4  Tripping characteristics
Maximum operating frequency
AC−1; 400 V IeOps/h 800
AC−3; 400 V IeOps/h 1000
AC−4; 400 V IeOps/h 300
Short−circuit rating
Short−circuit protection Maximum fuse
Type “2” coordination
400 V gG/gL 500 V A 20
690 V gG/gL 690 V A 20
Type “1” coordination
400 V gG/gL 500 V A 35
690 V gG/gL 690 V A 25
AC
AC−1 duty
conv. therm. current 3−pole 50 – 60 Hz
open
at 40 °C Ith A 22
at 50 °C Ith A 21
at 55 °C Ith A 21
at 60 °C Ith A 20
Enclosed Ith A 18
3
Conventional free air thermal current, 1−pole
open Ith A 50
Enclosed Ith A 45
AC−3 duty
Rated operational current AC−3 open, 50 – 60 Hz,
3−pole
220/230 V IeA 12
240 V IeA 12
380/400 V IeA 12
415 V IeA 12
440V IeA 12
500 V IeA 10
660/690 V IeA 7
Motor rating
220/230 V PkW 3,5
240V PkW 4
380/400 V PkW 5,5
415 V PkW 7
440 V PkW 7,5
500 V PkW 7
660/690 V PkW 6,5
AC−4 duty
Rated operational current AC−4 open, 50 – 60 Hz,
3−pole
220/230 V IeA 7
240 V IeA 7
380/400 V IeA 7
415 V IeA 7
440 V IeA 7
500 V IeA 6
660/690 V IeA 5
Motor rating
220/230 V PkW 2
240 V PkW 2,2
380/400 V PkW 3
415 V PkW 3,4
440 V PkW 3,6
500 V PkW 3,5
660/690 V PkW 4,4
DC
of three−phase capacitors open
DC−1 operation
60 V IeA 20
110 V IeA 20
220 V IeA 15
440 V IeA 1,3
DC−3 operation
4
60 V IeA 20
110 V IeA 20
220 V IeA 1,5
440 V IeA 0,2
DC−5 operation
60 V IeA 20
110 V IeA 20
220 V IeA 1,5
440 V IeA 0,2
Current heat loss (3−pole)
Current heat loss at Ith W 4,7
Current heat loss at Ie to AC−3/400 V W 1,1
Impedance per pole m& 2,5
Magnet systems
Voltage tolerance
AC operated
AC operated Pick−up × Uc0,8 – 1,1
Drop−out voltage AC operated
Drop−out voltage AC operated Abfall × Uc0,3 – 0,6
DC operated
DC operated Pick−up × Uc0,8 – 1,1
DC operated
DC operated Abfall × Uc0,15–0,6
Power consumption of the coil in a cold state and 1.0
× Uc
50 Hz Pick−up VA 24
50 Hz Pick−up W 19
50 Hz Sealing VA 4
50 Hz Sealing W 1,2
60 Hz Pick−up VA 29
60 Hz Pick−up W 23
60 Hz Sealing 4,4
60 Hz Sealing VA 1,3
50/60 Hz Pick−up VA 28
26
50/60 Hz Pick−up W 22
21
50/60 Hz Sealing VA 4,6
3,9
50/60 Hz Sealing W 1,4
1,2
DC operated Pick−up W 4.5
DC operated Sealing W 4.5
Duty factor % DF 100
Switching times at 100 % Uc (approximate values)
Main contacts
AC operated
5
Closing delay ms 20
Opening delay ms 15
DC operated
Closing delay ms 35
Opening delay ms 15
Arcing time ms 10
Electromagnetic compatibility (EMC)
Emitted interference to EN 60947−1
Interference immunity to EN 60947−1
Mounting position
Mounting position, AC− and DC operated
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn
E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net
Copyright 2005 by Moeller GmbH. Subject to modifications. HPL−C2005GB−INT V3.0